installed vrot 18-1 - Energo Group CANADA Inc

ENERGO GROUP CANADA INC.
AND
ENERGO-GROUP D.O.O..
SARAJEVO
BOSNIA AND HERCEGOVINA
VROT-18
e – mail: [email protected]
[email protected]
BASIC FACTS ABOUT ENERGO-GROUP (EG)
• Our factory facility is ISO9001:2000 certified with a manufacturing
capacity of 5000 transformers a year of all types for voltages up to
35kV. Factory website: http://www.fmt.rs
• The company’s R&D team of Electrical Engineers are constantly
researching, developing and testing new transformers in our lab per
special needs and requests and implementing new ideas and
technologies
• We have a long list of existing installation sites in different countries
such as: England, Sweden, Denmark, Germany, Romania, Bulgaria,
Greece, Croatia, Slovenia, Serbia, Montenegro, Bosnia and
Herzegovina, Sudan, Estonia, India, Saudi Arabia, United Arab
Emirates, South Africa…
• All of our transformers and equipment are tested and certified to the
latest standards in Europe, Asia and Africa such as: IEC, BS, VDE,
DIN, ANSI, GOST, JUS. We are in process to get ULC and CSA
approvals
• For more information please visit Energo Group Canada Inc.
website: www.egcanada.ca
Few of EGC Products
UNIQUE SMART DEVICE
TYPE “VROT 18-X”
FOR TRANSFER OF
MAXIMUM POWER LOAD
FROM STEP DOWN TRANSFORMER
TO THE END OF LOW VOLTAGE LINE,
ACTING AS A REPLACEMENT
SOLUTION FOR SUB STATIONS (SS)
10(20)(33)/0.208kV,50kVA,
IN THAT LOW VOLTAGE LINE
DEVICE PHOTOGRAPH “VROT 18”
MAIN TECHNICAL SPECIFICATION FOR DEVICE “VROT 18-1”
• VROT -18
•
•
•
•
•
•
•
•
•
•
•
•
•
-
Input Voltage [V] :
Output Voltage [V]
Power load ratio [kVA]
Maximal Voltage [kV]
Test Voltage 50Hz, 1min [kV]
Lighting impulse Voltage 1,2/50µs [kV]
Current ratio [A]
Transformer losses “Pcun [W]/Pfe[W] “
Transformer Power factor “cos φ”
Mechanical Protection
Ambient Temperature span:
Operating Temperature:
Installation:
1
208
120 ± 10%
12
1
3
6
100
150 / 60
0.97
IP 54
-55C to 75C
up to 135C
In any position
BENEFITS OF “VROT 18 -1” USED
IN LOW VOLTAGE SINGLE PHASE POWER LINES
•
THE END USERS HAVE ENERGY IN ACCORDING WITH EN 50160
•
PRIMARY CURRENT IS 36% LESS THAN SECONDARY OUTPUT
CURRENT, AND VOLTAGE DROP IS IN DIRECT FUNCTION OF
PRIMARY CONDUCTOR IN COMPARISION WITH CLASSIC
TRANSMISSION METHOD
•
POSSIBLE TO TRANSMIT 9 TIMES MORE LOAD FROM STEP DOWN
TRANSFORMER TO THE END OF THE POWER LINE IN COMPARISON
WITH CLASSIC TRANSMISSION METHOD , WITH THE SAME
PARAMETERS OF LOW VOLTAGE LINES
•
POSSIBLE TRANSMISSION OF DISTANCES UP TO 9 TIMES LONGER
THAN WITH CLASSIC TRANSMISSION METHOD, WITH THE SAME
PARAMETERS OF LOW VOLTAGE LINES
•
POWER LOSS IN TRANSMISSION IS 60% LOWER THAN WITH CLASSIC
TRANSMISSION METHOD, WITH THE SAME PARAMETERS OF LOW
VOLTAGE LINES UNDER STANDARD EN 50160
•
THERE ARE NO HARMONICS AND THERE IS BETTER PROTECTION OF
POWER LINE
BENEFITS OF “VROT 18 -1” USED
IN LOW VOLTAGE SINGLE PHASE POWER LINES - CONTINUED
•
CONSERVATIVE ESTIMATE: 30% LOWER CAPITAL INVESTMENT THAN
WITH STANDARD INDUSTRY PRACTICE
•
FAST, SIMPLE AND FLEXIBLE INSTALLATION OF VROT -18
•
VROT -18 DOES NOT NEED LARGE SPACE FOR INSTALLATION AND
NO MAINTENANCE REQUIREMENTS
•
SERVICE LIFE IS 20+ YEARS
•
WARRANTY IS 24 MONTHS FROM THE DELIVERED DATE TO THE END
USER
Example VROT 18-1 used in Europe
INSTALLED VROT 18-1
•
Nacin ugradnje
INSTALLED VROT 18-1
• ugradnja
Voltage results prior to installation of three phase VROT at
Velika Gorica, Zagreb, Croatia, original document in Croatian
(see red highlighted text translated in English)
Faze
L1, L2, L3
< 20
ms
20 < 100
ms
100 < 500
ms
0,5 < 1
s
1<3
s
3 < 20
s
20 < 60
s
>= 1
min
Prenapon>10%
1
-
-
-
-
-
-
-
Propad<10 %
-
-
-
-
-
-
-
-
10 < 15 %
700
223
34
4
1
2
-
-
15 < 30 %
-
8
5
3
2
-
-
-
30 < 60 %
-
-
1
-
-
-
-
-
60 < 99 %
-
-
-
-
-
-
-
-
Prekid
-
-
-
-
-
-
3
-
Snimanje dogañaja izvan intervala –10/+10 % nominalne vrijednosti
Broj prenapona: (NUMBER OF OVERVOLTAGES) 1
Broj propada:
(NUMBER UNDER VOLTAGES)
983
Broj prekida: (NUMBER OF POWER BREAKS)
3
Ukupno dogañaja i prekida: (TOTAL)
987 > 100
Norma određuje mjerni period od sedam dana, odnosno 168 sati bez
prestanka, a mjerni intervali unutar kojih se posmatraju pojedini parametri
su trajanja 10 minuta (1008 10-min intervala u tjednu), osim za
frekvenciju koja se posmatra u vremenskim isječcima od 10 s i napone
signalizacije koji se posmatraju u vremenskim isječcima od 3 s. Norma
postavlja fiksno one vrijednosti kao granične, koje ne smiju biti
prekoračene 95 % vremena monitoringa (za frekvenciju je to 99,5 %
vremena, a za napone signalizacije 99 % vremena).
Propad/prenapon je svaki prelaz
efektivne vrijednosti poluperiode napona
izvan granice od 230 V ± 10 %
(207-253 V).
Prekid napona je pad efektivne
vrijednosti poluperiode napona ispod
Izvršeno od: mr.sc Irena Šagovac dipl.el.ing. HEP-ODS d.o.o. Zagreb, 05.10.2012
Krunoslav Đurašin, dipl.ing. Rukovoditelj Odjela za vođenje pogona
HEP - OPERATOR DISTRIBUCIJSKOG SUSTAVA d.o.o.
ELEKTRA ZAGREB,10000 ZAGREB, GUNDULIĆEVA 32
Pogon Velika Gorica, Tel: 01/6370058, INT: 273058
1 % nazivnog napona.
Mob: 0038598/499900, VPN: 4837,Email: [email protected], www.hep.hr
Voltage results after installation of three phase VROT at
Velika Gorica, Zagreb, Croatia , original document in Croatian
(see red highlighted text translated in English)
Faze
L1, L2, L3
< 20
ms
20 < 100
ms
100 < 500
ms
0,5 < 1
s
1<3
s
3 < 20
s
20 < 60
s
>= 1
min
Prenapon>10%
1
-
-
-
-
-
-
-
Propad<10 %
-
-
-
-
-
-
-
-
10 < 15 %
700
223
34
4
1
2
-
-
15 < 30 %
-
8
5
3
2
-
-
-
30 < 60 %
-
-
1
-
-
-
-
-
60 < 99 %
-
-
-
-
-
-
-
-
Prekid
-
-
-
-
-
-
3
-
Snimanje dogañaja izvan intervala –10/+10 % nominalne vrijednosti
Broj prenapona: (NUMBER OF OVERVOLTAGES) 26
Broj propada:
(NUMBER UNDER VOLTAGES)
Broj prekida: (NUMBER OF POWER BREAKS)
49
3
Ukupno dogañaja i prekida: (TOTAL)
78 < 100
Norma određuje mjerni period od sedam dana, odnosno 168 sati bez
prestanka, a mjerni intervali unutar kojih se posmatraju pojedini parametri
su trajanja 10 minuta (1008 10-min intervala u tjednu), osim za
frekvenciju koja se posmatra u vremenskim isječcima od 10 s i napone
signalizacije koji se posmatraju u vremenskim isječcima od 3 s. Norma
postavlja fiksno one vrijednosti kao granične, koje ne smiju biti
prekoračene 95 % vremena monitoringa (za frekvenciju je to 99,5 %
vremena, a za napone signalizacije 99 % vremena).
Propad/prenapon je svaki prelaz
efektivne vrijednosti poluperiode napona
izvan granice od 230 V ± 10 %
(207-253 V).
Prekid napona je pad efektivne
vrijednosti poluperiode napona ispod
Izvršeno od: mr.sc Irena Šagovac dipl.el.ing. HEP-ODS d.o.o. Zagreb, 05.10.2012
Krunoslav Đurašin, dipl.ing. Rukovoditelj Odjela za vođenje pogona
HEP - OPERATOR DISTRIBUCIJSKOG SUSTAVA d.o.o.
ELEKTRA ZAGREB,10000 ZAGREB, GUNDULIĆEVA 32
Pogon Velika Gorica, Tel: 01/6370058, INT: 273058
1 % nazivnog napona.
Mob: 0038598/499900, VPN: 4837,Email: [email protected], www.hep.hr
Allowed Voltage on sensitive devices at customers
INSTALLED 3x VROT 18, THREE PHASE 50kVA, SOLUTION FOR
SUBSTATION 10(20)/0.4kV, 50kVA
METRIC DIMENSIONS - VROT 18
Type test for VROT 18
Maximum load transmission
Number of cables
Comparing distance