SECTION 27 1000 INSIDE PLANT CABLE AND EQUIPMENT PART 1 – GENERAL UNLESS NOTED OTHERWISE, "CONTRACTOR" REFERS TO THE TELECOMMUNICATION CONTRACTOR. 1.01 SCOPE A. This section describes the products and execution requirements related to furnishing and installing Category 6 Telecommunications Cabling and Termination Components and related subsystems as part of a Structured Cabling System in several building on the Lincoln University Campus. B. Rack, basket tray and horizontal (station) cabling is covered under this document. C. The contractor shall not disturb the existing cabling infrastructure unless specifically directed to do so by project drawings or by Lincoln University. D. Others will provide the network electronics for the LAN within the MDFs and IDFs and will be responsible for connecting the new cabling infrastructure to the LAN. The Contractor shall be available on site during the crossover to assist with any cabling issues that may occur during the transition. E. This Contractor is responsible for installing all necessary conduits and surface raceway for new technology outlet locations. F. This Contractor is responsible for providing and installing all sleeves through the wall penetrations. G. All cables and related termination, support, and grounding hardware shall be furnished, installed, wired, tested, labeled, and documented by the Contractor, as detailed in the following section(s). H. All cables and related termination, support, and grounding hardware shall be furnished, installed, wired, tested, labeled, and documented by the Contractor, as detailed in the following section(s). 1.02 RELATED WORK A. All work and materials shall conform in every detail to the rules and requirements of the National Fire Protection Association, the National Electrical Code, and present manufacturing standards. B. All materials shall be listed by UL and shall bear the UL label. If UL has no published standards for a particular item, then other national independent testing standards shall apply and such items shall bear those labels. Where UL has an applicable system listing and label, the entire system shall be so labeled. C. Other applicable standards are as follows: 1. ANSI/IEEE C2 – National Electrical Safety Code 2. NFPA 70-1996/1999 – National Electrical Code 3. TIA/EIA 568-B-1, 2, 3 Standards 4. IEEE/ANSI 142-1982 – Recommended Practice for Grounding of Industrial and Commercial Power Systems 5. ASTM B633 – Specification for Electrodeposited Coatings of Zinc on Iron and Steel 6. ASTM A653 – Specification for Steel Sheet, Zinc-Coated (Galvanized) by the Hot Dip Process 7. ASTM A123 – Specification for Zinc (Hot Galvanized) Coatings on Iron and Steel 8. ASTM A510 – Specification for General Requirements for Wire Rods and Coarse Round Wire, Carbon Steel INSIDE PLANT CABLE AND EQUIPMENT 27 1000 - 1 1.03 SUBMITTALS A. Submit five (5) sets of shop drawings for all materials proposed. Two (2) of these sets will be returned to the Contractor. Submittals shall be sent to Lincoln University OIT for review and approval. 1. Detail Drawings: Detail drawings include a complete list of equipment and material. Detail drawings shall contain complete wiring and schematic diagrams and other details required to demonstrate that the system has been coordinated and will function properly as a system. Drawings shall include equipment rack details, elevation drawings of telecommunications closet walls, and outlet faceplate details for all outlet configurations, sizes, and types of all cables. Drawings shall show proposed layout and anchorage of equipment and appurtenances, as well as equipment relationship to other parts of the work, including clearance for maintenance and operation. 2. Manufacturer’s Recommendations a. Where installation procedures or any part thereof are required to be in accordance with the recommendations of the manufacturer of the material being installed, printed copies of these recommendations shall be provided prior to installation. Installation of the item will not be allowed to proceed until the recommendations are received and approved. 1.04 RECORD DRAWING AND DOCUMENTATION A. Upon completion of the installation, the contractor shall provide three (3) full documentation sets to Lincoln University OIT for approval. Documentation shall include the items detailed in the subsections below. B. Documentation shall be submitted within five (5) working days of the completion of each testing phase (subsystem, cable type, area, floor, etc.). This is inclusive of all test results and draft as-built drawings. Draft drawings may include annotations done by hand. Machine generated (final) copies of all drawings shall be submitted within twenty (20) working days of the completion of each testing phase. C. The Contractor shall provide copies of the original test results. D. All documentation, including hard copy and electronic forms, shall become the property of Lincoln University OIT. E. Lincoln University OIT may request that a 10% random field re-test be conducted on the cable system—at no additional cost—to verify documented findings. F. Tests shall be a repeat of those defined above and under Testing and Acceptance. If findings contradict the documentation submitted by the Contractor, additional testing can be requested to the extent determined necessary by Lincoln University OIT, including a 100% re-test. This re-test shall be at no additional cost to Lincoln University. 1.05 TEST DATA – COPPER MEDIA A. The test result records saved by the tester shall be transferred into a Windows-based database utility that allows for the maintenance, inspection, and archiving of these test records. A guarantee shall be made that these results are transferred to the PC unaltered, i.e., “as saved in the tester” at the end of each test. Comma separated value (CSV) format is not acceptable. B. The database for the completed job – including twisted-pair copper cabling links, if applicable –shall be stored and delivered on CD-ROM. This CD-ROM shall include the software tools required to view, inspect, and print any selection of test reports. C. A paper copy of the test results shall be provided that lists all the links that have been tested with the following summary information: 1. The identification of the link in accordance with the naming convention defined in the overall system documentation. 2. The overall Pass/Fail evaluation of the copper channel-under-test, including the NEXT worst-case margin (margin is defined as the difference between the measured value and the test limit value). INSIDE PLANT CABLE AND EQUIPMENT 27 1000 - 2 3. 4. The overall Pass/Fail evaluation of the fiber link-under-test, including the Attenuation worst-case margin (margin is defined as the difference between the measured value and the test limit value). The date and time the test results were saved in the memory of the tester. 1.06 STATEMENTS A. Ten (10) days prior to the proposed test date, Contractor shall provide a test plan defining the tests required, ensuring that the system meets Owner operational and performance specifications. The test plan shall be approved before the start of any testing. The test plan shall identify the capabilities and functions to be tested, and must include detailed instructions for the setup and execution of each test and procedures for evaluation and documentation of the results. 1.07 CERTIFICATES A. Premises Distribution System: Written certification that the premises distribution system complies with the EIA ANSI/TIA/EIA-568B-1, 2, 3, EIA ANSI/TIA/EIA-569A, and EIA ANSI/TIA/EIA-606. B. Materials and Equipment: Where materials or equipment are specified to conform, be constructed, or be tested to meet specific requirements, certification that the items provided conform to such requirements. Certification by a nationally recognized testing laboratory (NRTL) that a representative sample has been tested to meet the requirements, or a published catalog specification statement to the effect that the item meets the referenced standard, will be acceptable as evidence that the item conforms. Compliance with these requirements does not relieve the Contractor from compliance with other requirements of the specifications. C. Installers 1. The Contractor shall have an RCDD (Register Communication Distribution Designer) on staff assigned to manage this project; documented proof of having an RCDD on staff shall accompany the proposal response. 2. All installing personnel shall have completed certified manufacturer training or BICSI (Building Industry Consulting Service International) installation training for UTP infrastructure systems, or the Contractor shall contract with manufacturer for installation of all proposed components. Company Certifications shall accompany the proposal response. 3. The Contractor shall submit certification that all the installers are factory certified to install and test the provided products. No less than half of the crew to be used for the telecommunications installation shall be trained by that manufacturer for the work. 1.08 DELIVERY, STORAGE, AND HANDLING A. Vendor will be responsible for all materials until completion of project. B. Cable shall be stored according to manufacturer’s recommendations at minimum. In addition, cable must be stored in a location protected from vandalism and weather. C. If cable is stored outside, it shall be covered with opaque plastic or canvas with provision for ventilation to prevent condensation and for protection from weather. If air temperature at cable storage location will be below 40 degrees Fahrenheit, the cable shall be moved to a heated (minimum 50 degrees Fahrenheit) location. If necessary, cable shall be stored off site at the contractor’s expense. D. If the contractor proposes to have a trailer on site for storage of materials, arrangements shall be made with Lincoln University OIT. E. Commercial off-the-shelf manuals shall be furnished for operation, installation, configuration, and maintenance for all products provided as a part of the premises distribution system. Specification sheets for all cable, connectors, and other equipment shall be provided. INSIDE PLANT CABLE AND EQUIPMENT 27 1000 - 3 1.09 WARRANTY A. The Contractor shall guarantee all materials, equipment, etc., for one year from date of Substantial Completion of this work. This guarantee shall include all labor, materials, and travel time. 1.10 CODE REQUIREMENTS A. ANSI/IEEE C2 National Electrical Safety Code B. NFPA 70-1990 National Electrical Code 4 C. EIA/TIA Standards PART TWO – PRODUCTS 2.01 HORIZONTAL COPPER CABLES A. All cables and equipment shall be furnished, tested, installed and wired by the Contractor. 1. All horizontal data cables shall terminate on modular patch panels in the telecommunications closet as specified on the drawings. 2. This specification defines the requirements for commercially available high performance Category 6 cable. 3. This cable shall be suitable for installation free-air, in building risers, in conduit, and/or in cable tray and shall carry CMP rating. 4. The cable design described herein shall exceed transmission performance of Category 6 cables. 5. Cables shall be Underwriters Laboratory (UL) listed, comply with Article 800 (Communications Circuits) of the National Electrical Code, and meet the specifications of NEMA (low loss), UL 444, and ICEA. Conductor shall also conform to the requirements for solid annealed copper wire in accordance with ASTM B 3. 6. All cables, termination components, and support hardware shall be furnished, tested, installed, and wired by the Contractor. 7. The contractor shall use blue cable for data and white cable for voice. B. IMPORTANT: Cable and termination components (jack, patch panel, wiring blocks) are specified to function as a system. The compatibility of the cable to be installed with the proposed termination components shall be recognized and documented by the termination component manufacturer. C. Category 6 cables shall be Berk-Tek Lanmark 1000, General CommandLinx, or approved equal by Mohawk. 2.02 INFORMATION OUTLET A. General 1. Station cables shall each be terminated at their designated workstation location in the connector types described in the subsections below. Included are modular jacks and faceplates. The combined assembly is referred to as the Standard Information Outlet (SIO). These connector assemblies shall snap into a mounting frame. 2. The telecommunications outlet frame shall accommodate or incorporate the following: a. A minimum of four (4) modular jacks, when installed on a wall-mounted assembly. b. A mechanism for adjusting the surface plate to a plumb position. 3. Multiple jacks are identified in close proximity on the drawings. The Contractor shall be responsible for determining the optimum compliant configuration based on the products proposed. 4. The same orientation and positioning of jacks and connectors shall be utilized throughout the installation. Prior to installation, the Contractor shall submit the proposed configuration for each SIO type for review by Lincoln University OIT. B. Outlet Faceplates 1. Faceplates shall be plastic and incorporate recessed designation strips at the top and bottom of the frame for identifying labels. Designation strips shall be fitted with clear plastic covers. INSIDE PLANT CABLE AND EQUIPMENT 27 1000 - 4 2. 3. 4. 5. C. Any unused jack positions shall be fitted with a removable blank inserted into the opening. Modular jacks shall have capability to incorporate a dust cover that fits over and/or into the jack opening. The dust cover shall be designed to remain with the jack assembly when the jack is in use. No damage to the jack pinning shall result from insertion or removal of these covers. Dust covers that result in deformation of the jack pinning shall not be accepted. All standard information outlets and the associated jacks shall be of the same manufacturer throughout each building. Faceplates shall be manufactured by Ortronics or Panduit. Surface Mount Interface Box 1. Low profile, surface mount boxes shall incorporate recessed designation strips at the top for identifying labels. Designation strips shall be fitted with clear plastic covers. 2. The box shall feature built-in cable management for both fiber and copper applications. 3. Any unused jack positions shall be fitted with a removable blank inserted into the opening. 4. Modular jacks shall have capability to incorporate spring-loaded shutter door for added protection from dust and other airborne contaminants. The dust cover shall be designed to remain with the jack assembly when the jack is in use. 5. The box shall have the capability to incorporate optional magnets that can be internally mounted. 6. Surface mount box shall be manufactured by Ortronics or Panduit. 2.03 MODULAR JACK A. Data jacks shall be non-keyed 8-pin modular jacks. B. Termination components shall be designed to maintain the cable’s pair twists as closely as possible to the point of mechanical termination. C. Jacks shall utilize a four-layer printed circuit board to control NEXT. D. Jack housings shall fully encase and protect printed circuit boards and IDC fields. E. Modular jack contacts shall accept 2500 plug insertions. F. Modular jack contacts shall be formed flat for increased surface contact with mated plugs. These contacts shall be arranged on the PC board in two staggered arrays of four to maximize contact spacing and minimize crosstalk. G. Modular jack contacts shall be constructed of Beryllium copper for maximum spring force and resilience. H. Contact Plating shall be a minimum of 50 micro inches of gold in the contact area over 50 micro-inch of nickel, compliant with FCC part 68.5. I. Jack termination shall be110 IDC, integral to the jack housing, laid out in two arrays of four contacts. J. Jacks shall utilize a paired punch down sequence. Cable pairs shall be maintained up to the IDC, terminating all conductors adjacent to its pair mate to better maintain pair characteristics designed by the cable manufacturer. K. Jacks shall utilize tin lead plated (60% tin/40%lead) phosphor bronze 110 insulation displacement contacts. L. Jacks shall terminate 22-26 AWG stranded or solid conductors. M. Jacks shall terminate insulated conductors with outside diameters up to .050”. N. Jacks shall be compatible with single conductor 110 impact termination tools. O. Jacks shall include translucent wire retention stuffer caps to hold terminated wires in place while allowing to conductors to be viewed in the IDC housing. Stuffer caps may also be used for wire termination with parallel jaw pliers. P. Jacks shall be compatible with EIA/TIA 606 color code labeling and accept snap on icons for identification or designation of applications. Q. Data jacks shall be ORANGE in color. INSIDE PLANT CABLE AND EQUIPMENT 27 1000 - 5 R. Voice jacks shall be BLUE in color. S. Jacks shall be terminated and marked as T568B wiring. T. Category 6 jacks shall be manufactured by Ortronics or Panduit. 2.04 FIBER OPTIC CONNECTORS A. The optical connector shall be SC-type (bayonet mount) for Single-Mode fiber and ST-type for fiber. B. The connector ferrule shall be ceramic or glass-in-ceramic. The optical fiber within the connector ferrule shall be secured with an adhesive. C. The attenuation per mated pair shall not exceed 0.35 dB (individual) and 0.2 dB (average). Connectors shall sustain a minimum of 200 mating cycles per EIA/TIA-455-21 without violating specifications. D. The connector shall meet the following performance criteria: 1. Test Procedure Max. Attenuation Change 2. Cable Retention (FOTP-6) 0.2 dB 3. Durability (FOTP-21) 0.2 dB 4. Impact (FOTP-2) 0.2 dB 5. Thermal Shock (FOTP-3) 0.2 dB 6. Humidity (FOTP-5) 0.2 dB 2.05 CABLE MANAGEMENT SYSTEM A. The cable management system shall be used to provide a neat and efficient means for routing and protecting fiber and copper cables and patch cords on telecommunication racks and enclosures. The system shall be a complete cable management system comprising enclosed, lockable floor mount racks and vertical and horizontal cable managers to manage cables on both the front and rear of the rack. The system shall protect network investment by maintaining system performance, controlling cable bend radius, and providing cable strain relief. B. MDF Enclosed, Lockable Racks 1. Unless otherwise noted on the project drawings, at the MDF room the Contractor shall provide and install enclosed, lockable equipment racks to house cable termination components (e.g., copper data and fiber optic) and network electronics (by others). Prior to installation, the Contractor shall coordinate exact placement with LU OIT. 2. The rack shall conform to the following requirements: a. Rack shall be 84" in height and shall be self-supporting. b. Channel uprights shall be spaced to accommodate industry standard 19" mounting and have pass-through holes with smooth edges to protect cables. c. Rack must be constructed of aluminum. d. Rack shall be double side drilled and tapped to accept 12-24 screws. Uprights shall also be drilled on back to accept cable brackets, clamps, power strip(s), etc. Hole pattern on rack front shall be per EIA/TIA specifications (5/8"-5/8"-1/2"). Hole pattern on the rear shall be at 3" intervals to accept cable brackets. e. Rack should be supplied with at least 24 spare screws. f. Rack should be supplied with a ground bar and #6 AWG ground lug. g. Equipment rack shall be Homaco 19-84-T2SD-FT*B. C. Vertical Cable Management 1. At the telecommunication rooms, vertical cable management shall be furnished and installed to adjacent racks to organize cables on front and rear of telecommunication racks. 2. Vertical cable managers shall include components that aid in routing, managing, and organizing cable to and from equipment. Panels shall protect network equipment by controlling cable bend radius and providing cable strain relief. Panels shall be a universal design mounting to EIA 19" or 23" racks. 3. Vertical cable management system shall feature the following: INSIDE PLANT CABLE AND EQUIPMENT 27 1000 - 6 a. 4. Open cabling section on the rear that provides easy access and routes cable bundles feeding into the back of patch panels and 1 RMU cable guide on the front designed for fanning and managing patch cords. b. Edge-protected pass-through ports designed for easy routing of cable from front channel to back. c. Vertical slots along the center separator to allow securing cable bundles neatly with management straps. d. Door/cover (front only) that is easily opened from the right or left and still easily removed to allow for quick moves, adds, and changes. e. Movable wire retainers to retain the cables during cover removal. Vertical cable management shall be CPI part # 30162-703. 2.06 HORIZONTAL CABLE MANAGEMENT A. Horizontal cable managers shall include components that aid in routing, managing, and organizing cable to and from equipment. Panels shall protect network equipment by controlling cable bend radius and providing cable strain relief. Panels shall be a universal design mounting to EIA 19" racks and constructed of steel bases with PVC duct attached. The duct fingers shall include retaining tabs to retain the cables in place during cover removal. The covers shall be able to hinge from either side yet still be easily removed to allow for quick moves, additions and changes. B. The cable managers shall be provided with movable wire retainers to retain the cables during cover removal and #12-24 mounting screws. An integral strain relief bracket shall be provided on either end of the duct to allow for easy cover placement. C. Horizontal cable managers shall be placed above and below each patch panel. The Contractor shall also supply eight (8) additional managers for network electronics (electronics provided by others). D. Horizontal cable management shall be Chatsworth part # 30130-719. 2.07 FIRE STOPPING MATERIALS A. All penetrations of firewalls shall be approved by the General Contractor before any penetrations are made. Should the Contractor find it necessary to penetrate any walls extending to the slab, it will be the responsibility of that Contractor to provide satisfactory sleeving and fire caulking both inside and outside of that sleeving. B. The Contractor is responsible for adhering to the following standards: 1. Conduit penetrations through fire-rated or smoke walls: Completely seal around the conduit penetration with Hilti FS 601 fire-rated sealant Tremco or 3M or approved equal. 2. Conduit sleeves through fire-rated or smoke wall: Completely seal around the conduit penetration with Hilti FS 601 fire-rated sealant Tremco or 3M or approved equal. Completely seal inner opening of the conduit sleeve with fire wool packing and Hilti FS 611A intumescent firestop sealant. 3. Cable bundles through fire-rated or smoke walls (without sleeves): Completely seal openings with Hilti FS 611A intumescent firestop sealant, Tremco or 3M or approved equal. C. A submitted response to this specification assumes that all firestopping will be provided as specified. The firestop manufacturer’s specifications and instructions shall be submitted with the final documentation. 2.08 CABLE HOOK SYSTEMS A. In the areas where the cables are required to be run above accessible ceilings in a “free-air” air handling plenum or in spaces having an exposed structure ceiling, a cable hook system shall be used. B. Cable hooks shall be capable of supporting a minimum of 30 lbs with a safety factor of 3. C. Spring steel cable hooks shall be capable of supporting a minimum of 100 lbs with a safety factor of 3 where extra strength is required. INSIDE PLANT CABLE AND EQUIPMENT 27 1000 - 7 D. Follow manufacturer’s recommendations for allowable fill capacity for each size of cable hook. E. Installation and configuration shall conform to the requirements of the ANSI/ EIA/TIA Standards 568A & 569, NFPA 70 (National Electrical Code), and applicable local codes. F. Cable hooks shall: 1. Have a flat bottom and provide a minimum of 1 5/8" cable bearing surface. 2. Have 90-degree radiused edges to prevent damage while installing cables. 3. Be designed so the mounting hardware is recessed to prevent cable damage. 4. Have a stainless steel cable latch retainer to provide containment of cables within the hook. 5. Have a retainer that shall be removable and reusable. 6. Be factory assembled for direct attachment to walls, hanger rods, beam flanges, purlins, strut, and floor posts, to meet construction conditions. G. Factory assembled, multi-tiered cable hooks shall be used where required to provide separate cabling compartments, or where additional capacity is needed. H. Cable hooks for non-corrosive areas shall be pre-galvanized steel, ASTM A653 G90. Where additional strength is required, cable hooks shall be spring steel with a zinc-plated finish, ASTM B633, SC3. I. Cable hooks for corrosive areas shall be stainless steel, AISI type 304. J. Cable hooks shall be B-Line series BCH21, BCH32 or approved equivalent products by other manufacturers that meet these specifications. 2.09 TWISTED PAIR TEST EQUIPMENT A. Test equipment used under this contract shall be from a manufacturer who has a minimum of five years experience in producing field test equipment. Manufacturers must be ISO 9001 certified. B. All test tools of a given type shall be from the same manufacturer and have compatible electronic results output. Test adapter cable shall be approved by the manufacturer of the test equipment. Baseline accuracy of the test equipment must exceed TIA Level III, as indicated by independent laboratory testing. C. Test equipment must: 1. Be capable of certifying Category 5, 5E, and 6 permanent links. 2. Have a dynamic range of at least 100dB to minimized measurement uncertainty. 3. Be capable of storing full frequency sweep data for all tests and printing color graphical reports for all swept measurements. 4. Include S-band time domain diagnostics for NEXT and return loss. 5. Be capable of running individual NEXT, return loss, etc., measurements in addition to AutoText. 6. Include a library of cable types, stored by major manufacturer. 7. Store at least 1000 Category 5e or 6 autotests in internal memory. D. The measurement reference plane of the test equipment shall start immediately at the output of the test equipment interface connector. There shall not be a time domain dead zone of any distance that excludes any part of the link from the measurements. E. The approved manufacturer of the test equipment is Fluke/Microtest. PART THREE – EXECUTION 3.01 EXAMINATION A. Verification of Conditions: Examine areas and conditions under which work is to be performed and identify conditions detrimental to proper and timely completion. B. Verify cable lengths comply with published standards. C. Notify Owner of installation that would exceed maximum lengths prior to installation of cable. D. Contactor shall consult with Owner regarding alternative routing or location of cable. INSIDE PLANT CABLE AND EQUIPMENT 27 1000 - 8 E. Do not proceed until unsatisfactory conditions have been corrected. 3.02 INSTALLATION REQUIREMENTS A. Contractor shall furnish, install and connect all cables, connectors, and equipment as shown on drawings and as specified above. B. It is the Contractor’s responsibility to survey the site and include all necessary costs to perform the installation as specified. This includes any modifications required to route and conceal horizontal distribution wiring. C. Beginning installation means contractor accepts all applicable terms and conditions. D. Contractor shall provide all required installation tools to facilitate cable pulling without damage to the cable jacket. Such equipment is to include, but not be limited to, sheaves, winches, cable reels, cable reel jacks, duct entrance tunnels, pulling tension gauge, and similar devices. All equipment shall be of substantial construction to allow steady progress once pulling has begun. Makeshift devices that may move or wear in a manner to pose a hazard to the cable shall not be used. E. All cable shall be pulled by hand unless installation conditions require mechanical assistance. Where mechanical assistance is used, care shall be taken to ensure that the maximum tensile load for the cable as defined by the manufacturer is not exceeded. This may be in the form of continuous monitoring of pulling tension, use of a “break-away,” or other approved method. F. Where unacceptable conditions are found, the Contractor shall bring this to the attention of the construction supervisor immediately. A written resolution will follow to determine the appropriate action to be taken. G. Qualified personnel utilizing state-of-the-art equipment and techniques shall provide all installation work. During pulling operation, an adequate number of workers shall be present to allow cable observation at all points of duct entry and exit as well as to feed cable and operate pulling machinery. H. Cable pulling shall be done in accordance with cable manufacturer’s recommendations and ANSI/IEEE C2 standards. Manufacturer’s recommendations shall be a part of the cable submittal. Recommended pulling tensions and pulling bending radius shall not be exceeded. Any cable bent or kinked to radius less than recommended dimension shall not be installed. I. All wiring shall be run “free-air,” in conduit, in a secured plastic raceway or in modular furniture as designated on the drawings. All cable shall be free of tension at both ends. PLENUM rated cable MUST be used in areas used for air handling plenums. J. Avoid abrasion and other damage to cables during installation. K. Pulling lubricant may be used to ease pulling tensions. Lubricant shall be of a type that is non-injurious to the cable jacket and other materials used. Lubricant shall not harden or become adhesive with age. L. The cable system shall be tested and documented upon completion of the installation as defined in the section below. M. A pull cord (nylon; 1/8” minimum) shall be co-installed with all cable installed in any conduit. Should it be found by Lincoln University OIT that the materials or any portion thereof furnished and installed under this contract fail to comply with the specifications and drawings with the respect or regard to the quality, amount of value of materials, appliances, or labor used in the work, it shall be rejected, removed, and replaced by the Contractor and all work distributed by changes necessitated in consequence of said defects or imperfections shall be corrected at the Contractor’s expense. 3.03 CABLE SUPPORT A. J-hooks fabricated to contain data/voice and video cables may be used to support 25 or fewer cables in each hook. J-hooks are to be fastened to building steel with beam clamps, suspended from ceiling slab with threaded rod, or anchored to the wall. All J-hooks are to be hung straight and level. No other installation technique will be authorized unless pre-approved. INSIDE PLANT CABLE AND EQUIPMENT 27 1000 - 9 B. Three tiered double-sided J-hook configurations shall contain a maximum of 25 cables per hook or 150 cables. Smaller configurations may be used as bundles decrease in size, maintaining no more than 25 cables per hook. C. Bundles surpassing 150 cables must be supported by hangers, fabricated of 3/8” threaded rod and 24” Unistrut. Hangers must also be installed where the installation of a three-tiered J-hook system is not appropriate for the ceiling space, or where blocked by other trades’ work. D. Cable bundles consisting of fewer than 10 cables may be supported by bridle rings or D-rings. E. All cable support in the main cable path shall be installed every four feet. Small cable bundles (under 25) not in the main path shall be supported every five feet. F. A sag shall be maintained between supports of 6”, to reduce cable strain. G. Tywraps are appropriate methods of securing cables, when properly used and not over tightened. Over tight Tywraps dent and pinch the cable jackets and shall not be allowed. Tywraps installed in air handling plenums shall be plenum rated. H. Proper cable support is extremely important to Lincoln University OIT, and care shall be taken by the Contractor to provide and install the appropriate supports. Supports found to be inadequate shall be replaced. 3.04 INFORMATION OUTLET A. Information outlets shall be flush mounted on wall-mounted boxes, in floor-mounted boxes, and on modular furniture. Any outlets to be added where these conditions are not met shall be positioned at a height matching that of existing services or as directed otherwise by the Site Coordinator and Lincoln University OIT. B. The Contractor is to coordinate the style of the telecommunication outlets to be installed in the floor mount boxes and surface mount raceways with Lincoln University OIT. 3.05 CABLE TERMINATION A. At the telecommunication closets, all data and voice cables shall be positioned on termination hardware in sequence of the outlet ID, starting with the lowest number. B. Termination hardware (blocks and patch panels) positioning and layout must be reviewed and approved by Lincoln University OIT prior to construction. The review does not exempt the Contractor from meeting any of the requirements stated in this document. C. Cable Termination – Data/Voice UTP 1. Data/voice patch panels shall be designed and installed in a fashion as to allow future station cabling to be terminated on the panel without disruption to existing connections. 2. Data patch panels shall be sized to accommodate a minimum of 20% growth in the quantity of stations relative to the initial installation. 3. At information outlets and data/voice patch panels, the installer shall ensure that the twists in each cable pair are preserved to within 0.5 inch of the termination for data/voice cables. The cable jacket shall be removed only to the extent required to make the termination. D. Cable Termination – Fiber Optic 1. All fibers shall be terminated using the specified connector type. Single Mode fiber will be terminated with SC connectors. Multi Mode fiber will be terminated with ST connectors. 2. All terminated fibers at the telecommunications closets shall be mated to couplings mounted on patch panels. Couplings shall be mounted on a panel that, in turn, snaps into the housing assembly. Any unused panel positions shall be fitted with a blank panel inhibiting access to the fiber optic cable from the front of the housing. 3. All couplings shall be fitted with a dust cap. 4. Fibers from multiple locations may share a common enclosure, but they shall be segregated on the connector panels and clearly identified. Fibers from multiple destinations shall be secured in a common enclosure, provided they are clearly identified INSIDE PLANT CABLE AND EQUIPMENT 27 1000 - 10 5. 6. as such. Fibers from different locations shall not share a common connector panel (e.g., “insert”). Slack in each fiber shall be provided as to allow for future re-termination in the event of connector or fiber end-face damage. Adequate slack shall be retained to allow termination at a 30” high workbench positioned adjacent to the termination enclosure(s). A minimum of one meter (~39”) of slack shall be retained regardless of panel position relative to the potential work area. Contractor shall install a plastic twist-on bushing on each end of interlocking armored fiber to protect cable from sharp edges of the armor. 3.06 COOPERATION A. The Contractor shall cooperate with other trades and Lincoln University OIT’s personnel in locating work in a proper manner. B. Should it be necessary to raise, lower, or move longitudinally any part of the work to better fit the general installation, such work shall be done at no extra cost to Lincoln University OIT, provided such decision is reached prior to actual installation. C. The Contractor shall coordinate the location of electrical outlets with respect to other installations before installing. 3.07 TESTING AND ACCEPTANCE A. The Contractor is responsible for performing acceptance tests as indicated below for each subsystem (backbone, station, etc.) as it is completed. B. The Contractor is responsible for supplying all equipment and personnel necessary to conduct the acceptance tests. Prior to testing, the Contractor should provide a summary of the proposed test plan for each cable type, including equipment to use, setup, test frequencies or wavelengths, results format, etc. Lincoln University OIT shall approve the method of testing. C. The Contractor shall visually inspect all cabling and termination points to ensure that they are complete and conform to the wiring pattern defined herein. The Contractor shall provide Lincoln University OIT with a written certification that this inspection has been made. D. The Contractor shall conduct acceptance testing according to a schedule coordinated with Lincoln University OIT. Representatives of Lincoln University OIT may be in attendance to witness the test procedures. The Contractor shall provide a minimum of one (1) week advance notice to Lincoln University OIT and Owner as to allow for such participation. The notification shall include a written description of the proposed conduct of the tests, including copies of blank test result sheets to be used. E. Tests related to connected equipment of others should be done only with the permission and presence of Contractor involved. The Contractor shall ascertain that testing only as required to prove the wiring connections are correct. F. The Contractor shall provide test results and describe the conduct of the tests, including the date of the tests, the equipment used, and the procedures followed. At the request of Lincoln University OIT, the Contractor shall provide copies of the original test results. G. All cabling shall be 100% fault free unless noted otherwise. If any cable is found to be outside the specification defined herein, that cable and the associated termination(s) shall be replaced at the Contractor’s expense. The applicable tests shall then be repeated. 3.08 COPPER STATION CABLES A. Station cabling testing shall be from the jack at the outlet in the work area to the termination block on which the cables are terminated at the MDF or IDF. B. Testing shall be of the permanent link. Contractor shall warrant performance, however, based on channel performance and provide patch cords that meet channel performance criteria. All cabling not tested strictly in accordance with these procedures shall be retested at no cost to Lincoln University OIT. C. Testing shall be from the jack at the SIO to the patch panel on which the cables are terminated at the wiring hub. INSIDE PLANT CABLE AND EQUIPMENT 27 1000 - 11 D. Horizontal “station” cables shall be free of shorts within the pairs and shall be verified for continuity, pair validity and polarity, and wire map (conductor position on the modular jack). Any defective, split, or mis-positioned pairs must be identified and corrected. E. Testing of the cabling systems rated at TIA Category 6 and above shall be performed to confirm proper functioning and performance. F. Testing of the transmission performance of station cables (Category 6) shall include the following: 1. Length 2. Attenuation 3. Pair to Pair NEXT 4. ACR 5. PSNEXT Loss 6. Return Loss 7. Pair to Pair ELFEXT Loss (Equal Level Far End Cross-Talk) 8. PSEFEXT Loss 9. Propagation Delay 10. Delay Skew 11. Return Loss G. The maximum length of station cable shall not exceed 90 meters, which allows 10 meters for equipment and patch cables. CATEGORY 6 (Permanent LINK) Frequency (MHz) Insertion Loss (Maximum dB) NEXT Loss Pair to Pair (dB) PS-NEXT Loss (dB; Worst Case) ELFEXT Loss Pair to Pair (dB) PSELFEXT loss (dB) 1.9 65.0 62.0 64.2 61.2 3.5 64.1 61.8 52.1 49.1 5.6 57.8 55.5 44.2 41.2 7.0 54.6 52.2 40.1 37.1 8.9 51.5 49.1 36.2 33.2 10.0 50.0 47.5 34.3 31.3 16.0 45.1 42.7 28.3 25.3 18.5 41.8 39.3 24.2 21.2 27.1 36.9 34.3 18.2 15.2 30.7 35.3 32.7 16.2 13.2 H. In the event results of the tests are not satisfactory, the Contractor shall make adjustments, replacements, and changes as necessary and shall then repeat the test or tests that disclosed faulty or defective material, equipment, or installation method. The Contractor shall make additional tests as the Engineer deems necessary at no additional expense to Lincoln University OIT or Consultant. I. All data shall indicate the worst-case result, the frequency at which it occurs, the limit at that point, and the margin. These tests shall be performed in a swept frequency manner from 1 MHz to highest relevant frequency, using a swept frequency interval that is consistent with TIA and ISO requirements. Information shall be provided for all pairs or pair combination and in both directions when required by the appropriate standards. J. Cables shall be tested to the maximum frequency defined by the standards covering that performance category. END OF SECTION INSIDE PLANT CABLE AND EQUIPMENT 27 1000 - 12 SECTION 27 1003 OUTSIDE-PLANT CABLE AND EQUIPMENT PART 1 – GENERAL UNLESS NOTED OTHERWISE, “CONTRACTOR” SHALL REFER TO THE TELECOMMUNICATION CONTRACTOR. LU SHALL REFER TO LINCOLN UNIVERSITY AND ITS STAFF. 1.01 RELATED DOCUMENTS A. Drawings and provision of the Contract, including the General and Supplementary General Conditions, and Special Conditions, apply to this section. B. All work and materials shall conform in every detail to the rules and requirements of the National Fire Protection Association, the National Electrical Code and present manufacturing standards. C. All materials shall be listed by UL and shall bear the UL label. If UL has no published standards for a particular item, then other national independent testing standards shall apply and such items shall bear those labels. Where UL has an applicable system listing and label, the entire system shall be so labeled. D. Other applicable standards are as follows: 1. ANSI/IEEE C2 - National Electrical Safety Code 2. NFPA 70-1999 - National Electrical Code 3. TIA/EIA Standards 4. IEEE/ANSI 142-1982 - Recommended Practice for Grounding of Industrial and Commercial Power Systems 5. EIA 445 Fiber Optic Test Procedures (FOTP) 1.02 SUMMARY OF WORK A. The contract includes providing a turnkey infrastructure outside plant fiber optic cabling system consisting of single mode fiber optic cable, conduits inside building and conduit outside buildings. B. The Single Mode (SM) outside plant rated cable shall be transitioned to Plenum rated cable within 50’ of the building penetration point. The plenum cable shall be installed to the MDF as identified on the project drawings. In lieu of this transition, the contractor may install EMT conduit from the building penetration point to the MDF termination point. C. The fiber optic cable shall be installed in conduit. The primary method of installation of the conduit is to be trenching and directional boring. D. LU understands that it owns and will be responsible for the cable upon acceptance of installation. Once the installation has been accepted, LU will be responsible for any repairs to the cable necessitated by accidents, fires, or other natural disasters. LU may request the services of the successful Contractor to accomplish repairs at the hourly cost to be quoted hereinafter. 1.03 SUBMITTALS A. Detail drawings including a complete list of equipment and material. Detail drawings shall contain complete route and schematic diagrams and other details required to demonstrate that the system has been coordinated and will function properly as a system. Drawings shall identify proposed route and anchorage of equipment and appurtenances, and equipment relationship to other parts of the work including clearance for maintenance and operation. 1.04 DELIVERY A. All material shall be delivered to its proper location and installed by the contractor without additional cost or expense to LU, which shall not be deemed to have accepted the system until the Date of Acceptance. OUTSIDE-PLANT CABLE AND EQUIPMENT 27 1003 - 1 B. During the time between delivery and acceptance, LU cannot be held liable for any damages to or theft of any components. It will, therefore, be the responsibility of the contractor to obtain insurance against loss, theft and damage. 1.05 OVERALL REQUIREMENTS A. Any subcontractors hired by the Contractor must meet the qualifications and abide by the requirements of this document. The successful Contractor will be held responsible for any work performed by subcontractors. B. All installations must meet NEC, Rural Electric Code, and NE Safety Code. C. All installations must meet city, county, and state requirements for crossing of all sidewalks and streets. D. All single mode fibers between the buildings are to be sealed, tested, and connectorized. E. Single mode fibers shall terminate on “SC” connectors. F. Multi mode fibers shall terminate on “ST” connectors. 1.06 CONTRACTOR’S RESPONSIBILITIES A. The Contractor is required to install, document and test all systems (procedures are outlined in following sections). B. The Contractor shall be responsible for the acquisition of the appropriate permits, licenses and/or franchises required to occupy the public rights-of-way of the various organizations (city, county, state) involved. The contractor will be authorized by LU to act as its agent for this purpose. It shall be the Contractor’s responsibility to secure and pay for these permits. C. The Contractor shall prepare all necessary documentation required to obtain the required permission from organizations controlling the rights-of-way. This shall include, but shall not be limited to, all drawings, details, letters and/or application forms required by the permitting or authorizing agency. D. The Contractor shall be responsible for establishing grades and elevations, checking of all interference, and shall verify all dimensions and locations in the field. E. When placing buried cable on public right-of-way, permits and state licenses will be generally required for the following: 1. Boring, plowing, trenching, or excavating on public right-of-way. 2. Closing or limiting traffic on a thoroughfare. 3. Attaching conduit or cables to bridges, culverts, or public structures. 4. Storing materials or machinery on public property. 5. Crossing highways, streets, and railroads by direct burial or by pipe pushing/road bores. 6. Crossing streams, navigable waters, drainage ditches, etc. F. The Contractor must re-verify building entrance and telecommunication room locations prior to installation. Prior to the furnishing or installing of any equipment, approval of equipment, locations, layout, and installation shall be obtained from LU OIT. G. The Contractor shall specifically note that the drawings are intended to only indicate in diagram format the extent, general character, and locations of work included. The exact routing of duct shall be determined by the existing structural conditions and other obstructions. H. The locations of equipment, conduits, etc., as shown on the drawings, are correct to the extent permitted by the scale of the drawings, but are subject to such modifications as may be found necessary or desirable at the time of installation in order to meet any structural conditions. Such changes shall be made by the contractor without extra charge, subject to approval of LU. I. The Contractor shall be responsible for fully coordinating all of the various parts of the work included under this document, and such other work of this contract as it may affect the installation, throughout the various phases of construction and before the ordering or fabrication of the various parts of the work, so as to ensure compliance with the drawings and specifications, and as necessary to provide the installations complete and in satisfactory operating condition. OUTSIDE-PLANT CABLE AND EQUIPMENT 27 1003 - 2 J. Shipping delays are the sole responsibility of the Contractor. K. It shall be the responsibility of the Contractor to verify the locations of all equipment such as manholes, handholes, pull boxes, and such other apparatus. The Contractor shall notify LU if the location, as shown on the drawings, conflicts with existing utilities or would make the device inaccessible for future maintenance. In such cases, the Contractor shall alert LU OIT of the condition before advancing the construction to a state where a change will reflect additional expenses. L. The Contractor shall be responsible to provide locating services for outside plant fiber optic cable to others, until Final Acceptance of the project. M. The Contractor will be required to provide notification and receive approval to all occupancies on selected route as to project purpose, scope, start and end dates, and contact for further information or problems. PART 2 – PRODUCTS 2.01 OUTSIDE PLANT UNDERGROUND ARMORED FIBER OPTIC CABLE A. Armored Fiber Optic Cable shall incorporate a corrugated Steel Armor Tape to provide for resistance to rodent attack and all other cable materials shall be all dielectric (no conductive materials). B. Armored Fiber Optic Cable shall be filled with a water-blocking compound. C. The outer sheath shall be marked with the manufacturer’s name, words identifying the cable type (e.g. “Optical Cable” or “Fiber Optic Cable”), year of manufacture, and sequential length markings. The actual length of the cable shall be within -0/+1% of the length markings. The marking shall be in a contrasting color to the cable jacket. D. Temperature Range: 1. Storage: -40 to +70C (no irreversible change in attenuation) 2. Operating: -40 to +70C E. Humidity Range: 0 to 100% F. Maximum Tensile Strength: 1. During Installation: 2700 Newton (600 lb. force) (no irreversible change in attenuation) 2. Long Term: 890 N (200 lb. force) G. Bending Radius: 1. During Installation: 20 times cable diameter 2. No Load: 10 times cable diameter H. The maximum pulling tension shall be 2700 N (608 lbf) during installation (short term) and 890 N (200 lbf) long term installed. I. The armored fiber optic cable shall be Corning # xxx RW5-14101A20 or other approved products, which meet these specifications. 2.02 SINGLE MODE OPTICAL FIBERS STRANDS A. Fiber Strands Type Single mode, doped silica core surrounded by a concentric glass cladding. B. Core Diameter: 8-9 -mm. All fibers shall be of the same nominal core diameter and profile. 1. Cladding Diameter: 125 + 1.0 -mm. 2. Core-to-Cladding Offset: < 0.8 -mm. 3. Cladding Non-Circularity: < 1.0%. 4. Coating Diameter: 245 + 10 -mm. 5. The coating shall be mechanically strippable without damaging the optical fiber. 6. Cutoff Wavelength (cabled fiber)<1260-nm. 7. Mode field diameter: 8.3 –9.8 m at 1300-nm; 10.5+1.0 mm at 1550 -nm 8. Zero Dispersion Wavelength (l0)- 1301.5 nm< l0 < 1321.5 nm. 9. Zero Dispersion Slope (S0): <0.092 ps/nm2 per km C. Fiber Attenuation: OUTSIDE-PLANT CABLE AND EQUIPMENT 27 1003 - 3 1. 2. @ 1300-nm @ 1550-nm 0.4 dB/km 0.3 dB/km D. The average change in attenuation at extreme operational temperature (-40 C to +70 C) shall not exceed 0.05 dB/km at 1550 nm. The magnitude of the maximum attenuation change of each individual fiber shall not be greater than 0.15 dB/km at 1550 nm. E. When tested in accordance with FOTP-3, “Procedure to Measure Temperature Cycling Effects in Optical Fibers, Optical Cable, and Other Passive Fiber Optic Components,” the average change in attenuation over the rated temperature range of the cable shall not exceed 0.05 dB/km at 1550 nm for single-mode fiber. The magnitude of the maximum attenuation change of each individual fiber shall not be greater than 0.15 dB/km at 1550 nm. F. Fiber Dispersion (maximum): 1. 1285-1330-nm 3.2-ps/nm per km 2. @ 1550-nm 18-ps/nm per km G. No single mode optical fiber shall show a point discontinuity greater than 0.1 dB at the specified wavelengths. Such a discontinuity or any discontinuity showing a reflection at that point shall be cause for rejection of that fiber by LU. 2.03 BOXES AND FITTINGS A. Malleable iron or steel insulating bushings shall be O-Z Electrical Manufacturing Company "B", and/or type "BLG" or an approved equal. B. EMT fittings shall be set screw steel insulator type. Die cast fittings shall not be installed. Split-threaded connectors will not be acceptable. Fittings shall be as manufactured by Crouse-Hinds, Killark, Appleton, T&B Companies or an approved equal. C. All supports, clamps, and anchors shall be galvanized steel or malleable iron. D. Provide electrical boxes as required for cable pulling and code compliance. E. Boxes shall be secured to conduit by means of conduit hubs if coded hubs are not provided on this box. F. Support boxes independently of conduit except for cast boxes that are connected to two rigid metal conduits, both supported within 12 inches of boxes. 2.04 HIGH-DENSITY POLYETHYLENE DUCT A. The duct shall be 4" High-Density Polyethylene (HDPE) and rated at SDR 11.5. This duct shall be manufactured to ASTM D2447, ASTM D3350 AND NEMA TC7 Specifications. B. The duct shall be listed per UL 651-B (Continuous length coiled HDPE conduit). C. The duct shall meet NEC 347 and 710 requirements for installation of nonmetallic conduit direct buried or concrete encased. D. The duct shall be available in both schedules 40 and 80 per ASTN D 2447. E. The Duct walls shall be pre-lubricated with silicone to reduce the frictional forces applied during cable installation F. The duct shall contain a measured pull tape. The pull tape shall be a minimum of 1200lbs in tensile strength. G. The duct shall be supplied with certified test reports. H. The Duct shall be Arnco, Carlon or other approved products, which meet these specifications. 2.05 FIBER OPTIC PATCH PANEL A. The fiber termination/splice panel shall be available in 72-fiber size. B. The panels shall provide fiber termination, splicing protection and associated fiber/pigtail storage and must include vertical cable guide management. C. The fiber optic patch panel components shall include front and rear covers, radius limiters, vertical cable guide, and designation labels. OUTSIDE-PLANT CABLE AND EQUIPMENT 27 1003 - 4 D. The fiber optic patch panel shall be able to be deployed in new frames or retrofitted into available chassis positions in existing frames. A key lock shall be installed on the front cover. E. Designation label areas shall be inside the front cover to record cable fiber and patch cord identification. Labels shall identify rows of 6paks that are provided for the bulkhead panel. F. A cable clamp kit shall be provided for outside plant (OSP) fiber cable that enters the connector panel. G. Removable covers shall be mounted at the front of the connector panel. Radius limiters shall enable to maintain a minimum fiber bend radius of 1.5 inches and permit coiling excess lengths of cable fibers or pigtails. H. A fiber optic patch panel shall accommodate several different adapters or receptacles using optional 6pak plates. I. Fiber optic patch panel shall accommodate splice kits to splice the pigtails to OSP cable fibers. The splice kit for the splice panel shall consist of a splice deck and splice chip. J. The splice tray shall accommodate up to 72 heat shrink fusion splices. The splice tray shall be fastened to the panel. K. The Patch panels shall be as follows: 1. ADC FL2-72 TS140 series or other equivalent products, which meet these specifications. 2. ADC FL1-H177NNN2-1100N series or other equivalent products, which meet these specifications. 3. ADC FL2-24 TS525 series or other equivalent products, which meet these specifications. 2.06 6PAK PLATES A. 6pak plates shall be Duplex style. B. The plate shall be used for mounting six adapter assemblies. C. The adapters/receptacles shall be installed in unique angled retainers for installation in the 6pak plate. The individual angled retainer and the fiber connector and fiber, or the entire 6pak plate shall be removable from the connector modules without tools. Blank plates shall occupy open positions within the panel. D. The plates shall be available with pre-terminated 9’ pigtails. E. The pigtails shall consist of a single outer jacket containing six color- coded 900µm fibers. F. One end of pigtail shall be terminated to SC connector for Single Mode fiber stile and installed into 6pack plug-in adapters. G. The pigtail shall be made of the same type of glass and have the same optical characteristics as the fiberglass of the optical cable it designed to be spliced to. H. The Plates shall be ADC or other equivalent products, which meet these specifications. I. The singlemode pigtails shall be ADC FL2-6P7SC603W or other equivalent products, which meet these specifications. 2.07 FIBER OPTIC CONNECTOR A. The Fiber Optical Connector shall be SC-type for Single Mode fiber. B. The Fiber Optical Connector ferrule shall be ceramic or glass-in-ceramic. The optical fiber within the connector ferrule shall be secured with an adhesive. C. The attenuation per mated fiber optic connector pair shall not exceed 0.35-dB. Fiber optic connector shall sustain a minimum of 200 mating cycles per EIA/TIA-455-21 without violating specifications. D. At each building stands of the fiber optic cable shall be terminated on 8º-angled fiber optic connector. Guaranteed Return Loss for these connectors shall be 65dB. E. The fiber optic connectors used for remaining single mode fiber strands shall be ultra PC polished. Guaranteed Return Loss for singlemode connectors shall be 55dB. OUTSIDE-PLANT CABLE AND EQUIPMENT 27 1003 - 5 F. The fiber optic connector shall meet the following performance criteria: 1. Test Procedure Max. Attenuation Change a. Cable Retention (FOTP-6) 0.2-dB b. Durability (FOTP-21) 0.2-dB c. Impact (FOTP-2) 0.2-dB d. Thermal Shock (FOTP-3) 0.2-dB e. Humidity (FOTP-5) 0.2-dB G. The fiber optic connectors shall be manufactured by Corning, ADC or other equivalent products, which meet these specifications. 2.08 UNDERGROUND ENCLOSURES A. Underground enclosures shall be constructed of a fiberglass-reinforced polymer material and have the same strength rating as concrete handholes of the same proportions. B. Underground enclosures shall be available in: 24"W x 36"L x 48"D. C. Underground enclosures shall be rated for use at sidewalk, driveway and parking lot areas. D. Underground enclosures shall: 1. Be flush-mounted to the existing grade and constructed with a load rating of AASHTO H-20. 2. Be equipped with a locking keyed mechanism. 3. Be equipped with cable racks, conduit entrances and strut inserts. 4. Be designed for a long life over a wide range of temperature extremes. 5. Feature interlock for concrete sidewalk retention. 6. Not be equipped with a solid bottom. E. The Underground enclosures shall be Newbasis Part #, FC2436WUC or other equivalent products, which meet these specifications. 2.09 CONDUIT AND FITTINGS AND SUPPORTS A. Conduit 1. Electrical metallic tubing (EMT): Fed. Spec. WW-C-563 2. Flexible steel conduit, commercial Greenfield: Fed. Spec. WW-C-566 B. Electrical metallic tubing fittings: 1. Fed. Spec. W-F-408 shall apply, except material shall be steel only. 2. Couplings and connectors shall be set screw type with two screws each. Couplings for conduit sizes 2-1/2 inches and larger shall be set screw type with four screws each. Set screws shall be case-hardened steel with hex head and cup point to firmly seat in wall of conduit for positive ground. Provide gland and ring compression type in damp locations. 3. Indent type connectors are not permitted. 4. Die-cast or pressure-cast zinc-alloy fittings of fittings made of pot metal are not permitted. C. Flexible steel conduit, Greenfield, fittings: 1. Fed. Spec. W-F-406 shall apply, except material shall be steel only. 2. Shall be multiple point type, threading into the internal wall of the conduit convolutions or set screw type. D. Expansions and deflections couplings: 1. UL 467 and UL 514 shall apply. 2. Shall accommodate, 1.9 cm (0.75 inch) deflection, expansion, or contraction in ay direction, and shall allow 30 degrees angular deflections. 3. Shall include internal flexible metal braid sized to guarantee conduit ground continuity and fault currents in accordance with UL 467, and NEC code tables for ground conductors. 4. Shall be watertight, corrosion-resistant, threaded for and compatible with rigid or intermediate metal conduit. 5. Jacket shall be flexible, corrosion-resistant, watertight, moisture and heat resistant molded rubber material with stainless steel jacket clamps. OUTSIDE-PLANT CABLE AND EQUIPMENT 27 1003 - 6 E. Conduit Supports: 1. All parts and hardware shall be zinc-coated or have equivalent corrosion protection. 2. Pipe Straps: Fed. Spec. FF-S-760, type 1, Style A or B. 3. Individual Conduit Hangers: Shall be designed for the purpose, and have pre-assembled closure bolts and nut and provisions for receiving hanger rod. 4. Multiple conduit trapeze hangers shall be not less than 1-1/2 by 1-1/2 inch, 12 gauge steel, cold formed, lipped channels. Hanger rods shall be not less than 3/8-inch diameter steel. 5. Solid Masonry and Concrete Anchors: Fed. Spec. FF-S-325. Anchors shall be self-drilling expansion shields, or machine bolt expansion anchors. 6. Where hangers or supports are attached to beams, trusses or other structural supports, the attachments shall be fireproofed equal to supporting members. PART 3 – EXECUTION 3.01 DIRECTIONAL BORING OPERATIONS A. All directional boring operations are subject to the following conditions: 1. The machine operator shall follow all current OSHA regulations, including the use of grounding mats and other safety measures. 2. The machine operator shall have control over the direction of the boring tool. 3. The bore crew must have, in their possession, a copy of the permit authorizing the company to perform work, and a copy of the approved drawing and specifications for the bore work location. 4. When possible, the Contractor shall mark the proposed running line and bore head location. Mark the proposed running line every 5’ to 10’, using a longitudinal line; mark the actual location with a white paint spot at the end of each stem push. Only white paint is approved for this use. 5. The bore is not allowed to deviate more than six (6) inches from the proposed marked running line, and the ends of the bore must be at the designated depth. 6. Slurry use shall be kept at a minimum and only used for head lubrication and/or spoils return. The Contractor shall calculate anticipated slurry use and monitor slurry use during the bore operation to determine slurry loss into the surrounding soil. 7. Slurry must be contained during the bore operation and must be removed prior to backfilling, with dry dirt. 8. During pull back, the mandrels shall be not more than two inches larger than the diameter of the duct or casing. 9. Shallow bores or other unsuccessful bores shall be abandoned and filled. 10. The bore operation shall be stopped if any damage occurs to a road surface and it shall remain inactive until corrective measures are taken. The Contractor is liable for any damage done to the right-of-way or structures. 11. Auger heads are not allowed more than six inches ahead of the casing being inserted. 12. Bore stems and cutting heads may have to be left in the ground if they cannot be retrieved through the bore hole. Open excavation to retrieve the parts is not allowed. 13. When boring near creeks and streams, silt fences shall be properly installed to prevent disturbed soil from flowing into the waterways and remain in place after the bore has been completed. 3.02 EXCAVATION AND TRENCHING REQUIREMENTS A. Make trench sides as nearly vertical (max depth is 48") as practical except where sloping of sides is allowed. B. Remove all rock, boulders, hard material, unstable material, and yielding and unsatisfactory materials within the limits indicated for trench excavation and dispose of off the site. Notify LU immediately in writing if it becomes necessary to remove such materials beyond the trench limits. Where excavations are deeper or wider than the trench limits in order to remove unsuitable materials, they shall be refilled with approved borrowed material. C. Existing concrete or granite curb encountered in excavation shall be temporarily supported or replaced in kind. Bituminous lip curb shall be disposed and replaced in kind. OUTSIDE-PLANT CABLE AND EQUIPMENT 27 1003 - 7 D. Excavation operations adjacent to and below existing structures and utilities shall be done manually. Start hand excavation on each side of the indicated obstruction and continue until the obstruction is uncovered or until clearance for the new grade is assured. Support uncovered lines or other existing work affected by the contract excavation until approval for backfill is granted by the LU’s Representative. Report damage to utility lines or subsurface construction immediately to the Consultant. E. Place "Road Closed" signs on temporary barricades at approaches to work or uncovered trenches. F. Keep excavated materials and construction equipment and materials a safe distance back from the edge of excavations to avoid overloading the sides of the trench and to prevent slides or cave-ins. G. Grade areas around trench as necessary to prevent surface water from flowing into excavations. H. Walkway and grassed areas left un-backfilled at the end of the workday shall be enclosed with snow fence until restored to grade. Roadway trenches shall not be re-opened to traffic unless either a road plate capable of sustaining HS-20 loading is in place or temporary gravel is placed to bring the trench area to finish grade. 3.03 CUTTING PAVEMENT A. Where trench excavation occurs in paved areas, saw cut existing pavement to obtain sound, vertical edges one foot wider than the indicated trench width on each side of the trench. When the saw cut is within two feet of an existing joint or curb, remove pavement to the existing joint or curb or as required by the city, etc. B. Existing pavements and base course beyond the indicated lines for trench excavation which have been disturbed, damaged or undermined shall be restored or replaced by the Contractor to match existing pavements and base course or as requested by the city, etc. 3.04 BACK FILLING A. Construct backfill in two operations (initial and final) as indicated and specified in this section. Initial backfill shall be select backfill material placed in 6-inch maximum loose lifts to one foot above conduit or duct unless otherwise specified. Bring up evenly on each side and along the full length of the conduit or duct structure. Ensure that no damage is done to the conduit or duct structure, or its protective coating or as required by the city, etc. B. Place the remainder of the backfill (final backfill) in 9-inch maximum loose lifts to the bottom of the sub-grade, unless otherwise specified. Compact each loose lift before placing the next lift. Do not backfill where the material in the trench is muddy, except as authorized or as required by the city, etc. C. Provide a minimum cover from final grade of 2-1/2 feet for fiber ducts unless otherwise indicated on the Drawings or as required by the city, etc. D. Where settlement occurs in trenches and pits due to improper compaction, excavate to the depth necessary to rectify the problem, then backfill and compact the excavation as specified herein and restore the surface to the required elevation or as required by the city, etc. E. The Contractor shall coordinate back filling with testing of utilities. Testing for the following shall be complete before final back filling: water distribution, sanitary sewer, steam compressed air, fuel oil, and refrigeration systems. 3.05 COMPACTION A. Use hand-operated, plate-type, vibratory or other suitable hand tampers in areas not accessible to larger rollers or compactors. Avoid damaging pipes and protective pipe coatings. Compact material in accordance with local code unless otherwise specified. If necessary, alter, change, or modify selected equipment or compaction methods to meet compaction requirement and meet requirements of the city, etc. OUTSIDE-PLANT CABLE AND EQUIPMENT 27 1003 - 8 3.06 PROTECTION OF EXISTING UTILITIES, STRUCTURES AND NEW WORK A. Excavation, backfill and compaction operations shall be done in such a manner to prevent cave-ins of excavations or the undermining, damage or disturbing of existing utilities and structures or of new work. Backfill shall be placed and compacted to prevent future settlement or damage to existing utilities and structures and new work and meet requirements of the city, etc. B. Any damage due to excavation, back filling or settlement of the backfill, or injury to persons or damage to property occurring as a result of such damage shall be the responsibility of the Contractor. All costs to repair such damage, in a manner satisfactory to LU's Representative, shall be borne by the Contractor at no additional expense to LU and meet requirements of the city, etc. C. Protect newly back filled areas and adjacent structures, slopes, or grades from traffic, erosion settlement, or any other damage. Repair and re-establish damaged or eroded grades and slopes and restore surface construction prior to acceptance. Protect existing storm drain inlets from water-borne soil and meet requirements of the city, etc. 3.07 RESTORATION A. The Contractor is responsible for repairs to any streets, sidewalks, grass areas, etc., which must be trenched or otherwise disturbed in the process of installation. In areas owned by the City, the City has final determination whether such repairs are acceptable. B. All sidewalks, streets, alleyways and landscaping shall be replaced to its original condition or better. C. Note: All existing conditions have been videotaped prior to construction activities to provide information of pre-existing conditions. 3.08 GRASSED AREAS A. After completion and acceptance of all conduit, excavation, and backfilling work in a given area, the Contractor shall place an appropriate amount of turf sod to cover all disturbed areas. The Contractor may choose to cut and remove turf prior to the area being disturbed. This would be used to place back over the disturbed area and meet requirements of the city, etc. 3.09 SIDEWALKS A. All sidewalks shall be constructed using the same backfill and compaction procedures used for street opening. B. Unless unusual conditions exist, sidewalk panels, which are cut into for construction, shall be replaced with full panels. New or prior construction saw cuts are not considered as panel ends. Sidewalk panels end at score lines, curbs, boulevards or property lines. If curb is part of the sidewalk panel the curb shall also be replaced. C. The Contractor shall take care in removing sidewalk panels. If adjacent panels are chipped the contractor will be required to replace them. 3.10 ROAD RESTORATION A. After completion and acceptance of conduit excavation, and back filling of road trench areas, 12 inches of compacted Gravel Borrow Subbase course shall be placed to a level three inches below the finish road grade. A temporary surface of Bituminous Surface Course Type I-1 shall be placed. B. After allowing 6 months for settlement of the road subbase, the Contractor shall place a saw cut of the pavement 12 inches beyond the limits of the temporary patch. Bituminous binder course shall be placed to within 1-1/2 inches of the finish road grade and a final course of bituminous Surface Course Type I-1 shall complete the roadwork. Reflectorized pigment pavement markings specially manufactured for roadway use shall be placed to restore any pavement striping that had been in place prior to this contract. OUTSIDE-PLANT CABLE AND EQUIPMENT 27 1003 - 9 3.11 WORK WITHIN BUILDINGS A. All cable taken into a building shall be terminated within fifty (50') of the point of entry into the structure. If the termination point (telecommunications room) is located further than 50' from the point of entry into the structure, the cable shall be placed in EMT conduit attached to the building entrance. The conduit shall be extended to the telecommunication room where the fiber is to be terminated. B. Any cable that is gel-filled must be properly sealed and tested at building entrance. C. At each building entrance, a maintenance loop of fiber 4 feet in diameter and 10 to 15 feet in length must be installed. D. The cable shall be lubricated at the entrance point to the conduit during installation. 3.12 CUTTING AND PATCHING A. Where it is necessary to do any cutting and patching, no cutting of beading walls, beams, etc., shall be done without the approval of LU’s Representative. All patching, finishing, etc., shall match the surroundings. All cutting and patching shall be done by workmen skilled in the trades. B. Holes through concrete and masonry in new and existing structures shall be cut with a diamond core drill or concrete saw. Pneumatic hammer, impact electric, hand or manual hammer type drills shall not be allowed, except where permitted as required by limited working space. C. Holes shall be located so as not to affect structural sections such as beams. D. Holes shall be laid out in advance. LU’s Representative shall be advised, prior to drilling through structural sections, for determination of proper layout. E. Floor, exterior wall and roof seals shall be watertight. Walls and floors that are cored for installation of conduit shall be sleeved with steel tubing, grouted, and the space between the conduit and sleeve filled as specified herein. F. Conduits shall extend one-inch minimum above finished floor. 3.13 FIRE STOPPING A. Structural Penetrations: Where conduits, wireways, busduct, and other electrical raceways pass through fire partitions, fire walls or walls and floors; install a firestop that provides an effective barrier against the spread of fire, smoke and cases. Firestop material shall be packed tight, and completely fill clearances between raceways and openings. B. All penetrations of firewalls must be approved by the LU before any penetrations are made. The Contractor shall provide satisfactory sleeving and fire caulking both inside and outside of that sleeving. If existing sleeving is to be utilized, it will be the responsibility of the Contractor to fire caulk inside the sleeving. C. The Contractor is responsible for adhering to the following standards: 1. Conduit penetrations through fire-rated or smoke walls: Completely seal around the conduit penetration with Hilti FS 601 fire-rated sealant or equal Tremco or 3M. 2. Conduit sleeves through fire-rated or smoke wall: Completely seal around the conduit penetration with Hilti FS 601 fire-rated sealant or equal Tremco or 3M. Completely seal inner opening of the conduit sleeve with fire wool packing and Hilti FS 611A intumescent firestop sealant. 3. Cable bundles through fire-rated or smoke walls (with out sleeves): Completely seal openings with Hilti FS 611A intumescent firestop sealant, or equal Tremco or 3M. 4. Cable tray penetrations through fire-rated or smoke walls: Completely seal openings with Hilti FS 635 (trowelable type) or equal Tremco or 3M. 5. A submitted response to this RFP assumes that all firestopping will be provided as specified. The firestop manufacturer’s specifications and instructions shall be submitted with the final documentation. OUTSIDE-PLANT CABLE AND EQUIPMENT 27 1003 - 10 3.14 SUPPORT AND ANCHORS A. The Contractor shall exercise judgment when supporting equipment. If support methods are questionable or not available, the Contractor shall call it to the attention of the Engineer prior to installation. B. Fasten hanger rods, conduit clamps, and outlet and junction boxes to building structure using expansion anchors, beam clamps, spring steel clips. C. Install hangers and supports, sleeves and fasteners in accordance with approved printed manufacturers' installation procedures, and as specified. D. Coordinate all affected trades and all aspects of the electrical work, including installation of raceways and wiring as necessary to interface installation of supporting devices with other work. E. Install hangers and supports, and attachments to properly support raceways, equipment and accessories from building structure. 3.15 CONDUIT INSTALLATION A. Installation shall be in accordance with U.L., N.E.C. as shown on the drawings and specified herein. B. Route conduit parallel and perpendicular to walls and adjacent piping and do not obstruct headrooms or walkways. C. Maintain minimum 6-inch clearance between conduit and piping. Maintain 12-inch clearance between conduit and heat sources such as flues, steam pipes, and heating appliances. D. Conduit shall be supported and clamped using hardware intended for the purpose. E. Conduit bends shall be made with standard conduit bending tools. Conduit deformed or flattened during bending shall be removed and replaced. F. Conduits cut in the field shall be coated with galvanized hot stick or galvanized spray approved for the purpose. G. Supports shall be provided every five (5) feet for conduits wherever possible, and within three (3) feet of boxes or fittings, the points of support to be determined in the field. The supports shall consist of approved types of clamps or straps secured by screws, bolts on wood or steel framework and decking, or expansion bolts in concrete, and brickwork. In no instance shall supporting bolts or screws protrude to the outside of building walls or roof. H. The complete raceway system shall become metallically continuous throughout its entire length and the entire system shall be electrically continuous and shall be thoroughly grounded in accordance with the N.E.C. I. Vapor seals shall be installed at locations required by the National Electrical Code. 3.16 DUCT INSTALLATION A. The primary method of installation of the High-Density PolyEthylene is trenching. The duct shall be joined at the "tie-in" locations using metal couplers designed to thread the two ends of HDPE conduits together. These couplers shall provide a pull-proof connection of the duct. B. The depth at which buried duct shall be placed will vary with local conditions. HDPC duct should be buried a minimum depth of: Location Depth Minimum cover in soil 42 in. Minimum cover under draining ditches 42 in. Minimum cover under railroads 60 in. below top of rail Minimum cover at roadway crossing 60 in. Minimum cover in rock 42 in. OUTSIDE-PLANT CABLE AND EQUIPMENT 27 1003 - 11 C. When crossing unimproved roads, streets and alleys that may later be paved or hard surfaced, the cable should be placed at a depth that retains sufficient cover following permanent grading of the road. D. When crossing major highways and railroads the duct shall be placed into 6” schedule 80 casing. E. The Contractor shall proof all conduit sections prior to installation of the fiber cable to ensure conduit integrity. After proofing of the duct, measurements will be taken to verify the length of the installed conduit. F. The Contractor shall leave a pull tape in the conduit with the cable after installation. G. Install a pull wire in all empty conduits consisting of one #12 steel or copper wire or heave duty nylon cord for small conduits (3 inch or smaller) and nylon rope for large conduits (over 3 inch diameter). H. Conduits 3 inches and larger, rigidly secured to building construction on opposite sides of a building expansion joint, shall be provided with expansion and deflection couplings. The couplings shall be installed in accordance with the manufacturer's recommendations. Conduits smaller than 3 inches shall be provided with junction boxes on both sides of the expansion joint, and connected by 15 inches of slack flexible conduit. Flexible conduit shall have a copper green ground bonding jumper installed. In lieu of this flexible conduit, expansion and deflection couplings as specified above may be installed. 3.17 SPLICE POINTS A. All splicing shall be made using fusion-splicing technology. All splices shall be single strand fusion splices. All splices shall be placed utilizing fusion splice trays. 3.18 CABLE SLACK A. The Contractor shall provide seventy-five feet (75') of cable slack at all splice locations. All other handholes, used for installation assistance shall contain thirty feet (30') of cable slack. Cable slack of one hundred feet (100') shall be provided on one side of any street crossings. B. At handholes, cable slack should be placed vertically in the hole. In the case of a buried splice point, the slack should be coiled and buried vertically (in line with the cable route). C. This excess slack shall provide added cable for restorations or reconfigurations without digging up large parts of the cable system. 3.19 UNDERGROUND ENCLOSURES (HANDHOLES) A. Handholes shall be placed at locations indicated on the drawing. B. The intermediate size handholes (24" x 36") are designed to assist in the cable placing operation. C. The handholes shall be placed on 6-inch deep rock/gravel bottom contained by wire mesh that allows drainage from the box and secures the rock/gravel in place to solidify the base of the handhole. D. All conduits entering or exiting the handholes will be scaled to prevent the movement of water through the duct. 3.20 BURIED WARNING TAPE A. When trenching is involved or required by certain conditions, i.e., customer or citizen request, topographical reasons or as directed by City forces, the use of a warning tape is required. A bright orange (preferably “ULCC” orange) warning tape with a minimum width of three inches shall be buried approximately one foot below the existing grade. As a minimum, the tape should be marked “WARNING-OPTICAL CABLE”. The tape shall be placed directly above the conduit to alert any excavator of the presence of an underground facility. 3.21 BONDING AND GROUNDING A. All metallic cable elements at splice points and building entrance must be bonded and grounded. OUTSIDE-PLANT CABLE AND EQUIPMENT 27 1003 - 12 B. Copper wire AWG #6 should be used, as a minimum. 3.22 INSTALLATION PRACTICES FOR FIBER OPTIC CABLE A. Fiber optic cable is a high-capacity transmission medium with qualities and characteristics, which can be degraded when it is subjected to excessive pulling tension, sharp bends, and crushing forces. B. The maximum pulling tension for armored cable is 2,700 Newtons (600 lbs). C. Maximum long-term crush forces for armored cable are 100N/cm (57.1 lb./in). D. The minimum bend radius for an armored cable during installation and following installation over the life span of the cable must be 20 times (20 x) the cable diameter. E. The minimum diameter required for pull wheels or rollers should be double the minimum bend radius. The contractor will be responsible to check manufacturer's specifications for the cable feed-chute, to make sure that the chute's critical dimensions and clearances are compatible with the placing cable. The chute must have a 20-inch minimum radius. 3.23 CABLE TERMINATION - FIBER OPTIC A. ALL fibers shall be spliced to 6-pack pigtails. B. All couplings shall be fitted with a dust cap. C. Slack in each fiber shall be provided as to allow for future re-termination in the event of connector or fiber end-face damage. Adequate slack shall be retained to allow termination at a 30” high workbench positioned adjacent to the termination enclosure(s). A minimum of 1-meter (~39”) of slack shall be retained regardless of panel position relative to the potential work area. D. Single-Mode fiber shall be terminated with SC connectors. 3.24 TEST/ACCEPTANCE CRITERIA A. Testing 1. The fibers utilized in the installed cable shall be traceable to the manufacturer. Contractor shall provide cable manufacturer’s test report for each reel of cable provided. These test reports shall include (1) manufacturer’s on reel attenuation test results at the specified wavelengths for each optical fiber of each reel prior to shipment from the manufacture and (2) on-the-reel bandwidth performance as tested at the factory. 2. Contractor is responsible for supplying all equipment and personnel necessary to conduct the acceptance tests. 3. Contractor shall conduct acceptance testing according to a schedule coordinated with the Consultant. May be in attendance to witness the test procedures. The Contractor shall offer adequate advance notice to the Consultant as to allow for such participation. B. Tests after Installation 1. Upon completion of cable installation and termination, the Fiber Optic cabling shall be tested to include: a. Optical Attenuation (“Insertion Loss” Method) b. Verification of Link Integrity (OTDR) c. Optical return loss (ORL) C. Optical Attenuation Testing 1. Optical Attenuation shall be measured on all terminated optical fibers in both directions of transmission using the “Insertion Loss” method. Measurement shall be inclusive of the optical connectors and couplings installed at the system endpoints. Access jumpers shall be used at both the transmit and receive ends to insure that an accurate measurement of connector losses is made. 2. Multi-mode fibers shall be tested in accordance with the TIA/EIA 526-14A, Method B at 850±30 nm and 1310± nm. Single mode fibers shall be tested in accordance with the TIA/EIA 526-7-1998. Method A.1. Testing shall be at 1300±20 nm and 1500±10 nm. 3. Attenuation of optical fibers shall not exceed the values calculated as follows: a. Attenuation (max.) = 2*C+L*F+S dB OUTSIDE-PLANT CABLE AND EQUIPMENT 27 1003 - 13 b. 4. D. Where C is the maximum allowable Mated Connector Loss £0.35 dB, L is the length of the run (in kilometers) and F is the maximum allowable fiber loss (in dB/km). S is the total splice loss £0.1 dB (# of splices * max. attenuation per splice). Documentation of the insertion loss testing for each fiber run shall be provided to LU to include a record of: a. Wavelength b. Fiber type c. Fiber and cable number d. Measurement direction e. Test equipment model and serial number f. Operator g. Test documentation must be stored in a floppy disk and printed as a hard copy with all test results labeled. The documentation must be turned over to LU OIT. h. All testing is to be done through connectors. i. Any fiber that fails testing must have appropriate corrective action taken to rectify the situation. Optical Time Domain Reflectometer (OTDR) Testing 1. All links shall be tested with an OTDR that are 330 feet (100 m) or longer. (Contractor shall supply the OTDR meter – see below.) Single mode fibers shall be tested at 1300/1500-nm (nominal) OTDR testing could be in one direction following worst-case wavelength selection when there are no splice points or interconnect points in the link. 2. Any link, which is longer than 330 feet (100 m) and has splice points or interconnect points in said link, shall be tested bi-directionally using worst-case wavelengths. 3. The OTDR(s) shall incorporate high-resolution optics optimized for viewing of short cable sections. Launch cables of adequate length (1000’ minimum) shall be used to allow viewing of the entire length of the cable, including the connectors at the launch and receive end. 4. OTDR’s used as part of these testing specifications shall be calibrated to sheath (jacket) length, not optical length by adjusting the unit’s index of refraction. 5. All OTDR traces shall maximize both the vertical and horizontal scales to the greatest extent possible and still fit the entire cable link trace on the screen with optimum resolution. 6. Testing shall be performed in accordance with the following requirements. Failure of a link at any part of the testing shall result in the contractor having to repair the problem and retest the installation. Cost for any required repairs and re-testing shall be borne solely by the contractor. 7. Reflective and non-reflective events shall be marked by OTDR, and the data for each event must be retrievable. 8. OTDR traces revealing a point discontinuity greater than 0.2-dB in a multi-mode fiber, or 0.1-dB in a single mode fiber at any of the tested wavelengths or any discontinuity showing a reflection at that point shall be a valid basis for rejection of that fiber by LU. 9. OTDR traces revealing a “Ghost” shall also be a valid basis for rejection of that fiber by LU. 10. The installation of that cable shall be reviewed in an effort to solve any problems that may be causing the fault. If such efforts do not remove the fault, that cable and the associated terminations shall be replaced at the expense of the Contractor. 11. All fiber shall be tested for attenuation loss using an OTDR set to 2-Point loss measurement parameters. Marker points shall be placed at the beginning and end of each backscatter signature recorded by the OTDR. The manufacturer's instructional guide can be used to determine proper placement of these markers. 12. Links that contain splice points or interconnect points shall also contain an additional "Events Display Table" to accompany the OTDR trace. This display shall show the distance to the events, distance between multiple events, each events loss in db, and a description of the event (reflective event, non-reflective event, gains and cable end). All attenuation event loss readings shall be in the LSA (Least Square Average) mode of the OTDR. 2-Point attenuation measurements at events are not acceptable. 13. Proper pulse width selection is required to minimize attenuation dead zone effect. OUTSIDE-PLANT CABLE AND EQUIPMENT 27 1003 - 14 14. Fiber links that sorter then 600 feet requires pulse width to set to 10ns. That equals to MM dead zone=23 feet (7 m), SM dead zone = 33 feet (10 m) 15. The OTDR display shall be recorded on computer diskettes with identification and numbering, sequences to be pre-approved by the Engineer. Each trace must contain as a minimum: a. cable/sheath length (not optical fiber length) b. 2-point db loss, attenuation in db/mile (db/km) c. fiber type d. wavelength used e. pulse width selection f. and fiber/cable identification g. The stored fiber trace shall allow full manipulation of the trace when viewed with the PC emulation software. Both a hard copy print out and diskette copy of each trace shall be submitted to LU OIT for approval. E. Documentation of the OTDR signature traces displaying the entire length of the cable run shall be provided to LU to include a record of: 1. Wavelength 2. Fiber type 3. Fiber and cable number 4. Measurement direction 5. Test equipment model and serial number 6. Operator F. ORL Testing 1. All connectors at single mode fiber links shall be tested for optical return loss (ORL) using OTDR. The OTDR shall be capable to measure connector spike with respect to the backscatter signal on the OTDR. This technique shall be accomplished by software embedded in the instrument. 2. The launch cords must be kept clean and periodically repolished to insure as perfect a surface finish as possible to match polishing the on connectors. 3. The single-mode connectors optical return loss shall be not less than 65 dB for APC connectors and 55 dB for UPC connectors. 4. Test documentation must be stored on a floppy disk and printed as a hard copy with all test results labeled. 3.25 DOCUMENTATION A. Drawing Records 1. The following requirements apply to all record drawings: a. They shall be maintained at the Contractor’s expense. b. All such drawings shall be provided as necessary for clarification. c. The record drawings shall be in 1”-25’scale. d. The Contractor shall indicate on the drawings the fiber optic cable location with the reference to the center of the street. e. The record drawings shall be returned to LU OIT on completion of the work and are subject to the approval of LU OIT. 2. The record drawings shall be submitted in the following formats: a. In one blueline set b. In one reproducible set c. In one CAD set 3. Test records: Test readings shall be recorded along with the annotation that these are post-installation readings. Printed copies of these readings shall be provided to LU upon completion of the project. Records are to include date of testing, name of technician, and readings of all above-described test results OUTSIDE-PLANT CABLE AND EQUIPMENT 27 1003 - 15 3.26 LABELING A. A labeling plan must be submitted to and approved by LU prior to installation, and the completed labeling must meet the approval of LU. EIA 606 standards are to be met. B. Cable: All cable must be clearly labeled by the Contractor at the telecommunication rooms (Brady marker or similar). C. Patch Panel: All SC connectors connected to patch panels must also be labeled on patch panel. All ST connectors connected to patch panels must also be labeled on patch panel. 3.27 FIBER OPTIC SYSTEM ACCEPTANCE A. The fiber optic outside plant system will be accepted by LU OIT when: 1. All of the work has been completed in accordance with the contract and specifications. 2. The system operates in conformance with manufacturer’s published specifications. 3. The system has completed a successful performance period. The performance period will begin on the day following the cutover and must continue for 30 consecutive days during which time the system will operate at an average effectiveness level of 99 percent or more. If for any reason this level cannot be maintained, a new 30-day performance period will be initiated. It is not necessary that one 30-day period expire before another performance period begins. 4. The Contractor has certified in writing to LU OIT when the cable is installed, operational in accordance with these specifications, and ready for use. 5. The final step in accepting buried cable installation will be a thorough inspection of the entire route from start to finish. The “as-built” drawings must be submitted to LU one week prior to final inspection. The drawings will be examined by LU OIT personnel and involved parties for conformance to LU plans, codes, regulations, and general accuracy. 6. The construction area above ground will be inspected to ensure the following: a. Restoration has been accomplished. b. Permanent markers have been installed immediately beside the cables. c. Road bores, if used, are properly completed and will not collapse a portion of the road. d. Debris and trash have been removed from the site. e. Other instructions specific to the installation have been completed to the project manager’s specifications. 7. All test results should be submitted in hard copy and in usable (MS Word) electronic format and meet specifications. 8. At this time upon LU’s written acceptance, operations control becomes the responsibility of LU. This constitutes Date of Acceptance. END OF SECTION OUTSIDE-PLANT CABLE AND EQUIPMENT 27 1003 - 16 SECTION 27 1200 COMMUNICATIONS SYSTEM IDENTIFICATION AND LABELING PART 1 – GENERAL 1.01 SCOPE A. This section describes the products and execution requirements relating to labeling of telecommunications cabling, termination components, and related subsystems. Covered systems include the following: 1. Equipment room backboards and equipment racks 2. Station cable and terminating equipment 3. Telecommunications grounds and related components 1.02 RELATED WORK A. Section 27100 – Communications Cable and Equipment 1.03 REFERENCE STANDARDS A. ANSI/NFPA – National Electric Code B. Missouri State Electrical Code – Volumes 1 & 2 C. NEMA, UL, TIA/EIA, and ANSI Standards, where applicable standards have been established D. ANSI/TIA/EIA 606 1.04 SUBMITTALS A. Submit in accordance with provisions of Section 17000 and shop drawings of all materials proposed. B. Prior to installation, the Contractor shall provide samples of all label types planned for the project. These samples shall include examples of the lettering to be used. Samples shall be mounted on 8 1/2” x 11” sheets annotated explaining their proposed use. PART TWO – PRODUCTS 2.01 LABELS A. All labels shall be permanent and be machine generated (e.g., Brady or Panduit). No handwritten or non-permanent labels shall be allowed. Labels shall be Brady “I.D. Pro” or XC-Plus or approved equivalent. Labeling on backboards and/or equipment racks may be pre-cut adhesive type. B. Characters on all labels shall be black printed on a white background. C. Label size should be appropriate to the cable size(s), outlet faceplate layout, patch panel design, or other related equipment sizes and layouts. D. All labels to be used on cables shall be self-laminating, white/transparent vinyl, and be wrapped around the cable sheath. The labels shall be of adequate size to accommodate the circumference of the cable being labeled and properly self-laminated over the full extent of the printed area of the label. 2.02 DOCUMENTATION A. All labeling will be documented on shop drawings listing each data port and voice port with the cable(s) (telecommunication room number), the data patch panel(s) letter designation, the data port number(s). B. All labeling will be documented in electronic and printed copies listing all data ports and their corresponding room numbers. PART THREE – EXECUTION 3.01 GENERAL A. Clean surfaces before attaching labels. COMMUNICATIONS SYSTEM IDENTIFICATION AND LABELING 27 1200 - 1 B. Install all labels firmly. Labels attached to terminating equipment such as backboards, faceplates, 110 blocks, and patch panels shall be installed plumb and neatly on all equipment. 3.02 LABELING OF CABLING AND TERMINATION COMPONENTS A. Backboard and Equipment Racks 1. Backboards and equipment racks shall be labeled by the Contractor identifying the telecommunication room. Additionally, equipment racks shall have an alpha character after the room number unique to that particular communications closet. For example, TR1-A would be the first rack in TR1. 2. Character height shall be 1-inch (minimum). 3.03 FIBER OPTIC BACKBONE, RISER CABLES, AND TERMINATION COMPONENTS A. All fiber optic backbone and copper (inter-building, riser, and tie) cables shall be identified AT BOTH ENDS with a designation that identifies where the opposite end of the same cable terminates (e.g., equipment room or telecommunications room I.D.). In addition, labeling of all fiber optic cables shall include the number of fibers in the cable. B. Each fiber optic termination panel shall be clearly labeled indicating the destination of the cable(s) and the fiber number of each fiber position. The cable identifiers are to be secured to (1) the side and (2) the front cover of the panel enclosure. 3.04 STANDARD INFORMATION OUTLET (SIO) FACEPLATES A. All faceplates shall be clearly labeled indicating the destination of the cable(s) (telecommunication room number), the data patch panel(s) letter designation, the data port number(s) on the data patch panel(s), and the voice cable number(s). B. Telecommunications outlets are to be labeled (1) on the cover of the assembly and (2) on each cable terminated at that location. C. Station cables shall be labeled within two inches of the cable end. 3.05 DATA PATCH PANELS A. All data patch panels shall be clearly labeled indicating the telecommunication room number, the data patch panel letter designation, and the data port number on the data patch panel (ports 1 through 48). Each telecommunication room shall start with data patch panel ‘A’ and continue through the alphabet. B. Station cables at the patch panels shall be labeled within two inches of the cable end. C. A data port schedule for each telecommunication room shall be created in spreadsheet format (Excel) with the telecommunication room number, data patch panel letter designations, data port numbers, and room numbers identified in the spreadsheet. In addition, for each data patch panel port, a field shall be provided in the spreadsheet for Lincoln University OIT to manage the cabling infrastructure by recording the device and any special notes pertaining to the room utilizing the data cable terminated to the port. D. A sample of the data and voice port schedules shall be provided to Lincoln University OIT, in the cable record book and in electronic format (Excel spreadsheet), with final documents provided on the Project Drawings. 3.06 FIBER OPTIC CABLES AND TERMINATION COMPONENTS A. All fiber optic cables, termination enclosures and connector panels, and splice closures shall be clearly labeled. B. In addition, labeling of all fiber optic cables shall include the number of fibers in the cable. C. Each fiber optic termination panel shall be clearly labeled indicating (1) the destination(s) of the cable(s) and (2) fiber number of each fiber position. The cable identifiers are to be secured to (1) the side and (2) the front cover of the panel enclosure. COMMUNICATIONS SYSTEM IDENTIFICATION AND LABELING 27 1200 - 2 3.07 GROUND SYSTEM LABELING A. All grounds should be labeled as close as practical to the point of termination (for ease of access to read the label). Labels shall be nonmetallic and include the following statement: “WARNING: If this connector or cable is loose or must be removed, please call the building telecommunications manger.” Refer to ANSI/TIA/EIA 606 for additional labeling requirements. END OF SECTION COMMUNICATIONS SYSTEM IDENTIFICATION AND LABELING 27 1200 - 3 THIS PAGE INTENTIONALLY LEFT BLANK
© Copyright 2025 Paperzz