“Nebula” high pressure water mist system installation requirements 1ST FIX (Installing high pressure hose(s) to nozzle location(s) ceiling mounted. Mist Fire Suppression Ltd (MFS). will need to install 22mm high pressure hose(s) from the agreed pump position to the agreed ceiling nozzle locations – NB. This will have been agreed on site following a survey undertaken by MFS engineers and the client’s representative (this will normally be the building contractor. However, please ensure whom so ever on site is the main point of contact and who makes decisions on the clients behalf is in attendance). The high pressure hose(s) must be installed within the building fabric, albeit this is a ceiling mounted system there may be a need to run high pressure hoses from the pump position. This may require the hoses being run in 22mm high pressure hose floors, and or walls to the first nozzle position. The client or the clients representative must ensure complete freedom of access through the agreed routes to enable to run the high pressure hose(s) without any obstructions, i.e. all routes agreed must be open and accessible, (MFS do not undertake any building works). 2nd Fix Electrical Requirements – per pump Before the second fix installation can commence all water and all electrical supplies to every pump location must be permanent and live. Please see abortive call charges information at the foot of these instructions. All details shown below relate to a single pump installation. In the case of multi pump installations all the requirements detailed below will need to be repeated in each pump position. Elite Fire Safety require a NON RCD protected supply run in FP200 (2.5mm) fire retardant grade cable to a 20amp lockable (rotary type) switch at the agreed pump position. The supply is to be wired from the client’s consumer unit (Fuse Board) – 17th edition compliant. The Non RCD circuit to be protected at the fuse board with a C20 breaker (per pump). 20 amp lockable switch (Rotary Type) C20 breaker Mist Fire Suppression Ltd Manufacturers and installers of Nebula HPWM systems for Greater London and the South West of England London office: 0207 167 6560 Bude office: 01288 355787 Email: [email protected] Web: www.mistfs.co.uk 2nd Fix – continued Plumbing requirements – per pump 22mm copper incoming cold water supply to the pump only. Minimum incoming water pressure 1 Bar ¾” + handle water isolator valve IMPORTANT NOTE The ¾” BSP Valve must be NO FURTHER than 300mm from the agreed pump position to allow connection to the rear of the pump unit with a flexible hose. Flexible hose connection between pump and incoming water supply, NO FURTHER than 300mm apart Mist Fire Suppression Ltd Manufacturers and installers of Nebula HPWM systems for Greater London and the South West of England London office: 0207 167 6560 Bude office: 01288 355787 Email: [email protected] Web: www.mistfs.co.uk Nebula supply pump dimensions and weight Height – 400mm Length – 600mm Depth – 300mm Weight – 45 kilograms Nebula supply pump typically positioned adjacent to incoming water supply i.e. under-stair cupboard or similar. Nebula high pressure water mist nozzle, ceiling mounted. Activated by 57° frangible break glass. Maximum operating pressure 140 Bar. ‘K’ factor (flow) 3 – 12 litres Finish options Stainless steel Chromed brass 16 m² coverage per nozzle 4 metre diameter spray Installation options Mist Fire Suppression Ltd Manufacturers and installers of Nebula HPWM systems for Greater London and the South West of England London office: 0207 167 6560 Bude office: 01288 355787 Email: [email protected] Web: www.mistfs.co.uk Option 1 1st fix – Running high pressure Hose(s) Free & unhindered access for the high pressure hose run from the agreed pump position to the agreed spray head position. We require a clear unhindered access to the pump position. Any chasing etc. will need to have been completed prior to us undertaking the first fix. 2nd fix – Installation of pump(s), spray head(s) and commissioning of the completed system This will be MFS last visit – All testing/commissioning will be completed at the 2nd fix stage Before the second fix installation can commence all water and all electrical supplies to each and every pump location must be permanent and live. (As per the previous pages in this document). All pumps, ceiling mounted nozzle locations must be ready and accessible for the commissioning of the system. Option 2 Full install – All works completed in a single site visit All the 1st & 2nd fix requirements will be carried out on a single visit. NB this option will only be carried out following full up-front payment of the project All the information contained within this contractors pack is designed to ensure the seamless installation of the Nebula high pressure water mist fire suppression system and must be strictly adhered. This document must be read and understood by the client or client’s representative thus avoiding the likelihood of any abortive calls or possible additional charges for revisits. Abortive call charges will be made if; There is no permanent water supply There is no permanent electrical supply Pump positions are not cleared and available for pump installation Agreed pump enclosures (if required) have not been installed Pump enclosures (if required) are not the correct size Unhindered access for high pressure hose installation is not facilitated. Our current abortive call charge is £150.00 + vat per day and will be levied without exception if our works are affected, delayed or aborted. Please refer to our Terms and Conditions sent with this quotation. To alleviate any potential site issues, a site survey will always be undertaken and all pump positions, spray head positions and hose runs agreed with the on-site MFS engineer and the client or client’s representative. Once agreed a signature will be required from the client or client’s representative on our site survey sheet agreeing that all parties understand the pre installation requirements of the Nebula system. T: 0207 167 6560 Mist Fire Suppression Ltd. 27 & 27A, Darnley Road. Gravesend. Kent. DA11 0RZ [email protected] Mist Fire Suppression Ltd Manufacturers and installers of Nebula HPWM systems for Greater London and the South West of England London office: 0207 167 6560 Bude office: 01288 355787 Email: [email protected] Web: www.mistfs.co.uk
© Copyright 2026 Paperzz