FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway A I A H e a l t h c a r e G ro u p Introductions Presenters – Coffman Engineers • Scott M.Twele, P.E. Operations Manager, Fire Protection Engineering – San Diego • Aman Shah, P.E. Senior Engineer, Fire Protection Engineering – San Diego • Steven Dannaway, P.E. Engineer, Fire Protection Engineering– Los Angeles 2 Agenda Applicable Codes, AHJs, Jurisdiction • Occupancy Classification • Defend-In-Place + Smoke Compartments • Means of Egress • Suites • Vertical Openings • Hazardous Areas/Incidental Uses • Corridors • HVAC • Fire Protection Systems • Removal of Acute Care Services (OSHPD) Note: Red text = 2016 code change • 3 Fire Record 4 Applicable Codes and Jurisdiction California • OSHPD – CBC 1.10 provides authority • OSHPD 1 (Hospitals) • OSHPD 2 (Skilled Nursing + Intermediate Care Facilities) • OSHPD 4 (Correctional Treatment Centers) • Local Jurisdictions • • Outpatient MOB OSHPD 3 (Licensed clinics + freestanding buildings under Hospital License) Applicable Codes • California Building Standards • California Building Code (CBC), based on the International Building Code (IBC) • CFC, CEC, CMC, CPC, etc. • NFPA Standards • Referenced by Chapter 35 of the CBC/Chapter 80 of the CFC. • NFPA 101 Life Safety Code (CMS + TJC) 5 CMS + NFPA 101 – Life Safety Code • Enforced by Centers for Medicaid and Medicare Services (CMS) – Agencies with “Deemed Status” conduct evaluations on behalf of CMS – ex. “The Joint Commission” (TJC) • CMS official adoption of 2012 editions of NFPA 101 and NFPA 99 – Effective 07/05/2016 – Surveys use 2012 starting 11/01/2016 • What facilities must comply with NFPA 101? – Hospitals, Long-term care facilities, Ambulatory Surgery Centers, Hospice inpatient facilities, religious non-medical healthcare institutions, inclusive care of the elderly – Defined in CMS Final Ruling on adoption of 2012 NFPA 101 • • CMS amendments to LSC Design to both CBC and NFPA 101 recommended! 6 Occupancy Classifications Healthcare Facility Occupancy Classifications Use CBC NFPA 101 Inpatient (> 24 hrs) Group I-2 Healthcare – Ch. 18 Outpatient > 6 Incapable Group I-2.1 Ambulatory – Ch. 20 Outpatient 1 < x < 5 Incapable Group B Ambulatory CBC 422 Ambulatory – Ch. 20 Outpatient, 0 incapable Group B Business – Ch. 38 • CBC did not adopt 2015 IBC change: Group I-2 two separate “condition” groups. • Outpatient Facilities - Define # of patients “Incapable of Self-Preservation”. Infusion/Chemo/Dialysis often fall under this category. • Ambulatory Healthcare (NFPA 101): 4 or more patients incapable Note: CMS amendment to NFPA 101 - Chapter 20 applies to ASC with 1 or more patients Incapable of Self Preservation Other Occupancies • Many facilities also contain Group B, Group A, Group S, and/or Group F-1 occupancies 7 Multiple Occupancies and Occupancy Separations Occupancy Separation – Group I-2 (discussion applies to I-3 too) 2016 CBC • 2013 CBC: Group I-2 = 2-hour separation from all occupancies, 3-hours from F-1 • 2016 CBC eliminates requirement. Accessory, Non-separated, or Separated Occupancy approaches permitted (careful! NFPA 101 for Healthcare – still requires 2-hour!) • 2016 CBC adds exception 3: “No separation required between Group B, E, R-2 sleeping units and S-2 occupancies accessory to Group I-2, I2.1, and I-3 of Type I.” 2013 CBC • 2016 CBC Table 508.4 footnote added about F1 commercial kitchen and I-2 (not Group I-3) reduces to 2-hours. OSHPD typically requires Central Plant type rooms to be classified as Group F-1 (chiller, boiler, etc.) (3-hours) 8 Defend-In-Place: “Total Concept” 9 Defend-In-Place Concept • Compartmentation • Smoke barriers, evacuation zones may include one or more smoke compartments • Corridor integrity • Hazardous rooms/areas • Facility Emergency Plan + Staff Training • CBC/CFC and NFPA 101 require emergency plans for Group I-2 • The best LS strategy will not function properly without proper staff training + emergency plan. • Means of Egress/Evacuation • Refuge Area to accommodate patients • Exits available so relocated occupants are not trapped • Fire Protection Systems • Suppression (sprinklers) • Detection and Zoning of Systems (fire alarm + sprinklers) • NFPA 99 requires sprinkler zoning to align with evacuation zones, NFPA 72 in combination with CBC/CFC indirectly require this. 10 Smoke Compartments • • • Group I-2 and Group I-2.1: Stories used for patient sleeping or treatment or other stories with more than 49 occupants, regardless of occupancy/use. Existing Group I2.1 exceptions Group B Ambulatory: Aggregate area of one or more of Ambulatory Care Facilities > 10,000 sq. ft. 2016 CBC Change: Added exception 3 to CBC 407.5 that correlates to NFPA 101 exceptions for smoke compartments: New Exceptions Existing Exceptions 11 Smoke Compartment Section Red = smoke barrier Blue = 2-hour fire barrier 12 Smoke Compartments • Maximum Area per Smoke Compartment: 22,500 sq. ft. California did not adopt 2015 IBC changes to increase smoke compartment size to 40,000 sq. ft. Remains 22,500 sq. ft., same as NFPA 101. • Maximum “Smoke Barrier” Travel Distance = 200 feet to a smoke barrier door. • • Refuge area calculation – Slight Variation between CBC and NFPA 101. • Low hazard areas – patient rooms, treatment rooms corridors, waiting areas, etc. Refuge Area Calculations CBC NFPA 101 All Floors Stories w/bedridden patients 30 sf per bedridden patient + 6 sf for ambulatory care recipients and other occupants 30 sf per bedridden patient Stories w/o bedridden patients 6 sf per occupant (total OL) 13 Smoke Compartments • Two means of egress required from each smoke compartment. • Opposite Swinging Doors at cross-corridor conditions. • Exits are not required from each individual compartment but cannot have all exits into same smoke compartment. No dead-end compartments! 14 Smoke Compartments • The only exit from a room is not allowed to be directly across a smoke barrier. 15 Means of Egress Even with smoke compartments + defend-in-place, compliant exiting is still required per CBC Chapter 10. 16 Chapter 10 – Means of Egress • CBC 1008 Means of Egress Illumination • Group I-2, exit discharge exterior landings – Minimum 1 footcandle upon loss of any single lighting unit during normal conditions. • Group I-2 emergency illumination – Minimum 0.2 footcandle upon loss of any single lighting unit. • Emergency illumination required in new spaces • Electrical equipment rooms • Fire Command Center • Fire Pump Room • Generator Rooms • Public restrooms with area greater than 300 sq. ft. 17 Means of Egress – Egress Width • Group I-2 occupancies do not qualify for the reduced egress factor exception of CBC. • 0.2 inches/occ. for doors/horizontal components and 0.3 in./occ. for stairways. Minimum Egress Width Requirements Egress Component Egress Width Stairways/Ramps 44 inches between handrails (I-2/I-2.1) (CA amendment) Doors 44-inch clear width – serving bed/gurney occ. (I-2/I-2.1) 32-inch clear width – otherwise Corridors 96 Inches – Group I-2, serving bed or gurney occupants or nonambulatory person 72 inches – Group I-2.1 or Group B Ambulatory, serving means of egress for bed or gurney occupants (Ch. 10) 96 inches – Group I-2.1 or Group B Ambulatory, corridors serving bed/gurney movement during normal day-to-day operations (OSHPD 3 – CBC Chapter 12) 18 Means of Egress – Horizontal Exits Group I-2: 2/3 exits via HE Other: 1/2 exits via HE 19 Means of Egress – Door Locking • NFPA 101 and IBC allow locked egress doors under certain conditions in healthcare occupancies. • CBC prohibits locked egress doors in the means of egress – SFM amendment • • • Delayed egress Local alarm at Unlocked egress door Restrict Access into Space • 2016 CBC – Group I-2 occupancies can pass through two doors with delayed egress • Relocation vs. Exiting – AMC? 20 Means of Egress – Other Considerations • Daylighting the basement – CBC 407.4.1.2 (California amendment) Group I-2 occupancies below grade • An exterior exit door is required at the basement level • • Egress Through Stairways on First Floor (OSHPD Interpretation): The means of egress on a Level of Exit Discharge is not permitted to egress through an exit stairway. A separate path of travel to an exterior egress door is required (not through the stairway). • In other than Group I-2 occupancies, 2016 CBC allows means of egress to pass through enclosed elevator lobbies. Prohibited in Group I-2 occupancies. Smoke containment system (smokeguard) is an option. 21 Means of Egress – Habitable Rooms • CBC 407.4.1 Group I-2 – Habitable Rooms require direct access to the corridor or shall be located within a “Care Suite.” • • OSHPD CAN 2-407.4.1 clarifies application of requirement Habitable rooms are: • Patient Areas: sleeping rooms, patient treatment rooms, staff • Staff areas: Nourishment rooms, clean/soiled utility rooms, lounges, locker rooms, work areas, consult rooms, offices, workstations, sleeping rooms, etc. • Visitor Areas: Waiting rooms, visitor lounges, etc. • Not included: • Individual bathrooms, closets, housekeeping rooms/similar spaces • Control rooms in radiology/imaging spaces, medication rooms from nursing stations, mixing rooms in pharmacies, small storage rooms, small clean/soiled linen storage rooms where no issuing or sorting rooms, MEP utility rooms • OSHPD CAN 2-407.4.1 additional clarifications • MRI + Radiology rooms can be defined as “care suites” – good! • Egress through Anteroom to corridor is permitted without a suite. 22 Suites – Group I-2 and Group I-2.1 Sleeping • Non-Sleeping • Non-Patient Care (NFPA 101). • • • 1-hour fire barrier separation from remainder of building, including adjacent suites. • OSHPD CAN 2-407.4.1 – MRI and Imaging Suites • Non-Patient Care Areas, CBC vs. NFPA 101 • Sleeping Suite Max Size (CBC 407.4.4.5.1) • 5,000 sq. ft. basic • 7,500 sq. ft. fully sprinklered • 10,000 sq. ft. fully sprinklered + smoke detection throughout suite. Non-Sleeping Suite Size (CBC 407.4.4.5.1) • 10,000 sq. ft. 23 Suites – Means of Egress • Non-Suite areas cannot egress through suites. • CBC amendment – the fire-rated corridor requirements do not apply in sprinklered Group I-2 suites. NFPA 101 and IBC do not require firerated corridors in Group I-2/Healthcare occupancies. 24 Suites – Means of Egress Suite Egress Requirements Type Two Means of Egress Travel Distance to Suite Boundary Sleeping Greater than 1,000 sf Non-Sleeping Greater than 2,500 sf CBC • 100 feet (one intervening room) • 50 feet (two intervening rooms) • 100 feet (two intervening rooms, fully sprinklered, smoke detection) NFPA 101 • 100 feet (NFPA 101) 25 Vertical Openings 26 Vertical Openings • CBC 404.5 Two-Story Atrium, Group I-2 • Smoke control is now required in 2-story atriums in Group I-2. I-2.1? • Other occupancies, three stories or more (same) Vertical Opening Options CBC – 712, 1019 NFPA 101 – 8.6 Atrium • I-2: Smoke control req. • Other: Smoke control > 3 stories Atrium • Smoke control req. Two-story Unprotected Opening • Prohibited in I-2, I-2.1 • Other occupancies, now permitted to contain an open exit access stairway Convenience Opening • Permitted in healthcare (I-2) • Open egress stairways prohibited No similar option Communicating Space Prohibited in healthcare (I-2) Would be allowed by CBC, no specific term/code section Partial Enclosure, Two-Story Opening Exit Access Stairways • Prohibited in I-2, I-2.1 • Multiple options for other occupancies Exit access stairways only permitted by one of the other options in NFPA 101, 8.6. 27 Vertical Openings • Consideration to both NFPA 101 and CBC compliance • Separation of floors with fire-rated construction to avoid openings: • • • • • Walls Vertical Shutters/Horizontal Sliding Doors (Openings) Doors complying with ASTM E 119 (equivalent to wall) Tyco Model WS sprinklers (Alternate Method) Occupancy classification/separation – I-2 occupancy more restrictive. Other classification allows for additional options. 28 Hazardous Areas – 2016 CBC 29 Hazardous Areas – NFPA 101 30 Hazardous Areas • • • Group I-2 and I-2.1: One-hour separation is typical. Other occupancies. sprinkler protection may be acceptable in lieu of 1-hour rating. Where sprinkler protection is permitted in lieu of a 1-hour rating, both codes require “smoke resistive construction” to separate these rooms. • • • • Full height walls Smoke Dampers at air transfer openings. Not req’d at duct penetrations. Doors shall be self-closing or automatic closing. No louvers. Undercuts compliant with NFPA 80 (3/4-inch). OSHPD classifies CUP rooms like boiler/chiller rooms as Group F-1 occupancies regardless of CBC Table 509. Occupancy Separation from Group I-2 = 3-hours. 31 Corridors – Construction Reqs • CBC vs. NFPA 101 vs. IBC Fire partitions vs. smoke-resistive vs. smoke partitions • CBC includes exceptions that reduce corridor protection to align with NFPA 101. • 1-hour fire partitions • FSDs (multiple exceptions) • Exceptions: Most doors can be non-rated. Do not require selfclosing or automatic closing. devices Smoke Resistive (no louvers). Positive Latching req. Roller latches prohibited • Doors must be self-closing/autoclosing if they swing into the “required width” of corridor. 32 Corridors • CBC 407.3.2 Corridor Glazing • Unlimited glazing permitted with 20-minute rated fire-protection glazing in approved frames + 1,296 sq. in. max panel. 2016 CBC 2013 CBC 33 Corridors – Obstructions • OSHPD has been restrictive about allowing equipment/storage within the corridor. • NFPA 101 now includes allowances/criteria for wheeled equipment in the corridor. (equipment/carts in use, furniture, medical carts not in use, patient lift and transport equipment not in use). • Conflicts between program/owner reqs and OSHPD enforcement of CBC. Wheelchair alcoves or gurney areas have been required to be separated from the corridor. Example of non-compliant storage arrangement open to corridor. 34 Corridors – Spaces Open to Corridor • Areas open to the corridor – Staff supervision + smoke detection in the corridor + area • Waiting areas • Nursing Stations • Gift Shops • Nursing Home/Psychiatric facility allowances 35 HVAC System – Fire/Smoke Dampers • Fire Barriers: Fire/smoke dampers required at all penetrations (California) • Corridors: Fire/smoke dampers required at penetrations. Exception for fully ducted system (minimum thickness + ducts = steel) where duct system does not serve corridor. Use this exception to strategically minimize FSDs • Smoke Barriers: IBC – Smoke dampers not required at smoke barrier penetrations for fully ducted system in sprinklered building. Not adopted by CBC • Exit Enclosures, Exit Passageways: Penetrations of exit components prohibited except those items necessary for exit component (sprinkler, fire alarm, lighting, ventilation, etc.). FSD Actuation Methods: Duct detectors vs. full area smoke detection (five methods in CBC 717. 36 HVAC System – Fire/Smoke Dampers HVAC System – Sequence of Operations • Early discussion – understand Owner requirements for HVAC system operation during a fire event. • What areas must HVAC system continue to operate? • Is full HVAC shutdown acceptable? • Critical Care Areas or Hazardous Exhaust? • Allows HVAC design development to achieve objectives without significant cost and complication. 38 Fire Protection Systems – Fire Alarm • Notification – Discuss with Owner and AHJ • Public vs. Private Mode Signaling • (CA) Audible notification appliances – chimes or similar sounding devices in patient areas. • (CA) In patient areas, visible notification appliances only may be acceptable. • CBC 915 Carbon Monoxide Detection • Section relocated from CBC 420 and increased in scope. • In certain conditions, CO detection required in Group I-2, I-4, R sleeping/dwelling units and Group E classrooms. 39 Removal of Acute Care Services • • • Based on OSHPD CAN 1-6.1.4.5.1 Existing facilities that do not satisfy SPC compliance can be decommissioned. OSHPD has laid out the process for removal of acute care services. General takeaways • “Split Jurisdiction” is not permitted multiple structures that are part of the same Detached Hospital Building • Exterior Wall or Fire Wall Separation And Seismic Separation is required for a building to be defined as a separate Freestanding nonhospital building. Only Free standing non-hospital buildings can be removed from OSHPD jurisdiction and moved to the Local Jurisdiction. • Buildings on the same lot cannot be applied to separate buildings that are under OSHPD and local jurisdiction. • Smoke Compartments + Egress from Hospital • Utilities must originate in hospital and not pass through decommissioned bldg. to access hospital. • Utilities can only be shared by bldgs. under OSHPD jurisdiction. Local jurisdiction require separate utilities. • Acute care services + patient access 40 Closing Thoughts Healthcare Facilities have a good fire record Credit the development of model codes and standards IBC and LSC for mitigation of the life safety hazards in such facilities. IBC/CBC trending towards NFPA 101 Safety features have been proven to establish a high level of safety in facility. A/E/C responsible for correctly implementing established safety features. Compartmentation, Fire Protection Systems, Means of Egress, Emergency Plan + Staff Training: TOTAL CONCEPT! [email protected] [email protected] [email protected] 41
© Copyright 2026 Paperzz