TEMPUS ENERGY: AC-GRIDS AND DC-GRIDS 1: Historical evolution from AC-grids to DC-grids Although in the early years of electricity production a lot of electrical grids were DCgrids, nowadays the great majority of the electrical grids are AC-grids. This switch from DC-grids to AC-grids has a number of technical reasons. Due to the need for a commutator, it is very difficult to build DC-generators generating high voltages. Especially when generating higher voltages (of for instance 24 kV), it is easier to construct alternators (AC-generators). An additional advantage arises when considering electrical motors. In general, constructing AC-motors (like the three phase induction motor) is easier and cheaper than constructing DC-motors. Moreover, a lot of AC-motors require less maintenance. When using AC, it is possible to use transformers. Due to these transformers, a generated voltage level can be transformed to a higher voltage level of 70 kV, 220 kV or even 380kV. These transformers have a long life expectancy (more than 30 years) and they have a high efficiency (even more than 99.9%). Transformers have a straightforward construction and they require almost no maintenance (no moving parts). When using a high voltage grid to inject power into a medium or a low voltage grid, transformers can be used to transform the voltage level to a lower level (for instance from 380 kV to 70 kV or from 11 kV to 400 V). By using transformers, it is possible to supply power at a low voltage level of 230 V and/or 400 V to a customer (reducing the risks related with electricity) and to use high voltage grids to transport large amounts of power over larger distances (reducing the losses in the grid). It is easier to interrupt AC-currents since these currents have two zero-crossings in one single period whereas a DC-current has no zero-crossings. When opening an electrical contact, the zero-crossing can be used to extinct the arc and it is sufficient to prevent re-ignition of the arc. When considering AC voltages, the insulation level of cables, appliances and machines must withstand the peak value and not only the RMS value. This peak value equals √2 or 1.41 times the RMS value. 2: HVDC-grids as an emerging technology Although all these technical aspects explain why nowadays the large majority of the grids are AC-grids, it is wrong to conclude that using DC to transport electrical energy is old-fashioned and the use of DC only has disadvantages. Using DC, can be an emerging and useful technological challenge. 2.1: Losses in AC and DC grids In order to understand why DC-grids still exist, it is useful to calculate and compare the energy losses in a single phase AC-grid, in a three phase AC-grid and finally in a DC-grid. A single phase grid contains two conductors each having a cross section S1. The three phase grid contains three conductors each having a cross section S3. The DC-grid contains two conductors each having a cross section S0. In order to make an appropriate comparison, assume these three types of grids use the same amount of copper (or aluminum). This implies 2 𝑆1 = 3 𝑆3 = 2 𝑆0 . (1) In order to have the same production cost when considering the conductors of a grid, also assume these three types of grids have the same type of insulation withstanding the same voltage level. V1 is the RMS value of the voltage of the AC-grid. V3 is the RMS value of the phase voltage of the three phase grid. V0 is the DC-voltage of the DC-grid. This implies √2 𝑉1 = √2 √3 𝑉3 = 𝑉0 . (2) Assuming these three grids transport the same power implies 𝑉1 𝐼1 = 3 𝑉3 𝐼3 = 𝑉0 𝐼0 . (3) Here, I1 is the RMS value of the current in the single phase AC-grid. I3 is the RMS value of the current in the three phase AC-grid. I0 is the DC-current in the DC-grid. By combining (2) and (3), one obtains that 𝐼1 = √3 𝐼3 = √2 𝐼0 . Based on this information, it is possible to calculate the Joule losses in the three grids. Here, R1 is the ohmic resistance of a conductor of the single phase AC-grid. Based on the law of Pouillet, R1 is inversely proportional with S1. R3 is the ohmic resistance of a conductor of the three phase AC-grid and R3 is inversely proportional with S3. R0 is the ohmic resistance of a conductor of the DC-grid and R0 is inversely proportional with S0. The Joule losses equal: - in case of the single phase grid: in case of the three phase grid: in case of the DC-grid: 𝑃𝐽1 = 2 𝑅1 𝐼12 . 𝑃𝐽3 = 3 𝑅3 𝐼32 . 𝑃𝐽0 = 2 𝑅0 𝐼02 . Verify that 𝑃𝐽3 = 0.75 𝑃𝐽1 . The Joule losses in a three phase grid are only 75% of the Joule losses in a similar single phase grid transporting the same power. This explains why three phase grids instead of single phase grids are used when transporting electrical energy. Finally, compare the Joule losses of a DC-grid and a three phase AC-grid. Verify that 𝑃𝐽0 = 0.67 𝑃𝐽3 . The Joule losses in a DC-grid are only 67% of the Joule losses in a similar three phase AC-grid. This explains why DC-grids are sometimes used when transporting large amounts of electrical energy over large distances (more than 750 km). 2.2: Investment costs related with HVDC-grids A disadvantage related with the use of DC-grids to transport electrical energy is the lack of transformers allowing to increase or decrease the voltage level. In practice, the situation visualized in Figure 1 combines the use of DC-grids and AC-grids. transformer rectifier inverter transformer DC Figure 1: Basic structure of a HVDC-grid Starting from a classical three phase AC-grid, the voltage level is increased using a transformer. A very high AC-voltage is obtained which will be rectified giving a very high DC-voltage (originally mercury-vapor rectifiers were used, nowadays semiconductor rectifiers are used). The very high DC-voltage will be used to transport the electrical energy over a long distance (HVDC: High Voltage Direct Current). At the other side of the DC-grid, an inverter converts this DC-voltage back to an ACvoltage. Using a transformer, the AC-voltage level is decreased and the power is injected into a classical three phase AC-grid. It is not only possible to transport active power from the left side to the right side. In case the left power electronic converter does not operate as a rectifier but as an inverter and in case the right power electronic converter does not operate as an inverter but as a rectifier, active power is transported from the right side to the left side. This is an emerging technology since it is not obvious to construct a rectifier and an inverter dealing with such high voltages. Such a rectifier and such an inverter require a considerable investment. This investment can only be justified when the energy is transported over a very long distance and the transported power is sufficiently large (for instance 2000 MW). Indeed, when preconceiving the energy losses, less copper (or aluminum) is required when using a HVDC-grid instead of a three phase AC-grid. However, only for sufficiently long distances the reduced use of copper is able to justify the installation cost of the rectifier and the inverter. This situation is visualized in Figure 2 (information provided by ABB). The DC terminal cost is much higher than an AC terminal cost but the DC line cost is lower implying a lower total investment when the distance is sufficiently large. Figure 2: Comparison investment of a HVDC grid and an AC grid Figure 3: Rectifiers and inverters used in a HVDC installation 3: Applications of HVDC-grids HVDC-grids are used to transport large powers over large distances. For instance, a HVDC-grid in Brazil transports power of the Itaipu hydroelectric power plant to the region of Sao Paulo. This installation contains two ± 600 𝑘𝑉 bipoles having a total rated power of 6300 MW and transporting the power over a distance of 780 km. Using HVDC-grids, it is also possible to connect two AC-grids having a different frequency. For instance in Japan (as visualized in Figure 4), the eastern and northern parts of Honshu and Hokkaido have a grid frequency of 50 Hz whereas the western Honshu, Shikoku, Kyushu and Okinawa operate at 60 Hz. The boundary between these two regions contains four back-to-back HVDC-substations operating as frequency converters (in case the rectifier and the inverter which are visualized in Figure 1 are located in the same station, a back-to-back HVDC-system is obtained). For instance the Higashi-Shimizu frequency converter operates with a DC voltage of 125 kV and has a maximum power of 300 MW. Figure 4: HVDC-grids in Japan Moreover, DC-grids also allow to interconnect grids having the same nominal frequency but which are not synchronized with each other. For instance, there is a DCcable interconnecting the British grid and the continental European grid. This HVDC Cross-Channel is a 2000 MW system and has a total length of 73 km containing 46 km submarine cables (an operating voltage of 270 kV). 3.1: DC-grids and renewable energy generation HVDC allows to transport large amounts of electrical energy over large distances. This is useful to transport the energy of large remotely located hydroelectric power stations (for instance the Three Gorges Dam in China, the Itaipu dam in Brasil) to the industrialized world. More recently and focused to the transportation of powers which are not that extremely high, is the use of HVDC light (http://www.abb.com/hvdc) which is used to transport the energy coming from onshore and offshore wind turbine parks. When considering the Thornton Bank (offshore, actually farshore wind turbine park) in Belgium, a three phase AC-grid having a voltage level of 150 kV is used to transport the power to land. For instance the Gotland project in Sweden (onshore wind energy) uses the HVDC light technology to transport the generated power. 4: HVDC-technology 4.1: A basic HVDC-installation Figure 5 visualizes a basic HVDC-installation. Converter 1 is a three phase six pulse thyristor rectifier and having a firing angle 𝛼1 smaller than 90°, the DC-voltage 𝐸𝑑1 is positive. Since the DC-current 𝐼𝑑 is positive, converter 1 behaves as a DC power source implying power is transported from the AC-line 1 to the DC-link. Figure 5: HVDC-installation Converter 2 is also a three phase six pulse thyristor rectifier but the thyristors are mounted upside down in comparison with converter 1. Notice however the anodes have a firing angle 𝛼2 larger than 90° implying the DC-voltage 𝐸𝑑2 is also positive. Since the DC-current 𝐼𝑑 is positive, converter 2 behaves as an inverter implying power is transported from the DC-link to the AC-line 2. In case 𝛼1 is larger than 90°, 𝐸𝑑1 is negative but 𝐼𝑑 remains positive. This implies converter 1 behaves as an inverter since power is transported from the DC-link to the AC-line 1. Since 𝛼2 is smaller than 90°, also 𝐸𝑑2 is negative. This implies converter 2 behaves as a rectifier since power is transported from the AC-line 2 to the DC-link. When using the HVDC-installation visualized in Figure 5, a power reversal occurs by changing the sign of the DC-voltage since it is not possible to reverse the sign of the DC-current. 4.2: Modeling the HVDC-grid and the power flow In Figure 5, the entire DC-line is modeled as a resistor. In general, a high voltage line can be modeled as a transmission line where an infinite number of infinitesimal small parts are cascaded. Figure 6 models such an infinitesimal small part of a transmission line. It is quite common to neglect the parallel resistances (1/𝐺 ). 𝑑𝑥 (especially when considering overhead lines). When considering AC transmission lines, the series inductances and the parallel capacitances must be taken into consideration. Due to this series inductances, a voltage drop occurs. Due to the parallel capacitances, a capacitive current is flowing which can reduce the transport capacity for active power of the transmission line. When considering a DC-line, the inductances and the capacitances have no impact on the steady state behavior implying the DC-line can indeed be modeled as a lumped resistor as visualized in Figure 5. No voltage drop across the inductance occurs and the transport capacity is not reduced by reactive power. Figure 6: Infinitesimal small part of a transmission line When considering Figure 5, the DC-current equals 𝐼𝑑 = 𝐸𝑑1 − 𝐸𝑑2 . 𝑅 By changing the firing angles 𝛼1 and 𝛼2 , the voltages 𝐸𝑑1 and 𝐸𝑑2 change. This implies 𝐼𝑑 changes and the transported power can be changed rapidly. Not only the magnitude of the transported power can be changed, by changing the sign of the voltages also a reversal of the sign of the power can be obtained. This is useful when using a HVDC-grid to interconnect two AC-grids in order to maintain the power equilibrium. 4.3: The DC-voltage In case the rectifier is a three phase six pulse rectifier with a firing angle 𝛼 = 15°, the DC-voltage is visualized in Figure 7 (neglecting the commutation overlap). This voltage is not constant, this voltage is a six pulse voltage. Figure 7: DC-voltage obtained by the rectifier Using smoothing inductors 𝐿1 and 𝐿2 as visualized in Figure 8, a ripple-free DCvoltage 𝐸𝑑 is obtained. The voltage ripple of 𝐸1𝐺 appears across 𝐿1 and the voltage ripple of 𝐸2𝐺 appears across 𝐿2 . Figure 8: HVDC-installation having inductors at DC-side 4.4: Impact on the AC-grid Notice converter 1 and converter 2 in Figure 5 and Figure 8 can only operate when the AC-grids line 1 (or network 1) and line 2 (or network 2) are available. The grid voltages are needed to obtain thyristor commutation. The grid voltages are needed when firing the gate of a thyristor and these grid voltages are also needed to turn off a previously conducting thyristor (due to the high voltages, each “thyristor” is composed of several thyristors connected in series and such a group of thyristors is called a valve, these series connected thyristors are triggered simultaneously at their gates behaving as one single super-thyristor). Notice converter 1 and converter 2 consume reactive power which has to be provided by the AC-grid (irrespective of the direction of active power flow i.e. irrespective whether the converter behaves as a rectifier or as an inverter). Moreover, the AC-grid current is not a sine. The grid current not only contains a 50 Hz fundamental current, it also contains harmonics. 4.5: Monopole and bipolar HVDC-implementations The HVDC-implementation of Figure 5 and Figure 8 contains a DC-grid having two conductors each having a cross section 𝑆0 . In order to obtain a further reduction of the required amount of copper (or aluminum), it is also possible to use a ground return as visualized in Figure 9 by connecting the converters with the earth using electrodes. Figure 9: HVDC monopole system with earth return Especially for long-distance transmission, using the earth and/or the sea as a return conductor is cheaper than using a dedicated neutral conductor. Notice however using the ground and/or sea as a return conductor also has its disadvantages: - there is electrochemical corrosion of long buried metal objects like pipelines, underwater earth-return electrodes in seawater may produce chlorine or otherwise affect water chemistry, the current path may result in a magnetic field affecting magnetic navigational compasses for ships passing over an underwater cable. In order to reduce the earth and/or sea current, bipolar transmission lines can be used as visualized in Figure 10. Bipolar transmission lines possess a positive and a negative line having a common ground return. The positive line is connected with converter 1 and converter 2. The negative line is connected with converter 3 and converter 4. Since converter 1 and converter 3 are mounted upside down and since 𝛼1 = 𝛼3 , the voltages 𝐸𝑑1 and 𝐸𝑑2 have an opposite sign. Also converter 2 and converter 4 are mounted upside down and they have the same firing angles 𝛼2 = 𝛼4 . Figure 10: Bipolar HVDC transmission line As visualized in Figure 10, converter 1 and converter 3 act as rectifiers since 𝐸𝑑1 𝐼𝑑1 and −𝐸𝑑2 𝐼𝑑2 are positive. Converter 2 and converter 4 act as inverters. Power is flowing over both lines from AC-network 1 to AC-network 2. The total ground current equals 𝐼𝑑1 − 𝐼𝑑2 which is usually small since the converters maintain equals currents in the positive and negative lines. Consequently, corrosion of underground pipes … is minimized. Moreover, the same transmission line towers can carry two lines which doubles the transported power with a limited increase in capital investment. Finally, if the power flow in one line is interrupted, the other line can continue to function (delivering half the normal power). Figure 11: Bipolar HVDC transmission line Figure 11 shows the same bipolar HVDC transmission line as Figure 10 but using different firing angles, the direction of active power flow is reversed. 4.6: Practical implementation of a HVDC-connection Figure 12 visualizes a practical implementation of a HVDC-connection (a monopole system). Notice AC-network 1, AC-network 2, transformers T1 and T2, the two converters, the single wire HVDC-connection and the two ground electrodes. Finally, notice a microwave communications link useful to communicate about the power that must be transported from one side to the other side. Figure 12: Practical implementation of a HVDC-connection As already mentioned, converter 1 and converter 2 each consume reactive power at AC-grid side. In order to limit the reactive power supplied by the grid, reactive power sources 𝑄1 and 𝑄2 are needed. In principle, these reactive power sources can be capacitors. However, taking the high voltage level and the large number of required MVAR’s into account, the use of a synchronous capacitors is more common. A synchronous capacitor is an overexcited synchronous motor generating reactive power. Such a synchronous motor is mechanically unloaded i.e. the consumed active power is as small as possible. By controlling the excitation current, the generated reactive power can also be controlled. In both AC-grids, three phase series-resonant LC-filters are placed in parallel with the grid voltage. These series-resonant filters reduce the harmonic components in the grid current. Indeed, by supplying (part of) the harmonics required by the rectifier/inverter (e.g. 5th, 7th, 11th, 13th harmonics), these harmonics need not be supplied by the ACgrid anymore. Since the DC-voltage at the DC-side of the rectifier/inverter has a ripple (as visualized in Figure 7), also at DC-side passive filters are placed to obtain a constant voltage 𝐸𝑑 . To obtain this goal, in Figure 8 two inductors (L1 and L2) are placed. In Figure 12, more complex passive filters are used. A first series-resonant LC-filter tuned at 300 Hz (C6 and L6) and a second series-resonant LC-filter tuned at 600 Hz (C12 and L12) are used to short circuit the 300 Hz and the 600 Hz components in the DC-voltage. These series LC-filters in combination with inductors L provide a constant voltage 𝐸𝑑 . Figure 13: HVDC electricity pylon 5: HVDC-light technology The classical HVDC technology connects two AC networks each having a stable grid voltage. These grids allow the natural line commutation of the thyristor-controlled converters and they supply the reactive power consumed by the converters. 5.1: The use of a static generator Figure 14 visualizes a static three phase generator. At the DC-side, two capacitors 𝐶1 are connected in series. The main part is a self-commutated converter containing six IGBT’s and six diodes. Using this converter, the DC-voltage can be converted into a PWM voltage. Using inductances 𝐿1 and carrier-frequency series filters (𝐿2 , 𝐶2 and 𝑅2 ), a sine voltage is obtained. The self-commutating converter of Figure 14 is able to transmit active power from the DC-side to the AC-side and vice versa. Moreover, the converter is able to supply reactive power to the AC-grid or to consume reactive power from the AC-grid (which is not the case when considering the line commutated converters visualized in Figure 12). At DC-side, the total voltage 𝐸𝐻 is the sum of two voltages 𝐸𝑑 = 𝐸𝐻 ⁄2. There is a neutral point N between the two capacitors 𝐶1 . PWM voltages appear between the terminals a, b, c and N. These PWM voltages fluctuate between +𝐸𝑑 and −𝐸𝑑 at the carrier frequency 𝑓𝐶 . The fundamental of the line to neutral voltage (usually 50 Hz or 60 Hz) is available between the terminals d, e, f and N. The carrier frequency 𝑓𝐶 and the harmonics are filtered out by 𝐿1 , 𝐿2 , 𝐶2 and 𝑅2 . Figure 14: Static generator 5.2: A basic HVDC-light installation Figure 15 visualizes a HVDC-light installation. Reactors 𝑥, corresponding with inductances 𝐿1 in Figure 14, connect a three phase power grid with converter 1. A DClink, modeled as a resistance 𝑅, connects converter 1 and converter 2. Converter 2 supplies power to the load by way of reactors 𝑥 (corresponding with inductances 𝐿1 in Figure 14). In Figure 15, the carrier-frequency series filters are omitted to simplify the circuit. In case the load in Figure 15 is replaced by e.g. wind turbine park, a reversal of the active power flow occurs and power is flowing from converter 2 to converter 1. Figure 15: HVDC-light installation 5.3: Power control in a HVDC-light installation: steady state [a] [b] Figure 16: Phasor diagrams of a HVDC-light installation Figure 16 [a] visualizes the phasor diagram of the voltages and the line current for phase 𝑎 in Figure 15 at grid side. Suppose voltage 𝐸1𝑁 leads voltage 𝐸4𝑁 by 𝜃1 degrees. The active power consumed by one single phase of converter 1 equals 𝑃= 𝐸1𝑁 𝐸4𝑁 𝑠𝑖𝑛𝜃1 . 𝑥 Here, P is the power for one single phase, 𝐸1𝑁 and 𝐸4𝑁 are RMS values of phase voltages. The magnitude and the phase of 𝐸1𝑁 are imposed by the grid. Since 𝑥 is fixed, it is possible to adjust the magnitude of 𝐸4𝑁 and the angle 𝜃1 in order to obtain the required P. Since there are two degrees of freedom (𝐸4𝑁 and 𝜃1 ), it is possible to operate at unity power factor i.e. the grid current 𝐼1 is in phase with 𝐸1𝑁 (as visualized in Figure 16). Since the power of one single phase equals 𝑃 = 𝐸1𝑁 𝐼1 , the magnitude of 𝐼1 is known implying also 2 𝐸4𝑁 = √𝐸1𝑁 + 𝑥 2 𝐼12 is known. To obtain the required 𝑃, also 𝜃1 is known. Figure 16 [b] visualizes the phasor diagram of the voltage and the line current at load side for phase 𝑎 in Figure 15. Suppose the current 𝐼𝑎 in phase a lags an angle 𝜃𝑎 with respect to 𝐸𝑑𝑁 . The voltage drop across the reactance 𝑥 equals 𝑗𝑥𝐼𝑎 implying 𝐸𝑎𝑁 = 𝐸𝑑𝑁 + 𝑗𝑥𝐼𝑎 . In Figure 16 [b], 𝐸𝑎𝑁 leads 𝐸𝑑𝑁 by 𝜃𝑏 degrees implying the active power P flows from converter 2 to the load. The power P for one single phase equals 𝑃= 𝐸𝑎𝑁 𝐸𝑑𝑁 𝑠𝑖𝑛𝜃𝑏 = 𝐸𝑑𝑁 𝐼𝑎 𝑐𝑜𝑠𝜃𝑎 . 𝑥 𝐸𝑎𝑁 and 𝐸𝑑𝑁 are phase voltages. Since the losses in the converters (and also all other losses) are neglected, a total power 3 𝑃 is transported along the DC-connection. This implies 𝐼𝑑 = 3𝑃 . 𝐸𝐻 Summarizing, when considering a steady state condition and neglecting all losses, 3𝑃 =3 𝐸1𝑁 𝐸4𝑁 𝐸𝑎𝑁 𝐸𝑑𝑁 𝑠𝑖𝑛𝜃1 = 𝐸𝐻 𝐼𝑑 = 3 𝑠𝑖𝑛𝜃𝑏 . 𝑥 𝑥 In order to prevent clipping of the peaks of the sinusoidal waveshapes, the peak value of the line-to-neutral voltage must never exceed 𝐸𝐻 ⁄2. In case the peak value of this line-to-neutral voltage equals 80% of 𝐸𝐻 ⁄2, the effective value of the line-to-line voltage equals 𝐸𝐿𝐿 = √3 1 0.8 𝐸𝐻 √2 2 implying 𝐸𝐻 ≈ 2 𝐸𝐿𝐿 . 5.4: Power control in a HVDC-light installation: transient behavior Under steady-state conditions, the active power of the load is constant. When losses are neglected, the same power is transported by the DC-connection (implying a constant 𝐸𝐻 and a constant 𝐼𝑑 ) and this power is consumed by converter 1. In case the power consumed by the load decreases while 𝐸4𝑁 and 𝜃1 remain constant, the power input to the DC-cable will be larger than the power output. The excess of energy will be stored in the capacitors 𝐶1 implying a fast increase of the voltage 𝐸𝐻 . The control system of converter 1 will detect this increase of 𝐸𝐻 and will adjust 𝐸4𝑁 and 𝜃1 in order to decrease the active power extracted from the AC-grid by converter 1. Finally, the DC-voltage 𝐸𝐻 will remain close to its nominal value. This way of controlling the active power flow avoids the need for a communication link between the two converters as it is the case for the classical HVDC-approach of Figure 12. 5.5: Practical applications of the HVDC-light technology HVDC-light mainly has the same applications as the classical HVDC technology. It is possible to transport power over large distances, it is possible to connect AC-grids having a different frequency, it is possible to connect grids which are not synchronized with each other. Notice however, the HVDC-light technology has a lower power rating. The first commercial HVDC-light transmission system connects an onshore wind power plant in Gotland (a Swedish island in the Baltic Sea) to the city of Visby. This approach allowed to use underground cables instead of overhead transmission lines. This HVDC-light project is commissioned in 1999 (so much more recent than the classical HVDC-technology) having a power rating of 50 MW using a DC voltage of ±80 𝑘𝑉 over a distance of 70 km (ABB Gotland HVDC light). Figure 17: HVDC-light cable
© Copyright 2025 Paperzz