Toshiba JK Series Medium Voltage OEM Power Cells

MEDIUM VOLTAGE VACUUM CONTACTOR
T300MVi
JK OEM POWER CELLS
Reliability in motion
Reliability in motion
400 AMPERE AT 2300-6600
VOLTS (7200 VOLT MAX)
DRAWOUT AND FIXED APPLICATIONS
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
JK OEM PART NUMBER
GCV5084L03G01
GCV5084L03G02
GCV5084L03G03
GCV5084L03G04
GCV5084L04G00
GCV5084L04G01
GCV5084L04G02
GCV5084L05G01
GCV5084L05G02
GCV5084L06G01
GCV5084L06G02
DESCRIPTION
Fix type OEM
with single
barrel fuse clips
Fix type OEM
with double
barrel fuse clips
Fix type for
CPT/PT/CB
APPLICATION
Motor hp rating up to 1500hp
Motor hp rating up to 3000hp
Includes Toshibaʼs Isolation
Bolted Pressure Switch for
disconnecting CPT/PTʼs Provision
to fix mount 1 or 2 CPT/PTʼs
w/mounting provision for
secondary low voltage circuit
breaker.
Fix type for CPT/PT/LS Includes Toshibaʼs Isolation
Bolted Pressure Switch for
disconnecting CPT/PTʼs Provision
to fix mount 1 or 2 CPT/PTʼs w/
limit switch.
Drawout type without
Used when up stream protection
fuses
is provided.
Drawout type OEM
Motor hp rating up to 1500hp
with single
barrel fuse clips
Drawout type OEM
Motor hp rating up to 3000hp
with double
barrel fuse clips
Fix latched type OEM
For distribution loads (400 A
with single
MAX) , transformer or 3 phase
barrel fuse clips
capacitor switching
Fix latched type OEM
For distribution loads (400 A
with double
MAX) , transformer or 3 phase
barrel fuse clips
capacitor switching
Drawout latched type For distribution loads ( 400 A
OEM with single
MAX) , transformer or 3 phase
barrel fuse clips
capacitor switching
Drawout latched type For distribution loads (400 A
OEM with double
MAX) , transformer or 3 phase
barrel fuse clips
capacitor switching
New application
using JK OEM Power
Cell for outdoor skid
mounted compressor
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
The above table is based on general load data and standard application. Lower limitations may apply
on specific applications (i.e. applications above 6600 feet elevations).
CONTACTOR RATINGS
HCV-5HA
Rated Voltage
7200 Volts
Rated Current
400 Amps
Interrupting Capacity
7000A RMS Symmetrical @5000V
Max.
4500A RMS Symmetrical @7200V
Max.
1200/Hour
Permissible Switching
Frequency
Mechanical Life
2,500,000 Operations
Electrical Life
250,000 Operations
Closing Time
80 ms or less
Opening Time
25 ms or less
Arcing Time
10 ms or less
Pick-Up Voltage AC or DC
85% Rated (Hot) - 70% Rated
(Cold)
Drop-Out Voltage AC or DC
50% Rated (Hot) - 40% Rated
(cold)
Rated Control Voltage AC
115/120 or 230/240 V 50/60 Hz
Rated Control Voltage DC
120/125 or 240/250 V
Coil Circuit Inrush
670 VA AC (700 W DC)
Coil Circuit Holding
85 VA AC (85 W DC)
3 N.O. - 3 N.C.
Auxiliary Contact
Arrangement
Auxiliary Contact Rating
10 A, 600 V (NEMA Class A600)
HCV-5HAL (Latched Type Only)
300/Hour
Permissible Switching
Frequency
Mechanical Life
250,000 Operations
Tripping Voltage
40-60% Rating DC
Tripping Current
4.8 A DC Max
General Application and Load Data
System
Voltage
0.8PF
Ind/Syn
Motor
1.0PF Syn
Motor
3 Phase
Transformer
3 Phase
Capacitor
2.2-2.5kV
3.0-3.3kV
4.0-5.0kV
6.0-6.6kV
1750HP
2250HP
3000HP
4500HP
2000HP
2500HP
3500HP
5000HP
1500kVA
2000kVA
3000kVA
4000kVA
1500kVAR
2000kVAR
2000kVAR
2000kVAR
The above table is based on general load data and standard application. Lower limitations may apply
on specific applications (i.e. applications above 6600 feet elevations).
CONTACTOR
RATINGS- Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
CTi Automation - Phone:
800.894.0412
HCV-5HA
This Pumping Station is equipped with Air Contactor Type
Across the Line Starters and was faced with the high cost
of replacement parts and un-scheduled downtimes. Local
OEM modified the existing cubicles and replaced two of
the six old style starters with the JK OEM Power Cells.
The remainders of the old style Air Contactors were
replaced during scheduled maintenance shut downs.
JK OEM Power Cells installed and connected in customers existing cabinetry.
This Pumping Station is equipped with Air Contactor Type Across the Line Starters
Modified
Cubicles
and was faced with the high cost of replacement parts
andStarter
un-scheduled
downtimes.
with the JK OEM Power
Cells two of the six old style starters
Local OEM modified the existing cubicles and replaced
with the JK OEM Power Cells. The remainders of the old style Air Contactors were
replaced during scheduled maintenance shut downs.
This Pumping Station is equipped with Air
Across the Line Starters and was faced wi
of replacement parts and un-scheduled dow
OEM modified the existing cubicles and
the six old style starters with the JK OEM
The remainders of the old style Air C
replaced during scheduled maintenance shu
Modified Starter
Cubicles with the JK
OEM Power Cells
Modified Starter Cubicles
with the JK OEM Power
Cells
JK OEM Power Cells installed and connected in customers existing cabinetry.
The Power Cells was used to replace old style AIR DRAWOUT CIRCUIT
BREAKER Controlgear protecting and controlling motor loads within an existing facility. The continuous failure of the mechanical mechanisms and costly
electrical contact replacement forced the user to consider replacing the entire
existing Controlgear. Valuable real-estate and labor dollars was saved by reusing the existing cabinets and conduits plus upgrade to current vacuum technology electrical controllers.
Existing Air Breaker Cubicle
with the Old Style Air Circuit
Breaker installed
ting Air Breaker Cubicle with the
Style Air Circuit
Breaker installed
CTi Automation
- Phone:
JK OEM Power
Cell installed in
Existing Cubicle
Existing Air Breaker Cubicle with the
Old Style AirWindow
Circuit Breaker
Viewing
to installed
view the position of the
Isolation Switch Blades
Viewing Window
the Isolation Sw
Viewing
Isolation Bolte
Viewing Port
Operating Ha
for Fuses
JK OEM Power Cells installed and connected in customers existing cabinetry.
Isolation Bolted Pressure Switch Operating Handle
800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]
JK OEM Power Cell installed in Existing
The JK OEM Power Cells are UL Listed
The compact design will allow for either motor or distribution applications.
Design can be totally front accessible.
The OEM Power Cells are designed to replace existing air or old vacuum contactor applications when used for motor or small distribution feeders.
The kit provides you with state-of-the-art Toshiba vacuum technology and the patented
bolted pressure isolation switch.
Standard features include:
•
Patented bolted pressure isolation switch
•
Main power fuse clips (single or double barrel)
•
Mechanical interlocking system
•
Toshiba HCV-5HA vacuum contactor
The JK OEM Power Cells will allow the customer to use their standard cubicles, wiring
methods and components.
������������������������������������������������
��������������������������������������������������
���������������������������������
�������������������������������
������������������������
�����������������
�����������������������
������������
��������������������������
�������������������������
������������
����������������
����������������
�����������������
��������������
������������������
�������������������
�����������������������
�����������������������
��������������������
�����������������
��������������������
����������������
��������������
������������������
�������������
�����������
����������������
���������
������
���������������������������������
��������������������
�����������������
�����������������������
�������������������
�����������������������������
5.00
5.00
����������������
����������������
����������������������
���������������������
��������������������
�����������������������
��������������
�����������������������
��������
32.56
8.67
DRAWOUT CONFIGURATION
1.00
POWER
ISOLATION
SWITCH
O
N
2.25
4.50
O
F
21.05
29.29
F
22.73
20.03
LINE TERMINALS
14.58
15.86
8.98
LOCKED
26.53
31.80
TOP VIEW
RIGHT SIDE
23.83
FRONT VIEW
26.220
FIXED MOUNTED CONFIGURATION
POWER
ISOLATION
SWITCH
O
N
2.25
4.50
29.29
O
F
F
20.03
20.03
LINE TERMINALS
19.71
22.06
LINE TERMINALS
14.58
3.62
3.000
22.06
FRONT VIEW
31.80
SIDE VIEW
26.225
TOP VIEW
Houston,Texas
G7 Drive
Low Voltage Motor
UPS
Product Warranty
Toshiba offers a comprehensive warranty program on its full line of industrial
products. Consult your salesperson or the factory for specific information.
Medium Voltage Drive
Customer Support Services
Toshiba offers 24-hour service nationwide. For assistance of any type,
800-894-0412
Medium Voltage
Motor
Need to Know More?
With more than a half a million square feet under one roof, Toshiba’s facility in Houston, Texas is one of the largest drive and motor
manufacturing facilities in the U.S. From this facility, Toshiba offers solutions which include integrated motor drive packages, turnkey
bypass assemblies and custom jobs built to your specification. Be sure to visit out web site for the lat-est information on Toshiba
products.
Exceed all Expectations….
At Toshiba drives are what we do best. In an effort to significantly reduce the long lead-times and expensive custom engineering
often associated with the manufacture of medium voltage drives, Toshiba now offers a line of products to meet the ever changing
needs of out most valuable assets: our diverse, worldwide customer base. Through intense interaction with our customers we have
been able to develop the best product for medium voltage motor applications
Reliability in motion