HPA 12 Centrifugal - Admor HVAC Products

Product Specification
930091-0024
HPA12 (60 Hz, Centrifugal)
Air Source Heat Pump
For Water Heating
General - Colmac HPA heat pumps can be successfully applied wherever there is a need for
large amounts of hot water and there is a source of warm air available. The Colmac HPA is best
suited for supplying hot water in facilities where demands for hot water and space cooling are
concurrent.
Apartments, Condominiums, Hotels, Hospitals, Dormitories, Restaurants, Nursing Homes,
Laundries, Kitchens, Food Processing Plants, and Photographic Processing Plants located in
warm climates are a few of the possible heat sources that can be utilized by the HPA heat pump.
Depending on the temperature of the waste heat source, the HPA can produce potable hot water
for as little as 1/4 the energy used by a conventional boiler or electric resistance heater.
These packaged air source water heating pumps are factory wired, charged, and tested. Low
operating noise levels, high capacity, high efficiency, and environmentally safe refrigerants are
integrated into this new design.
General Specifications:




Water Heating Capacity *:
Cooling Capacity *:
Heating COP *:
Cooling COP *:
207.1 MBH
159.7 MBH
4.4
3.4
* 70°F Potable Water Inlet, 140°F Potable Water Outlet, 75°F Entering Air Wet Bulb
Standard Features:









Environmentally friendly R134a refrigerant.
Copeland scroll compressor.
Vented double wall, stainless steel, brazed plate condensers (potable water).
Adjustable TXV, moisture indicating sight glass, liquid line filter drier.
Bronze hot water circulating pump (potable water).
TM
Electronic temperature control valve (e-TCV )
Factory built and tested copper tube, aluminum fin evaporators.
Automatic controls include high and low pressure cutouts, compressor time delay relay,
normal run and fault indicating lights, phase failure relay.
Fully enclosed cabinets are offered in mill finish aluminum, galvanized steel, 304 SST,
and 316 SST.
Performance Data
HPA12 Heating Capacity
vs.
Entering Air Temperature
120 F LWT
140 F LWT
200
180
160
140
120
40
60
80
190
170
150
130
110
90
70
100
40
100 F LWT
80
HPA12 Cooling COP
vs.
Entering Air Temperature
120 F LWT
140 F LWT
100
100 F LWT
120 F LWT
140 F LWT
160 F LWT
6
6
5
Cooling COP
Heating COP
60
Entering Air Wet Bulb ( F)
160 F LWT
7
140 F LWT
160 F LWT
Entering Air Wet Bulb ( F)
HPA12 Heating COP
vs.
Entering Air Temperature
120 F LWT
210
Cooling Capacity (MBH)
220
100 F LWT
HPA12 Cooling Capacity
vs.
Entering Air Temperature
160 F LWT
240
Heating Capacity (MBH)
100 F LWT
COLMAC WaterHeat
5
4
3
4
3
2
2
1
40
60
80
100
40
Entering Air Wet Bulb ( F)
60
80
Entering Air Wet Bulb ( F)
Note: Based on entering potable water temperature of 70°F.
930091-0024
100
Unit Dimensions
COLMAC WaterHeat
24 [610]
24 [610]
24 [610]
36 [914]
SERVICE CLEARANCE
AIR
FLOW
AIR
FLOW
ELECTRICAL ACCESS
72 15/16 [1852]
42 15/16 [1090]
MECHANICAL ACCESS
42 3/4 [1085]
Unit Weight
Dry Weight:
1300 Lbs.
Electrical Data
Line Voltage
Rated Load Amps (RLA)
Locked Rotor Amps (LRA)
208-230/60/3
460/60/3
63.3 A
31.0 A
340 A
179 A
930091-0024
Colmac reserves the right to change product design and specifications without notice.
For more information on Colmac products call us at 1-800-926-5622 or visit us online at: