HM700ADISTKIT ELECTRODE STEAM HUMIDIFIER DISTRIBUTION KIT INSTALLATION INSTRUCTIONS CAUTION Before Servicing 1. Disconnect main power source before accessing internal compartments. 2. The plumbing and electrical compartments contain high voltage components and wiring. Access should be limited to licensed HVAC professionals only. 3. During and following operation of the humidifier, the steam components in contact with the steam such as the cylinder, steam lines, steam distributors, and condensate lines can become hot and burn if touched. Please consult HM700 Installation manual for reference. 4. Installations of humidity equipment installed by unqualified personnel or the use of nonHoneywell parts and components will void warranty. Steam Distributor The HM700ADISTKIT is a remote mount, stainless steel steam distribution kit used with the HM700 Electrode Steam Humidifier. The distributor is installed in a ventilation duct to distribute the steam produced by the HM700. The HM700ADISTKIT consists of a steam distributor, steam hose, condensate hose, and installation hardware. The steam distributor should be installed as close as possible to the humidifier. Short steam distribution lines minimize condensate loss and the possibility of generating backpressure in the steam distribution line. STEAM DISTRIBUTION Steam generated by the humidifier may be introduced into the air in several different ways. The most common method for adding the steam into the air is to mount a steam distributor tube in a supply air duct as shown in Fig. 2. STEAM LINE The steam line between the cylinder steam outlet and the distributor serves two purposes: it is used as a conduit to transfer the atmospheric steam from the humidifier to the distributor, as well as providing a means to remove condensate. See “Steam Lines and Condensate Return Instructions” on page 2 for information on selecting steam lines. CONDENSATE RETURN Whenever steam is distributed condensate is formed in the distribution system. Insulating steam lines is one important way to reduce the amount of condensate formed. Steam lines are sloped so that condensate does not collect in the lines and create a restriction to steam flow. The condensate must be collected and removed from the system so that it does not build up and leak into the duct. Condensate can be returned to the HM700 fill cup to reduce water waste or can be fed to drain. KIT CONTENTS: • Stainless steel nozzle • Insulated hose (5 ft.) • Hose support brackets • Screws • Clamps • Installation Instructions TOOLS NEEDED (NOT SUPPLIED): • Screwdriver • Pliers (optional) 33-00160EFS-01 HM700ADISTKIT Steam Lines and Condensate Return Instructions The following instructions must be followed for installation of steam lines for the HM700. Failure to use recommended material and exceeding maximum recommended length in Table 4, or failure to follow any other steam line installation instructions will result in improper operation and could void the warranty. Table 1. Recommended Steam Line Material for HM700 Duct. Steam Output Material Voltage lbs/hr (kg/hr) Steam Hose MED-L Copper Tube 110/120V 3.85 (1.75) 220/240V 7.7 (3.5) 7/8 in. 3/4 in. Maximum Steam Line Length * Stainless Steel Tube ft 0.875 x 0.049W Possible Losses Minimum Max Static Airflow CFM Pressure (m) lbs/hr (kg/hr) 7 (2) 0.5 (0.2) 115 12 (3.5) 1.5 (0.7) 230 3.0 in. w.c. * The use of steam line other than copper, stainless steel tube or Honeywell supplied steam line will void the warranty and may adversely affect the operation of the humidifier. * When using copper or stainless steel tubing (other than the supplied tubing), insulation is recommended due to high temperature safety as well as reduced condensate. Condensate Return Guidelines For Main Steam Lines CAUTION Plumbing to be performed by licensed HVAC 1. Use vertical condensate leg of distributor only. Do not over-tighten clamp. 2. Condensate traps on steam mains must be located at all low points in the system, at each elevation change and or directional change. 3. Horizontal runs of steam must rise 2 in. per foot (10º) when flow is going upwards away from condensate trap, and fall 1/2 in. per foot (2º) when flow is going downwards towards a condensate trap. 4. In a horizontal run of the steam main, condensate traps must be located at regular intervals. 5. The condensate trap itself is a section of piping connected to the bottom of the main. A full size tee must be used to create a condensate trap to allow the condensate to fall away from the steam flow. 6. Vertical drop of the condensate trap should be 1.5 times the diameter of the steam main but no less than 12 in. 7. A p-trap should be installed at the bottom of the condensate trap. The center to center trap height should be 2 in. greater than duct static pressure (see Figure 1). To return condensate for HM700, insert copper tube (supplied with equipment) half way into the condensate opening of the fill cup along with the spring clamp (supplied with equipment). professionals only. Drain water from humidifier can be very hot. Do not drain to public sink. All plumbing work should be done according to local plumbing code. CAUTION Installation Do not mount in area where freezing can occur. Do not mount on floor. Humidifiers produce steam at atmospheric pressure. No devices which could block steam output should be connected to the steam outlet. Steam lines must be installed so that no restriction can produce backpressure in the humidifier. Regardless of selecting on/off or modulating control method, Honeywell humidifiers must have a closed circuit across its on/off security loop control terminal to operate. Honeywell highly recommends the use of a duct high limit humidistat. Steam Line Installation 1. 2. 3. 4. 5. Honeywell steam hose should only be used on short steam runs (under 15 feet). Ensure that no condensate produced in the steam line will remain trapped. Steam naturally flows upward and condensate naturally flows downward. Ensure steam line properly supported so that no sags or dips are present. All bends should be done in large radius 12 in. minimum. Steam hose will soften when and may kick if too tight a radius is used which can cause a blockage and excessive back pressure. Horizontal runs of steam must rise 2 in. per foot (10º) when flow is going upwards away from the humidifier, or fall 1/2 in. per foot (2º) when flow is going downwards away from the humidifier. 33-00160EFS—01 Insert the condensate hose into the condensate return hole at the top of the unit, and over the copper tube. Fasten in place with the spring clamp. 2 HM700ADISTKIT SPRING CLAMP INSERT HOSE OVER COPPER TUBE AND FASTEN WITH SPRING CLAMP SPRING CLAMP 3/8” OD COPPER TUBE M35761 Fig. 1. Condensate return. Mount distributor nozzle to side of duct. Fig. 2. HM700 Duct Distributor Installation. 3 33-00160EFS—01 HM700ADISTKIT Steam Line Installation Examples 12 (305) 2 (51) MINIMUM 12 (305) MINIMUM RADIUS 12 (305) MINIMUM RADIUS 12 (305) MINIMUM BEFORE ANY BEND CONDENSATE LINE 12 (305) MINIMUM BEFORE ANY BEND SUPPORT BRACKETS SUPPORT 1 BRACKETS CONDENSATE LINE CONNECT CONDENSATE HOSE TO FILL CUP OBSTRUCTION CONNECT STEAM HOSE TO CYLINDER 12 (305) 2 (51) MIN. MINIMUM 12 (305) MINIMUM USE FULL SIZE CONDENSATE TEE AT LOW POINT. SLOPE TO DRAIN LINES UP TO “T” AND IMMEDIATELY AFTER IT. TO DRAIN 1 HOSE WILL SOFTEN OVER TIME. PROPER SUPPORT IS NECESSARY. M35719 M35717 Fig. 3. Steam distributor above humidifier (hose). Measurements in inches (mm). 12 (305) MINIMUM RADIUS 12 (305) MINIMUM BEFORE ANY BEND Fig. 5. Steam distributor below humidifier with obstruction (hose). Measurements in inches (mm). CONDENSATE TRAP NOT 12 (305) BELOW DISTRIBUTOR SUPPORT BRACKETS NO CONDENSATE TRAP AT VERTICAL TRANSITION 12 (305) MINIMUM STEAM LINE NOT SLOPED CONDENSATE TRAP TO DRAIN M35718 Fig. 4. Steam distributor below humidifier (hose). Measurements in inches (mm). M35720 Fig. 6. Common steam line installation errors. Measurements in inches (mm). For more information on maintenance and replacement, please visit http://yourhome.honeywell.com or call 1-800-468-1502 or 1-800-814-9452. Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.com ® U.S. Registered Trademark © 2015 Honeywell International Inc. 33-00160EFS—01 M.S. 11-15 Printed in United States
© Copyright 2026 Paperzz