Distribution Kit Installation - Honeywell

HM700ADISTKIT
ELECTRODE STEAM HUMIDIFIER DISTRIBUTION KIT
INSTALLATION INSTRUCTIONS
CAUTION
Before Servicing
1. Disconnect main power source before
accessing internal compartments.
2. The plumbing and electrical compartments
contain high voltage components and wiring.
Access should be limited to licensed HVAC
professionals only.
3. During and following operation of the
humidifier, the steam components in contact
with the steam such as the cylinder, steam
lines, steam distributors, and condensate lines
can become hot and burn if touched. Please
consult HM700 Installation manual for
reference.
4. Installations of humidity equipment installed by
unqualified personnel or the use of nonHoneywell parts and components will void
warranty.
Steam Distributor
The HM700ADISTKIT is a remote mount, stainless steel
steam distribution kit used with the HM700 Electrode
Steam Humidifier. The distributor is installed in a
ventilation duct to distribute the steam produced by the
HM700.
The HM700ADISTKIT consists of a steam distributor,
steam hose, condensate hose, and installation hardware.
The steam distributor should be installed as close as
possible to the humidifier. Short steam distribution lines
minimize condensate loss and the possibility of
generating backpressure in the steam distribution line.
STEAM DISTRIBUTION
Steam generated by the humidifier may be introduced
into the air in several different ways. The most common
method for adding the steam into the air is to mount a
steam distributor tube in a supply air duct as shown in
Fig. 2.
STEAM LINE
The steam line between the cylinder steam outlet and the
distributor serves two purposes: it is used as a conduit to
transfer the atmospheric steam from the humidifier to the
distributor, as well as providing a means to remove
condensate. See “Steam Lines and Condensate Return
Instructions” on page 2 for information on selecting
steam lines.
CONDENSATE RETURN
Whenever steam is distributed condensate is formed in
the distribution system. Insulating steam lines is one
important way to reduce the amount of condensate
formed. Steam lines are sloped so that condensate does
not collect in the lines and create a restriction to steam
flow. The condensate must be collected and removed
from the system so that it does not build up and leak into
the duct. Condensate can be returned to the HM700 fill
cup to reduce water waste or can be fed to drain.
KIT CONTENTS:
• Stainless steel nozzle
• Insulated hose (5 ft.)
• Hose support brackets
• Screws
• Clamps
• Installation Instructions
TOOLS NEEDED (NOT SUPPLIED):
• Screwdriver
• Pliers (optional)
33-00160EFS-01
HM700ADISTKIT
Steam Lines and Condensate Return Instructions
The following instructions must be followed for installation of steam lines for the HM700. Failure to use recommended
material and exceeding maximum recommended length in Table 4, or failure to follow any other steam line installation
instructions will result in improper operation and could void the warranty.
Table 1. Recommended Steam Line Material for HM700 Duct.
Steam Output
Material
Voltage
lbs/hr
(kg/hr)
Steam
Hose
MED-L
Copper
Tube
110/120V
3.85
(1.75)
220/240V
7.7
(3.5)
7/8 in.
3/4 in.
Maximum
Steam Line
Length
*
Stainless
Steel Tube
ft
0.875 x
0.049W
Possible Losses
Minimum Max Static
Airflow CFM Pressure
(m)
lbs/hr
(kg/hr)
7
(2)
0.5
(0.2)
115
12
(3.5)
1.5
(0.7)
230
3.0 in. w.c.
*
The use of steam line other than copper, stainless steel tube or Honeywell supplied steam line will void the warranty
and may adversely affect the operation of the humidifier.
*
When using copper or stainless steel tubing (other than the supplied tubing), insulation is recommended due to high
temperature safety as well as reduced condensate.
Condensate Return Guidelines For Main
Steam Lines
CAUTION
Plumbing to be performed by licensed HVAC
1. Use vertical condensate leg of distributor only. Do
not over-tighten clamp.
2. Condensate traps on steam mains must be located
at all low points in the system, at each elevation
change and or directional change.
3. Horizontal runs of steam must rise 2 in. per foot
(10º) when flow is going upwards away from condensate trap, and fall 1/2 in. per foot (2º) when flow
is going downwards towards a condensate trap.
4. In a horizontal run of the steam main, condensate
traps must be located at regular intervals.
5. The condensate trap itself is a section of piping connected to the bottom of the main. A full size tee
must be used to create a condensate trap to allow
the condensate to fall away from the steam flow.
6. Vertical drop of the condensate trap should be
1.5 times the diameter of the steam main but no
less than 12 in.
7. A p-trap should be installed at the bottom of the
condensate trap. The center to center trap height
should be 2 in. greater than duct static pressure
(see Figure 1).
To return condensate for HM700, insert copper tube
(supplied with equipment) half way into the condensate
opening of the fill cup along with the spring clamp
(supplied with equipment).
professionals only.
Drain water from humidifier can be very hot. Do
not drain to public sink.
All plumbing work should be done according to
local plumbing code.
CAUTION
Installation
Do not mount in area where freezing can occur.
Do not mount on floor.
Humidifiers produce steam at atmospheric
pressure. No devices which could block steam
output should be connected to the steam outlet.
Steam lines must be installed so that no restriction
can produce backpressure in the humidifier.
Regardless of selecting on/off or modulating
control method, Honeywell humidifiers must
have a closed circuit across its on/off security
loop control terminal to operate. Honeywell
highly recommends the use of a duct high limit
humidistat.
Steam Line Installation
1.
2.
3.
4.
5.
Honeywell steam hose should only be used on
short steam runs (under 15 feet).
Ensure that no condensate produced in the steam
line will remain trapped. Steam naturally flows
upward and condensate naturally flows downward.
Ensure steam line properly supported so that no
sags or dips are present.
All bends should be done in large radius 12 in.
minimum. Steam hose will soften when and may
kick if too tight a radius is used which can cause a
blockage and excessive back pressure.
Horizontal runs of steam must rise 2 in. per foot
(10º) when flow is going upwards away from the
humidifier, or fall 1/2 in. per foot (2º) when flow is
going downwards away from the humidifier.
33-00160EFS—01
Insert the condensate hose into the condensate return
hole at the top of the unit, and over the copper tube.
Fasten in place with the spring clamp.
2
HM700ADISTKIT
SPRING CLAMP
INSERT HOSE OVER
COPPER TUBE AND
FASTEN WITH
SPRING CLAMP
SPRING
CLAMP
3/8” OD COPPER TUBE
M35761
Fig. 1. Condensate return.
Mount distributor nozzle to side of duct.
Fig. 2. HM700 Duct Distributor Installation.
3
33-00160EFS—01
HM700ADISTKIT
Steam Line Installation Examples
12 (305)
2 (51)
MINIMUM
12 (305)
MINIMUM
RADIUS
12 (305)
MINIMUM
RADIUS
12 (305)
MINIMUM
BEFORE
ANY BEND
CONDENSATE
LINE
12 (305)
MINIMUM
BEFORE
ANY BEND
SUPPORT
BRACKETS
SUPPORT 1
BRACKETS
CONDENSATE
LINE
CONNECT
CONDENSATE
HOSE TO FILL
CUP
OBSTRUCTION
CONNECT
STEAM
HOSE TO
CYLINDER
12
(305)
2 (51)
MIN.
MINIMUM
12 (305)
MINIMUM
USE FULL SIZE CONDENSATE
TEE AT LOW POINT. SLOPE TO DRAIN
LINES UP TO “T” AND
IMMEDIATELY AFTER IT.
TO DRAIN
1 HOSE WILL SOFTEN OVER TIME. PROPER SUPPORT IS NECESSARY.
M35719
M35717
Fig. 3. Steam distributor above humidifier (hose).
Measurements in inches (mm).
12 (305)
MINIMUM
RADIUS
12 (305)
MINIMUM
BEFORE
ANY BEND
Fig. 5. Steam distributor below humidifier with
obstruction (hose). Measurements in inches (mm).
CONDENSATE
TRAP NOT 12
(305) BELOW
DISTRIBUTOR
SUPPORT
BRACKETS
NO
CONDENSATE
TRAP AT
VERTICAL
TRANSITION
12 (305)
MINIMUM
STEAM LINE
NOT SLOPED
CONDENSATE
TRAP
TO DRAIN
M35718
Fig. 4. Steam distributor below humidifier (hose).
Measurements in inches (mm).
M35720
Fig. 6. Common steam line installation errors.
Measurements in inches (mm).
For more information on maintenance and replacement, please visit http://yourhome.honeywell.com
or call 1-800-468-1502 or 1-800-814-9452.