Magnetic compensation of Vertical Magnetic Field of Neighboring rows.
We are asked to provide compensation of the vertical magnetic field in pot lines
with the following specifications.
Available Data:
Potline
1. Side by Side cells in one or two lines, two rows per line.
2. Current =400 Ka, following in clockwise direction
3. The length of the cells is 14m
4. Centerline to centerline distance between rows of the same line is R1 and
between the nearest rows of the two lines is R2.
5. Presume very long lines (neglect the contribution of the crossover bus bars)
Group Discussion VIII
Magnetic compensation of Vertical Magnetic Field of Neighboring rows.
We are asked to provide compensation of the vertical magnetic field in pot lines
with the following specifications.
Available Data:
Compensation Loop:
1. Distance from the cell centerline to the compensation loop =10m
2. Total length = 1000m
3. Current density in the compensation loop = 400 Ka /m2
4. Busbar density = 2700 kg/m3
5. Busbar resistivity = 0.035
6. Busbar cost = 3000 $ /ton
7. Cost of energy = 40 $ /MWH
Group Discussion VIII
Question 1:
First consider only one line in the smelter. What is the minimum distance
between the two rows, which would give a maximum vertical field of 0.5
mT at the centre of the cells ? Discuss practical aspects of building such a
line.
Group Discussion VIII
Answer 1:
Using the formula B= I / (5R)
Where current is 400 kA, magnetic field of 0.5 mT,
R = I / (5B)
R=400 / 5*0.5
R = 160 m
Conclusion is : Inorder to have the Bz field from the neighboring rows
smaller than 0.5 mT, the pot rows should be at a distance >160 m.
This is not practical since the plant will occupy lot of space.
So to justify a compensation loop is better solution than separating
potroom.
Group Discussion VIII
Question 2:
1. In a two-line smelter, investigate the influence of different ratios of
R2/R1 on the vertical magnetic field in each row. Specifically, take
R1=80 m and determine R2 which would give complete self
compensation of BZ in the two inner rows.
Group Discussion VIII
Answer 2:
R1= 80 m, R2 =?
Magnetic field in the inner row indicated by yellow rectangle is;
Bz=I/5 ( -1/R1 + 1/R2 – 1/(R1+R2))
This field should be ZERO for perfect compensation.
400/5 ( -1 /R1 + 1/R2 – 1/ (R1+R2)) =0
This equation can only be solved for the ratio of R2/R1 = X
= 1/R1 (-1 + 1/X – 1/(1+X)) =0
R2 = 0.618
The solution to this equation is X = R2/R1 = 0.618.
For R1= 80 m, R2 = 49.4 m.
Group Discussion VIII
Question 3:
1.
In a one line smelter with a row-to-row distance of 80m, compensate BZ due to
neighboring row with a single internal loop as shown in the lecture. Assuming that
the loop is at the level of the liquid metal pad and that BZ at the cell centre is 0 .
Calculate the current needed. With this current calculate BZ at the two ends of the
cell. Is there a problem with this compensation ?
Group Discussion VIII
Answer 3:
Bz from neighboring row = - 400 kA / (5*80) = - 1.0 mT
Current required in the (compensation loop) at a distance of 10 m from
the centerline is 50 kA.
Bz at near end of the Pot is calculated as = 400 / 5*73
= -1.1 mT
Bz from the loop at near end = 50 / 5 *3 = 3.2 mT
Total field at the near end = 3.2 mT – BZ
= 3.2 mT – 1.1 mT
= 2.1 mT
Bz from the neighbor row of the pot line at far end = 400 kA/ (5*87) = -0.92 mT
Bz from the loop at Far end = 50 / 5*17 = 0.59 mT
Total field at far end = 0.59 mT – 0.92 mT
= - 0.33 mT
Far side is under compensated
Near Side is over compensated.
Group Discussion VIII
Question 4:
1. In the smelter of problem 3) use a magnetic compensation loop
around each building, carrying a current of 25 kA, calculate the
magnetic field at the cell centre and at each end. Compare these
fields with those found in problem 3). Is this compensation good ?
The magnetic filed from the inner part of the loop and the outer part of
the loop add up.
Bloop at pot centre = 25 /(5*10) + 25 / (5*10)
= 1.0 mT
BZ from loop at near end = 25 / (5*3)
= 1.6 mT
Total at near end = 1.6 - 1.1
= 0.5 mT
The compensation is good.
Group Discussion VIII
Question 5:
For a 25 kA compensation loop around each building, calculate the
busbar cross section, bus bar voltage drop, busbar cost and the cost of
energy dissipated in the compensation loop each year.
A = I /j = 25kA / (400 kA / m2)
= 0.0625 m2
Volume= 0.0625 x 1000m
= 62.5 m3
Mass = 2700 x 62.5
= 168,750 kg = 168.75 tons
Bus Bar Cost= 168.75 * 3000$ / ton
= 506,000 $ for one compensation loop.
Group Discussion VIII
Question 5:
For a 25 kA compensation loop around each building, calculate the busbar
cross section, bus bar voltage drop, busbar cost and the cost of energy
dissipated in the compensation loop each year.
Cost of Energy / Year:
P=V*I
V= R*I
= 0.035 m* 1000 m * 400 kA/m2
= 14 000 mV = 14 V
So, P = 14 V * 25 kA
P = 350 kW = 0.35 MW
So energy cost is calculates as = 0.35 MW X 8760 (Total h / Year)
= 3066 MWh
= 3066 MWh* 40 $ (energy cost)
= 122,640 $ / Year.