Windings with Various Numbers of Turns per Phasor Boris Dotz1, Dieter Gerling2 1 2 FEAAM GmbH, Neubiberg, Germany, [email protected] Universitaet der Bundeswehr Muenchen, Germany, [email protected] Abstract— Although windings with various numbers of turns per coil have been presented in several papers in the past, a closed theory on applying different turn ratios in electrical machine windings has not been published yet. Conditions under which different turn ratios can be used to improve the MMF spectrum of electrical machines are therefore discussed in this paper. Analytical expressions for winding factors as well as expressions for turn ratios are derived and several examples are presented. It is shown that winding topologies presented in earlier publications possess a similar structure and can therefore be easily described by a zone factor or a group factor with two distinct turn numbers. A+ a) A+ b) A– A– Fig. 1. Exemplary stars of phasors a) unequal zones b) equal zones. Keywords— Electrical machines; fractional slot concentrated windings; winding factors; MMF harmonics I. ∑ INTRODUCTION The idea of using various numbers of turns per coil to improve the MMF spectrum of electrical machines goes back to at least 1935. In [1] Heller and Kauders discussed a distributed winding named after Michael Surjaninoff. The suggested winding topology utilizes two turn numbers, whereby all odd/even slots have two coil sides with / turns respectively and the turn ratio is given by ⁄ = 2⁄√3. As the benefit for distributed windings was rather low compared to increased manufacturing costs, the winding did not appear in later publications. During the last years fractional slot concentrated windings (FSCW) received increasing attention due to some advantages over distributed windings [2]. As stator teeth are often wound individually in FSCW, using various numbers of turns per coils becomes a more practical possibility. Cistelecan et al. presented a four-layer winding for 12 slots and 10 poles per base winding (12/10) showing that different numbers of turns can improve the MMF spectrum [3]. In [4] a two-layer 12/10 winding with different numbers of turns per coil side was discussed. For distributed concentric windings a study of different numbers of turns per coil was presented in [5]. It has been shown that the THD can be minimized by applying different numbers of turns and that therefore the MMF function can be improved. Despite above publications, a detailed discussion on different numbers of turns including winding factor analysis has not been published yet. Therefore the aim of this research is threefold: First, classical winding factor theory is used to discuss conditions under which various numbers of turns can lead to an improved MMF. Based on those findings, closed analytical expressions for winding factors are derived. Second, it is shown that already known windings can be divided into two groups: Those utilizing the zone factor and others using the group factor. b) a) ∑ Fig. 2. Exemplary voltage phasor configuration with and turns per coil for a) main spatial harmonic and b) parasitic spatial harmonic. The sum denotes the geometric sum of all considered phasors. Third, applying the developed theory new windings are presented briefly. This paper is structured as follows: After preliminary notes in section II, the main theory is presented in section III. The fourth section discusses the zone factor and its application to known and new windings. Section V derives the group factor and gives examples on its application. Although main examples focus on FSCW, the developed terms can be easily applied to distributed windings as well. II. PRELIMINARY NOTES AND MAIN IDEA The following research uses well-known theory of induced voltages per coil side, per coil, or per coil group. The relative phase shift of induced voltages with respect to each other can be depicted using the star of phasors, which is sometimes referred to as the star of slots. To apply the theory at its broadest spectrum, latter term is omitted. The more general term star of phasors is used instead, where each phasor can represent the induced voltage either per coil side (single-layer winding), per coil (double-layer winding), per coil pair (fourlayer winding), per coil group or per winding zone. A phase winding can be divided into 2 zones, one + and one – zone 978-1-5090-4281-4/17/$31.00 ©2017 IEEE for each phase. In general the zones do not need to be of equal length, meaning that the + zone can have more or less phasors than the – zone. Fig. 1 a) depicts a configuration where the + zone consists of two phasors while the – zone consists of 4 phasors. To calculate the distribution factor + and – zones of one phase need to be considered. Doing so, the distribution . In contrast, Fig. 1 b) factor is referred to as the zone factor depicts a configuration, where + and – zones are of equal length. To calculate the distribution factor it is therefore sufficient to consider only one group of three phasors. Following this approach the distribution factor is referred to as the group factor . Please note that the configuration in Fig. 1 a) can also be described by groups of two phasors, where + and – zones consist of 1 and 2 groups respectively. Therefore the most common description of the distribution factor is given by [6] , = , ⋅ , , (1) where denotes the ordinal number of the spatial harmonic. To comprehend the main idea of compensating MMF harmonics Fig. 2 depicts an exemplary configuration of voltage phasors for a given winding. As can be seen, resulting and phasors point in the same direction for the main working wave, while they may point in different directions for a parasitic spatial harmonic. Choosing a proper turn ratio = ⁄ will then allow the geometrical sum of and phasors to be of equal length leading to a zero induced voltage per winding phase, i.e. leading to a zero winding factor for the considered spatial harmonic. III. THEORY ON VARIOUS NUMBERS OF TURNS All considerations in this research are performed for base windings. A base winding is defined as the smallest number of poles 2 so that the phasor diagram does not repeat. For windings utilizing the first spatial harmonic = 1 as its working harmonic the base winding includes two poles only. The angle between two adjacent phasors is given by = (2 )⁄ , where denotes the total number of slots. The fictive commutator pitch allows for calculating the difference of adjacent phasor positions and is given by = ⋅ , (2) where is the smallest integer for which becomes an integer. For distributed windings = 1 per base winding so = 1 . The winding factor can be expressed by , = ∑ | | ∑ ⋅ , (3) denotes the number of conductors, the current where magnitude and direction for phasor . The symmetry axis is given by the angle . = arg(∑ ⋅ ) With the number of slots per pole and phase being the following theorem can be stated. (4) = ⁄ Theorem 1: Considering a symmetrical phase winding excited by symmetrical currents with a phase shift of 2 ⁄ each and neglecting those harmonics which cannot induce the winding (line-line) in case of a star connection, the following holds true: The winding under investigation has at most different absolute winding factors. Proof 1: Because the phasor distribution of the star of phasors is the same after steps, there are at most different winding factors ∈ 1, . For ∈ ℕ , is given by = 2 (per base winding) and the ordinal number is given by = +2 , where ∈ ℤ . So there are ⁄(2 ) = winding factors left. For ∈ℕ , = , = + and again ⁄ = . For a full proof utilizing symmetrical components please refer to [7]. Theorem 2: To compensate a winding factor with and and phasors of each turns per phasor the distribution of phase must have the same symmetry axis. Proof 2: , given by (3) must equal zero for a given ordinal number. Therefore ∑ cos( ) + ∑ sin( ) = 0. Consequently each term in square brackets must equal zero. Assuming (without limitation) positive phasors and distinguishing between and leads ∑ cos( ) = 0 for the first ) + ∑ cos( to ∑ sin( ) + ∑ sin( ) = 0 for the and second bracket. If sine or cosine sums are zero the symmetry axis is either the real or the imaginary axis respectively. In )⁄∑ cos( ) and general = − ∑ cos( )⁄∑ sin( = − ∑ sin( ) , which leads to )⁄∑ cos( ) = ∑ sin( ) ∑ sin( )⁄∑ cos( Finally tan( ) = tan( ) and = + , ∈ ℤ. This is the first main result of this work. It limits the number of possible distributions of and phasors to the symmetrical ones (e.g. Fig. 2). Please note that distributions providing a low THD in [5] are symmetrical ones. It can be further shown that for symmetrical distributions of and phasors given by (4) can be calculated using = , (5) counts the phasors under consideration. From where theorem 2, the following can be stated Theorem 3: A winding factor can be set to zero if theorem 2 and N > 0 are satisfied. Proof 3: Follows directly from theorem 2 and its proof. N > 0 simply states that the resulting phasors must point in opposite directions (Fig. 2). When more than two turn numbers shall be utilized to compensate more than one winding factor, theorem 2 can be generalized to Theorem 4: Let denote the integer of different turn numbers , , …, . To compensate ( − 1) different winding factors, all , ∈ 1; phasors must have the same symmetry axis. Proof 4: Without limitation the proof is shown for = 3. Let ( ) denote the vector of the geometrical sum of phasors for ordinal number . To compensate a winding factor , A+ (North Pole) a) A– (South Pole) A+ b) A– Fig. 3. Star of phasors for a 12/10 winding. a) Without b) with transposed coils from north to south pole and various turn numbers. ( )+ ( ) + the following must hold true ( ) =0. The same applies for , it is ( ) + , ( ) + ( ) =0. Both equations can only be satisfied when all ( ) are linearly dependent, i.e. point along the same axis. Again all resulting turn ratios must be positive similar to theorem 3. In general it can be seen that various configurations can be used to set distinct winding factors to zero. In the following some examples are described in detail. ZONE FACTOR WITH VARIOUS NUMBERS OF TURNS PER GROUP IV. A. First Grade Windings First grade windings are defined by ∈ℕ [8]. Consequently the number of phasors per zone is equal for north and south pole regions. Fig. 3 shows a 12/10 winding with two phasors each pole (“pole” refers to + or – phasors respectively which is in accordance with the Tingley Chart). To achieve a symmetrical configuration according to theorem 3 one north pole phasor needs to be transposed to the south pole region ∈ℕ . For ∈ℕ two phasors shall be when transposed from the north pole to the south pole. Afterwards and turns are assigned alternately around the star of phasors. The zone factor is given by , = 1 1 cos + − ( ) cos( )− (6) ( + Γ) , + Γ) cos( where / counts the phasors with / turns respectively. The first sum takes into account all north pole phasors, while the second represents all south pole phasors. The distance from the north to the south pole region is given by Γ= ( − + )⁄2 [9]. Treating (6) as a geometric series the zone factor can be simplified. Considering only odd harmonics (6) results in , = 4 ⋅ (1 + sin ) 4 sin(να ) cos +cos( − +2 4 − 4 (7) −2 ). A four-layer winding is modelled as two double-layer windings which are shifted with respect to each other. The winding Fig. 4. Normalized MMF function and its reconstruction for = = −0.5 p.u. and = √3⁄2. = ∙ factor is then given by the pitch factor. The shifting factor , ∙ is ⋅ =sin( = 1 p.u. , where denotes ), (8) when the current direction is kept unchanged. ℎ counts the number of phasors the second winding is shifted by. When the current direction is reversed (7) becomes , ⋅ =sin( ). (9) To get to the final four-layer winding, the second winding needs to be shifted by ℎ = /2 steps and the current direction needs to be reversed. Consequently, the total winding factor results in , = cos ⋅ sin 4 ⋅ (1 + 4 sin(να ) ) − +2 4 ⋅ − + cos( 4 −2 ) sin = To compensate the winding factor for results in ( )=− cos cos − − 4 4 (10) 2 the turn ratio −2 +2 . (11) Eq. (10–11) provide the second contribution of this research. = 1, = 3 and = 1 the turn Setting = 2⁄5 with = √3⁄2 . Thus, the winding presented in ratio results in [3] is fully described. Fig. 4 shows a reconstruction of the MMF applying (10– 11). As the phasors represent coils, the resulting winding is a four-layer winding with various numbers of turns per coil. Assuming two single layer windings, each phasor will represent a coil side. Applying the same procedure, the resulting winding will be a two-layer winding with various numbers of turns per coil side. While the pitch factor becomes = sin( ∙ ⁄2) for the latter case (10–11) are still valid and the winding presented in [4] is fully covered as well. For all 12/10 windings = √3⁄2 provides minimal THD and the cancellation of the first subharmonic (Fig. 5). THD and winding factors are summarized in Table 1. The harmonic distortion is calculated according to Fig. 5. Normalized MMF spectrum for a 12 slots 10 or 14 poles fourlayer winding. ∑ ∈ℕ , = Fig. 7. Normalized MMF spectrum for an 18 slots 14 poles four-layer winding. , , . , (12) A new winding can be designed by choosing = 3 ⁄ 7 with = 1 and = 5 (Fig. 6). The turn ratio will now allow to compensate the winding factor either for =1 = 1.3473) or for = 5 ( = 2.5321). Fig. 7 shows the ( = 1. Besides cancelling MMF for the first case and for = winding factors, the THD can be minimized setting ( = 1.9390 (Table 2). It can be shown from (7) that ( )) ⁄ ( ) ≠ 0 and ( ( = )) ⁄ ( ) < 0 . So the main winding factor increases for > 1. As and are assigned alternately slot current loading is the same for all slots. Additionally when ⁄ 2 ∈ ℕ each stator tooth will and one with turns. So only one type carry one coil with of pre-wound teeth is needed (Fig. 8). Studies on four-layer windings with equal turn numbers can be found in [10, 11]. … C- A+ A- B+ B- B- B+ C- C+ A- A+ A+ A- B+ B- C+ C- C- A+ A+ A- A- A+ C+ C- C- C+ C+ C- B- B+ B+ B- B- B+ A+ 1 2 3 4 5 6 7 8 9 /2 Fig. 8. Winding topology of an 18 slots 14 poles four-layer winding with various numbers of turns per coil. Only the first half of the base winding is depicted. TABLE 2: : WINDING FACTORS FOR AN 18 SLOTS 14 POLES FOUR-LAYER WINDING WITH VARIOUS TURN RATIOS 18/14 FL , , , THD TABLE 1: WINDING FACTORS FOR A 10 SLOTS 12 OR 14 POLES FOUR-LAYER WINDING WITH VARIOUS TURN RATIOS 12/10 FL , , , THD =1 0.0173 0.9012 0.8959 = √3/2* 0 0.8966 0.8906 … =1 0.0066 0.1041 0.8457 0.8220 = 1.94 0.0076 0.0276 0.8648 0.8010 = 1.35 0 0.0686 0.8556 0.8070 From Fig. 6 it can be seen, that five south pole and one north pole phasors allow to form three symmetrical pairs. Let the outer two south pole phasors represent turns, the inner two and the middle north and south pole phasor turns. The zone factor is then given by * Cistelecan et al. [3] To emphasize theorem 4 one more example on four-layer FSCW shall be discussed briefly. A+ A+ (North Pole) a) A– (South Pole) b) A– Fig. 6. Star of phasors for an 18/14 winding. a) Without b) with transposed coils from north to south pole and various turn numbers. , = cos(0 cos(8 ) + cos(10 ) − cos(9 ) − cos(7 ) − ) + cos(11 ) . (13) As = = 7 is the main working wave, it is possible to cancel winding factors for = 1 and = 5 setting = = 1.2660. The main winding factor including 1.8794 and the pich factor results in , = 0.8610. The MMF spectrum is depicted in Fig. 9. It can be seen that all but slot harmonics are cancelled. From above it can be stated that satisfying theorem 3 and 4, first grade windings allow to compensate all except the main winding factors by utilizing different turns per coil in four-layer and per coil side in double-layer configuration. Furthermore for full pitched distributed windings different numbers of turns per coil can be applied directly, as the pitch factor cancels even harmonics. It is interesting to note that consequently double-layer full pitched Fig. 9. Normalized MMF spectrum for an 18 slots 14 poles four-layer winding with three different turn numbers. Fig. 11. Normalized MMF spectrum for a 9 slots 8 poles double-layer winding. windings can theoretically perform similar to cage windings with phases. (14) windings, all remaining harmonics are then increased. Similar to section IV-A the THD can be minimized. The needed turn = 1.0642 providing only marginal ratio results in improvement. Fig. 11 shows the MMF spectra of the doublelayer configuration with equal turns per coil and with = 1.5321. Again the winding topology can be improved by using a four-layer configuration. Utilizing (8–9) and (14) two possibilities are then given to shape the MMF of the resulting winding: the turn ratio and the shifting distance ℎ. Setting = 1 and h = 4 in (9) the winding presented in [3] can be reproduced. With = 1.5321 the first spatial subharmonic is cancelled additionally. Discussed configurations are summarized in Table 3. Because and phasors are not assigned strictly alternately for second grade windings, slot current loading is not equal for all slots, making it further necessary to adjust slot width. Eq. (13) shows that specific 12 result in a vanishing winding factor. In contrast to first grade winding, this is even possible for coil turns in two-layer configurations. Please note that all windings discussed so far possess a similar structure, which is given by various numbers of turns per group and unequal zones. This is exactly the winding structure named after Surjaninoff in [1]. B. Second Grade Windings Second grade windings are defined by ∈ ℕ [8]. Fig. 10 shows the star of phasors for a base FSCW with 9 Slots and 8 poles, = 3/8. It can be seen that the distribution of phase A phasors is symmetrical to the vertical axis. Assigning north pole phasors to and south pole phasors to allows to cancel harmonics according to theorem 2 and theorem 3. Klima derived a closed analytical term for the zone factor valid for distributed and fractional slot windings with equal number of turns [7]. With for (A+) and for (A–) the zone factor can be rewritten to , = ( ( ( )= ) ( ) ( ) ( ( / ) ( / ) / ) ) . (15) As = 3, there are three different winding factors present, which besides the main winding factor are given by = 1,2. Because the winding factor for the fourth and the fifth spatial harmonic is the same, unbalanced radial pull cannot be avoided completely. Nevertheless the influence of the first and the second winding factor can be avoided by compensating either the first or second winding factor. Opposing first grade A+ (North Pole) A– (South Pole) Fig. 10. Star of phasors for a 9/8 winding. Phase A phasors (blue) are symmetrical to the vertical axis. TABLE 3: WINDING FACTORS FOR A 9 SLOTS 8 POLES WINDING TOPOLOGY WITH VARIOUS TURN RATIOS 9/8 , , , , THD Double-Layer 1 0.0607 0.1398 0.9452 1.0871 1.53 0 0.2156 0.9512 1.1190 1.06 0.0522 0.1504 0.9460 1.0862 Four-Layer ℎ = 4 0.71 1* 1.53 0 0.0357 0.0207 0.1386 0.0548 0.0899 0.9367 0.9266 0.9367 1.0306 1.0550 1.0252 * Cistelecan et al. [3] V. GROUP FACTOR WITH WITH VARIOUS NUMBERS OF TURNS PER PHASOR Fig. 12 a) depicts a base winding with = 18 slots and = 3. Instead of zones, the illustrated winding can also be composed of 6 groups with 3 phasors each. According to Fig. 1 and theorem 2, it follows that utilizing different turn ratios each group can be designed to compensate winding factors. The distribution of and phasors must now be symmetrical within each group (Fig. 12 b). The group factor can be A+ (North Pole) a) A– (South Pole) A+ b) A– Fig. 12. Star of phasors for a base winding with = 18 and = 3. a) with equal turn numbers b) with two different turn numbers assigned alternately within each group. Fig. 14. Normalized MMF spectrum for a 18 slots 2 poles single-layer distributed concentric winding. calculated by , ∑ = ( ) cos( ), (16) counts the number of phasors per group. When where and are assigned alternately within each group and ∈ℕ the group factor (16) reduces to , = 1 +1 + 2 −1 2 ⋅ ⋅ +1 + sin 2 ) sin( sin −1 2 (17) . Again distinct spatial harmonics can be compensated by ( )= ( ( ) ) . (18) Two examples shall now be discussed in detail. Setting = 18 , = ⁄ = 3⁄7 a double-layer FSCW is designed. Assigning and according to Fig. 12 b) either the first or the fifth spatial harmonic can be compensated. In contrast to the four-layer case remaining parasitic harmonics are then increased. Fig. 13 shows the normalized MMF spectrum for = 1 and = 2.8794. The THD is minimal for = are summarized in 0.945. Winding factors for different Table 4. The second example on various turn numbers applying the group factor considers a distributed single-layer concentric winding with = 18, = ⁄ = 3⁄1 . This example has Fig. 13. Normalized MMF spectrum for an 18 slots 14 poles double-layer winding. been discussed previously in [5]. The total winding factor is given by , = , . (19) Again several spatial harmonics can be compensated by choosing a turn ratio according to (18). Fig. 14 illustrates the MMF spectrum where the winding factor for the seventh harmonic is set to zero. Fig. 15 shows the THD over the turn . It can be seen that although stated differently in [5] it ratio is indeed possible to improve total harmonic distortion. The minimum THD is given at = 1.0620. Harmonic distortion can be improved by using a turn ratio of e.g. 20/19, a ratio not considered in [5]. Please note that setting = 1 all presented terms reduce to the classical ones derived by Klima [6]. TABLE 4: WINDING FACTORS FOR AN 18 SLOTS 14 POLES WINDING TOPOLOGY WITH VARIOUS TURN RATIOS =1 0.0378 0.1359 0.9019 0.8823 18/14 DL , , , THD VI. = 2.879 0 0.3867 0.8914 1.0505 = 0.6527 0.0582 0 0.9076 0.9159 APPLICATION RELATED REMARKS Regarding broad applications the authors do not think that a winding generally not well suitable for a specific problem becomes an attractive solution by employing various turn numbers. Main challenges remain the more complex manufacturing balanced off by small improvements on the MMF spectrum. On the other side, once a winding is selected, this study allows to easily check if further improvement is for an 18 slots 2 poles distributed Fig. 15. THD over turn ratio single-layer winding. numbers of turns per group and unequal zones or by equal zones and various numbers of turns per phasor. Fig. 16. Zone factors for an 18 slots 14 poles four-layer winding over turn ratio . possible. Although very distinct turn ratios have been discussed above, derived analytical equations are not limited to those cases. In fact, several turn ratios can lead to an improved performance. Fig. 16 shows the winding factors over turn ratio for an 18 slots 14 poles winding (refer to Fig. 8). It can be seen ∈ 1; 1.841 leads to decreased parasitic that any turn ratio spatial harmonics , , and to an increased main winding factor . Likewise, in case of machine problems arising , from specific spatial harmonics e.g. magnetic noise, this research enables to quickly check if the problem can be dealt with directly through adjusting turn numbers. VII. CONCLUSIONS This research presented a systematic approach on windings with various turn numbers. The main results can be summarized as follows • Applying different turn numbers, − 1 winding factors can be set to zero. Therefore all but the main winding factor can be set to zero in the most general case. • To allow for a cancellation of winding factors, phasors with different turn numbers must have the same symmetry axis. • Windings with various turn numbers known so far possess a similar structure, which is given by various • This allows to easily find similar yet unpublished windings. This includes fractional slot as well as distributed windings for single-, double- or multilayer topologies. • Zone- and group factors for alternately assigned turn numbers are derived. It is shown that turn numbers allow for several optimization targets, i.e. cancellation of specific winding factors or the minimization of the total harmonic distortion. REFERENCES [1] F. Heller and W. Kauders, “The Görges Polygon (Das Görgessche Durchflutungspolygon),” Archiv für Elektrotechnik, vol. 29, no. 9, pp. 599–616, 1935. [2] A. M. EL-Refaie, “Fractional-slot concentrated-windings synchronous permanent magnet machines: Opportunities and challenges,” IEEE Trans. Ind. Electron, vol. 57, no. 1, pp. 107–121, 2010. [3] M. Cistelecan, F. J. T. E. Ferreira, and M. Popescu, “Three phase toothconcentrated multiple-layer fractional windings with low space harmonic content,” IEEE Energy Conversion Congress and Exposition, pp. 1399– 1405, 2010. [4] G. Dajaku, Wei Xie, and D. Gerling, “Reduction of low space harmonics for the fractional slot concentrated windings using a novel stator design,” IEEE Trans. Magn, vol. 50, no. 5, pp. 1–12, 2014. [5] W. Ouyang, A. El-Antably, Surong Huang, and T. A. Lipo, “Analysis of optimal stator concentric winding patterns design,” Proceedings of the Eighth International Conference on Electrical Machines and Systems, pp. 94–98, 2005. [6] W. Kauders, “Classification of AC-Windings Part 1 (Systematik der Drehstromwicklungen Teil 1),” Elektrotechnik und Maschinenbau, no. 50, pp. 88-94 a. 106-108, 1932. [7] V. Klima, “On the theorem of the sum of squares of winding factors invariance,” Acta Technica CSAV, no. 3, pp. 365–388, 1979. [8] J. Pyrhonen, T. Jokinen, and V. Hrabovcová, Design of rotating electrical machines. Chichester, U.K: Wiley, 2008. [9] A. Binder, Electrical machines and drives (Elektrische Maschinen und Antriebe: Grundlagen Betriebsverhalten). Berlin, Heidelberg: Springer, 2012. [10] P. B. Reddy, A. M. El-Refaie, and K.-K. Huh, “Effect of number of layers on performance of fractional-slot concentrated-windings interior permanent magnet machines,” IEEE Trans. Power Electron, vol. 30, no. 4, pp. 2205–2218, 2015. [11] A. Abdel-Khalik, S. Ahmed, and A. Massoud, “Effect of multilayer windings with different stator winding connections on interior PM machines for EV applications,” IEEE Trans. Magn, p. 1, 2015.
© Copyright 2026 Paperzz