rudox mitsubishi natural gas generator set rm1000g - ENER

RUDOX MITSUBISHI NATURAL GAS GENERATOR SET
RM1000G
RATED OUTPUT for 60 HZ
Continuous duty
1000 KW
For unlimited hours per year and 100%
load factor
OVERALL DIMENSIONS
LENGTH
WIDTH
HEIGHT
DRY WEIGHT
190 INCHES
65 INCHES
85 INCHES
26500 POUNDS
CLEAN EXHAUST EMISSIONS
Emissions
NOx
CO
NMHC
__ g/bhp – hr_
.7
.5
.2
PERFORMANCE CHARACTERISTICS
Standard Rudox generator sets have high
performance components to meet the toughest
applications.
- PRECISE VOLTAGE REGULATION
+ ½ % Steady State
+ 1 % from no load to full load
- PRECISE FREQUENCY CONTROL
The Woodward electronic isochronous
governor has 0% droop, no load to full load,
and + 1/4 % steady state.
- PERMANENT MAGNET EXCITATION
Provides excellent performance with heavy
SCR loads. 300% full load current available
for 10 sec. during short circuit condition.
EXCELLENT FUEL EFFICIENCY
Fuel Consumption
6800 BTU/hphr
9495 BTU/kwh
At 100% load based on L. H. V.
Natural Gas Supply Requirements*
Gas Use
Pressure (psi) % of Total Gas
· Main gas
2.5
90%
· Pre-chambered gas
35 to 40
10%
*Requires a maximum of 10 million BTU/hr. of pipeline
quality gas at 1040 BTU/CF ± 5%
VOLTAGE RANGE
- HIGH MOTOR STARTING CAPACITY
250% of rated capacity for 10 seconds;
- LOW EMISSIONS
The Mitsubishi LeanBurn engine has low
emissions without any after treatment
- PARALLELING OPTIONS
Controls can be added for completely
automatic multi-unit synchronization
and load sharing.
3 WIRE
60HZ
416 - 480
208 – 240
----------------------------------------4 WIRE
240/416 - 277/480
120/208 - 138/240
NOTE: 4.1 and 13.8 KV are also available
RUDOX
THE COMPLETE SUPPLIER OF QUALITY PRODUCTS
SALES - RENTALS - PARTS - SERVICE
GENERATOR SET SPECIFICATIONS - 60 HZ - 100% loaded
KW
KVA
HP
BMEP
Combustion air flow
Heat rejection to ambient
1000
1250
1445
160 psi
3630 CFM
10070 BTU/min.
NATURAL GAS ENGINE
Type
Combustion chamber
Compression ratio
Engine speed
Cylinder arrangement
Displacement
Exhaust flex diameter (min)
Muffler diameter (min)
Maximum exhaust back pressure
Intercooler water requirement
RM1000G
Heat rejection to jacket water
Heat rejection to intercooler
Exhaust gas flow
Exhaust temperature
Jacket water coolant flow
Jacket water temperature
33585 BTU/min
12593 BTU/min
3793 SCFM
800º F
489 GPM
190 to 205º F
Mitsubishi GS16R-PTK
4 cycle, water-cooled, turbocharged, intercooled with separate coolant flow
Ultra Lean Burn with pre-chamber ignition
11.5:1
1800 RPM
60 degree vee 16 cylinder
3989 cubic inch; bore, 6.69; stroke. 7.09
12 inches (inside)
12 inches (inside)
23.6 inches of water
Maximum 110º F at 132 GPM
STANDARD EQUIPMENT
- Mitsubishi GS16R-PTK natural gas engine
- Newage Stamford generator (HCI634K) rated for
105º C rise with 3 phase static voltage regulator
(MX321) and permanent magnetic excitation. All
rated per NEMA Code with class H insulation.
- Heavy duty structural steel subbase
- Woodward isochronous governor and air/fuel
rated controller
- Free standing control panel with:
Altronic CPU95 ignition system, automatic
start/stop control, gauges for oil pressure,
cylinder temp., battery voltage, water temp.,
running hours, AC amps, AC volts, frequency,
KW, KVA, and power factor
- 24 volt automatic electric start system
- 30 amp battery charger
- Engine safety switches & Pre-alarms:
low oil pressure, high water temperature,
overspeed, overcrank, high exhaust temperature,
low gas pressure, ignition fault
- Residential silencer with stainless steel flexible
connection
- 24 volt lead acid battery, rack and cables
- Flexible fuel lines
- Catalytic convertor for CO and MNHC
- Local computer with 6 screens for real time and
historical data display
- Remote telephone access to local computer
OPTIONAL EQUIPMENT
- Remote-type radiator for jacket water
- Critical silencer
- Heat exchangers
- Remote radiator for intercooler
- Closed loop evaporative cooler for
intercooler
- Thermostatic valve for intercooler
- Auxiliary pump for intercooler
- Gas compressor system
- 2 Bearing generator close coupled with
flexible coupling
- Outdoor enclosures
- Jacket water heaters
- Automatic transfer switch
- High voltage generator – 4160 or 13800
- Main line circuit breaker
- Remote annunciator
- High ambient radiator rating
- Vibration dampers
- Paralleling controls
- Pre-alarms
- Others, as required
Specifications are subject to change without notice
3/2009