Desigo® Fire Safety System
Leased-Line / City-Tie Module
Model FCI2020-U1
ARCHITECT AND ENGINEER SPECIFICATIONS
• Connects a Desigo Fire Safety System
to a municipal call box
All connections are supervised by all Desigo
(fire and intelligent voice communication) systems
Installed on the Model FC2005 fire-alarm control panel’s
(FACP) main board, Model FCM901-U2
Installed on Desigo 252-point (Model FCI2016-U1) and
504-point (Model FCI2017-U1) periphery boards
• Provides system-event data over leased
telephone lines
• Power-limited protection
•
UL 864 9th Edition Listed, ULC Listed;
FM, CSFM and NYC Fire Department Approved
Product Overview
Model FCI2020-U1 is used as an optional
module, giving a local-energy output for
municipal call-box connections. Additionally, a
leased-line / city-tie module provides reversepolarity output for leased-line connections.
Model FCI2020-U1 is installed on the 252-point
(Model FCI2016-U1) and 504-point (FCI2017U1) periphery boards, respectively, but is
installed on the back of the main board (Model
FCM901-U2) used with Desigo 50-point
addressable panels.
When an optional leased-line / city-tie module is
used on Desigo 50-point panels, a wiring harness
(Model FCA901-U1) must be ordered separately.
When used for connection to a municipal call
box, the city-tie function supports Alarm-event
transmission.
When used for leased-line
connection, the module supports two (2) leased
telephone lines for transmitting Alarm, Trouble
and Supervisory system events.
The Leased-Line / City-Tie Module is FM (#3010); CSFM
(#7165-0067:0259), and FDNY (#6104) Approved.
Additionally, the programming software is held in flash
electrically erasable programmable read-only memory
(EEPROM).
Temperature and Humidity Range
Model FCI2020-U1 is UL 864 9th Edition Listed for
indoor dry locations within a temperature range of 120
+/- 3°F (49 +/- 2°C) to 32 +/- 3°F (0 +/- 2°C) and a relative
humidity of 93 +/- 2% at a temperature of 90 +/- 3°F (32
+/- 2°C).
Related Documentation
Product Data Sheet
FC2005
(50-point addressable panel)
Number
6813
FC2025
(252-point addressable panel)
FC2050
6815
(504-point addressable panel)
FV2025
(252-point intelligent voice addressable panel)
FV2050
6821
(504-point intelligent voice addressable panel)
Leased-Line / City-Tie Module
s Industry, Inc.
Building Technologies Division
6810
Technical Data
Supply
Inputs
Leased-line ‘Normal’ (Standby)
Leased-line Alarm Current
Leased-line Supervisory
Operating
Currents
City-tie ‘Normal’ (Standby)
City-tie Alarm Current
Voltage
+24VDC,
Admissible cable
cross-section
nominal (open)
1.6mA
+24VDC, nominal (open)
22.5Ω, max
350mA
+24VDC, nominal (open)
0 VDC
-24VDC, nominal (open)
2 ─ 5Ω
25mA
+24VDC, nominal (open)
-24VDC, nominal (open)
2 ─ 5Ω
25mA
Two (2) screw terminals
12 ─ 22
American Wire Gauge (AWG)
System Interface
Plug-in-type connection
Supervisory condition
O
U
T
P
U
T
S
Open-circuit-supervision current
Output 1
Alarm operation
{City-Tie}
Loop resistance at Alarm
Maximum-shorted current
‘Normal’ operation
Trouble operation
Output 1
{Leased-Line}
Alarm operation
Circuit resistance
Maximum-shorted current
‘Normal’ operation
Output 2
Supervisory condition
{Leased-Line} Circuit resistance
Maximum-shorted current
Design
Connections
Model FCI2020-U1
Dimensions:
Physical
Properties
27mA @ 24VDC, nominal
40mA @ 24VDC, nominal
9mA @ 24VDC, nominal
2mA @ 24VDC, nominal
13mA @ 24VDC, nominal
24VDC, nominal;
(18 ─ 28VDC for battery)
2.75” ─x─ 3.2”
(7 cm. ─x─ 8.13 cm.)
{ W -x- H }
Model FCI2020-U1
Weight:
1.3 Lbs. (590g)
Details for Ordering
Model
Part
Number
FCI2020-U1
S54400-A57-A1
Optional Leased-Line / City-Tie Module
FCI2016-U1
S54400-A55-A1
Periphery Board used with 252-point addressable panels
FCI2017-U1
S54400-A56-A1
Periphery Board used with 504-point addressable panels
FCM901-U2
S54433-B100-A1
Main Board (used specifically for 50-point {FC2005} FACPs)
FCA901-U1
S54433-C106-A1
Wiring Harness | Leased-Line/ City-Tie Module | 50-point FACPs
Description
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.
Fire Safety
8 Fernwood Road
Florham Park, NJ 07932
s Industry, Inc.
Building Technologies Division Tel: (973) 593-2600
FAX: (908) 547-6877
URL:
www.USA.Siemens.com/Desigo-Fire-Safety
(SII-FS)
Printed in U.S.A.
Fire Safety
1577 North Service Road East
Oakville, Ontario
L6H 0H6 / Canada
Tel: [905] 465-8000
URL: www.Siemens.CA
June 2016
Supersedes sheet dated 2/2013
(Rev. 3)
© Copyright 2026 Paperzz