Guidance for the Installation Of LPG and LPG Fired Equipment in

The Nationwide Caterers
Association (NCASS)
Guidance for the Installation Of LPG and LPG
Fired Equipment in
Catering Trailers, Converted Vehicles, Portable
Kitchens, Carts, Trolleys and Bikes.
Rev 8 - Aug 2012
Further copies are available from:
The Nationwide Caterers Association
Association House. 89 Mappleborough Rd, Shirley, Solihull, West Mids. B90 1AG.
Tel: 0121 603 2524 Fax: 0121 474 3938
Email: [email protected] Web: www.ncass.org.uk
Copyright: The Nationwide Caterers Association (NCASS) 2011. This document may be freely copied or communicated provided that it is not
changed in any way and that NCASS are acknowledged as the copyright owner
Page
Contents
SECTION 1
Introduction
Definitions
Advice to purchasers of mobile catering trailers and van conversions
Legislation / regulations
2
4
8
10
SECTION 2 - Design & Construction
Weight considerations
Positioning of cylinders
11
12
SECTION 3 Gas installation and pipework Cylinders & hoses
High pressure stage
Automatic changeover devices
Manual changeover devices
Pressure regulators
Regulator hoses
Multi cylinder installations
Cylinder compartments / housings
Pipework
Emergency control valve (ECV)
Connection from rigid pipework to appliances
13
13
13
13
13
14
14
15
18
18
19
SECTION 4 - Appliances
CE marking
Appliance siting
Water heaters
Domestic cookers
LPG refrigerators
Built in LPG generators
Standalone generators
Fryers & chip ranges
20
20
20
20
20
21
21
21
SECTION 5 - Ventilation
Minimum requirements for ventilation of unit
Canopies & flues
Specific requirements for forced extract canopies
22
22
23
SECTION 6 – Maintenance & Gas Safety Check
The registered gas engineers inspection
Routine safety checks
Hired in equipment
24
25
25
SECTION 7 – Fire Precautions
26
Appendices
Gas safety record
Enforcement officers checklist
28
29
Page 2
Section 1 - Introduction
These guidelines have been prepared in consultation with those involved in the Mobile &
Outside Catering industry, specifically:
•
•
•
•
•
•
•
•
•
•
•
•
•
Catering trailer manufacturers and van converters (10)
Calor Gas
EU Skills
Gas Safe Register
Gas Safe registered engineers (several)
Gastec
IGEM (Institute of Gas Engineers and Managers)
OPGO (Organisation for Professional Gas Engineers)
PKL Group
Staffordshire Fire Service
The Institute of Fire Prevention Officers
UKLPG
Wessex Fire Service
It has been compiled by The Nationwide Caterers Association.
Scope
This guidance only covers commercial catering trailers, and vehicles that have been
converted to become mobile catering vehicles, portable kitchens, carts, trolleys and
bikes which use Liquefied Petroleum Gas (LPG) supplied by cylinders for the purpose of
cooking, storing or preparing food for sale or distribution and fuelling generators used in
conjunction with the catering business.
It does not included vehicle mounted LPG tanks or vehicles propelled by LPG.
It does not include cooking equipment intended for domestic or leisure purposes, such
as domestic barbecues.
Purpose
This document provides practical guidance for the installation and safe use of LPG and LPG
fired equipment in the instances covered by The Scope’.
“This guidance has been developed by The National Caterers Association (NCASS) in
consultation with the other organisations and industry experts listed in Section 1 to help
caterers, their employers, and gas engineers to make health and safety improvements in
the mobile & outside catering industry. This guidance may go further than the minimum
you need to do to comply with the law and NCASS acknowledges the support of the
Health and Safety Executive in producing this guidance."
‘Health & Safety Executive’
Page 3
Definitions
‘A’ Frame
The ‘A’ shaped frame at the front of a catering trailer that connects the chassis to the
towing hitch.
Annual Gas Safety Check
A check to ensure safe operation of gas appliances, pipework and flues, carried out by a
suitably qualified Gas Safe engineer, with competence to work on commercial LPG mobile
catering units.
Automatic Changeover Device
A valve to allow two or more LPG cylinders to be connected at once. When the service
bottle runs low the regulator automatically switches over to the reserve bottle. There is a
period that both bottles are being used. The point at when this happens depends on the
gas rate required by the appliances and the maximum take-off rate of the cylinder.
The indicator on the changeover valve points to the service bottle and tells the user its
status, when the service bottle is totally empty the indicator normally turns red, you can
simulate this by turning off the cylinder valve. At this point the reserve bottle is being used.
Only turn over the changeover valve to point to the reserve bottle when the service bottle
is completely empty, this is to get all the expensive gas out of the bottle and used up. The
indicator will start showing red when there is still a considerable amount of gas in the
service bottle.
When the changeover valve is turned over to the other cylinder, the reserve bottle
becomes the service bottle and the empty one needs changing for a full new reserve
bottle.
Changeover valves will ensure an uninterrupted gas supply to the appliances and reduces
the number of trained personnel needed to be able to change cylinders safely.
Bain Marie
Used for keeping food hot i.e. Above 63º C
Bain marie’s are available in a wide variety of shapes, sizes, and in either wet or dry types.
BLEVE - (Boiling Liquid Evaporating Vapour Explosion)
An explosion of a Gas cylinder that happens when the cylinder wall has failed and the
liquid gas explodes, causing a fireball with a size and duration depending on the amount
and type of gas released. This is not a manageable emergency other than quick
evacuation out of an exclusion zone that takes into account that propane gas cylinders can
be thrown 50 meters away in any direction, the minimum safe distance from a potential
BLEVE involving propane cylinders of 19 kg and above is 100 meters.
Page 4
Butane Gas
Butane, while not as commonly used as propane, is nonetheless a very popular fuel, but
not recommended for commercial mobile / outdoor catering.
CE Marking (CE Mark)
A mandatory conformance mark on many products first placed on the single market in the
European Economic Area (EEA), since 1 January 1996, to indicate that a product satisfies
the requirements of the Gas Appliances (Safety) Regulations 1995.
Competent Person
For the purpose of this guidance a competent person is someone who has had basic
training in the safe use and handling of LPG for the purpose of changing cylinders etc.
Cylinders
A portable container designed in accordance with the relevant British & European
Standards for the storage of Liquefied Petroleum Gas under pressure that can be refilled
by an authorised filling plant.
Cylinder Valve
The device sited at the top of the cylinder to enable discharge of the gas when open and
seal the cylinder when not open. It also incorporates a pressure release valve that opens
when the internal pressure of the cylinder gets too high or when the cylinder gets too hot.
This can happen when the cylinder reaches 70 degrees, It is therefore very important that
cylinders are kept in an upright position as the release rate when liquid comes out is 250
times higher than when gas comes out. The other reason is that when a cylinder valve is
open and the coming out is on fire it must not be impinging on adjacent cylinders as these
can then fail with a BLEVE as a result.
Enforcement Officers
Trading Standards Officers, Health and Safety Inspectors or Environmental Health
Officers.
Flame Supervision Device (FSD) also known as a Flame Failure Device
(FFD)
A device fitted to an appliance to stop gas from flowing when there is no flame present.
The most common type is a thermoelectric valve that uses a thermocouple to generate a
minute amount of electricity to hold a magnetic valve open.
Page 5
Flueless Appliance
A gas appliance that by its design does not require connection to a flue / chimney.
Flued Appliance
An appliance that must be connected to a flue or chimney to take products of combustion
safely to the outside air.
Gas Appliance
For this guidance a device manufactured and tested to a relevant standard and CE
marked (where necessary), fuelled by LPG for the purpose of cooking, heating, lighting or
chilling of foodstuffs and liquids.
Gas Safety Report
A report completed by a registered gas engineer stating to what extent a gas installation
complies with gas safety standards.
Gas Work
The installation, adjustment, maintenance, commissioning, de-commissioning, purging, or
adjustment of gas installation pipework, appliances or associated fittings in accordance
with the Gas Safety (Installation and Use ) Regulations 1998 (GSIUR).
LPG
Liquefied Petroleum Gas either Propane or Butane to BS 4250.
Non Return or Check Valve
A device that permits the gas flow in only one direction, typically found in the POL
connector on the pigtail. Wall blocks that have one or two pigtails joining a female POL
connector will normally also have non return valves fitted. The excess flow valve is the
same valve that will slam shut when the cylinder is opened too quickly or when the take-off
rate exceeds the excess flow shut off rate.
OPSO / UPSO Valve
A safety device that protects the downstream gas installation against dangerous pressure
situations, OPSO valves cut off the supply when the pressure gets too high, UPSO valves
cut off the supply when the pressure gets too low.
Page 6
Pigtails
The connection between the propane tank and regulator is commonly called the pigtail.
The pigtail connects to the service valve of the propane cylinder and the inlet connection of
the regulator. This connection is relatively small in diameter which initially restricts the flow
of gas from the tank to the regulator. Pigtails should be replaced when the regulator is
replaced.
POL Connection
The name of the type of valve connection for propane cylinders in the UK, it uses a left
hand thread and a conical nose. Regulators can be connected to the cylinder with a POL
connector or with a pigtail tube between the cylinder and the regulator. A POL spanner is
30 mm wide spanner, remember that left hand thread goes the other way round than
normal thread. In Ireland the gas cylinders use a different connector; these are known in
the UK as Butane connectors. In the USA a slightly different version to the British POL
connectors are used and these are not compatible.
Propane Gas
Propane (C3H8) (also called commercial propane) is the gas mostly used in catering in the
UK. It is available in various sized cylinders painted red or orange. It is stored in liquid form
under pressure in the cylinder and will evaporate to the gas form when gas is used.
A 47 kg cylinder will contain 100 litres of liquefied gas, when evaporated this will turn into
25 cubic meters of gas.
Registered Gas Engineer
An engineer registered with Gas Safe Register and for this purpose, qualified to install,
commission and maintain commercial catering equipment fuelled by LPG in mobile
catering installations.
Regulator (Cylinder)
A device that maintains a constant outlet pressure which can be fitted to the cylinder
directly or connected remotely to the cylinder with a suitable hose ( pigtail to BS 3212/2 or
BS 1763). Suitable fixing positions / methods are described later.
Some regulators are single stage and reduce the pressure to 37 mbar and others are
reducing the pressure to 1.5 bar and supply a second regulator downstream that reduces
the 1.5 bar into the 37 mbar which is the pressure required to fuel appliances.
Take Off Rate / Evaporation Rate / Gas Freezing
The rate at which the liquid inside a cylinder evaporates. This can be expressed in kg per
hour, cubic meter per hour or kilowatts per hour. In the catering industry kilowatts per hour,
is normally used.
Page 7
Gas freezing is where we want to use more gas than the maximum take-off rate, The
result is that the gas pressure at the regulator outlet is reduced so the amount of heat at
the appliance is also reduced. This reduction is not linear, half the inlet pressure is still
more than half the gas rate. The maximum take-off rate depends on the ambient
temperature of the gas cylinder and on how full it is.
Hot Water Boiler
An appliance for the purpose of heating water to boiling point.
Water Heater
An appliance for the purpose of heating water to a set temperature.
Page 8
Advice to Purchasers of Mobile Catering Trailers and Van Conversions
New Trailers
A newly built gas installation should come with written evidence that the installation
complies with current safety legislation. It should contain details of what the installation
consists of and who checked that it complies.
We advise any potential purchaser to ask for a Gas Safety Report if one is not
automatically supplied. The reason being that it is likely that if you apply to work on a site,
or at an event you may be asked to provide it before you are allowed to work.
Second Hand Trailers
It is recommended when buying a second hand trailer to ensure it has been issued a Gas
Safety Report within the previous 12 months.
If in any doubt get it checked by a suitably qualified registered gas engineer before you
commit to a purchase or alternatively purchase from an NCASS approved catering trailer
manufacturer or van converter.
Page 9
Legislation / Regulations
There are several pieces of legislation that have a bearing on this guidance:
•
The Health and Safety at Work etc. Act 1974.
•
The Gas Safety (Installation & Use) Regulations 1998.
•
The Road Vehicles (Construction and Use) Regulations 1986, as amended.
•
The Carriage of Dangerous Goods and Use of Transportable Pressure Equipment
Regulations 2004.
•
The Gas Appliances (Safety) Regulations 1995.
•
The Carriage of Dangerous Goods by Road Regulations 1996.
•
The Carriage of Dangerous Goods (Classification, Packaging and Labelling and use
of Transportable Pressure Receptacles) Regulations 1996.
•
Provision and Use of Work Equipment Regulations 1998.
There are also normative documents that are relevant:
UKLPG:
•
Technical Fundamentals.
•
COP 24 Pt 3 LPG cylinders in mobile catering vehicles.
•
COP 24 Pt 4 use of LPG Cylinders for catering and outdoor functions.
British Standards Institute:
•
BS5440 pt 1& 2 Flueing and ventilation.
•
BS5482-1 & BS6891 specification for pipework.
•
BS EN 1949 LPG systems in vehicles.
•
BS6173 catering installations.
This list is not exhaustive.
Page 10
SECTION 2 - Design and Construction
Weight Considerations
As LPG cylinders are very heavy items and, when full, can weigh twice the marked weight
of the cylinders LPG contents, consideration must be given to the following:
1)
When in a trailer
•
•
•
•
•
•
•
2)
Stable towing.
The trailer remains within the trailer manufacturers maximum recommended weight.
This should be taken to mean the permissible maximum weight, also known as the
gross vehicle weight.
The nose weight does not exceed the towing bracket recommended limits.
The trailer does not exceed the recommended towing weight of the towing vehicle.
The combined weight of the towing vehicle and the trailer do not exceed the
recommendations of the towing vehicle manufacturer.
Manual handling.
Driver licensing conditions.
When in a converted vehicle
That it does not take the vehicle over its recommended MAM (Maximum Allowable Mass)
This should be taken to mean the permissible maximum weight, also known as the gross
vehicle weight.
Page 11
Positioning of Cylinders
Cylinders carried in either a trailer or a converted vehicle should be located in a position
that minimises the risk of damage in case of an accident whilst in transit.
Where pipes exit the compartment, the annular space should be fire stopped.
The gas box should be constructed from fire proof material that gives 30 minutes fire
resistance. There should be a warning sign on the access door indicating that highly
flammable LPG is stored within.
Fig 1.Typical mobile catering trailer layout with a cylinder compartment at the front on the
‘A’ frame
Page 12
Gas Installation and Pipework
Design
Cylinders and hoses
For design purposes the nominal take off rate of a 19 kg cylinder is 20 kW and for a 47 kg
cylinder 33 kW the design should be based on average use of the gas when an automatic
changeover valve is used and based on maximum use without change over valve. Use kW
to express gas rate for convenience.
Appliances that have kg/hr rating on the indicator plate can be translated by multiplying
the kg/hr by 14 to get the kW rate. If it indicates cubic meter per hour then multiply this
figure by 26 to get the kW rating. The installation must be designed for maximum use,
diversification factors are not normally used.
If the installation has more than one cylinder on the same side of a changeover valve, it is
recommended to use splitters at the changeover valve end and use pigtails that are fitted
with a non-return / excess flow valve in the POL connector.
If the daisy chain method is used, there can be problems with gas release when cylinders
are being changed and with the excess flow valve slamming shut. Daisy chain connection
of multiple gas cylinders should only be used in special circumstances.
The pigtails should be as short as reasonably practical, and always run uphill to avoid
ingress of oil residues into the regulator.
There is no expiry date on hoses but they should be replaced as soon as they show signs
of wear, aging, damage, weathering or cracks. Hoses older than 5 years should be
rigorously checked.
Hoses that carry gas from cylinders to regulators must have factory swaged connections
and cannot be used with just home-made crimps.
High Pressure Stage
High Pressure stage pigtails should be contained with the cylinder compartment / housing
or, in the case of external cylinders, within the tamper proof enclosure as shown in Fig 2
Automatic Changeover Devices
Automatic changeover devices should have non return valves at the high pressure inlet to
prevent discharge of gas when changing cylinders and an indicator to show which cylinder
is in use.
Manual Changeover Devices
Must have a means of identifying the cylinder in use.
Pressure Regulators
The primary regulator should comply with BSEN 12864 and be correctly matched to the
type of gas.
Page 13
The size of the regulator depends on the amount of gas needed. They are rated in kg/hr
and every kg equals 14 kw. The regulator must not be undersized. The type of regulator
also depends on the installation size. Single stage regulators are normally available in
5kg/hr sizes. That is 56 kw.
Larger installations require two stage regulators, the first stage will reduce the pressure
from 10 bar cylinder pressure to 1.5 bar and the second stage reduces it from 1.5 bar to 37
mbar, the normal appliance operating pressure. When there are more than 3 cylinders
connected to an automatic change over valve, an Over Pressure Shut Off valve(OPSO) is
required, these are available in two types, suitable for first stage or second stage
applications. The second stage version is the one that has to be used in catering
installations. Combined second stage regulators and OPSO valves are available from
Hamilton Gas Products.
Regulators that incorporate limited relief valves (usually second stage regulators) should
have the valve discharge routed to outside with a tube diameter of 10 mm or higher
The regulator must be either mounted on the cylinder or fixed to the wall of the
compartment and cannot be left loose.
Regulator Hoses (sometimes referred to as Pigtails)
Flexible hoses should have factory fitted swaged or crimped connections (not hose clips),
be manufactured to BS 3212 type 2 and it is recommended that these be replaced every
(5) years from date of manufacture or three years from the date of purchase or when signs
of wear or damage is identified. Pigtails should not be any longer than 1m.
Purpose made stainless steel Pigtails are available which can give a longer service life.
Multi Cylinder Installations
When more than two cylinders are connected the changeover valve should be fitted with
an Overpressure Shut Off.
It is also possible to have two gas installations in a trailer, provided that it is readily visible
that the gas supply and emergency shut off valve and procedure is laid out in such a way
that it is not likely to have untrained staff isolate the wrong installation in an emergency. A
gas installation must not be fed by more than one regulator or more than one supply.
Where gas installations are designed to have the gas supply on more than one point of the
installation, systems of work should be in place to ensure that it is not practically
happening that there are two supplies feeding a single installation.
When the installation needs multiple cylinders to provide the required gas, they must be
connected with tee pieces at the changeover valve and not normally daisy chained as in
Fig 2. The reason for this is that daisy chained cylinders have to be turned off before any
of them can be changed and that the final pigtail between the nearest cylinder and the
regulator has to convey too much gas, the excess flow valve can slam shut. The pigtails
should incorporate non return valves in the POL connector.
Page 14
Or replacements.
Cylinder Compartments / Housings
Where trailers / converted vehicles have cylinder compartments they must be:
•
•
•
•
•
•
•
•
•
•
The enclosure must be ventilated at high and low levels, to a mminimum levels of
2% of the compartment floor area, equally distributed between high and low levels.
The compartment must be accessible from the outside only.
Have a means of securing cylinders from movement during transit.
Have a means of preventing unauthorised access.
Have a 1 hour fire barrier to the trailer wall.
Only contain the regulator, pigtails, gas spanner and cylinders, no other materials
should be stored in the compartment.
Have only the required number of cylinders to operate the equipment plus a reserve
of the same capacity.
Have an LPG Flammable Gas warning sign on the external side of the door to the
compartment.
Have cylinder changing instructions within the compartment
Have all connections between the compartment and the inside of the trailer fire
stopped.
Page 15
Cylinders not stored in a compartment that forms part of the trailer or vehicle
should be as 1 & 2 below:
1) When cylinders are not stored in a compartment but outside the trailer and over 500 mm
from it:
•
•
•
•
•
•
•
Kept 1m from the trailer in a tamper proof enclosure.
A warning notice must be displayed on the enclosure
The LPG must be distributed using a suitable system such as shown in Fig 3 which
must comprise of an isolation valve, regulator, permanently fixed to the wall of the
enclosure or on a stable post.
The enclosure must be ventilated at high and low levels, to a mminimum level of 2%
of the compartment floor area, equally distributed between high and low levels.
Have only the required number of cylinders to operate the equipment plus reserve
cylinders of the same capacity.
Have cylinder changing instructions within the compartment.
Cylinders must be on a level, flat non combustible surface and if over 13kg should
be secured to prevent them falling over.
Pigtails should be a maximum of 2m (as distinct from 1m when cylinders are stored
in a compartment that forms part of the trailer or vehicle.
Fig3. Cylinders stored further than 500mm from trailer / vehicle
Page 16
2) When cylinders are not stored in a compartment but are stored within 500mm of the
trailer/ unit:
•
•
•
•
•
•
•
•
They must be in a tamper proof enclosure with the side backing onto the trailer,
being constructed from materials that will provide 1 hour fire resistance to the body
of the trailer.
The enclosure must be ventilated at high and low levels, to a minimum level of 2%
of the compartment floor area, equally distributed between high and low levels.
A warning notice must be displayed on the enclosure.
The enclosure must only contain the regulator, pigtails , gas spanner and cylinders
Have only the required number of cylinders to operate the equipment plus reserve
cylinders of the same capacity.
Have cylinder changing instructions within the compartment.
Cylinders must be on a level, flat non combustible surface and if over 13kg should
be secured to prevent them falling over.
Pigtails should be a maximum of 1m in length.
Fig4. Cylinders stored within 500mm from trailer/ vehicle
Pipework
All LPG installations and maintenance should be carried out by a registered gas engineer
unless it is undertaken in premises which are outside the scope of GSIUR.
Page 17
The size of the pipework should be adequate to ensure that the flow and pressure at each
appliance at the anticipated maximum system load is within the limits specified by the
appliance manufacturer. This should be based on a maximum pressure drop of no more
than 2.5 mbar between the outlet of the regulator and any appliance inlet when under
maximum load.
•
•
•
•
•
Internal pipework should be constructed from solid drawn copper, stainless steel
corrugated stainless steel or steel, with soft solder, compression or malleable iron
fittings.
Copper pipework and soft soldered fittings should not be used where temperatures
are likely to exceed 100º C.
Pipework running under the vehicle should have mechanical protection All pipework
should be adequately secured to the structure of the vehicle / trailer.
Jointing compound should not be used.
Pipe runs should be designed to facilitate cleaning, laid out and protected to avoid it
being easily damaged.
Emergency Control Valve (ECV)
An emergency isolation valve must be installed inside the cooking area at either the point
where the low pressure pipework enters the cooking area or adjacent to the exit point of
the cooking area.
For single cylinder installations, the cylinder valve can be used as emergency shut off
valve.
A notice clearly identifying the purpose of the valve and the direction of shut off must be
clearly visible. Instructions for emergency procedures should also be displayed, but these
can be incorporated together as shown in Fig 5.
Figure 5 Sample EIV notice
Page 18
Connection from rigid pipework to appliances
Appliances can be connected to the rigid pipework either directly or by means of a purpose
made hose with factory fitted end connector to BS 669-2.
If rigid pipework is used it should be designed to allow for any movement in transit.
Appliance Isolation
All appliances must have a means of isolating it from the gas supply. This can be done in
the following ways:
• A suitable shut-off valve as Fig 6
• A quick release valved coupler, for use
• Hoses must be manufactured to BS669
with Bayonet Gas Catering Hose as Fig 7
part 2 marked suitable for LPG.
Fig 6. Appliance isolation using a shut-off valve and rigid pipework
Fig 7. Quick release valved coupler and a bayonet gas catering hose
Page 19
SECTION 4 - Appliances
CE Marking
If first placed on the EU market since 1 January 1996, gas appliances must be CE marked
which indicates that they have been tested and certified by a ‘Notified Body’.
Appliance Siting
All gas appliances within the installation should:
• be installed in accordance with the manufacturer’s installation instructions and
relevant British Standards.
• be located on a level, non-combustible surface.
• be sited away from combustible materials.
• Allow for adequate cleaning.
• be fixed so as to prevent movement unless they are of a portable nature such as a
kettle, toaster or counter top fryer.
• be sited so as not to obstruct passage ways or exits.
Water heaters
Water heaters should be installed as per the manufacturer’s instructions and flued if
required.
Some appliances can be installed without a flue as long as it has only a single point outlet,
but manufactures instructions must be complied with.
It is recommended that flued or preferably room-sealed water heaters are used.
Domestic Cookers
Domestic cookers that do not have a Flame Supervision Device for all burners should not
be used.
LPG Refrigerators
LPG fridges are not generally made for commercial use and therefore should be
discouraged, if they are being used there must be a notice clearly visible to say that the
device must not be in use whilst the trailer / vehicle is in motion.
Consideration should be given to fridges which can be run off the battery whilst the vehicle
is in motion.
Built in LPG Generators
Where a generator is built into the catering unit body:
•
•
•
It must only be accessible from the outside of the body.
The compartment must have a fire resistance of at least 1hour.
It must be connected to the gas supply by either appliance isolation valve or a quick
release valved coupler.
Page 20
•
•
•
The compartment doors must be vented at high and low level.
The exhaust system must be designed and positioned so as to :
o Ensure that the system itself cannot become a source of combustion.
o The combustion gases cannot become a source of combustion
The generator must be earthed, and the trailer fitted with an earthing point to enable
the attachment of an earthing rod.
The caterer should be advised that they must read the manufacturer’s instructions and that
regular maintenance and checks will be necessary to ensure the continued safe running of
the generator.
Stand Alone Generators
•
•
•
•
Stand alone generators must be CE marked, where necessary.
The generator must have an earth rod.
It must be sited well away from the gas compartment and any other source of
combustion.
It must be sited so that combustion gases cannot gain ingress to the working area.
The caterer should be advised that they must read the manufacturers instructions and that
regular maintenance and checks will be necessary to ensure the continued safe running of
the generator.
Fryers and Chip Ranges
These must be fitted according to the manufacturer’s installation instructions and, where
necessary, be located beneath a ventilation canopy incorporating a flue to the outside.
Exception can be made for single or twin basket counter top fryers with a total oil capacity
not exceeding 14 litres provided that the vehicle or trailer ventilation design guarantees
adequate removal of fume emissions to sustain a safe working environment.
The range must incorporate a manually resettable over temperature thermostat that will
operate if the oil or fat exceeds 230ºC.
Page 21
SECTION - 5 Ventilation
It is essential that adequate free ventilation is provided in cooking areas, this must be fixed
and at high and low levels, and include vermin screens.
Notices should be sited next to ventilation points to inform the operator that these be kept
clean and free of blockages. The serving hatch of the vehicle should not be considered as
part of the purpose provided combustion ventilation to the unit.
Minimum requirement for ventilation
Ventilation should be sized at the rate of 25cm2 per kW for the total of all the appliances or
100cm2 whichever is the greatest. The purpose provided combustion air provision should
be divided equally between high and low levels via two or more purpose provided
ventilation grilles. The ventilation grilles should be labeled ‘Do not block – combustion air
ventilation grilles’ or similar.
A warning notice should be clearly visible in the trailer stating that no appliance should be
operated without either the door or the hatch being open. This is in addition to the required
minimum purpose provided combustion air ventilation requirements.
Canopies and Flues
Natural draught canopies should not be considered as part of the high level purpose
provided combustion air ventilation requirement.
Any canopy must extend a minimum of 150 mm beyond the appliance cooking area on all
sides and should be easily cleanable with removable filters and made from nonflammable
and non-corrosive materials.
Flues and canopies must be fixed to the trailer or vehicle so as to prevent movement in
transit.
Any flue system should be installed in accordance with the appliance manufacturer’s
installation instructions and terminated so the products of combustion can discharge safely
at all times. When positioning the vehicle and before operating any appliance with a flue
system, due consideration must be given to the surrounding area and any obstructions
that may affect flue performance. This will include overhanging tress, proximity to adjacent
mobile catering vehicles, etc.
An open-flued appliance must not be used in a vehicle incorporating a forced extraction
canopy due to the adverse effect the fan may have on flue performance.
Page 22
Specific Requirements for Forced Extract Canopies
Where forced mechanical extract canopies are installed, they must be electrically
interlocked with the canopy, so that if the draught in the canopy fails to meet the minimum
extract requirements, the appliance is prevented from operating. It must not be possible to
override this safety interlock.
Fig 8 Interlocking the extract canopy to the fryer
Page 23
Section 6 - Maintenance and Gas Safety Check
Gas appliances and flues must be maintained in a safe condition. It is recommended that
servicing is undertaken in accordance with manufacturer’s instructions, usually every 12
months. Any maintenance work should only be undertaken by a registered gas engineer
and any problems affecting its safe operation rectified as soon as possible.
Once the registered gas engineer is satisfied that the equipment is working satisfactorily
and that the installation is safe and within permitted operational tolerance, a suitable gas
safety record should be issued such as the one in Appendix 1.
The gas safety record should contain the following information as a minimum:
•
Name and address of the owner/operator of the installation.
•
Details of the installation.
•
Appliance description, like make and model.
•
Operating pressure.
•
Results of tightness test.
•
Statement whether the installation complies with current safety legislation.
•
List of safety issues identified their severity and remedial action taken.
•
Name and address of registered business who performed the safety check.
•
Name and signature of the operative who performed the check.
•
Date of completion of the report and the expiry date of the report.
•
Advice to the owner/operator that the record needs to be kept for 3 years and that a
safety check should be done at least annually.
The gas safety record should be one that is intended specifically for the purpose of mobile
catering trailers and van conversions (see appendix 1).
It is recommended that the business keep a copy of the certificate for at least five years.
Page 24
The Registered Gas Engineer’s Inspection
It is appreciated that CE marking plates on appliances that could now be over a decade
old it may be difficult to find or read due to rigorous cleaning and the built-in nature of the
appliances.
If the CE mark cannot be located and there is no other indication that the appliance was
CE marked, the registered engineer should assess the safety of the equipment and
classify it appropriately against the Gas Industry Unsafe Situations Procedure.
Where additional safety devices are required, these may be fitted, providing they do not
result in the appliance no longer conforming to relevant standards to which it is purports to
comply (e.g. CE marking). Flame supervision devices for example may be retro-fitted in
accordance with the guidance contained in Gas Safe Register Technical Bulletin 044.
The gas safety record should as a minimum contain the information shown in annex 1.
Where equipment can be seen to of been manufactured since 1996 and does not conform
to CE standards then the manufacturer should be reported to The Health & Safety
Executive.
Routine Safety checks
The business owner or a nominated person should on a regular basis (at least once every
one month of operation) or if the trailer or vehicle has been stood unused for a period of
more than one month) check the following:
•
•
•
•
Cylinder / regulator/ changeover device condition - should be free from damage.
Gas hose condition - hoses and connectors should be clean and free from damage
or abrasion.
Visual check to indicate correct operation of appliances. If in any doubt as to the
safe working of an appliance the appliance it must be isolated using the appliance
isolating valve or the quick release valved coupler and a suitably qualified
registered gas engineer called to carry out any repairs or replacements.
Gas pipes and connections.
Under no circumstances must anyone who is not a suitably qualified Gas Safe registered
engineer carry out any modification or repair to the gas installation or appliances, this is a
criminal offence.
If you smell gas at any time isolate at the supply and contact a registered gas engineer.
Hired-In Equipment
The owner of hired-in catering trailers, converted vehicles and equipment has the
responsibility of maintaining the equipment in a safe condition and a gas safety certificate
is issued. However the hirer of the vehicle should take reasonable steps to ensure that
these checks have been undertaken before using the vehicle.
Page 25
Section 7 - Fire Precautions
Fire Risk Assessments are compulsory under the Regulatory Reform Fire Service Order
and Fire (Scotland) Regulations 2006 for all companies that employ more than 5 staff
(overall throughout all their locations,) and must be in a written format. This should be
carried out by a competent person.
If less than 5 employees, although it is still required, it is not necessary to record it in writing.
Following the theme of good practice, and in the event of the person who does have the
knowledge not being available when the information is requested by an authorised authority, it is
advisable to make a record in simple form, which could consist of one or two pages.
If less than 5 employees it is good practice to carry out a fire risk assessment on the units that
are being operated.
The guidelines for fire protection equipment are;
Where oil/fat frying or a griddle is used:
• Fire Blanket (this may change in the near future)
• 6ltr Wet Chemical Extinguisher
Where waste bins are provided/used:
• 6ltr Water Fire extinguisher
Where generators and/or electrical equipment are used:
• 2ltr CO2 Fire extinguisher, however this may need to be increased to take into account the
number and types of equipment being used.
Where BBQ’s are used
• 6ltr Water Fire extinguisher
The siting of a designated fire point for the extinguishers is to form part of the set up and
operational process
Training
Staff should be trained in the use of extinguishers and their purpose, training records should form
part of the operational process.
Maintenance
Extinguishers and fire blankets should be maintained regularly and be serviced annually by a
competent person in accordance with BS 5306.
Page 26
Additional for Motorised Units:
An additional dry powder extinguisher should be available for engine fires within the cab if
it is separated from the cooking area.
Staff should be trained in the use of extinguishers and their purpose.
Extinguishers and fire blankets should be maintained regularly and be serviced annually
with a label attached to each item showing the inspection date and the engineer’s details.
Page 27
Appendix 1 – Sample Gas Safety Record
Page 28
Appendix 1- Gas Safety Record
Page 29
Appendix 2 - Enforcement Officers Checklist
Item
Check
Gas Safety Record
Is it within date?
Conformity
Does it have the required information as annex
1?
Is the engineer on the gas safe register with the
required competencies?
Quantity of LPG
There should be no more LPG in situ than the
amount required for fuelling the appliances and
an equivalent reserve?
Fixed LPG cylinder
compartment
If trailer has a fixed cylinder compartment, is it
tamperproof, ventilated high & low levels with a
gas warning notice on the door?
Exterior Cylinders
Are cylinders protected from interference i.e. in
a cage?
Is the cage ventilated at high and low levels?
Are cylinders secured to keep them upright?
Is a gas warning label clearly visible?
Can the supply be isolated from the
installation?
Appliances
Are the appliances as per the gas safety record
in number and type?
If fryers are in use other than counter top type,
do they have an extract canopy and are they
interlocked with the gas supply?
Trailer fixed
ventilation
Does the trailer have high and low level fixed
ventilation points and are they unobstructed?
Do they have do not obstruct notices present?
Fire Precautions
Is there an emergency control valve (ECV)
installed and is it clearly identified?
Are the recommended fire precautions in
place and serviced?
Page 30