System Management (Field Installed) Chiller Plant Control Chillervisor System Manager / Sequence of Operations (Controls) Note: The following is a sample of a typical sequence of operation that may be adapted for each particular project. This is provided as a suggestion on how to write a sequence of operation. This sample sequence assumes a chilled water plant with centrifugal chillers and one smaller reciprocating chiller. The sequence of the chillers is to change based on calendar date. The ACR sensor is located in the common chilled water supply line. Differential pressure control is also required. 4.1 Chiller System Manager (CSM) A. Description: 1. General: The Chiller System Manager, CSM, shall issue enable/disable commands to each chiller PIC. A running status from the PIC to the CSM shall only be validated when the PIC has confirmed that the chiller auxiliary equipment (chilled water pump, cooling tower, oil pump, etc.) is and has operated correctly. Each time a chiller is commanded on the CSM shall fully open the differential pressure valve(s). Whenever a chiller is running, the CSM shall modulate the differential pressure valve to maintain its adjustable differential pressure setpoint. The valve(s) opening rate shall be unrestricted to open the valve(s) quickly when a chiller starts. The closing rate shall be restricted to help prevent unstable operation. 2. Occupancy: The CSM shall through its internal time schedule, an operator initiated timed override or a network command enable the chilled water plant control unless the operator has disabled the program through the toggle enable/disable point. 3. Summer/Winter Selection Mode: The CSM shall automatically select one of two different chiller sequences based on operator adjustable calendar dates of Oct. 1st (Winter mode) and April 1st (Summer mode). This sequence assumes that no chillers are running when the season changeover occurs and does not use the soft start demand limiting program. If the operator requests, the sequence shall be expanded to include both. 4. Summer Mode (with feathering chiller): After the CSM has determined that it is in occupied mode, it shall start the feathering chiller and allow its local PIC to control its capacity by sending the PIC a local Chilled Water setpoint to maintain. Each PIC shall maintain its own ramping and loading rates. 5. Additional Cooling Required: The first lead chiller shall be enabled to start if the inhibit timers are below the unoccupied time, the pulldown rate is less than .5°F/ minute, the running capacity is above a calculated value, and the supply water temperature is above the current supply water temperature setpoint plus an adjustable delta temperature value. After the CSM has proven that the first lead chiller was started successfully, it shall disable the feathering chiller. If the start inhibit timers are clear and the ACR routine determines that another stage of cooling is required, the feathering chiller shall once again be enabled. This sequence will continue to assume that load continues to increase until all chillers are enabled to run ending with the feathering chiller. 6. Reduced Cooling Required: The feathering chiller shall be disabled when the CSM determines through a load target program that the average %kW of all running chillers is at or below the corrected RCR kW setpoint, the control sensor is below its setpoint (plus the delta temperature entered), and the stop requirements for the delay timers have cleared. If the load continues to decrease and all of the requirements detailed above are true, the last lag chiller started shall be stopped and the feathering chiller shall be enabled. If the load continues to drop and all the RCR load conditions detailed above are still true, the feathering chiller shall be stopped. If the load continues to drop and all RCR requirements are true, the CSM shall start the feathering chiller and after proving its run status the CSM shall stop the next lag chiller. This sequence will continue to assume that load conditions decrease until all chillers except for the feathering chiller are off. 7. Summer Mode — Faulting: If the feathering chiller is faulted by the CSM, it shall automatically send a stop command and start the next chiller in the sequence until the feathering chiller is available again. If the CSM faults any of the other chillers in the sequence, it shall automatically send a stop command to the faulted chiller, and shall start the next available chiller(s) until the on-line capacity is greater than or equal to the current load capacity (tons) prior to the fault. If the total on-line capacity is greater than or equal to the current load capacity prior to the chiller fault an additional chiller shall not be started. 8. Winter Mode (starting lead chiller): After the CSM has determined that it is in occupied mode it shall start the reciprocating chiller and allow its local PIC to control its capacity by sending the PIC a local chilled water setpoint to maintain. Each PIC shall maintain its own ramping and loading rates. 9. Additional Cooling Required: The next chiller in the sequence shall be enabled to start if the inhibit timers are below the unoccupied time, the pulldown rate is less than .5°F/minute, the running capacity is above an operator entered value, and the supply water temperature is above the current supply water temperature setpoint plus an adjustable delta temperature value. After the CSM has proven that the first lead chiller was started successfully, it shall disable the reciprocating chiller and it shall be moved to the end of the start sequence. If the start inhibit timers are clear and the ACR routine determines that another stage of cooling is required, the second lead chiller shall be enabled. This sequence will continue to assume that load continues to increase until all chillers are enabled to run ending with the reciprocating chiller. 10. Reduced Cooling Required: The last lag chiller started shall be disabled when the CSM determines through a load target program that the average %kW of all running chillers is at or below the corrected RCR kW setpoint, the control sensor is below its setpoint (plus the delta temperature entered), and the stop requirements for the delay timers have cleared. If the load continues to decrease and all of the requirements detailed above are true, the next lag chiller started shall be stopped. When the load has reached a point that the CSM is ready to disable the last lead chiller, the CSM shall start the reciprocating chiller and after it has proven its running status, it shall disable the last centrifugal chiller. 11. Winter Mode — Faulting: If the reciprocating chiller is faulted by the CSM it shall automatically send a stop command and start the next lead chiller in the sequence. The reciprocating chiller shall be removed from the sequence until the chiller becomes available again. If the CSM faults any of the other chillers in the sequence, it shall automatically send a stop command to the faulted chiller, and shall start the next available chiller if the on-line capacity is greater than or equal to the current load capacity (tons) prior to the fault. If the total on-line capacity is greater than or equal to the current load capacity prior to the chiller fault, an additional chiller shall not be started. 12. Unoccupied: The CSM shall automatically index the chilled water plant to an occupied mode based on its internal time schedules. When the chilled water plant becomes unoccupied, all chillers shall be stopped at one minute intervals.
© Copyright 2026 Paperzz