Cooling floor, radiant floor cooling, cooling capacity Andrzej ODYJAS* THE RELATION BETWEEN TYPE OF COOLING LOADS AND CAPACITY OF COOLING FLOOR SYSTEM Floor cooling system performance largely depends on the type of cooling loads occurring in the room. In the case of a convective cooling load capacity of the system is small, however, receive in the event of radiation directly on the floor of the system significantly increases productivity. The article describes the results of numerical simulations, whose aim was to determine system performance, depending on the type of cooling load for the fixed assumptions of utility. It also sets out the maximum system performance while maintaining a minimum temperature of the floor 20 0C. 1. INTRODUCTION Floor cooling systems do not belong to the most popular air conditioning systems, they are quite new systems and the conditions of performance are not well known. They can be successfully used for cooling in conjunction with an air system, which aims to ensure the quality of indoor air and humidity. It was commonly thought that their cooling capacity is low and that they should be more as a supporting and complementary systems compared to traditional air conditioning systems. However, in certain conditions, their performance can be greatly increased. This is true in the case of thermal radiation directly receive in the floor. In commercial buildings usually occur two types of radiant flux. Short wave radiation which comes from direct solar radiation and long wave radiation that comes from internal sources of heat, land radiation, and spaces inside the room. In practice, the largest flux of radiation on the floor is the direct solar radiation from the sun. __________ * Institute of Environmental Engineering, Poznan University of Technology. 2. SIMULATION MODEL In order to determine the maximum possible efficiency of the cooling floor system in the rooms numerical model which allows to simulate thermal conditions was developed. The numerical model take into account the short-wave radiation (sunlight) falling directly on the floor, as well as long wave radiation emitted by internal heat sources and radiation flux exchanged between surfaces of the room. In the model, short-wave radiation emission coefficient for the floor was adopted equal to 0.8, while for the long-wave radiation emission coefficient of all the surfaces assumed equal 0.9. Also it was taken into account convective heat streams put into the indoor air by internal heat sources and possible heat flows delivered to the room with the air vent. Simplified diagram of heat exchange in the room shown in Figure 1. Ventilation Heat sources Water Short wave radiation Long wave radiation Convection Fig. 1. Simplified schematic of heat transfer in a room Room dimensions used in the simulation were a x b x h 4.68 x 3.00 x 4.00 m with a window in the outer wall with an area of 3.4 m2. The floor and pipes system was divided into 100 rectangles, and the inside air with adjoining walls on three separate areas with a height: lower 0.3m, middle 2.4m, upper 0.3m. The floor was assumed two-dimensional, while the other divisions one dimensional heat flow. Each of the 100 rectangles and each surface separately exchange the heat with the rest of the surfaces in the room. Coefficients of heat transfer by convection was conditional on the temperature difference between air and the each surface. A more detailed description of the model is in a separate articles on this topic [2,3]. 3. ASSUMPTIONS FOR THE SIMULATION It is known that the main limitation of floor cooling performance is its temperature, which should not fall below 190C - 200C, both in terms of comfort as well as to the possible condensation of moisture on the floor [1,4,5]. In addition to the type of cooling loads occurring in the room the system performance also depends on other factors. The basic ones are: the layout and thermal resistance of flooring materials, in particular the external cladding, the emission coefficient of them, short wave radiation long all surfaces in the room, spacing and arrangement of the pipes in the floor, the temperature and flow rate of water in the floor. The simulations were performed assuming no contribution from mechanical ventilation. Structural solutions of the room and other parameters were adopted in the most typical way for the system. The most important of these are presented in Figure 2. INTERNAL WALLS 3 2300kg/m ; 840 J/kgK; 1,5 W/mK 6 cm 4 cm 2200kg/m3; 1000 J/kgK; 1,6 W/mK 30kg/m ; 1450 J/kgK; 0,04 W/mK STYROFOAM 11 cm 2500kg/m3; 1000 J/kgK; 1,8 W/mK 1cm 900kg/m3; 1000 J/kgK; 0,25 W/mK CONCRETE PLASTER 3 CERAMIC TILES JOINTLESS CONCRETE ADIABATE 600kg/m3; 8400 J/kgK; 0,3 W/mK 900kg/m3; 1000 J/kgK; 0,25 W/mK 3 900kg/m ; 1000 J/kgK; 0,25 W/mK COOLING FLOOR 1 cm 6 cm PLASTER CELLULAR CONCRETE 1cm 1cm PLASTER 600kg/m ; 8400 J/kgK; 0,3 W/mK CELLULAR CONCRETE 3 24 cm STYROFOAM 10 cm 30kg/m3; 1450 J/kgK; 0,04 W/mK EXTERNAL WALL CEILING Fig. 2. The design parameters of the room Cooling loads occurring in the room was divided into 5 types: A - 100% convection to the air space into the central air zone B - Mixed: convection 50% + 50% long wave radiation brought proportionately on all surfaces in the room C - 100% long-wave radiation brought on all surfaces in the room in proportion to their share in total room area D - 100% short-wave radiation (solar) brought directly on the entire floor space E - Mixed: convection 25% + 25% of long wave radiation brought proportionately on all surfaces in the room + 50% short-wave radiation equally brought to the entire floor space The closest to the real cooling load type is the type E, which corresponds to 50% share of the burden from the cold internal sources and 50% receive in the solar radiation directly to the floor. The simulation algorithm was varied levels of cooling loads in order to achieve the set temperature in the central zone of air space equal to 24 0C and 260C alternatively. 4. RESULTS AND DISCUSSION The first series of simulations were performed assuming a fixed set of the power system: the input water temperature equal to 160C, water flow rate 20dm3/hm2 of floor, pipes spacing in the floor 10cm of a double meander in the system, stood outside the room temperature equals 240C and 260C alternatively. The simulation results are shown graphically in Figure 3. The figure also describes the minimum floor surface temperature, which occurs in the places where pipes enter into the floor. The assessment of the results shows that in the case of convective cooling load type (type A), system performance is small, the order of 22 to 28 W/m2, depending on the maintenance of the internal air temperature 240C and 260C. In the case of mixed cooling loads (type E), reaching values of 39-50 W/m2, whereas in the case of direct radiation receive in the floor (type D) are much larger in a row from 68 to 86 W/m2. Be noted, however, that the minimum floor surface temperatures are exceeded in cases A, B, and part C and E, but well above 200C in the case of D. Because of to low temperatures of the floor surfaces an additional series of simulations were done. In these simulations was assumed a variable water inlet temperature in order to reach the floor surface temperature equal to 200C. In addition to D-type load flow were increased to 100 dm3/hm2 and two-collector pipe system were used so that the water velocity in the pipes was real. The results are shown in Figure 4. The figure also indicated the inlet water temperature in order to reach the min. floor temperature equal 200C. The unit floor cooling capacity [W/m2] The floor average cooling capacity, depending on the type of cooling loads (inside air temperature 240C and 260C) 200,0 180,0 160,0 140,0 120,0 100,0 80,0 60,0 A Internal heat sources convection 100% B Internal heat sources: convection 50% + long wave radiation 50% tair=240C tair=260C twater=160C V =20dm3/h m2 40,0 22,4 28,3 C Internal heat sources: long wave radiation 100% D Short wave radiation on the floor 100% 85,8 E Internal heat sources 50% (c.25% + r.25%) + short wave radiation on the floor 50% 68,5 49,5 47,6 27,3 34,5 39,2 38,2 20,0 0,0 18,0 18,6 18,5 19,1 19,5 20,3 22,0 23,5 19,5 20,4 The minimum floor surface temperature [0C] Fig. 3. The average cooling floor capacity for the fixed parameters of power, depending on the type of cooling loads. The unit floor cooling capacity [W/m2] The floor average cooling capacity, depending on the type of cooling loads (the floor min. temperature 200C) 500,0 450,0 400,0 350,0 300,0 250,0 A Internal heat sources convection 100% B Internal heat sources: convection 50% + long wave radiation 50% C Internal heat sources: long wave radiation 100% D Short wave radiation on the floor 100% 226,1 200,0 150,0 tair=240C tair=260C E Internal heat sources 50% (c.25% + r.25%) + short wave radiation on the floor 50% 150,4 100,0 50,0 29,8 33,6 53,5 50,2 14,4 22,5 19,3 18,7 18,0 18,3 17,3 17,0 15,4 Inlet water temperature [0C] 34,7 0,0 9,7 4,5 16,9 15,2 Fig. 4. The average cooling floor capacity for a minimum floor surface temperature equal to 20 0C, depending on the type of cooling load. The results obtained further reduce the efficiency of the floor in the conditions of convective heat gain to the level of 14-22 W/m2 floor and increase system performance significantly in the case of direct radiation on the floor, up to 150 - 226 W/m2 floor. However, due to very low supply water temperature (9,70C and 4,50C), to obtain such performance is quite nonrealistic in practice, but shows a "hidden" capabilities of the system under specific conditions (radiation flux directly on the floor surface). But, this is only possible if the water which flow in the floor is able to receive such a large heat. 5. CONCLUSION Before drawing final conclusions from the simulations, one has to take into account, that the results of simulation were obtained by the system after reaching a steady thermal state. Achieve similar performance in terms of normal day conditions will not always be possible because both the large thermal resistant of the system and other surfaces of the room as well as variation of cooling loads in the rooms during the day. The simulations show that floor cooling system achieves the greatest efficiency in the case of direct thermal radiation receive in the floor. This situation may occur when solar radiation receive the floor through the windows, glass facades or roof illuminates. In further stages of research, it is planned to study performance of the cooling floor system under conditions similar to the real, alternating a day of sunlight falling on the floor in a manner dependent on the world direction of the outer wall and glazing and the current position of the sun on the horizon. REFERENCES [1] CAUSONEA F., BALDINB F., OLESEN B.W., CORGNATIA S., Floor heating and cooling combined with displacement ventilation: Possibilities and limitations, Energy and Buildings 42 (2010) 2338–2352. [2] GÓRKA A., ODYJAS A., Numeryczny model działania systemu posadzki chłodzącej, XIII International Conference : Air & Heat - Water & Energy 2011, Wrocław-Kudowa, 2011. [3] ODYJAS A., GÓRKA A., Określanie obciążeń chłodniczych w radiacyjnych systemach chłodzenia pomieszczeń, XII International Conference : Air conditioning protection and district heating 2008, Wrocław-Szklarska Poręba, 2008, PZITS, 327-332. [4] OLESEN B.W., Possibilities and limitation of radiant floor cooling. ASHRAE Transaction: Reserch 103, 1997, 42-48. [5] OLESEN B.W., Thermal comfort requirement for floors occupied by bare feet. ASHRAE Transactions 83 (2), 1977. WPŁYW TYPU OBCIĄŻEŃ CHLODNICZYCH NA WYDAJNOŚĆ SYSTEMU POSADZKI CHŁODZĄCEJ Wydajność systemu posadzki chłodzącej w znacznym stopniu uzależniona jest od typu obciążeń chłodniczych występujących w pomieszczeniu. W przypadku obciążeń chłodniczych typu konwekcyjnego wydajność systemu jest niewielka, jednak w przypadku promieniowania trafiającego bezpośrednio na posadzkę wydajność system znacząco wzrasta. W artykule opisano wyniki symulacji numerycznych, których celem było określenie wydajności systemu w zależności od typu obciążeń chłodniczych przy ustalonych założeniach użytkowych. Określono również maksymalną wydajność systemu przy zachowaniu minimalnej temperatury powierzchni posadzki równej 20 0C.
© Copyright 2026 Paperzz