Fireboxes

English
Fireboxes
The instruction booklet is an integral part of the product.
600HT - 610 HT - 650HT - 655HT
installation, use and
maintenance instructions
Riverside, Goods Road, Belper, Derbyshire. DE56 1 UU
Tel. 01773 820940 • Fax 01773 820477
e-mail: [email protected] • web site: www.robeys.co.uk
English
SUPPLEMENTARY INSTALLATION INSTRUCTIONS FOR THE UK MARKET
TO BE READ IN CONJUNCTION WITH THOSE IN THE INSTRUCTION BOOKLET
READ THE INSTRUCTION BOOKLET AND THESE SUPPLEMENTARY INSTRUCTIONS
CAREFULLY BEFORE INSTALLATION
These instructions together with those in the instruction booklet cover the basic principles to ensure the satisfactory
installation of the stove, although detail may need slight modification to suit particular local site conditions.
In all cases the installation must comply with current Building Regulations, Local Authority
Byelaws and other specifications or regulations as they affect the installation of the stove.
It should be noted that the Building Regulations requirements may be met by adopting the
relevant recommendations given in British Standards BS 8303, BS 6461 and BS 7566 as an
alternative means to achieve an equivalent level of performance to that obtained following the
guidance given in Approved Document J.
Please note that it is a legal requirement under England and Wales Building Regulations that the
installation of the stove is either carried out under Local Authority Building Control approval or
is installed by a Competent Person registered with a Government approved Competent Persons
Scheme. HETAS Ltd operate such a Scheme and a listing of their Registered Competent Persons
can be found on their website at www.hetas.co.uk.
HEALTH AND SAFETY PRECAUTIONS
Special care must be taken when installing the stove such that the requirements of the Health and Safety
at Work Act are met.
Handling
Adequate facilities must be available for loading, unloading and site handling.
Ensure compliance with the “Manual Handling Operations 1992 Regulations” as amended. Mechanical
handling equipment may be required.
Fire Cement
Some types of fire cement are caustic and should not be allowed to come into contact with the skin. In
case of contact wash immediately with plenty of water.
Asbestos
This stove contains no asbestos. If there is a possibility of disturbing any asbestos in the course of
installation then please seek specialist guidance and use appropriate protective equipment.
Metal Parts
When installing or servicing this stove care should be taken to avoid the possibility of personal injury.
Wear suitable gloves
STOVE PERFORMANCE
In the UK the stove has been approved by HETAS Ltd as an intermittent operating appliance for burning
wood logs only.
It should be noted that it is an offence to burn wood logs in this stove if it is installed within a Smoke
Control Area in the UK.
2
H07024510 / DT2000575 - Rev. 00
PREPARATORY WORK AND SAFETY CHECKS
IMPORTANT WARNING
This stove must not be installed into a chimney that serves any other heating appliance.
Chimney
In order for the stove to perform satisfactorily the chimney height must be sufficient to ensure an adequate
draught of approximately 15 Pa so as to clear the products of combustion and prevent smoke problems
into the room.
NOTE: A chimney height of not less than 4.5 metres measured vertically from the outlet of the stove to
the top of the chimney should be satisfactory. Alternatively the calculation procedure given in BS
5854:1980 may be used as the basis for deciding whether a particular chimney design will provide
sufficient draught.
The outlet from the chimney should be above the roof of the building in accordance with the provisions
of Building Regulations Approved Document J.
If installation is into an existing chimney then it must be sound and have no cracks or other faults which
might allow fumes into the house. Older properties, especially, may have chimney faults or the cross
section may be too large i.e. more than 230 mm x 230 mm. Remedial action should be taken, if required,
seeking expert advice, if necessary. If it is found necessary to line the chimney then a flue liner suitable
for solid fuel must be used in accordance with Building Regulations Approved Document J.
Any existing chimney must be clear of obstruction and have been swept clean immediately before
installation of the stove. If the stove is fitted in place of an open fire then the chimney should be swept
one month after installation to clear any soot falls which may have occurred due to the difference in
combustion between the stove and the open fire.
If there is no existing chimney then either a prefabricated block chimney in accordance with Building
Regulations Approved Document J or a twin walled insulated stainless steel flue to BS EN 1856 can be
used. These chimneys must be fitted in accordance with the manufacturer’s instructions and Building
Regulations.
A single wall metal fluepipe is suitable for connecting the stove to the chimney but is not suitable for
using for the complete chimney. The chimney and connecting fluepipe must have a minimum diameter
of 150 mm and its dimension should be not less than the size of the outlet socket of the stove.
Any bend in the chimney or connecting fluepipe should not exceed 45°. 90° bends should not be used.
Combustible material should not be located where the heat dissipating through the walls of fireboxes or
flues could ignite it. Therefore when installing the stove in the presence of combustible materials due
account must be taken of the guidance on the separation of combustible material given in Building
Regulations Approved Document J and also in these stove instructions.
If it is found that there is excessive draught in the chimney then either an adjustable flue damper or
alternatively a draught stabiliser should be fitted. The adjustable flue damper should not close off the
flue entirely but should in its closed position leave a minimum continuous opening free area of at least
20 % of the total cross sectional area of the flue or fluepipe.
Adequate provision e.g. easily accessible soot door or access doors, must be provided for sweeping the chimney
and connecting fluepipe, also to permit visual checks on the integrity of the flue when the appliance is serviced.
H07024510 / DT2000575 - Rev. 00
3
English
There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to
emit fumes into the room.
Hearth
The hearth should be able to accommodate the weight of the stove and its chimney if the chimney is not
independently supported. The weight of the stove is indicated in the brochure.
English
The stove should always be installed on a non-combustible hearth of a size and construction that is in
accordance with the provisions of the current Building Regulations Approved Document J.
The clearance distances to combustible material beneath, surrounding or upon the hearth and walls
adjacent to the hearth should comply with the guidance on the separation of combustible material given
in Building Regulations Approved Document J and also in these stove instructions.
If the stove is to be installed on a wooden floor, it must be covered with a non-combustible material at
least 12mm thick, in accordance with Building Regulations Approved Document J, to a distance of 30 cm
in front of the stove and 15 cm to each side measuring from the door of the combustion chamber.
Combustion air supply
In order for the stove to perform efficiently and safely there should be an adequate air supply into the room
in which the stove is installed to provide combustion air. This is particularly necessary if the room is
double-glazed or a flue draught stabiliser is operating in the same room as the appliance.
It may be necessary to increase the air vent size in property with low air permeability [≤ 5.0 m3/(h.m2)]
The provision of air supply to the stove must be in accordance with current Building Regulations Approved
Document J. An opening window is not appropriate for this purpose.
Connection to chimney
All the stoves have a rear and/or top flue gas connector that allows connection to either a masonry
chimney or a prefabricated factory made insulated metal chimney in accordance with the instructions for
the appliance given in the instruction booklet.
Commissioning and handover
Ensure loose parts are fitted in accordance with the instructions given in the instruction booklet.
On completion of the installation allow a suitable period of time for any fire cement and mortar to dry out,
when a small fire may be lit and checked to ensure the smoke and fumes are taken from the stove up
the chimney and emitted safely to atmosphere. Do not run at full output for at least 24 hours.
On completion of the installation and commissioning ensure that the operating instructions for the stove
are left with the customer. Ensure to advise the customer on the correct use of the appliance with the fuels
likely to be used on the stove and warn them to use only the recommended fuels for the stove.
Advise the user what to do should smoke or fumes be emitted from the stove. The customer should be
warned to use a fireguard to BS 6539 in the presence of children, aged and/or infirm persons.
Make provision for securing a suitable guard where applicable.
Carbon Monoxide Alarm
A carbon monoxide alarm complying with BS EN 50291 must be fitted in the same room as the appliance
in accordance with the current Building Regulations Part J. It should be positioned on the ceiling at least
300mm from any wall or, if it is located on a wall, as high up as possible (above any doors and windows)
but not within 150mm of the ceiling. The alarm should also be between 1m and 3m horizontally from the
appliance.
4
H07024510 / DT2000575 - Rev. 00
SUPPLEMENTARY USER OPERATING INSTRUCTIONS
TO BE READ IN CONJUNCTION WITH THOSE IN THE INSTRUCTION BOOKLET
WARNING NOTE
Properly installed, operated and maintained this stove will not emit fumes into the dwelling. Occasional
fumes from de-ashing and re-fuelling may occur. However, persistent fume emission is potentially
dangerous and must not be tolerated. If fume emission does persist, then the following immediate action
should be taken: (a) Open doors and windows to ventilate room
(b) Let the fire out or eject and safely dispose of fuel from the appliance
(c) Check for flue or chimney blockage and clean if required
(d) Do not attempt to relight the fire until the cause of the fume emission has been identified and corrected.
If necessary seek expert advice.
The most common cause of fume emission is flueway or chimney blockage. For your own safety these
must be kept clean at all times.
IMPORTANT NOTES
General
Before lighting the stove check with the installer that the installation work and commissioning checks
described in the installation instructions have been carried out correctly and that the chimney has been
swept clean, is sound and free from any obstructions. As part of the stoves’ commissioning and handover
the installer should have shown you how to operate the stove correctly.
Use of fireguard
When using the stove in situations where children, aged and/or infirm persons are present a fireguard
must be used to prevent accidental contact with the stove. The fireguard should be manufactured in
accordance with BS 8423:2002.
If the fire is left unattended a spark guard to BS3248, specification for spark guards for use with solid fuel
appliances should be used.
Chimney cleaning
The chimney should be swept at least once a year for smokeless fuels and a minimum of twice a year
for wood and other fuels. It is important that the flue connection and chimney are swept prior to lighting
up after a prolonged shutdown period.
If the stove is fitted in place of an open fire then the chimney should be swept one month after installation
to clear any soot falls which may have occurred due to the difference in combustion between the stove
and the open fire.
In situations where it is not possible to sweep through the stove the installer will have provided alternative
means, such as a soot door. After sweeping the chimney the stove flue outlet and the flue pipe connecting
the stove to the chimney must be cleaned with a flue brush.
H07024510 / DT2000575 - Rev. 00
5
English
READ THE INSTRUCTION BOOKLET AND THESE INSTRUCTIONS CAREFULLY
BEFORE USING THE STOVE
Extractor fan
There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to
emit smoke and fumes into the room.
English
Aerosol sprays
Do not use an aerosol spray on or near the stove when it is alight.
Use of operating tools
Always use the operating tools provided when handling parts likely to be hot when the stove is in use.
Chimney Fires
If the chimney is thoroughly and regularly swept, chimney fires should not occur. However, if a chimney
fire does occur turn the air control setting to the minimum, and tightly close the doors of the stove. This
should cause the chimney fire to go out in which case the control should be kept at the minimum setting
until the fire in the stove has gone out. The chimney and flueways should then be cleaned. If the chimney
fire does not go out when the above action is taken then the fire brigade should be called immediately.
After a chimney fire the chimney should be carefully examined for any damage. Expert advice should be
sought if necessary
Permanent air vent
The stove requires a permanent and adequate air supply in order for it to operate safely and efficiently.
In accordance with current Building Regulations the installer may have fitted a permanent air supply vent
into the room in which the stove is installed to provide combustion air. This air vent should not under any
circumstances be shut off or sealed.
HETAS Ltd Approval
Please note that HETAS Approval only covers the use of wood on the stove and approval does
not cover the use of other fuels either alone or mixed with other fuels, nor does it cover
instructions for the use of other fuels.
USER OPERATING INSTRUCTIONS - WOOD
The instructions detailed in the section / in the instruction booklet should be followed.
Door operation
Describe door operation and use of the tool to open and close the doors, if appropriate.
Lighting of fire
Place some firelighters or paper and dry kindling wood on the grate and cover with a small amount of fuel.
Set air controls to maximum and set light to firelighters or paper. Close the doors and allow fire to burn
until fuel is well alight then load with more fuel and adjust air controls to the required level of heat output.
Before relighting the fire clean the firebed of excess ash and clinker and empty the ashpan.
Refuelling
Keep the firebox well filled (the fuel may be sloped up from the front firebars), but do not allow fuel to spill
over the top of the front fire bars. Take care that fuel does not project over the front fire bars or damage
to the glass may be caused when the doors are closed
6
H07024510 / DT2000575 - Rev. 00
Flueway cleaning
It is important that the baffle plate and all the stove flueways are kept clean. When burning smokeless
fuels they should be cleaned at least monthly. When burning other fuels they should be cleaned at least
once a week, and more frequently if necessary.
More soot will be deposited on the baffle plate and in the flueways if the stove is run at low levels for long
periods. If this is the case then more frequent cleaning will be necessary.
Cleaning and maintenance
The instructions detailed in the section “Maintenance” in the instruction booklet should be followed.
Trouble shooting
The instructions detailed in the relevant section in the instruction booklet should be followed together
with the following additional items:
1. Fire Will Not Burn
Check that:
a)the air inlet is not obstructed in any way,
b)that chimneys and flueways are clear,
c) that a suitable fuel is being used,
d)that there is an adequate air supply into the room,
e)that an extractor fan is not fitted in the same room as the fire.
2. Fire Blazing Out Of Control
Check that:
a)the doors are tightly closed,
b)the air control is turned down to the minimum setting,
c) the air inlet damper is closed and that it is not prevented from closing completely by a piece of ash,
d)a suitable fuel is being used,
e) the door seals are in good condition.
DT2011502-00
Registered Office: Robeys Ltd, Goods Road, Belper Derbyshire DE56 1UU
Tel +44(0)1773 820940 Fax +44(0)1773 820477 Email [email protected] www.robeys.co.uk
Company No. 5741182
Director: Mark Robey Company Secretary: Sharon Robey
H07024510 / DT2000575 - Rev. 00
7
English
Remove any sooty deposits from the baffle plate.
Dear Customer,
Thank you for having chosen one of our products, which is the result of years of experience and continuous research aimed at making a
superior product in terms of safety, reliability and performance.
This booklet contains information and advice for safe and efficient use of your product.
English
DT2010001-01
DT2010139-00
IMPORTANT INFORMATION
•
•
•
•
•
•
This instruction booklet has been prepared by the manufacturer
and is an integral part of the product. In the event of sale or
relocation of the product make sure this booklet accompanies it,
since the information contained in it is addressed to the purchaser
and to anyone involved in the installation, use and maintenance
of the product.
Read the instructions and the technical information contained in
this booklet carefully before proceeding with installation, use or
any repairs.
The observance of the instructions and technical information in
this instruction booklet guarantees the safety of persons and
property; it also ensures more efficient operation and an increased
lifespan.
Gruppo Piazzetta S.p.A. cannot be held responsible for damage or
injury due to failure to comply with the instructions for
installation, use and maintenance given in this booklet, or due to
unauthorised alterations or to the use of other than original spare
parts.
Appliance installation and use must conform with the
manufacturer’s instructions as well as with European and national
legislation and local regulations.
The wall against which the product is to be placed must not be of
•
•
•
•
•
•
•
•
wood or any other flammable material. For correct installation it
is also important to maintain safety distances (refer to the section
entitled “MINIMUM SAFETY DISTANCES”).
Prior to completing installation of the surround, light the stove
and when it has heated up check that the grate and that the flue
connection is correct.
Check that the floor where the product is to be installed is
perfectly level.
Do not fix the heater unit in any way whatsoever, but simply place
it next to the surround.
When handling the steel parts of the surround or the ceramic
parts it is advisable to use clean cotton gloves to avoid leaving
fingerprints that are difficult to remove at first time of cleaning
The firebox must be assembled by two persons.
This appliance has been designed solely for heating. It is not
recommended for cooking foods.
Stop using the product in the event of fault or malfunctioning.
The product you have purchased may differ slightly from the one
illustrated in this booklet since the pictures are only given as an
indication and not an exact portrayal.
See the guarantee certificate enclosed with the product for the terms, limitations and exclusions.
In line with its policy of constant product improvement and renewal, the manufacturer may make changes without notice.
This document is the property of Gruppo Piazzetta S.p.A.; no part of it may be disclosed to third parties without the written permission
of Gruppo Piazzetta S.p.A.
All rights reserved by Gruppo Piazzetta S.p.A..
DT2010140-02
REFERENCE STANDARDS
UNI EN 832 . . . . . . . . . . . . . . . . . . . . . . . .Thermal performance of buildings - Calculation of energy use for heating
UNI EN 13229 . . . . . . . . . . . . . . . . . . . . . .Inset appliances including open fires fired by solid fuels - Requirements and test methods
UNI 10683:2005 . . . . . . . . . . . . . . . . . . . . .Heating appliances fired by wood or other solid biofuels - Installation requirements
UNI EN 13384 . . . . . . . . . . . . . . . . . . . . . .Chimneys - Thermal and fluid dynamic calculation methods
UNI 7129 . . . . . . . . . . . . . . . . . . . . . . . . . .Gas plants for domestic use fed by network distribution
UNI 10847 . . . . . . . . . . . . . . . . . . . . . . . . .Chimneys for generators feeded with liquid and solid flues - Maintenance and inspection
EN 1856-1 . . . . . . . . . . . . . . . . . . . . . . . . .Chimneys - Requirements for metal chimneys - Part 1: System chimney products
EN 1856-2 . . . . . . . . . . . . . . . . . . . . . . . . .Chimneys - Requirements for metal chimneys - Part 2: Metal liners and connecting flue pipes
UNI EN 1443 . . . . . . . . . . . . . . . . . . . . . . .Chimneys – General requirements
DIN 18 895 . . . . . . . . . . . . . . . . . . . . . . . . .Fireboxes
DIN 51731 class of measurement HP2 . .Fuels
8
H07024510 / DT2000575 - Rev. 00
SECTION
TITLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
1.10
1.11
1.12
1.13
1.14
1.15
1.16
GENERAL RULES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
SINGLE FLUEWAY OR CHIMNEY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
SOOT INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
CHIMNEY STACK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
PERMANENT VENTILATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
INSTALLATION ENVIRONMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
CAPACITY LOAD OF THE FLOOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
HEATING CAPACITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
METHOD OF HEAT DIFFUSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
SUITABLE HEAT INSULATING MATERIALS . . . . . . . . . . . . . . . . . . . . . . . .16
MINIMUM SAFETY DISTANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
CONNECTION TO THE FLUEWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
LINING WALL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
HOOK GRILLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
WOOD MANTEL PROTECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
ELECTRIC POWER SUPPLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
PREVENTION OF DOMESTIC FIRE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
2.1
2.2
2.3
2.4
2.5
2.6
TECHNICAL DATA AND SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . .20
DESCRIPTION OF THE APPLIANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
ACCESSORIES AND EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
PRODUCT IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
FIREBOX DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
2.0
3.0
PREPARATION FOR INSTALLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
4.0
INSTALLATION OF THE SMOKE DAMPER . . . . . . . . . . . . . . . . . . . . . . . .26
5.0
5.1
5.2
5.3
3.4
5.5
5.6
5.7
5.8
5.9
USE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
FUEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
SMOKE DAMPER REGULATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
COMBUSTION AIR REGULATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
LIGHTING FOR THE FIRST TIME . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
LIGHTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
OPENING THE DOOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
NIGHTTIME OPERATION AT MINIMUM . . . . . . . . . . . . . . . . . . . . . . . . . .30
OPERATION UNDER ADVERSE WEATHER CONDITIONS . . . . . . . . . . . . .31
OVERHEATING AND EXTINGUISHING . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9
6.10
6.11
6.12
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
PERIODIC CECKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
CLEANING THE CERAMIC CLADDING . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
CLEANING THE STEEL PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
CLEANING THE PAINTED METAL PARTS . . . . . . . . . . . . . . . . . . . . . . . . .32
CLEANING THE GLASS (DAILY) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
CLEANING THE GRATE AND THE ASH TRAY . . . . . . . . . . . . . . . . . . . . . .33
DISPOSAL OF ASHES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
CLEANING ALUKER® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
REMOVING THE SMOKE BAFFLE PLATES . . . . . . . . . . . . . . . . . . . . . . . .34
CLEANING THE FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
SHUTTING DOWN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
CLOSING DOOR SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
6.0
5.0
English
DT2010187-01
INDEX
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
DECLARATION OF CONFORMITY STOVE 600 HT . . . . . . . . . . . . . . . . . . .37
DECLARATION OF CONFORMITY STOVE 610 HT/B . . . . . . . . . . . . . . . . .38
DECLARATION OF CONFORMITY STOVE 650 HT - 655T HT - 655E HT . .39
This booklet code H07024510 / DT2000575 - Rev. 00 - (06/2010) comprises 40 pages.
H07024510 / DT2000575 - Rev. 00
9
DT2012089-00
1.0 GENERAL RULES
Before proceeding with installation, choose the most suitable position for your firebox according to the indications given in the paragraph
“MINIMUM SAFETY DISTANCES” and to all the indications below.
English
Fig. 1
CHIMNEY POT
FLUEWAY
CONNECTION TO FLUE
HOOD GRILL
LINING WALL
INSPECTION
SOOT DOOR
CONTROL FOR FLUE DAMPER.
NOTE, CAN BE ON SIDE
MINIMUM SAFETY
DISTANCES
PROTECTION FOR
ORNAMENTAL LEDGE
FRESH AIR INTAKE
FIXED AIR OUTLET
POWER SWITCH
MINIMUM SAFETY DISTANCES
POWER SUPPLY
CHECK FLOOR FOR LOAD
BEARING CAPACITY
MULTIFUOCO VENTILATION
SYSTEM
DT2033014-00
10
H07024510 / DT2000575 - Rev. 00
1.1
DT2012124-00
SINGLE FLUEWAY OR CHIMNEY
Every appliance must have a vertical flue pipe operating by natural
draught to discharge the combustion gases outdoors.
Fig. 2
English
The flue must:
- comply with regulations in force in the place of installation of the
appliance;
- be sealed to the products of combustion, waterproof, suitably
insulated, made with materials resistant to the corrosion of the
gases and to stress;
- be connected to just one stove, firebox or extraction hood;
- be properly sized, with constant free internal section, equal to or
greater than the diameter of the flue pipe of the stove and at least
3.5 m in length;
- be mainly in a vertical position with a deflection from the axis of no
more than 45° (Fig. 2);
- be at a suitable distance from combustible or flammable materials,
ensured by an air gap or suitable insulating material;
- be of uniform internal section, preferably round. Square or
rectangular sections must have rounded corners with a radius of at
least 20mm and a maximum ratio between the sides of 1.5
(Fig. 3-4-5);
- the walls must be smooth if possible and without narrowing. Bends
must be regular and without discontinuity (Fig. 6).
MINIMUM 3,5 M
MAX 45°
X
NO
It is forbidden to connect any other appliance to the flue either
permanently or temporarily.
It is forbidden to pass other air ducts or service pipes inside
the flue pipe, however large it is.
If the flue pipe is an incorrect size or installed other than in
compliance with the above instructions, Gruppo Piazzetta
S.p.A. cannot be held liable for malfunctioning of the product,
damage to property or injury to persons or animals.
DT2030258-00
Fig. 4
Fig. 3
R
Ø
DT2030050-00
Fig. 5
mi
n.
20
L (<
_ 1,5 x P)
)
P
DT2030189-00
1.2
DT2030188-00
Deposit of creosote
Fig. 6
Deposit of creosote
R(
(m
in
.2
0)
NO
DT2030190-00
DT2010031-01
SOOT INSPECTION
We recommend that the flue must have a chamber for collecting solid matter and any condensate located below the connection and which
may be easily inspected by means of an airtight door. (Fig.1)
H07024510 / DT2000575 - Rev. 00
11
1.3
DT2012091-00
CHIMNEY STACK
Fig. 7
English
The flue must be fitted at the top with a flue terminal designed to aid
dispersion of the products of combustion in the atmosphere.
Fig. 8
B
B*
B
The flue terminal must comply with the following requirements:
- it must have an internal section and shape the same as the flue;
- it must have a useful outlet section of not less than twice that of the
flue;
- the part of the flue that emerges from the roof or remains in contact
with the outside (e.g. in the case of an open loft), must be covered
with brick or tile elements and well insulated. It must be built in such
a way as to prevent the penetration of rain, snow and foreign matter
into the flue and to ensure that in the event of winds from all directions
and angle, discharge of the combustion products is assured (flue
terminal with down-draught cowl);
- any buildings or other obstacles that are higher than the flue terminal
must not be too close to the actual terminal Fig. 9;
- the flue terminal must be positioned in such a way as to ensure
adequate dispersion and dilution of the angle of the roof and position
see Fig. 10.
*B free area is
twice that of A
A
DT2030051-00
A
DT2030191-00
Fig. 9
6-8 m
Clearances to easily ignited roof coverings (e.g. thatch) need to be
increased in accordance with the building regulations part J.
DT2030052-00
Fig. 10
The illustration and table identify the
minimum requirements as dictated by
Building Regulations
E
CHIMNEY TERMINATION
F
G
A
C
D
B
N.B. All dimensions relate
to the bottom edge of the
terminal opening
Any adjacent
building structure
whether connected
or not
DT2011502-00
Dimension Minimum distance measured from the top of the chimney construction, excluding any pot or terminal
A
2, 3 metres horizontally clear of the roof surface, eg. if the roof pitch is 45°, then the chimney should project 2, 3 metres
above it.
B
1 metre, provided A is satisfied, or 600 mm above the ridge if G is less than 600 mm.
C
1 metre above the top of any flat roof, and the top of any openable root light, dormer window or ventilator, etc.,
if it is located within 2, 3 metres.
D/E
12
If D is less than 2, 3 metres, E shall be not less than 600 mm.
F
600 mm above the ridge.
G
Edge of chimney to roof ridge.
H07024510 / DT2000575 - Rev. 00
DT2012090-00
PERMANENT VENTILATION
To ensure trouble-free operation the stove/firebox must have the
necessary air available for combustion and this is provided through
the permanent air vent.
Fig. 11
The permanent air vent must:
- have a total free cross section at least equal to the size given in the
paragraph “TECHNICAL DATA”;
- be protected by a grille or suitable guard provided it does not
reduce the minimum recommended section;
- be in a position whereby it cannot be obstructed.
The airflow necessary for the fire may be obtained in different ways:
- through a permanent air vent direct into the room of installation;
- with ducting through pipes direct to the room of installation,
increasing the recommended minimum free cross section by at
least 15%;
- from an adjacent room to the place of installation provided this air
flows freely through permanent apertures communicating with the
outside.
Canopy
grille
English
1.4
Permanent
air vent
DT2030259-01
Fig. 12
If the appliance is being fitted within an existing firebox
recess, specialist advice should be sought before fitting any
permanent ventilation within this area.
The adjacent room from which air is taken must not have a
low pressure compared to the exterior due to a counter
draught caused by the presence in that room of another
appliance in use or of a suction device.
The permanent apertures in the adjacent room must comply
with the requirements given above.
Combustion air must not be taken from adjacent rooms used
as a garage or a combustible materials store or for activities
posing a fire hazard.
DT2030260-01
Fig. 13
The air supply must comply with the current copy of the
Building Regulations Approved Document J.
DT2030261-01
H07024510 / DT2000575 - Rev. 00
13
1.5
DT2010033-01
INSTALLATION ENVIRONMENT
The appliance should be installed in a location which allows safe and convenient use as well as easy maintenance. If the product being
installed requires an electrical socket, the room must also be provided with an earthed power supply in accordance with current regulations.
The room where the appliance is to be installed must comply with the following requirements:
English
they must not be used as a garage, store for combustible material or for activities with a risk of fire.
They must not be in a vacuum in relation to the outside environment due to the effect of contrary draught caused by the presence
in the room where the firebox is installed of another appliance or an extractor device.
Do not use two stoves, a firebox and a stove, a stove and a wood-fired cooking range, etc. in the same environment, since the
draught of one could affect the draught of the other.
• Recirculation type cooker hoods without an extractor fan may only be used in kitchens.
• Gas appliances of type C are allowed (refer to current legislation and regulations in the place of installation)
Gas appliances of type B are not allowed (refer to current legislation and regulations in the place of installation)
The stove or firebox must not be fitted where there are collective type ventilation ducts with or without extractor fan, other devices
or other appliances such as: forced ventilation systems or other heating systems using ventilation to change the air. Such systems
could cause a vacuum in the environment of installation even if installed in adjoining or communicating rooms.
The stove or firebox must not be used: in stairwells except in buildings with no more than two apartments; in corridors for common
use; in bedrooms; in bathrooms or shower-rooms.
1.6
DT2010171-00
CAPACITY LOAD OF THE FLOOR
Check the load-bearing capacity of the floor by adding together: the weight of the protections (lining walls), insulating materials, surround
(given in the surround instruction booklet) and the stove (given in the paragraph “TECHNICAL DATA”).
If the floor has an unsuitable load-bearing capacity, take adequate countermeasures.
1.7
DT2010130-01
HEATING CAPACITY
Check the heating capacity of the appliance by comparing the rated power given in the paragraph “TECHNICAL DATA” with the power required
by the environment to be heated.
The energy requirement may be calculated approximately by multiplying the square metres of area by the height of the ceiling; the result is
then multiplied by a coefficient, which depends on the degree of insulation of the building, that is, on internal and external factors of the
dwelling:
a) Internal factors: type of window and door frames, thickness of the insulation and walls, type of building materials, presence of stairwells,
walls with extensive glazing, high ceilings, position of the rooms to be heated in relation to other adjacent heated or unheated rooms, …
b) External factors: geographical position, average outdoor temperature, exposure, wind speed, latitude, altitude, …
Example of approximate calculation of the energy requirement to heat a fixed volume to 18/20° C:
The coefficient that is normally used is determined according to the real conditions as they occur case by case.
- From 0.04 to 0.05 kW per cubic metre in a well insulated environment
- From 0.05 to 0.06 kW per cubic metre in a poorly insulated environment
3 rooms measuring 20m2 X (H ceiling) 2.7m = 162 m3 (volume)
In an environment with a good degree of insulation, an average value (coefficient) of 0.045 kW may be taken
162 (volume) X 0.045 (kW) = 7.3 kW necessary (6300 kcal/h)
Conversion 1kW = 860 kcal/h
Consult a heating technician or engineer for a correct check and calculation of the requirement of the environments to be heated
(see “REFERENCE STANDARDS”).
Rated power being equal, products with the Multi-fire system can evenly distribute heat throughout the rooms to be heated.
14
H07024510 / DT2000575 - Rev. 00
1.8
DT2010172-00
METHOD OF HEAT DIFFUSION
Diffusion with the Multifuoco System®
An original Piazzetta system designed to distribute heat evenly
throughout the environment, even for several rooms on different
floors.
Fig. 14
CEILING
English
The Multifuoco System® is very simple to install. It is necessary to
install the ventilation kit, following the instructions given with the
same, before positioning the stove and installing the surround.
After having installed the ventilation kit, it is necessary to connect
the warm air outlets to the fan using 75mm diameter hoses.
The warm air outflow may be sent in a maximum of four directions
using two “Y-elements”. It is advisable to install closable warm air
outlets and only one of these may be installed at a distance of less
than six metres from the stove, keeping the remaining outlets closed
so that distribution may be adjusted as required.
With the Multifuoco System® the KNOCKOUTS on the rear of the
stove must NOT BE REMOVED, otherwise the apertures must be
covered over with a metal plate sealed with silicone resistant to high
temperatures and fixed with self-drilling screws. (Figure 16 - 17)
Under no circumstances must collars and any knockouts on the
upper part of the stove (see figure 14) be obstructed in order to allow
proper operation of the Multifuoco System® and the regular outflow
of the warm air that stratifies inside the internal hood and comes out
the hood grilles.
For the size of the hood grille, see the “TECHNICAL DATA” paragraph
under “Minimum section of duct for convective air with open inlet
and outlet”.
DT2030263-00
Fig. 15
The warm air ducts must be in non-flammable, resilient and
if possible smooth material. To decrease heat loss the pipes
must be suitably lagged with insulating material.
For best installation of the Multifuoco System®, Piazzetta
supplies as optionals: Inlet/Outlet with closure; Wall
Inlet/Outlet with closure; Suction Inlet/Outlet with fan; Hose;
Y element; Connecting bend; Hose clamp. See the area
dealer for other available accessories.
DT2030264-00
Diffusion by natural convection
For the stove to work by natural convection the knockouts on the rear (Figure 16 - 17) must be opened during installation in order to allow
the warm air to flow upwards and out.
There must be apertures or grilles located underneath the grate (see figure 15) with “Minimum section of duct for convective air with open
inlet and outlet” that cannot be closed and are at least the size indicated in the “TECHNICAL DATA” paragraph.
A passage for air must be made in the top part of the surround so that the heat may flow out from the internal hood through the hood grilles.
For the hood grille size, see the “TECHNICAL DATA” paragraph.
The air may be ducted in this mode to adjacent rooms.
H07024510 / DT2000575 - Rev. 00
15
Fig. 16
English
Use the rear collars on the stove for warm air ductwork and
leave the front ones for normal outflow by natural convection
towards the hood grille. If all the collars are to be used for air
ductwork, a hood grille must be installed in any case for the
normal outflow of stratified warm air.
KNOCKOUTS
(DO NOT KNOCKOUT
IF USING MULTIFUOCO
SYSTEM)
DT2030523-00
Fig. 17
KNOCKOUTS
(DO NOT KNOCKOUT
IF USING MULTIFUOCO
SYSTEM)
DT2030524-00
Warm air outlet grille heat radiation area
A safety area must be ensured around the warm air outlet grille,
within which there must be no flammable objects (furniture, carpets,
curtains...).
The safety area includes 600mm from the outer edge of the grille.
Figure 18
Fig. 18
AIR OUTLET GRILLE HEAT
DT2030172-00
1.9
DT2010173-01
SUITABLE HEAT INSULATING MATERIALS
Type of suitable heat insulating materials.
Material:
mineral fibre; ceramic fibre; rock wool.
Form:
sheets; mat; shells.
Specifications: specific weight of at least 245 kg/m³ with working temperature limit of at least 1000°C.
Thermal conductivity λ (400°C) ≤ 0.1 W/mK
Thickness:
as shown in the figures in the paragraph “MINIMUM SAFETY DISTANCES”.
If the insulating material is not lining the walls, it must be fixed all over the surface of the walls with anchorage points every
30cm.
Material coded “AGI Q132” or “DIN 18895” is allowed for heat insulation.
16
H07024510 / DT2000575 - Rev. 00
DT2011906-00
MINIMUM SAFETY DISTANCES
8 cm
Fig. 19
- FLAMMABLE WALLS: the stove may be installed near flammable
walls provided suitable protection consisting of insulating and noncombustible material is inserted.
To insulate the stove and to install the surround correctly, construct
a lining wall in non-flammable material (e.g. fireresistant
plasterboard or masterboard) and insert a “C” thick layer of
insulating material between the two walls.
Always leave a gap “A” between the stove and the lining wall. (Fig.
19 - 20)
Flammable
wall
English
Walls
20 cm min.
1.10
Insulating
material
- NON-FLAMMABLE WALLS: always leave a gap of 5 cm between
the stove and the lining wall.
D
Ceiling
- FLAMMABLE CEILING: create an 8 cm false ceiling of nonflammable material.
The minimum distance between the false ceiling and connection to
the flueway must be 20 cm, while the flue connection must be
insulated with at least 3 cm thick non-flammable material that is
resistant to high temperatures. (Fig. 19 - 20)
If the surround canopy and the flue connection are metal, the
minimum distance from the false ceiling may be reduced to 10 cm,
but the insulation of the connection to the flueway must be at least
6 cm thick.
B
E
Flammable
floor
A
C
R
- NON-FLAMMABLE CEILING: the minimum distance between the
ceiling and connection to the flueway must be 20 cm.
DT2032811-00
Floor
If the floor is made of flammable material, it must be protected with
a layer of insulating material of thickness “E” while an air space “D”
must be left between the firebox and the floor. (Fig. 19)
For insulation, use insulating material with the
characteristics given in the paragraph “SUITABLE HEAT
INSULATING MATERIALS”.
Fig. 20
Flammable
wall
Insulating
material
A
Danger area for radiation
C
There is a radiation area in front of the stove which must be kept free
of any flammable element, such as: carpets, curtains, wood
furnishings, ornaments, flammable liquids, fire-lighting products or
firewood, etc.
This area is defined by the distance “R”. (Fig. 19 - 20)
R
DT2032812-00
Failure to comply with the above could cause a fire!!!
The minimum safety distances to be observed are given in the table
below:
MODELS
600-610-650-655 HT
A
clearance from stove to flammable wall at the side
cm
5
B
clearance from stove to flammable wall at the rear
cm
5
C
thickness of insulating material for wall to side/rear
cm
10
D
clearance from stove to flammable floor
cm
See feet height (pg. 22-24)
E
thickness of floor insulating material
cm
6
R
minimum clearance from stove front to flammable material
cm
100
H07024510 / DT2000575 - Rev. 00
17
1.11
DT2011907-00
CONNECTION TO THE FLUEWAY
Connection to the flueway must be done using pipes as short as
possible without narrowing or restrictions and with a maximum slope
of 45° from the vertical..
Fig. 21
Insulation
20
Pipes and bends or elbows must be made in compliance with current
regulations
45°
Maximum
20
WARNINGS WITH REGARD TO FLAMMABLE WALLS OR CEILING:
If the connection has to go through elements or walls in heatsensitive flammable materials, create a layer of at least 20 cm
insulation around the pipe. (Fig. 21)
Insulation
FLUE
After having drilled a hole in the wall to insert the pipe through into
the flueway, the air gaps must be filled with non-flammable, resilient
materials with a reduced capacity of heat transmission (e.g.
lightweight concrete). Fig. 22
Check that the connection to the flueway is gas/smoke-tight, since
the appliance operates in a vacuum.
DT2030269-01
Wall to be protected
It is recommended that the connector pipes be insulated with
insulating material having the characteristics given in the
paragraph “SUITABLE HEAT INSULATING MATERIALS”.
Fig. 22
Check that the pipe does not penetrate too far into the flueway,
thereby choking the pipe for the passage of smoke and combustion
gases.
Air gaps
FLUE
English
Flexible metal or asbestos-cement pipes must not be used
Wall connection
flange
DT2030270-00
1.12
DT2011913-00
LINING WALL
The surround or the lining wall of the firebox must be self-supporting regardless of the materials with which it is made and under no
circumstances must it come into contact with the firebox. Furthermore, the surround must be made with non-flammable materials in
compliance with regulations.
For Gruppo Piazzetta S.p.A. surrounds, follow the instructions enclosed with the product.
Testing and lighting for first time
Only a visual inspection can be made in the intermediate stage for fireboxes, stoves and appliances that must be assembled or clad with
brickwork or require the use of cement binders. In this case operation of the whole installation must be tested after all the building works
directly connected with the “LIGHTING FOR THE FIRST TIME” test have been completed, following the instructions given in the booklet.
18
H07024510 / DT2000575 - Rev. 00
DT2010177-00
HOOD GRILLE
Fig. 23
A non-closable hood grille must be installed without
connecting it to the stove so that the warm air that has
stratified inside the lining wall can flow out.
MIN. 30 CM
MIN. 30 CM
DT2030271-00
With a ceiling over 3 metres high, a NON-CLOSABLE hood
grille must be installed on the hood lining at a height of 30cm
from the ceiling to allow the stratified air to flow out.
DT2010178-00
WOOD MANTEL PROTECTION
Fig. 24
Wood
mantel
1 cm
The expansion joint is in ceramic fibre, which has the
function of insulating the surround from the metal structure of
the stove.
1 cm
Hood or surround
Wooden finishes, e.g. wood mantels, may be mounted on the
surround.
Wood mantels must be:
- installed outside the heat radiation area;
- self-supporting;
- installed with 1cm air gap from the surround or from the heating
part (Fig. 24).
Firebox
1.14
English
FLAMMABLE MATERIALS
CEILING IN FLAMMABLE MATERIAL
MIN. 30 CM
The hood grille has the function of allowing air to pass from inside
the hood to the environment or vice versa if the Multifuoco system
is installed.
Warm air comes out of the hood grille with the natural convection
system and it is therefore necessary to maintain the safety distances
from flammable materials such as: flammable ceilings or walls,
ledges/beams, furniture, curtains, etc.. The hood grille must be
installed at least 50cm from the ceiling and with at least 30cm safety
distance to the sides.
For the hood grille size, see the “TECHNICAL DATA” paragraph.
FLAMMABLE MATERIALS
1.13
Surround
Expansion joint
Load-bearing axis
DT2030272-00
DT2010179-01
1.1
NORMATIVE
DI RIFERIMENTO
1.15
ELECTRIC
POWER
SUPPLY
Make sure there is a power socket 230V 50Hz in the rear stove wall ready for installing the ventilation kit and a switch on the outside of the
cladding to be able to cut off the power supply during maintenance or when the appliance is not being used.
The installation must be earthed and fitted with a circuit breaker in accordance with current wiring regulations.
The installation of any electrical services during the installation of this appliance must be carried out by a registered competent electrician
and in accordance with the requirements of the latest issue of BS 7671.
When connected ensure that the power cable does not come into contact with hot parts.
1.1
1.16
DT2010027-02
NORMATIVE DI
PREVENTION
OFRIFERIMENTO
DOMESTIC FIRES
The product must be installed and used in compliance with the manufacturer’s instructions and European and national standards as well
as local regulations.
when a flue pipe passes through a wall or a ceiling, special installation methods must be applied (protection, thermal insulation,
distances from heat-sensitive materials, etc.) See the paragraph “CONNECTION TO THE FLUEWAY”
- It is also recommended that all elements made of combustible or inflammable material, such as beams, wooden furniture, curtaining,
flammable liquids, etc. be kept outside the heat radiation range of the stove and at a distance of at least 1m from the heating block.
- For other information, see the paragraph “MINIMUM SAFETY DISTANCES” and “CONNECTION TO THE FLUEWAY”.
- The flue pipe, chimney stack, chimney and fresh air intake must always be free of obstructions, clean and checked periodically, that is, at
least twice during the seasonal period from the lighting of the stove and during its use. When the stove has not been used for some time
it is advisable to carry out the checks mentioned above. For further information, consult a chimneysweep.
- Only use recommended fuels (See paragraph “FUEL”).
- Ensure compliance with building regulations document J.
H07024510 / DT2000575 - Rev. 00
19
DT2010627-00
2.0 TECHNICAL DATA AND SPECIFICATION
English
1.1
2.1
DT2010626-00
NORMATIVE DIOF
RIFERIMENTO
DESCRIPTION
THE APPLIANCE
The firebox is an excellent solution because of its core.
The firebox is made entirely in thick gauge steel. It comes ready for use without needing any laborious assembly work.
It ensures high heating efficiency, reduced consumption and safe use.
Heat is diffused by: radiation, conduction, natural convection or forced convection with application of the Multifuoco System, which is an
exclusive ventilation system for quickly and evenly distributing heat at floor level that has been created by the Piazzetta R&D Department.
All the firebox are fitted with a metal hood that wraps around and covers the firebox canopy and allows a greater recovery of heated air. By
connecting hoses to the holes on the metal hood, heated air may be distributed by natural convection also to adjacent rooms.
With the Multifuoco System, the air is taken up from the grille located on the canopy backplate, it enters the metal hood and upon passing
through special gaps is distributed by forced convection through the outlets located in the lower part of the cladding or distributed to adjacent
rooms through relative ducts. (See paragraph “METHODS OF HEAT DIFFUSION”).
No. Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Qty.
1 Aluker® front side panel . . . . . . . . . . . . . . . . . . . . . . . . .2
2 Aluker® rear back panel . . . . . . . . . . . . . . . . . . . . . . . . .2
3 Aluker® back panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
4 Grate grid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
5 Ash drawer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
6 Fireguard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
7 Grate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
8 Lower smoke baffle plate 688x345 600 HT . . . . . . . . . .1
Lower smoke baffle plate 760x370 610 HT . . . . . . . . . .1
9 Upper smoke baffle plate 685x200 600 HT . . . . . . . . . .1
Upper smoke baffle plate 776x240 610 HT . . . . . . . . . .1
600 HT - 610 HT
DT2030274-02
No. Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Qty.
1 Aluker® side panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2 Aluker® back panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
3 Air diffuser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
4 Grate grid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
5 Ash drawer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
6 Fireguard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
7 Grate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
8 Lower Smoke baffle plate 494x210 . . . . . . . . . . . . . . . .1
9 Upper Smoke baffle plate 467x207 . . . . . . . . . . . . . . . .1
650 HT - 655E HT - 655T HT
DT2030512-02
Spare Parts can be obtained from Robeys Limited. Contact details are on page 1 of the instructions.
20
H07024510 / DT2000575 - Rev. 00
DT2010183-00
ACCESSORIES AND EQUIPMENT
Description
Silicone paint spray can
Valve with smoke damper control
Hood grille 145x390
Air intake grille 175x325
Hexagonal door handle tool
Pipes and bends for connection to flueway
Accessories for hot air ductwork
Multifuoco System® ventilation kit
2.3
Accessories
In kit
In kit
In kit
In kit
In kit
Optional
Optional
Optional
English
2.2
DT2010181-00
FEATURES
Fuel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .wood (see “FUEL“ paragraph)
Firebox . . . . . . . . . . . . . . . . . . . . . . . . . . .painted steel
Hearth . . . . . . . . . . . . . . . . . . . . . . . . . . . .Aluker®
Grate and grid . . . . . . . . . . . . . . . . . . . . . .cast iron
Fireguard . . . . . . . . . . . . . . . . . . . . . . . . . .removable
Ash tray . . . . . . . . . . . . . . . . . . . . . . . . . . .removable
Door . . . . . . . . . . . . . . . . . . . . . . . . . . . . .automatic rise n’fall door with ceramic glass heat-resistant up to 750°C
Smoke outlet . . . . . . . . . . . . . . . . . . . . . . .top
Hood shell . . . . . . . . . . . . . . . . . . . . . . . . .aluminised steel
2.4
DT2011543-00
PRODUCT IDENTIFICATION DATA
Every product is identified by a rating plate showing the model and
the performance of the appliance as well as a plate giving the serial
number.
Both plates are located on the bottom shield below the ash drawer.
A label bearing the serial number is also applied on the cover last
page of the “Installation, operation and maintenance” booklet.
Always give the information shown on these plates to the dealer or
the Service Centre when requesting service or spare parts.
Fig. 25
Product name
Serial number
DT2030944-00
Fig. 26
PRODUCTION IDENTIFICATION AND RATING PLATE
DT2030945-00
H07024510 / DT2000575 - Rev. 00
21
English
2.5
DT2010327-02
TECHNICAL DATA
Rated heat output
Consumption at rated heat output
Thermal efficiency
CO content (with 13% O2)
Approved in accordance with standard
Test report No.
Flue diameter
Hearth opening (WxH)
Grate surface area
Weight
Size of packaging (WxDxH)
Fresh air intake (recommended minimum section)
Combustion air flow rate with open intake
Convective air inlet/outlet (recommended minimum section)
U.M.
600 HT
610 HT
650 HT
655T HT
655E HT
kW
kg/h
%
%
cm
cm
cm2
kg
cm
cm2
m3/h
cm2
10
3.55
74
0.18
EN 13229
CS-06-081
20
68x43
1900
190
88x62x176
200
93
350/350
12.5
4.05
75
0.17
EN 13229
CS-07-056
25
77x47
2550
200
97x65x183
300
350/350
8
2.94
72.5
0.18
EN 13229
CS-06-080
20
48x31
1100
190
72x50x186
200
93
350/350
8
2.94
72.5
0.18
EN 13229
CS-06-080
20
48x31
1100
190
72x65x186
200
93
350/350
8
2.94
72.5
0.18
EN 13229
CS-06-080
20
48x31
1100
190
72x65x186
200
93
350/350
These data are obtained using beech wood with moisture content below 20% and with intervals between stoking-up of approximately one hour.
Appliance for intermittent use.
Technical data with closed grate for flue calculations
Rated heat output
Smoke flow rate
Average temp. of smoke in the flue
Minimum draught
U.M.
600 HT
610 HT
650 HT
655T HT
655E HT
kW
g/s
°C
Pa
10
13.72
290
12
12.5
13.3
304
10
8
11.24
280
12
8
11.24
280
12
8
11.24
280
12
The above values correspond approximately to a flue with section Ø 25 cm up to 4.5 m in height and Ø 20 over 4.5 m.
For model 610 HT: Ø 30 cm up to 4.5 m in height and Ø 25 over 4.5 m.
2.6
DT2010628-00
FIREBOX DIMENSIONS
Model 600 HT
Ø 20
27
28
10
65
164
51
38
21
44
20
55
45
35
70
84
DT1020235-01
Measurements in cm.
22
H07024510 / DT2000575 - Rev. 00
Model 610 HT
Ø 25
29
30
English
11
67
171
55
38
21
65
14
59
49
45
79
93
DT1020260-01
Measurements in cm.
Model 650 HT
Ø 20
19,5 23,5
10
63
173
75
53
25
18
48
43
35
55
67
DT1020261-01
Measurements in cm.
H07024510 / DT2000575 - Rev. 00
23
Model 655E HT
Ø 20
19,5 23,5
11,5
English
10
68
173
70
53
25
18
43
10
48
43 35
54,5
55
67
DT1020262-01
Measurements in cm.
Model 655T HT
19,5 23,5
Ø 20
11,5
10
68
173
70
53
25
18
43
10
48
43
35
54,5
55
67
R 41
DT1020263-01
Measurements in cm.
24
H07024510 / DT2000575 - Rev. 00
DT2010326-00
3.0 PREPARATION FOR INSTALLING
- Carefully read all the information contained in the section
“GENERAL RULES” before installing the firebox.
- Unpack the firebox.
Fig. 27
English
- Release the counterweight by slackening the relative screw to be
found inside the upper part of the door (Fig. 27 and 28).
DT2030516-00
Fig. 28
DT2030517-00
- Release the grate by unscrewing the wing nut (Fig. 29), remove the
wood shims and the metal section to be found under the grate and
then replace the grate.
- Where present, remove the polystyrene parts fixing the two smoke
baffle plates to the inside of the firebox.
- Fit the “Multifuoco System®” ventilation kit, if required, following
the sequence given in the respective instructions and refer to the
paragraph “METHODS OF HEAT DIFFUSION”.
Fig. 29
DT2030518-00
- Adjust the height of the grate, adjusting the feet of the hearth in
relation to the chosen surround and making the hearth level. The
firebox is provided with feet allowing the height of the grate to be
raised 25 cm above the ground (Fig. 30). If this height needs to be
increased, insert suitable shims.
- Fit the smoke damper (see “INSTALLATION OF SMOKE DAMPER”).
- Connect the firebox to the flue as indicated in “CONNECTION TO
THE FLUE”.
- Light for the first time and check that the firebox is working
properly (see “LIGHTING FOR THE FIRST TIME”).
- If the check is successful, proceed with installation of the surround.
Fig. 30
25 cm
DT2030519-00
H07024510 / DT2000575 - Rev. 00
25
DT2010328-00
4.0 INSTALLATION OF THE SMOKE DAMPER
English
The hearth is provided with a smoke damper with articulated rod
which aligns with the angle of inclination to which the damper is
being set. For installation purposes proceed as follows:
- Position the damper [2] in its seat and keep it in a vertical position.
- Insert the rod [1] fully into the damper [2]. During this operation,
the tongue [3] remains facing downwards. (Fig. 31)
- Proceed with the installation of the smoke outlet pipe and its
connection to the flue as indicated in the section with the same
name.
- Construct or finish the preparation of the lining and of the facing
wall.
- Insert the wooden plug provided into the box [4] and thread it onto
the rod [1].
- Then determine the exact position of the box which must follow
the angle of the facing wall. By moving the box with the plug, the
rod [1] remains as a guide and it will thus be possible to determine
the ideal position of the box, rod and facing wall.
- Cut off the rod [1] at 1 cm inside the outer face of the wall.
- Thread on the plate [5] and screw it to the box [4].
- Fit the handle [6], ensuring that the position of the damper
corresponds to that of the plate.
Fig. 31
DT2030520-00
Fig. 32
If the facing wall is of fire resistant plasterboard (Fig. 33),
the box [4] is secured to the wall by screwing on the plate [5]
after turning up the side edges.
DT2030521-00
Fig. 33
WALL OF
PLASTERBOARD
1 CM
PART. “A”
WALL OF
PLASTERBOARD
PART. “A”
1 CM
RISES
DT2030522-00
26
H07024510 / DT2000575 - Rev. 00
DT2010329-00
5.0 USE
DT2010055-02
5.1
DT2010043-00
FUEL
Use well-seasoned and dry wood with less than 20% moisture content.
Wood that is ready to burn must have been dried in the open air sheltered from rain or snow for at least 2 years after having been cut.
The lower the moisture content of the wood the higher its heating power. Freshly cut wood has 50% less heat value than dry wood.
Burning wood that is too wet means wasting most of the calories for evaporation of the water contained in it and, in particular, the walls of
the combustion chamber and the flue become fouled and encrusted thereby affecting efficiency.
The table below shows how the heating power decreases as the moisture content increases.
Moisture content (W)
Seasoning time
20
30
40
after 2 years
after 1 year
after 6 months
HEATING POWER OF THE WOOD (Beech)*
Kcal/kg
kWh/dm
3400
2.9
2900
2.8
2410
2.7
kWh/kg
4
3.4
2.8
3
* Approximate values.
2,5
2,0
1,5
1,0
0
BE
EC
LO H
CU
ST
OA
K
AS
H
BE
EC
H
BI
RC
H
LA
RC
H
PI
N
PO E
PL
AR
AL
DE
W R
IL
SI LOW
LV
ER
F
SP IR
RU
CE
0,5
TE
Mediocre or poor fuels
- Timber that is not recommended comes from the family of conifers,
willow, poplar and alder. These light soft woods are resinous and
therefore create more soot, few embers and incandescent sparks,
while requiring more frequent cleaning of the flue and the firebox.
- Another characteristic of softwood is that it gives a lively but shortlived flame and the consumption is higher for the same heat output.
3,0
W
HI
Good fuels
- Recommended timber comes from the family of broadleaf
hardwoods: beech, hornbeam, oak, false acacia, ash, birch,
maple, elm.
- All low-resin and close-grained woods (that is hard and heavy
timber) are most suitable, since they provide the stove with a
steady, continuous flame.
Heating Power (KW h/dm 3 w=20%)
It is a good rule to purchase timber during the summer (June-July), since woods are cut down mostly in the autumn and you can therefore
be sure that the timber has already been seasoned for approximately 1 year.
Firewood can be classified in two qualities: “good” and “mediocre or poor".
This classification is according to the heat yield of the wood, the longest flame time it provides, its composition and density.
Approximate value referred to ONE cubic decimetre of evenly shaped pieces of
wood with approx. 20% moisture content.
DT2010053-00
Unsuitable fuels
- Never use wet wood, tarred wood or pellets.
- It is also best not to use: refuse (rubbish), waste paper; paper briquettes; plywood or chipboard; fibreboard; packaging materials; painted
wood or wood coated with synthetic material, plastic laminates, cardboard or milk cartons.
Under no circumstances use liquid fuel of any kind whatsoever.
All these materials or similar ones could be hazardous for the user, damage the firebox, the flue connection and the flue, and, last
but not least, pollute the environment.
H07024510 / DT2000575 - Rev. 00
27
English
Certain basic facts can be all-important for best performance and getting the most out of your appliance. Please find below some basic
information intended to be of use with regard to the choice of firewood, the adjustment of the dampers and proper operation of the appliance.
During operation, some parts of the appliance (door, handle, dampers, surround) can reach high temperatures. Therefore exercise great
care and take all necessary precautions.
When you need to add wood to the firebox or to adjust the air flow, use the glove or the hand protector provided.
If the door of the product fails to close automatically, operation with the firebox open will only be possible with constant checking of the flame.
English
Log size
The size of the wood logs can also affect the efficiency of the product.
It is essential for the wood to be arranged on the grate on top of a
layer of embers.
The logs must not touch the aluker or the glass window nor must
they be put on top of each other. Place the wood as shown in the
figure 34.
We therefore recommend using logs of the following size:
- perimeter approx. 30/35 cm;
- lwength approx. 20–25–30 cm according to the type of hearth.
Fig. 34
Perimeter
Under no circumstances use liquid fuel of any kind
whatsoever.
All these materials or similar ones could be hazardous for the
user, damage the firebox, the flue connection and the flue,
and, last but not least, pollute the environment
5.2
Le
ng
ht
DT20300063-00
DT2011210-00
SMOKE DAMPER REGULATION
600 HT
610 HT
650 HT
655T HT - 655E HT
SMOKE DAMPER POSITION
FIREBOX IN OPERATION AT NOMINAL POWER
LIGHTING OR STOKING-UP OF FIREBOX
CLOSED ()*
OPEN
CLOSED ()*
OPEN
OPEN (*)
OPEN
OPEN (*)
OPEN
(*) Position referred to a draught of 12 Pa
When lighting the firebox, put the damper to the open “APERTO” position until a bed of embers has been formed.
Once the firebox is properly lit, put the damper to the operating position, which may vary according to the atmospheric conditions, the type
of flue and consequently the draught. You will learn by trial and error which is the best position for the smoke damper.
Before putting in any logs, always set the damper to the open “APERTO” position. After having put in the wood, set the damper
back to the functioning position.
Fig. 35
A
B
C
DT2030515-02
Damper positions: closed (A), 1/2 open (B), open (C).
28
H07024510 / DT2000575 - Rev. 00
DT2010333-00
COMBUSTION AIR REGULATION
The rated thermal efficiency is determined with the air damper. Pay
attention to the positions given in the table below according to the
fuels being used.
The positions given below refer to rated efficiency. Since efficiency
also depends on atmospheric and climatic conditions and therefore
on the draught, the most suitable position will be found with
experience.
Regulation is carried out as shown in figure.
Reference should also be made to the paragraph “SMOKE DAMPER
REGULATION”.
Fig. 36
CLOS
ED
OPEN
English
5.3
DT2030526-00
Regulation and quantity of material to be burned for rated power:
600 HT
610 HT
Material to be burned
650 HT
655T HT
655E HT
See “FUEL” paragraph
Air damper position
Not fitted
OPEN
OPEN
OPEN
OPEN
Smoke damper position
CLOSED
CLOSED
OPEN
OPEN
OPEN
Maximum quantity of fuel to be burned
See “TECHNICAL DATA” paragraph
Data obtained in a laboratory qualified to issue certification.
Should the flue have a strong draught exceding 12 [Pa], the smoke damper must be moved towards the closed “CHIUSO” position.
An excessive increase in fuel and excessive opening of the air/smoke dampers, compared to the values given in the table, leads
to an increase in appliance heat, decrease in efficiency and an increase in wood consumption.
5.4
DT2010045-03
LIGHTING FOR THE FIRST TIME
Before lighting, remove the supplied accessories (see “ACCESSORIES AND EQUIPMENT” paragraph) and flammable elements
from the grate or from the ash drawer and remove any elements of carriage used to protect any part of the stove.
If provided in the kit, it is very important to remove the paint spray can, which could explode.
There are two important stages when lighting the appliance for the first time: the operating test and start-up.
1.
Operating test
- Before carrying out the operating test, check that everything has been installed correctly (see section “GENERAL RULES”).
- Start with the lighting stage (see paragraph “LIGHTING”).
- The first load should be reduced by 50% of the normal recommended amount.
Should smoke come out:
• do not open the door of the stove;
• close the combustion air dampers (MINIMUM position) only on appliances with combustion air damper;
• let the fire go out slowly;
• open all doors and windows to ventilate the room;
• do not remain in the room or re-enter until you are sure it is safe to do so;
• check the cause of malfunctioning.
Do not extinguish the fire with water as this could damage the grate
2. Start-up
- During this first time of operation it is recommended to use the appliance at minimum capacity, stoking the grate for at least the first
day with only 50% of the logs usually indicated as normal.
- Keep the air dampers in the operating position (except for lighting), see paragraph “COMBUSTION AIR REGULATION”.
- This stage allows all the parts to settle down and fumes caused by paints/varnishes, greases or oily liquids used in manufacture to
disappear.
- Air the room well in this initial stage.
- This procedure must be carried out with the forced ventilation system turned off.
After this, the appliance will no longer emit odours due to paint evaporation and must only be stoked up with the indicated nominal amounts.
H07024510 / DT2000575 - Rev. 00
29
5.5
DT2010330-00
LIGHTING
When lighting the fire, the grate should be brought quickly to working
temperature. If it is done slowly, condensation will inevitably form
and cause blackening of the grate and the glass
Fig. 37
Fig. 38
- Put the air or smoke damper to the open position (MAXIMUM)
(see paragraphs “COMBUSTION AIR REGULATION” or “SMOKE
DAMPER REGULATION”). Fig. 37 Fig. 38
- Place the material for kindling (paper, firelighter, etc.) in the centre
of the grate and add small pieces of soft wood (fir) in the form of
DT2030064-00
DT2030065-00
a pyramid. To light the soft wood quickly, open the door by approx.
two centimetres for 5–10 minutes. Figure 38
- Once the bed of embers has been created, stoke-up with the recommended amounts of fuel. Keep the door closed except when adding more
fuel and adjust the combustion air or the smoke damper as instructed in the respective paragraphs “COMBUSTION AIR REGULATION” or
“SMOKE DAMPER REGULATION”.
5.6
DT2010046-00
OPENING THE DOOR
The door must remain closed while the stove is alight, otherwise it
could damage the inside of the stove. The door must be opened
slowly, holding it slightly ajar for a moment before opening it
completely. Open the door when the flame has died down and
certainly never when the flame is very intense.
Fig. 39
Hexagonal door handle tool
E06030230
English
Put the fuel into the grate according to the methods described below:
Always use the hexagonal door handle tool provided.
Do not slam the door shut otherwise the glass could break.
DT2031080-00
5.7
DT2010047-00
NIGHT TIME OPERATION AT MINIMUM
After normal operation during the day, the appliance may continue to operate for a few hours at night.
When stoking up the fire for the last time in the evening, ensure that the bed of embers is sufficient, put the wood in the grate and then set
the combustion air dampers to minimum. Night time operation of the stove at minimum depends on the type of wood (a very hard wood is
recommended), the flue draught and the weather.
The amount of wood to put on and the necessary adjustment of combustion air flow will be learned with experience (see the paragraph
“COMBUSTION AIR REGULATION”).
The next morning, start up the fire at maximum to burn off any creosote formed during the night. Creosote deposits start to form when the
flue temperature falls to below 150 °C. To prevent this from happening it is important to try to maintain the grate of the appliance at normal
working temperature (rated heating efficiency phase) as long as possible.
Prolonged operation of the stove at minimum could require more frequent cleaning of the grate and the flue.
30
H07024510 / DT2000575 - Rev. 00
5.8
OPERATION UNDER ADVERSE WEATHER CONDITIONS
DT2010048-00
During the intermediate seasons with adverse weather conditions or when outdoor temperatures are higher, a sudden rise can cause
malfunctioning of the draught, thereby impeding proper smoke discharge. In this case the grate must be loaded with only a little wood and
the primary air damper be set fully open so that the wood burns faster and thereby stabilises the draught.
5.9
DT2010051-00
OVERHEATING AND EXTINGUISHING
English
In the event of overheating or if some appliance parts or the flue turn red:
- immediately stop the supply of fuel;
- do not open the stove door;
- close the air dampers (MINIMUM position);
The fire will go out due to lack of air.
When the appliance has cooled down, find the cause of the problem and if necessary call in specialised personnel.
In the event of fire, extinguish with a fire extinguisher.
Do not extinguish the fire with water.
Air the room well before using it again in order to get rid of any smoke and combustion gases.
H07024510 / DT2000575 - Rev. 00
31
DT2010111-02
6.0 MAINTENANCE
All maintenance work (cleaning, any replacements, etc.) must be carried out when the firebox is shutdown and cold.
Do not use materials that could scratch or damage the glass, since scratches could become cracks. Under no circumstances use abrasive
substances.
English
DT2010057-02
6.1
DT2010058-00
PERIODIC CHECKS
Check for any formation of creosote in the pipes connecting to the flue and inside the flue during the seasons when the appliance is in
operation, inspecting them at least once every two months.
The combustion of the wood (especially if moisture content is higher than 30%) produces pitch and other organic vapours that give rise to
creosote. The formation of creosote causes fouling, which obstructs the flue and the passage of smoke.
“Creosote” is inflammable and can catch fire, causing serious damage to both the flue and to the structure of the dwelling.
Only use recommended fuels (see “FUEL” paragraph).
If creosote has accumulated, it must be removed to reduce the risk of fire and to improve heat exchange.
The following must be free from obstruction and inspected at least once every two months:
- the flueways (connection to the flue, flue pipe, chimney stack);
- the fresh air intake;
- the appliance hearth (correct position of the plates, the ash tray, the grate and grid, deflectors, smoke dampers, etc);
- the ventilation system (apertures, air ducts, grilles) if installed.
Check that the automatic door closing system and the air dampers are in proper working order.
Maintenance of all the above heating system must be carried out at least once a year before the season when it will be used. We
also recommend periodically checking the whole heating system during the period of operation until the time when it will not be
used for several months.
6.2
DT2010059-03
CLEANING THE CERAMIC CLADDING
The ceramic cladding must first be cleaned with a soft dry cloth before using any detergent (even mild detergent).
Products are available on the market which are suitable for cleaning ceramics as well as concentrated products for cleaning porcelain. These
will remove oil, ink, coffee and wine stains, etc.
Never soak the ceramic cladding or clean it with cold water when it is still hot as the thermal shock could cause it to crack.
6.3
DT2010060-00
CLEANING THE STEEL PARTS
The steel sections of the cladding should be cleaned with a soft, dry cloth before applying any detergents. Afterwards it is recommended that
you use a degreasing agent such as acetone or vinegar diluted in water.
6.4
DT2010061-03
CLEANING THE PAINTED METAL PARTS
When cleaning the painted metal parts of the product use a soft cloth moistened with water
Never clean metallic parts using alcohol, solvents, petroleum-based products, acetones or other degreasing or abrasive substances.
In the event of such substances being used the manufacturer will not be responsible for any damage caused.
Discolouration of metallic parts may be the result of misuse.
32
H07024510 / DT2000575 - Rev. 00
6.5
DT2010700-00
CLEANING THE GLASS (DAILY)
If the appliance is very slow to heat up in the ignition phase due to fuel that isn’t completely dry, this is likely to cause a build-up of tar on
the glass. This will eventually burn off when the appliance is operating at full capacity. If the tar is left to build up over a long period it will
require more effort to remove. We therefore recommend that the glass be cleaned daily before lighting the stove.
The glass should be cleaned when cold using ammonia-based degreasing agents and not corrosive substances such as solvents.
Only for the purpose of cleaning the glass, the hinged-type door may
be opened using the door handle tool provided in the kit. Insert the
door handle tool into the relative hole in the door and turn to open
English
Do not use any material that could scratch or spoil the glass, as scratches may develop into cracks or breaks.
Fig. 40
In case of breakage
Every one of our hearths comes with a door fitted with a 4 mm thick
pyroceram panel resistant to thermal shock up to 750°C. This can
only be broken by heavy impact, such as banging the door too hard.
In the event of breakage replace with original Gruppo Piazzetta S.p.A.
parts only.
Do not operate the appliance if the glass is broked or cracked.
Seal control
Proper tightness of the door seal is essential for optimal product
performance. It is therefore recommended that the seals be checked
periodically or after a long period of use for signs of wear or damage.
If necessary replace them using Gruppo Piazzetta S.p.A. original
spare parts.
6.6
DT2031079-00
DT2010063-00
CLEANING THE GRATE AND THE ASH TRAY
The grate and the ash tray must be cleaned daily. Using the grate for a whole day contributes to the accumulation of ash or residual combustion
products. If cleaning is not done regularly there will be an excess of residues, which will affect appliance efficiency.
The ash tray also needs emptying regularly, because if it fills up and obstructs the grate grid it will cause appliance malfunction.
6.7
DT2010049-04
DISPOSAL OF ASHES
Ash from natural (non-treated) wood burned in stoves or open fireboxes is composed mainly of calcium, silicon, potassium and magnesium
oxides. The ashes can therefore be used as a fertiliser for plants or in the garden, albeit not exceeding 2.6 kg per 10m2 annually.
The ashes should be placed in a metal container with a sealed cover. The sealed container should be placed on a non-combustible
surface at a safe distance from combustible materials until the cinders have been completely extinguished.
Only when they have been fully extinguished can the ashes be thrown away with organic waste, assuming that nails or other nonorganic material are not present.
6.8
DT2010064-00
CLEANING ALUKER®
The interior of the unit has been constructed from an innovative material called “Aluker”.
Aluker is based on substances that are completely non-toxic and is heat-resistant up to 1400°C.
In spite of its considerable strength it is not recommended that you throw large pieces of wood forcefully against the bricks.
Aluker darkens when the stove is first lit but returns to its natural colour gradually as the bricks warm up.
Some advice for optimum use of Aluker bricks:
- Don’t use water to put out the fire - leave the bricks to cool by themselves;
- Don’t scratch Aluker bricks with metal objects;
To clean Aluker bricks use an ordinary brush.
H07024510 / DT2000575 - Rev. 00
33
DT2010334-00
REMOVING THE SMOKE BAFFLE PLATES
The appliance is fitted with two smoke bafle plates, which are
designed to lengthen the path of the flue gas or smoke by increasing
the heat exchange surface area. The smoke baffle plates rest on
supports inside the fireboxes, as shown in figure 41-42.
Should it be necessary to replace the smoke baffle plates, unscrew
the hexagon nut (for the fireboxes 650HT and 655HT only) to be
found on the left part of the smoke baffle plates, push the smoke
baffle plates upwards, turn them downwards and remove them.
Fig. 42
View of the smoke baffle plates model 600 HT - 610 HT
Upper smoke
baffle plate
Fig. 41
View of the smoke baffle plates model 650 HT - 655 HT
Upper smoke
baffle plate
Lower smoke
baffle plate
Smoke baffle
plates supports
English
6.9
Lower smoke
baffle plate
View of the lower smoke baffle plate from below
DT2030529-00
6.10
DT2030530-00
DT2010065-01
CLEANING THE FAN (ONCE A YEAR)
All cleaning and maintenance operations must be carried out after DISCONNECTION OF THE POWER.
Pursuant to current regulations on the safety of electrical equipment, you must contact a Piazzetta After-Sales Service Centre or a
qualified electrician for all and any work connected with installation, maintenance or servicing that involves access to electrical parts.
Dust can accumulate in the ventilation kit and in particular in the holes of the protective cover of the fan, the grilles and the fan blade, which
should therefore be cleaned once a year. Use a vacuum cleaner or compressed air, being careful with the electrical parts.
The ventilation kit must be disassembled for proper cleaning. Follow the installation procedure in the reverse order (see the instructions
enclosed in the kit).
6.11
DT2010068-00
SHUTTING DOWN
Before any long period during which the firebox will be inactive we recommend that you carry out a thorough cleaning, thereby avoiding
encrustations and oxidations which will be difficult to clean later. We also recommend that as a preventative measure you carry out a general
checkup as outlined in the paragraph headed “PERIODIC CHECKS”.
After a period of inactivity problems relating to the expansion of parts or the release of odorous gases may arise. We therefore recommend
that upon restarting the unit you do not immediately run it at full power. Nor should you activate the ventilation system until the odorous gases
have dispersed. This problem can be dealt with by simply airing the room.
6.12
DT2010379-01
CLOSING DOOR SYSTEM
This operation should be carried out by specialised personnel.
The “rise n’fall” door closing system must be checked periodically, at least once every two years; attention must be paid in particular to
lubricating the roller located inside the double glazing or, depending on the model, the pulleys located outside the double glazing.
34
H07024510 / DT2000575 - Rev. 00
DT2010069-01
7.0 TROUBLESHOOTING
Cause
Problem
The window becomes
excessively dirty
Condensation forms
Difficulty in lighting
Smoke comes out of the firebox in adverse weather conditions
English
Some of the above problems could be resolved by following the instructions. Only qualified persons must carry out work on the
stove and only when it is cold and disconnected from the power supply (pull out the plug).
Unauthorised tampering with the appliance or use of other than original spare parts invalidates the warranty and relieves the
manufacturer of all and any liability.
The manufacturer shall not be liable for any problems caused by lack of or inefficient maintenance or by failure to comply with the
instructions in the product installation and operating guide.
Remedy
Lack of draught
Open the smoke damper.
Check the smoke/gas discharge pipe
Wet wood
Use dry wood
Use of mediocre or poor class fuels
Change the type of fuel
(See “FUEL” paragraph)
Too little combustion air
Open the air dampers more, if
installed
Section of flue too large
Reduce the section by inserting a well
insulated pipe with suitable section
inside the flue
Flue not adequately insulated
Clad the flue with hollow tiles or
other insulating materials
Slow combustion and therefore low
smoke temperature
Burn smaller and dry logs.
Open the primary air damper more, if
installed
Air or smoke dumper closed
Put the combustion air dampers, if
installed, to maximum position and
fully open the smoke damper
Logs too large
Use smaller logs
Wood too wet
Burn drier wood
Lack of draught
Open the smoke damper.
Check the smoke/gas discharge pipe
Chimney stack has no down-draught
cowl
Replace the chimney stack with one
that has a down-draught cowl
Flue not suitably insulated
Clad the flue with hollow tiles or
other insulating materials
H07024510 / DT2000575 - Rev. 00
35
Problem
English
Insufficient heat
Too little and only lukewarm air flows
from the outlets
The fan does not work (*)
Noisy fan (*)
Smoke comes out upon opening the
door
Cause
Remedy
Quantity of wood less than necessary
for nominal efficiency
Use the quantity of wood indicated
in the instructions (See “TECHNICAL
DATA” paragraph)
Undersized grate for the environment
to be heated
Integrate with another product
Inadequate insulation for the environment in which the firebox is installed
Insulate well with suitable materials
Oversized fresh air intake
Decrease the intake section
Pipework not insulated
Suitably insulate
Pipework too long or with too many
bends
Change the path, complying with the
ventilation kit instruction booklet
Too many branches
Change the path
Environment too large for capacity of
the fan and power of the product
Heat fewer rooms or use the stove as
a supplementary source of heat
Incorrect connection to power supply
Correct the connection according to
the assembly diagram
Electronic regulator damaged
Replace the regulator
Power failure
Power the appliance
Presence of dust or similar in the fan
Clean the fan
Vibrations
Check fan position
Worn rotating parts
Replace the fan
Door opened too fast
Keep the door just ajar for a few
seconds before fully opening
There are still flames
Only open the door when just embers
remain in the grate
(*) Pursuant to current regulations on the safety of electrical equipment, you must contact a Piazzetta After-Sales Service Centre
or a qualified electrician for all and any work connected with installation, maintenance or servicing that involves access to
electrical parts.
36
H07024510 / DT2000575 - Rev. 00
COPY
COPY
COPY
www.miotto.it
Product serial number, to be quoted when requesting service
from the Gruppo Piazzetta After-Sales Service Centre.
Via Montello, 22
31011 Casella d’Asolo (TV) - ITALY
Tel. +39.04235271 - Fax +39.042355178
www.piazzetta.it
e-mail: [email protected]
Gruppo Piazzetta S.p.A. Technical Department - cod. H07024510 / DT2000575 - Rev. 00 - (06/2010)
UK