FIRE SUPPRESSION SYSTEM INDOLOK BAKTI UTAMA, PT – Business Area System 5 February 2013 INTRODUCTION Api dapat terjadi dikarenakan adanya tiga unsur yang berhubungan yang dikenal dengan istilah “TRIANGLE OF FIRE /SEGITIGA API”, tiga unsur tersebut adalah : 1. Unsur Oksigen 2. Unsur Bahan bakar / Combustible material 3. Unsur Panas / Heat Proses pemadaman api dapat dilakukan dengan menghilangkan atau memisahkan paling sedikit salah satu dari 3 unsur tersebut, salah satu caranya dengan menggunakan gas bertekanan. 31 July, 2017, page 2 TRIANGLE OF FIRE THREE ANGEL OF FIRE Api akan timbul ketika bahan bakar, oxidizer dan sumber api sudah menyatu atau tercampur pada tingkat tertentu. Bahan bakar Oxidizer Padat : plastik, serbuk kayu, fiber, partikel logam Cair : bensin, aseton, eter, pentana Gas : asitilen, propana, metana, karbon monoksida, hidrogen Padat : metal peroksida, amonium nitrit. Cair : hidrogen peroksida, asam nitrat, asam perklorat Gas : oksigen, flourine, klor, flour Sumber api Korek api, listrik statis, puntung rokok,dll 31 July, 2017, page 3 FIRE SUPPRESSION SYSTEM ANGEL OF FIRE THREE Merupakan System Pemadaman Kebakaran Otomatis dengan menggunakan media Gas atau bahan kimia untuk memadamkan api. Ada beberapa sistem pemadaman api dengan menggunakan gas bertekanan sebagai media untuk proses pemadaman api, diantaranya : 1. FM200 System HFC-227ea 2. Argonite System IG-55 (50% Argon / 50% Nitrogen) 3. CO2 System 4. NOVEC 1230 31 July, 2017, page 4 FK 5-1-12 / C6F12O FM200 SYSTEM FLOWCHART 31 July, 2017, page 5 HOW THE SYSTEM WORK? Sistem dapat dioperasikan secara otomatis dan manual. System berjalan secara otomatis selama 24 jam. Dengan Pengoperasian secara otomatis biasanya akan menimbulkan kejadian-kejadian dibawah ini: Bila rangkaian Zone Detector 1 & 2 dalam kondisi alarm (maka alarm bell dan multi alert akan berbunyi). Tegangan output akan bekerja, mengaktifkan electric actuator, sehingga valve ditabung akan terbuka, maka gas akan keluar didalam ruang yang diproteksi. Jika Detector yang didalam ruangan tidak berfungsi, sedangkan didalam ruang tersebut terjadi sumber kebakaran, maka untuk mengeluarkan Gas dapat dilakukan dengan mengaktifkan tombol “ Manual Release”. Setelah Gas keluar maka lampu DNE diatas ruangan akan menyala. Selama Gas terpancar, jangan membuka ruangan tersebut sampai Gas habis. 31 July, 2017, page 6 HOW THE SYSTEM WORK? Pengoperasian secara manual, dilakukan bila listrik PLN atau panel tidak berfungsi, maka harus mengikuti langkah dibawah ini: Ketahui dengan pasti ruangan yang terjadi kebakaran. Tentukan tabung yang berhubungan dengan ruangan yang terjadi kebakaran Pastikan ruangan tertutup rapat Kemudian tarik “ pin pengaman “ dan tekan tuas (lever actuator) yang terdapat pada tabung. 31 July, 2017, page 7 HOW THE SYSTEM WORK? Output Input Strobe Lamp + Bell Alarm MCFA A Manual Release & Abort switch Ion Smoke Detector Photo Smoke Detector Smoke cause from fire 31 July, 2017, page 8 Fire Suppressed Input Output Gas FM 200 discharge to Room FM 200 Activated WIRING INSTALLATION (Conventional) Zone 1 Zone 2 220 VAC Abort Manual Release Alarm Horn& Strobe 31 July, 2017, page 9 WIRING INSTALLATION (Conventional/Zone 1 Active) Zone 1 Zone 2 220 VAC Abort Manual Release Alarm Horn& Strobe 31 July, 2017, page 10 WIRING INSTALLATION (Conventional/Zone 2 Active) Zone 1 Zone 2 220 VAC Abort Manual Release Alarm Horn& Strobe 31 July, 2017, page 11 WIRING INSTALLATION (Conventional/Cross Zones) Zone 1 Zone 2 220 VAC Abort Manual Release Alarm FM200 31 July, 2017, page 12 Horn& Strobe WIRING INSTALLATION (Conventional/Manual Release) Zone 1 Zone 2 220 VAC Abort Manual Release Alarm FM200 31 July, 2017, page 13 Horn& Strobe WIRING INSTALLATION (Addressable) Zone 1 220 VAC Zone 2 Abort Output Mod Manual Release Input Mod Input Mod Output Mod Alarm Output Mod Horn& Strobe Output Mod 31 July, 2017, page 14 Fire System Application Area SYSTEM FIRE DETECTION SYSTEM FIRE ALARM GAS AREA SYSTEM DETECTION OFFICE/ADMIN Building yes n/a Power House yes yes Factory Plant yes n/a Warehouse yes n/a Fuel Tank Area yes n/a Boiler Area yes yes Power Plant yes yes MCC Panel Room yes n/a Laboratories yes yes/no Jetty Area yes n/a Conveyor yes n/a Yard area yes n/a Control Room yes n/a Transformer Area yes n/a Furnace yes yes 31 July, 2017, page 15 FIRE SUPPRESSION SYSTEM FIRE FIGTHING SYSTEM Novec 1230 Hydrant Sprinkler Waterspray Foam Fire /FM 200 CO2/Inert gas System System System System Extinquisher yes n/a yes yes n/a n/a yes n/a yes yes n/a yes n/a yes n/a n/a yes n/a n/a yes yes n/a n/a yes yes n/a n/a yes n/a n/a yes n/a yes yes yes n/a n/a yes n/a yes yes yes n/a yes yes yes yes n/a yes yes n/a yes n/a n/a n/a yes yes n/a yes yes n/a n/a yes n/a n/a yes n/a n/a n/a yes n/a n/a yes yes n/a n/a yes n/a n/a yes n/a n/a n/a n/a yes n/a n/a n/a n/a n/a yes n/a n/a yes n/a yes n/a yes n/a n/a yes n/a yes n/a yes FM200 SYSTEM INDOLOK BAKTI UTAMA, PT – Business Area System 2 May 2012 INTRODUCTION In today’s global business environment, the need for clean agent fire suppression has never been greater. 31 July, 2017, page 17 FM200 IS THE RIGHT CHOICE FM-200 is the best protection for your business Fast and efficient performance Safe for people / Human friendly No collateral damage Environmentally responsible 31 July, 2017, page 18 CHEMISTRY PERFORMANCE REMOVES HEAT SO FIRE CAN NOT SUSTAIN ITSELF CF3CHFCF3 (Is compound of Carbon, Fluorine & Hydrogen) 31 July, 2017, page 19 STANDARIZATION PERFORMANCE UL listed FM approved 31 July, 2017, page 20 FAST AND EFFICIENT PERFORMANCE Suppresses all classes of fires Class A Surface Fires - wood, paper etc Class B – flammable liquids Class C – electrical equipment 31 July, 2017, page 21 NO COLLATERAL DAMAGE FM-200 is a CLEAN AGENT that doesn’t leave oily residues, particulates, water or corrosive material. With FM-200 could be eliminates collateral damage to high tech equipment, artwork and other delicate and sensitive objects. After it has been discharged, it can be removed by simple ventilation, allowing businesses to resume their normal operation almost immediately. 31 July, 2017, page 22 HUMAN SAFETY FM-200 is so safe, it has been designated as a replacement for CFCs as propellant in medical inhalers. 31 July, 2017, page 23 ENVIRONMENTAL RESPONSIBILITY Zero Potential to Deplete Ozone 31 July, 2017, page 24 APPLICATIONS Critical electronics system Computer Room with data processing equipment Bank Vaults File rooms and data archives etc 31 July, 2017, page 25 FM200 PIPE LAYOUT 31 July, 2017, page 26 FM200 SYSTEM EQUIPMENTS SYSTEM COMPONENTS 31 July, 2017, page 27 FM200 SYSTEM EQUIPMENTS (Conventional) Panel,SYSTEM Control PanelCOMPONENTS RP-2002E Battery 12 V - 6,5/ 7 AH Sealed Acid Relay for Shutdown Photoelectric smoke detector Ionization smoke detector Manual release & abort switch (Notifier) Alarm bell Horn Strobe Do Not Enter light Evacuate light Manual release label Door warning label Cylinder Assembly, 125 lbs. Discharge Hose, Cylinder strap Gas FM 200 Electric Control Head, Stackable, 24 VDC (Ex. Proof) Lever operated control head Pressure switch, 3 pole double throw Discharge nozzle 31 July, 2017, page 28 RP-2002E / Notifier Panasonic / Local OMRON 2151 / System Sensor 1451 / System Sensor NBG 12LRA + SBA-10 SSM24-6 / System Sensor P2R / System Sensor Local Local Local Local KIDDE KIDDE KIDDE DUPONT KIDDE KIDDE KIDDE KIDDE FM200 SYSTEM EQUIPMENTS (Addressable) SYSTEM COMPONENTS NFS-320 Intelligent Fire Alarm Panel; Back Up Battery Relay for Shutdown Photoelectric smoke detector Ionization smoke detector Manual release & abort switch Alarm bell Horn Strobe Do Not Enter light Evacuate light Manual release lable Door warning lable Module, FCM-1 CH Control Flashcan Module, FMM-101 CH Monitor with flashcan Relay Module FRM-1 CH with flashscan Cylinder Assembly, 125 Lbs Discharge Hose, Cylinder strap Gas FM 200 Electric Control Head, Stackable, 24 VDC (Ex. Proof) Lever operated control head Pressure switch, 3 pole double throw Discharge nozzle 31 July, 2017, page 29 Notifier Panasonic OMRON FSP-851 CH FSI -851 CH NBG 12LRA + SBA-10 SSM24-6 P2R Local Local Local Local FCM-1 FMM-101 FRM-1 KIDDE KIDDE KIDDE DUPONT KIDDE KIDDE KIDDE KIDDE FM200 CYLINDER COMPONENTS 31 July, 2017, page 30 EFFICIENT PERFORMANCE Compact storage space requirements Halon 1301 CO2 Inert Gas 31 July, 2017, page 31 EXCEPTION FM200 system shall not be used to extinguish fires in : chemicals containing their own supply of oxygen, such as cellulose nitrate, gunpowder. Mixtures containing oxidising materials, such as sodium chlorate or sodium nitrate. Reactive metals, such as sodium, potassium, magnesium, titanium, and zirconium. All above materials would in case of fire create an explosion. 31 July, 2017, page 32 THANK YOU INDOLOK BAKTI UTAMA, PT – Business Area System 5 February 2013 EXAM FOR TRAINING FIRE SUPPRESSION SYSTEM 1. Sebutkan dan jelaskan apa yang dimaksud dengan segitiga api! 2. Sebutkan beberapa macam Fire Suppression menurut media pemadamannya! 3. Sebutkan dan Jelaskan tahapan / langkah-langkah kerja dari mulai pendeteksian sampai dengan pemadaman pada Fire Suppression System! 4. Berdasarkan NFPA (National Fire Protection Association) CO2, FM-200 dan Fire Alarm System mengacu kepada NFPA berapa? 5. Dari beberapa ruangan berikut, apakah efektif jika digunakan FM-200 sebagai media Fire Suppression-nya: a. Server Room c. MCC Room e. Transformer Field b. Control Room d. Power House f. Sodium chlorate Storage 6. Sebutkan dan Jelaskan mengapa FM-200 menjadi solusi terbaik untuk Fire Suppression System? 7. Jika sebuah Ruangan Server dengan ukuran (PxLxT) 5 x 8 x 3.5 Meter (menggunakan Raised Floor 0.3 meter) ingin diproteksi dengan FM-200, sebutkan berapa banyak detector yang harus digunakan dan jumlah gas yang diperlukan. GOOD LUCK!!! 31 July, 2017, page 34
© Copyright 2026 Paperzz