buildings Article Nearly Zero Energy Buildings: An Overview of the Main Construction Features across Europe Giulia Paoletti *, Ramón Pascual Pascuas, Roberta Pernetti and Roberto Lollini EURAC Research, Institute for Renewable Energy, Viale Druso 1, 39100 Bolzano, Italy; [email protected] (R.P.P.); [email protected] (R.P.); [email protected] (R.L.) * Correspondence: [email protected]; Tel.: +39-0471-055-661 Academic Editors: Francesco Guarino and Sonia Longo Received: 28 March 2017; Accepted: 23 May 2017; Published: 31 May 2017 Abstract: Nearly Zero Energy Buildings (nZEBs) represent the backbone to achieve ambitious European goals in terms of energy efficiency and CO2 emissions reduction. As defined in the EPBD, by 31 December 2020, all of the new buildings will have to reach a target of nearly zero energy. This target encourages the adoption of innovative business models as well as the technology development in the building sector, aimed at reducing energy demand and exploiting local renewable energy sources (RES). Assessing the share of implementation and the performance of technologies in new or renovated nZEBs is strategic to identify the market trends and to define design guidelines with the most effective solutions according to the context. In this regard, this paper analyses the construction features of a set of nZEBs, collected in 17 European countries within the EU IEE ZEBRA2020 project, with a special focus on the influence of the boundary conditions on the technologies adopted. The results show a general high insulation level of the envelope and recurrent specific technologies in the Heating Ventilation Air Conditioning (HVAC) system (i.e., heat pumps and mechanical ventilation), while the climatic conditions do not drive significantly the design approach and the nZEB features. Keywords: nearly Zero Energy Buildings; construction features; technology solution sets 1. Introduction The Energy Performance of Buildings Directive (EPBD 2010/31/EU) [1] established that all of the new constructions, from 31st December 2020, will have to reach the standard nearly Zero Energy Buildings (nZEBs), which implies a large scale deployment of this kind of buildings. As defined in the art.2, a ‘nearly Zero-Energy Building’ is a building with very high-energy performance that should cover the nearly zero energy (or at least a very low amount of it) required by on site or nearby energy production from Renewable Energy Source (RES). Such qualitative definition leaves a lot of space for national interpretation and for the adoption of the quantitative indices to be considered (i.e., performance targets, amount of renewables to be integrated, CO2 emissions, etc.). Due to this reason and to specific local conditions as well as construction practice, European countries have adopted their own definition, and there are some relevant inconsistencies across Europe [2–4]. In France, for example, an nZEB has to accomplish the “RT2012” (national law), which requires a primary energy consumption lower than 60 kWh/(m2 ·year) in new residential buildings (including heating, DHW, cooling, ventilation, lighting and auxiliary systems) and variable value limits for new non-residential buildings, as lower than 110 kWh/(m2 ·year) in office buildings (including heating, DHW, cooling, ventilation, lighting and auxiliary systems). Whereas in Austria, the “OIB Directive 6” (national law) establishes that a building is an nZEB when the primary energy is less than 160 kWh/(m2 ·year) in new residential (including heating, DHW, cooling, ventilation and electric appliances) and less than 170 kWh/(m2 ·year) in non-residential (including heating, DHW, cooling, ventilation, electric appliances and lighting). On the other hand, in Italy, the “DM 20 of Buildings 2017, 7, 43; doi:10.3390/buildings7020043 www.mdpi.com/journal/buildings Buildings 2017, 7, 43 2 of 22 June 2015” (national law) defines the primary energy limits of nZEBs using a calculation process based on reference buildings and introduces a minimum rate of renewables (including heating, DHW, cooling, ventilation in residential buildings and also lighting and mobility of persons (e.g., elevator) in non-residential ones). Further than the comparative analysis of the European nZEB definitions, the project EU IEE ZEBRA2020 aims to assess the current state of transition of the building stock towards the nZEB target and to define solutions to overcome the identified market barriers. In fact, the project highlighted that, despite the technologies for nZEBs are ready and proven, the average EU rate of new nZEB construction is low and is increasing slowly, and thus targeted national countermeasures should be adopted. In this regard, the identification of best practices, performance targets, technology solution sets and the definition of design guideline represent strategic actions that can support the designers in planning new nZEBs. These issues represent the key factors to foster the uptake of nZEB across Europe; in fact, there are a large number of European projects and an extensive literature in this field. In fact, there are several papers dealing with the definition of the general effective design approach based on cost-optimal principles [5,6], and that analyzes specific technologies influencing the nZEB performances. In particular, the focus is on the envelope features [7,8], the HVAC system components [9–11] and the integration of renewable energies [12]. Nevertheless, although the large number of papers dealing with the topic, currently, the impact of the technologies as well as the final performances are evaluated or by simulation activities or by monitoring a reduced number of real buildings. Currently, an evaluation of the nZEB features and related performances based on a large sample of buildings is missing. The main reason is the lack of structured and populated databases including nZEB data across Europe. In fact, in the past recent years, several European projects dealt with the setup of building databases, that represent an important starting point for this work, but none of them is specifically focused on nZEBs. Among all, the main databases considered are: “EU IEE TABULA-EPISCOPE” [13], aimed at classifying the building stock in representative typologies, “EU H2020 ODYSSE-MURE” [14] that includes data to assess the general trends at country level and effectiveness of energy related implemented policies, “EU IEE ENTRANZE Data Tool” [15] and “EU IEE ENTRANZE Cost Tool” [16], that include detailed information on a set of buildings but are not specifically focused on nZEB. Moreover, in the report “A harmonized database to share nZEBs good practices” [17] is described the framework and the main information to be collected for setting up a database for nZEBs in the Mediterranean-climate zone; nevertheless, it is not yet populated with a significant number of buildings. Finally, it is under development the new release of the “EU Building Stock Observatory” (https://ec.europa.eu/energy/en/eubuildings), an online database that monitors the energy performance of buildings across Europe and collects the building stock characteristics, the costs and state of implementation of relevant EU Directives across the Member States. “EU Building Stock Observatory” is an online database developed for the European Commission by Building Performance Institute Europe (BPIE) in collaboration with Ecofys, Energy Research Centre of the Netherlands (ECN), Enerdata, Seven and many national partners. The next developments will be focused on building renovation and nZEB. The development of the database in EU IEE ZEBRA 2020 started from the structure and the indicators of these available tools. It is specifically focused on nZEBs, including buildings features, technical systems, passive and active solutions adopted, and it was populated with a significant number of cases that allows for carrying out analyses on the performances and on the features of nZEBs buildings across Europe. The analysis reported in this paper represents a first step for the elaboration of an nZEB design guideline, and aims to identify the recurrent technology solutions, and the related performances in the nZEB building stock across Europe. The main nZEB features were identified by analyzing the solutions Buildings 2017, 7, 43 3 of 22 implemented in nZEB, considering both residential and non-residential buildings, new and renovated ones. The analysis is conducted in 17 European countries presenting different climatic conditions, building regulations and local nZEB definitions. 2. Methodology In order to identify the nZEBs’ features, we performed an investigation in 17 European countries (Austria, Belgium, Czech Republic, Denmark, France, Germany, Italy, Lithuania, Luxemburg, Norway, Poland, Romania, Slovakia, Spain, Sweden, Netherlands and United Kingdom) on design strategies and technologies implemented on a sample of 411 residential and non-residential buildings. The analyzed buildings were identified in reports and Energy Performance Certificate (EPC) databases within the project EU IEE ZEBRA2020. In addition, the data collection was focused on buildings constructed or renovated after 2010, in order to represent the picture after the EPBD recast. Each country data elaboration was based on different sample size according to the availability of information. It is estimated that most of the collected buildings fulfill the nZEBs target as defined at national and regional level. Nevertheless, when the data collection was taking place, some countries (e.g., Germany and Spain) involved in the analysis lacked of an official nZEB definition [3,4]. In these cases, we included in the sample a set of exemplary cases of high energy-efficient constructions. European Climatic Zone Local climate conditions are defined as “the weather conditions prevailing in an area in general or over a long period” (https://en.oxforddictionaries.com/definition/climate). As the history of architecture shows, the local climatic conditions have been one of the most significant factors that influence the building features. In the last century, the technology improvement changed the design approach and the impact of the climate boundaries on the architectural features decreased; thus, the buildings present homogeneous features across Europe. Currently, the introduction of the nZEB target increased the importance of reducing the energy needs, and the ‘passive design’ according to the local climate conditions becomes a recurrent practice. The main reason is that the implementation of passive design strategies allows for taking advantage of the local energy sources and reducing the energy needs for heating or cooling, also influencing the aesthetics and the functional building features. In most of the cases, the energy performance indicators are based on climatic zones identified by external temperatures. Nevertheless, other factors like humidity, atmospheric pressure, wind, precipitation or solar radiation also play an important role in the energy needs of a building. A common standard for the classification of European climatic zones and for the consequent performance target normalization are still missing and in several studies, analysis or projects, a different classification is being used (e.g., MORE-CONNECT (http://www.more-connect.eu/the-project/concept-andapproach/), GE20 (http://geoclusters.eu/), iNSPiRe (http://inspirefp7.eu/), TABULA and EPISCOPE (http://episcope.eu/iee-project/tabula/), 4RinEU (http://www.4rineu.eu/), etc.). Moreover, each country has defined its own national climatic zone classification in relation to the specific climatic characteristics, and according to them, also the variable limits of energy performance indicators [18]. Within EU IEE ZEBRA2020 project, each nZEB included in the analysis was associated to the related Heating Degree Days (HDD) and Cooling Degree Days (CDD) using the same calculation method [18]. In order to determine the values of HDD and CDD, we assumed identical reference temperatures for all nZEBs’ location (15 ◦ C for HDD and 18.5 ◦ C for CDD), and we adopted average daily temperature values of the last 36 months (the data were gathered from http://www.degreedays.net) [2]. Nevertheless, the level of accuracy of the climatic data for describing the conditions of the selected nZEBs can be affected by the distance between the building and the nearest weather station. In fact, different case studies, although located in different microclimates areas with different environment features (e.g., altitude, slope, orientation, soil type, solar irradiation), present the same HDD and CDD, due to the lack of more detailed data. Buildings 2017, 7, x FOR PEER REVIEW 4 of 22 Buildings 2017, 7, 43 4 of 22 Buildings 2017, 7, x FOR PEER REVIEW 4 of 22 In order to classify the buildings, we adopted three winter climates (warm, mild and cold) according to HDD, as shown Figure 1. In order order to to classify classify the the buildings, buildings, we we adopted adopted three three winter winter climates climates (warm, (warm, mild mild and and cold) cold) In according to HDD, as shown Figure 1. according to HDD, as shown Figure 1. Figure 1. Classification of nZEBs by countries, according to HDD (15 °C) and CDD (18.5 °C). Definition of three winter rigidity levels (warm HDD15 < 1000; mild 1000 ≤ HDD15 < 2000 and cold ◦ C) and CDD (18.5 ◦ C). Definition Figure Classification of nZEBs by countries, according to HDDto (15 Figure 1.1. Classification of nZEBs by countries, according HDD (15 °C) and CDD (18.5 °C). HDD ≥ 2000). Note: one point can include more than one building, because one point represents a of three winter rigidity levels (warm HDD15 < 1000; mild 1000 ≤ HDD15 < 2000 and cold HDD ≥ 2000). Definition of three winter rigidity levels (warm HDD15 < 1000; mild 1000 ≤ HDD15 < 2000 and cold location. Note: one point can include more than one building, because one point represents a location. HDD ≥ 2000). Note: one point can include more than one building, because one point represents a location. It is possible to point out that the buildings located in Norway, United Kingdom, Belgium, It is possible to point out that the buildings located in Norway, United Kingdom, Belgium, Denmark and Austria present a reduced climate variability, while those in Italy and Spain have larger Denmark and Austria a reduced variability, those inUnited Italy and Spain have larger It is possible to present point out that the climate buildings located while in Norway, Kingdom, Belgium, ranges of HDD and CDD, according to the different climate zones in the countries. ranges of HDD and CDD, according to the different climate zones in the countries. Denmark and Austria present a reduced climate variability, while those in Italy and Spain have larger It is important to point out that, due to the reduced number of buildings available in the sample, It is important out that, due to thein reduced number of buildings available the ranges of HDD and CDD, according to the different climate zones in the countries. as shown in Figure to2, point the technology analysis the warm climatic zone could have a in lower sample, as shown in Figure 2, the technology analysis in the warm climatic zone could have a lower It is important to point out that, due to the reduced number of buildings available in the sample, representativeness than the analysis in the mild and cold climates. representativeness than2, the analysis in theanalysis mild andin cold as shown in Figure the technology the climates. warm climatic zone could have a lower representativeness than the analysis in the mild and cold climates. Figure 2. Share of nZEBs collected in relation to the climatic zones. Figure 2. Share of nZEBs collected in relation to the climatic zones. 3. Data Collection Figure 2. Share of nZEBs collected in relation to the climatic zones. 3. Data Collection As showed in Table 1, the analysis is based on 411 nZEBs (recently constructed or renovated) 3. Data Collection located in 17 European countries. Buildings 2017, 7, 43 5 of 22 Table 1. Number of nZEBs collected in each European country. Country Number of nZEBs Austria (AT) Belgium (BE) Czech Republic (CZ) Denmark (DK) France (FR) Germany (DE) Italy (IT) Lithuania (LT) Luxemburg (LU) Netherlands (NL) Norway (NO) Poland (PO) Romania (RO) Slovakia (SK) Spain (ES) Sweden (SE) United Kingdom (UK) Total 30 15 9 9 30 31 100 8 8 15 31 23 29 9 32 15 17 411 The collected data were deduced from EPCs, building databases and reports on energy efficiency buildings, providing information on: • • • • • • • • • • type of building: residential and non-residential; type of construction: new and renovated; year of construction or renovation; location and climate conditions (HDD and CDD); energy performance: heating demand, understood as energy need (heat to be delivered to, or extracted from, a conditioned space to maintain the intended temperature conditions during a given period of time [19]) and primary energy demand (energy that has not been subjected to any conversion or transformation process [20]) according to national standards; envelope features: thermal transmittance (U-values) and insulating materials; windows features: thermal transmittance (Uwin -value), type of glass, solar gain (g-value) and frame material; passive strategies implemented: sunshade, natural ventilation, night cooling, evaporative cooling, sunspaces, thermal mass or green roof; HVAC systems: typology of heating, cooling, Domestic Hot Water (DHW) and mechanical ventilation systems; Renewable Energy Systems (RES) installed: photovoltaic or solar thermal systems. All of the above-mentioned information for the building samples is available in the ‘Data tool nZEB buildings’, an online tool elaborated within EU IEE ZEBRA2020 project (www.zebra2020.eu), where main nZEB features are shown by use (residential and non-residential), by country and by climatic zone. 4. Data Analysis The sample is composed by 64% “residential” and 36% “non-residential” buildings, in line with the rates of the European building stock [21]. In addition, 81% of the selected nZEBs are “new buildings”, while the “renovated buildings” represent the 19%. Due to the different existing definitions and calculation approaches developed in Europe, a direct comparison among the level of global energy performance indicators cannot be performed. In particular, one of the most critical parameters is the primary energy demand, since it is calculated The sample is composed by 64% “residential” and 36% “non‐residential” buildings, in line with the rates of the European building stock [21]. In addition, 81% of the selected nZEBs are “new buildings”, while the “renovated buildings” represent the 19%. Due to the different existing definitions and calculation approaches developed in Europe, a Buildings 2017, 7, 43 6 of 22 direct comparison among the level of global energy performance indicators cannot be performed. In particular, one of the most critical parameters is the primary energy demand, since it is calculated through different energy balance methods, with different boundary conditions, primary energy through different energy balance methods, with different boundary conditions, primary energy factors, factors, CO2 equivalent emissions, and with different contributions of active and passive systems (i.e., CO2 equivalent emissions, and with different contributions of active and passive systems (i.e., heating, heating, cooling, lighting, ventilation). cooling, lighting, ventilation). Consequently, we focused the analysis on the heating demand, since the discrepancies between Consequently, we focused the analysis on the heating demand, since the discrepancies between countries in the calculation approach are reduced due to the common standard for the energy balance countries in the calculation approach are reduced due to the common standard for the energy balance calculation provided by the EN ISO 13790 [19]. calculation provided by the EN ISO 13790 [19]. Moreover, within this work, in order to reduce the inconsistencies due to the calculation method, Moreover, within this work, in order to reduce the inconsistencies due to the calculation method, we analyzed quantitative parameters calculated through EU standards (i.e., thermal transmittance), we analyzed quantitative parameters calculated through EU standards (i.e., thermal transmittance), values coming from the technical sheets (i.e., efficiency of the HVAC devices), as well as qualitative values coming from the technical sheets (i.e., efficiency of the HVAC devices), as well as qualitative data (i.e., the typology of technological systems installed). data (i.e., the typology of technological systems installed). 4.1. Heating Demand 4.1. Heating Demand The analysis on the nZEBs “heating demand” were made according their HDD and in relation The analysis on the nZEBs “heating demand” were made according their HDD and in relation to to the use of the buildings and construction typology, as shown in Figure 3. the use of the buildings and construction typology, as shown in Figure 3. (a) (b) Figure 3. Heating demand of nZEBs in relation to the use of the buildings, as well as the construction Figure 3. Heating demand of nZEBs in relation to the use of the buildings, as well as the construction type, new buildings (a) and renovated buildings (b) according to HDD (15 °C). type, new buildings (a) and renovated buildings (b) according to HDD (15 ◦ C). It can be pointed out that the coefficient of determination of the regression (R2) is very low in all It can be pointed out that the coefficient of determination of the regression (R2 ) is very low in cases (new or renovated and residential or non‐residential buildings). Accordingly, there is no all cases (new or renovated and residential or non-residential buildings). Accordingly, there is no significant relation between the nZEB heating demand and HDD and the analyzed buildings present significant relation between the nZEB heating demand and HDD and the analyzed buildings present high performance levels despite the climate conditions. Furthermore, it could be deduced that the high performance levels despite the climate conditions. Furthermore, it could be deduced that the adoption of the energy efficiency technology is not strongly affected by the climate condition, with adoption of the energy efficiency technology is not strongly affected by the climate condition, with different levels of effort in design solutions. In fact, in the 93% of the buildings, the “heating demand” different levels of effort in design solutions. In fact, in the 93% of the buildings, the “heating demand” is lower than 40 kWh/(m2∙year). is lower than 40 kWh/(m2 ·year). Going into more detail for each climatic zone, the boxplots of Figure 4 show the median value Going into more detail for each climatic zone, the boxplots of Figure 4 show the median value of of heating demand of nZEBs according to use of the building (residential and non‐residential) and heating demand of nZEBs according to use of the building (residential and non-residential) and type type of construction (new and renovated). of construction (new and renovated). It can be noticed that the median values of the heating demand tend to grow according to the HDD, for all the building typologies and uses, as shown in Figure 4. Nonetheless, in each climate rigidity, the interquartile ranges (i.e., central rectangle that includes the 50% of the “heating demand” values) of new buildings result in being more compact and lower than the renovated ones. This outcome highlights Buildings 2017, 7, x FOR PEER REVIEW 7 of 22 It can be noticed that the median values of the heating demand tend to grow according to the HDD, for all the building typologies and uses, as shown in Figure 4. Nonetheless, in each climate rigidity, the interquartile ranges (i.e., central rectangle that includes the 50% of the “heating demand” Buildings 2017, 7, 43 7 of 22 values) of new buildings result in being more compact and lower than the renovated ones. This outcome highlights the difficult implementation in existing buildings of energy efficient measures like installation of insulating materials, improvement of the airtightness, and reduction of thermal the difficult implementation in existing buildings of energy efficient measures like installation of bridges. insulating materials, improvement of the airtightness, and reduction of thermal bridges. Figure 4. Heating demand of nZEBs according to use (residential and non-residential) and type of Figure 4. Heating demand of nZEBs according to use (residential and non‐residential) and type of construction (new (new and and renovated) renovated) for for different different climate climate condition. condition. Note: Note: in in warm warm climates climates for for both both construction renovated residential and new non-residential buildings, the limits of the interquartile ranges (central renovated residential and new non‐residential buildings, the limits of the interquartile ranges (central rectangle) correspond to the only two values of Heating Demands of the collected nZEBs. rectangle) correspond to the only two values of Heating Demands of the collected nZEBs. 4.2. Features of the Thermal Envelope 4.2. Features of the Thermal Envelope The history of the architecture shows that, until the 19th century, building materials and features The history of the architecture shows that, until the 19th century, building materials and features were strictly connected to the context, typical construction techniques and climate conditions. were strictly connected to the context, typical construction techniques and climate conditions. The of the building building stock characteristics (e.g., dimensional, The analysis analysis of European the European stock characteristics (e.g., technological, dimensional, functional, performed within EU FP7‐iNSPiRE project (FP7‐iNSPiRE technological,etc.), functional, etc.), performed within EU FP7-iNSPiRE project (FP7-iNSPiRE project: project: www.inspirefp7.eu) [22], highlighted that the thermal envelope features of existing buildings change www.inspirefp7.eu) [22], highlighted that the thermal envelope features of existing buildings change according to the rigidity of the climate. In particular, the HDD strongly affect the envelope thermal according to the rigidity of the climate. In particular, the HDD strongly affect the envelope thermal transmittance: buildings located in cold winters (high value of HDD) present reduced envelope “U‐ transmittance: buildings located in cold winters (high value of HDD) present reduced envelope value” in both opaque and transparent parts, as shown in Figure 5. “U-value” in both opaque and transparent parts, as shown in Figure 5. On the contrary, as shown in Figure 6–8, the thermal transmittance of the envelope components On the contrary, as shown in Figures 6–8, the thermal transmittance of the envelope components in nZEBs result in being very similar in different climate zones. In addition, no remarkable variations in nZEBs result in being very similar in different climate zones. In addition, no remarkable variations between new or renovated and residential or non‐residential buildings can be highlighted. This result between new or renovated and residential or non-residential buildings can be highlighted. This result is 2 ·K). is the minimum requirements set legislation, by national which usually duedue to theto minimum requirements set by national whichlegislation, is usually around 0.30is W/(m 2 around 0.30 W/(m ∙K). Figure 6 shows the average nZEB thermal transmittance of the external envelope according to Figure 6 shows the average nZEB thermal transmittance of the external envelope according to HDD: Figure 6a reports U-values highlighting the use of the building (residential or non-residential), HDD: Figure 6a reports U‐values highlighting the use of the building (residential or non‐residential), while Figure 6b highlights the kind of intervention (new or renovated building). As both graphics show, while Figure 6b highlights the kind of intervention (new or renovated building). As both graphics no significant differences can be observed between the type of use and the type of the intervention. show, significant differences can ofbe wall observed between the type use and the type of the Inno general, the medium values thermal transmittance areof always very low: between 2 2 intervention. 0.12 W/(m ·K) in places with high HDD to 0.20 W/(m ·K) in zones with low HDD. In some cases, the thermal transmittance of external walls are higher than 0.35 W/(m2 ·K), most of all in buildings located in ‘warm climates’ (HDD < 1000), where the minimum requirements for U-values are less restrictive. Higher wall thermal transmittance values have been observed in renovated historic buildings or in buildings with a particular interest located in the three climate zones, where the envelope performance improvements, (i.e., installation of insulating materials), are limited due to the conservation constraints. Buildings 2017, 7, 43 Buildings 2017, 7, x FOR PEER REVIEW Buildings 2017, 7, x FOR PEER REVIEW 8 of 22 8 of 22 8 of 22 Figure 5. 5. U‐values U‐values of of external external walls walls of of the the building building stock stock before before renovation renovation in in different different European European Figure U-values of external walls of the building stock before renovation in Figure 5. different European climate areas with respect to HDD. Source: EU FP7‐iNSPiRe project. D6.5‐Position Paper on Systemic climate areas with respect to HDD. Source: EU FP7-iNSPiRe project. D6.5-Position Paper on Systemic climate areas with respect to HDD. Source: EU FP7‐iNSPiRe project. D6.5‐Position Paper on Systemic Energy Renovation [22]. Energy Renovation [22]. Energy Renovation [22]. (a) (a) (b) (b) Figure 6. (a) Thermal transmittances of walls of nZEB according to HDD, and in relation to the use of Figure 6. (a) Thermal transmittances of walls of nZEB according to HDD, and in relation to the use of Figure 6. (a) Thermal transmittances of walls of nZEB according to HDD, and in relation to the use of the buildings (residential and non‐residential); (b) type of intervention (new and renovated buildings). the buildings (residential and non‐residential); (b) type of intervention (new and renovated buildings). the buildings (residential and non-residential); (b) type of intervention (new and renovated buildings). In general, the medium values of wall thermal transmittance are always very low: between 0.12 In general, the medium values of wall thermal transmittance are always very low: between 0.12 A2 similar analysis was carried out for all the2building components (i.e., wall, roof, floor, and W/(m2∙K) ∙K) in in places places with high high HDD HDD to to 0.20 0.20 W/(m W/(m2∙K) ∙K) in in zones zones with with low low HDD. HDD. In In some some cases, cases, the the W/(m windows), as shownwith in Figure 7. 2∙K), most of all in buildings located thermal transmittance of external walls are higher than 0.35 W/(m 2 thermal transmittance of external walls are higher than 0.35 W/(m ∙K), most of all in buildings located The breakdown for the building elements confirms the general trend identified for the average in ‘warm climates’ (HDD < 1000), where the minimum requirements for U‐values are less restrictive. in ‘warm climates’ (HDD < 1000), where the minimum requirements for U‐values are less restrictive. envelope U-value; in fact, the performances of the building components present a weak correlation Higher wall thermal transmittance values have been observed in renovated historic buildings or in Higher wall thermal transmittance values have been observed in renovated historic buildings or in with the external climate conditions, as highlights by coefficient of determination (R2 ). The box plots buildings with a a particular particular interest interest located located in in the the three three climate climate zones, zones, where where the the envelope envelope buildings in Figure 8with show the interquartile ranges (central rectangle) that include the 50% of the “U-values” performance improvements, improvements, (i.e., (i.e., installation installation of of insulating insulating materials), materials), are limited limited due to to the the performance of each building components. The interquartile ranges of opaque envelopeare (walls, roofs,due and floors) conservation constraints. conservation constraints. result in being very compact, with median values ranging from 0.12 W/(m2 ·K) to 0.16 W/(m2 ·K): A similar analysis similar analysis was was carried carried out out for all for all the the building building components (i.e., components (i.e., wall, wall, roof, roof, floor, floor, and and A windows), as shown in Figure 7. •windows), as shown in Figure 7. Walls between 0.11 W/(m2 ·K) and 0.17 W/(m2 ·K) (median U at 0.14 W/(m2 ·K)); W-value • • • Roofs between 0.09 W/(m2 ·K) and 0.15 W/(m2 ·K) (median UR-value at 0.12 W/(m2 ·K)); Floors between 0.12 W/(m2 ·K) and 0.23 W/(m2 ·K) (median UF-value at 0.16 W/(m2 ·K)); Windows between 0.85 W/(m2 ·K) and 1.04 W/(m2 ·K) (median UWin-value at 0.96 W/(m2 ·K)). This analysis confirms that he thermal transmittance of the nZEBs’ components is homogeneous across the three climatic zones. Buildings 2017, 7, x FOR PEER REVIEW Buildings 2017, 7, 43 9 of 22 9 of 22 (a) (b) (c) (d) Figure 7. Thermal transmittances of walls (a); roofs (b); ground floors (c) and windows (d) of nZEB Figure 7. Thermal transmittances of walls (a); roofs (b); ground floors (c) and windows (d) of nZEB in in relation of the use of the buildings (residential and non‐residential) according to HDD. relation of the use of the buildings (residential and non-residential) according to HDD. The breakdown for the building elements confirms the general trend identified for the average envelope U‐value; in fact, the performances of the building components present a weak correlation with the external climate conditions, as highlights by coefficient of determination (R2). The box plots 2∙K) to 0.16 W/(m 2∙K): 2∙K)); result in being very compact, with median values ranging from 0.12 W/(m Walls between 0.11 W/(m2∙K) and 0.17 W/(m2∙K) (median UW‐value at 0.14 W/(m 2∙K) and 0.15 W/(m2∙K) (median UR‐value at 0.12 W/(m2∙K)); Roofs between 0.09 W/(m2∙K) and 0.17 W/(m 2∙K) (median UW‐value at 0.14 W/(m2∙K)); Walls between 0.11 W/(m 2∙K) and 0.23 W/(m2∙K) (median UF‐value at 0.16 W/(m2∙K)); Floors between 0.12 W/(m 2 Roofs between 0.09 W/(m ∙K) and 0.15 W/(m2∙K) (median UR‐value at 0.12 W/(m2∙K)); 2∙K) and 1.04 W/(m2∙K) (median UWin‐value at 0.96 W/(m2∙K)). Windows between 0.85 W/(m 2∙K) and 0.23 W/(m 2∙K) (median UF‐value at 0.16 W/(m2∙K)); Floors between 0.12 W/(m 2∙K) and 1.04 W/(m2∙K) (median UWin‐value at 0.96 W/(m2∙K)). 2017, 7, 43 Buildings Windows between 0.85 W/(m (a) 10 of 22 (b) (a) (b) Figure 8. Thermal transmittance of walls, roofs, floors (a) and windows (b). Figure 8. Thermal transmittance of walls, roofs, floors (a) and windows (b). Figure 8. Thermal transmittance of walls, roofs, floors (a) and windows (b). This analysis confirms that he thermal transmittance of the nZEBs’ components is homogeneous across the three climatic zones. This analysis confirms that he thermal transmittance of the nZEBs’ components is homogeneous Figure 9 reports the share of insulating materials of walls and roofs. It is remarkable that “EPS” is Figure 9 reports the share of insulating materials of walls and roofs. It is remarkable that “EPS” across the three climatic zones. the most common material used in walls, while “stone wool” is the preferred option for roofs. is the most common material used in walls, while “stone wool” is the preferred option for roofs. Figure 9 reports the share of insulating materials of walls and roofs. It is remarkable that “EPS” is the most common material used in walls, while “stone wool” is the preferred option for roofs. (a) (b) (a) (b) Figure 9. Share of insulating materials used in walls (a) and roofs (b). Note: the charts include the Figure 9. Share of insulating materials used in walls (a) and roofs (b). Note: the charts include the buildings according to the collected information. buildings according to the collected information. Figure 9. Share of insulating materials used in walls (a) and roofs (b). Note: the charts include the buildings according to the collected information. It can be noticed that the “EPS” is used in 30% of the building for the wall insulation walls and It can be noticed that the “EPS” is used in 30% of the building for the wall insulation walls and only for the 15% for the roofs. On the contrary, the use of “wood fiber” for roof insulation increases onlyIt can be noticed that the “EPS” is used in 30% of the building for the wall insulation walls and for the 15% for the roofs. On the contrary, the use of “wood fiber” for roof insulation increases around 10% in comparison to the wall application. only for the 15% for the roofs. On the contrary, the use of “wood fiber” for roof insulation increases around 10% in comparison to the wall application. In this regard, insulating materials with higher thermal capacity offer better performance during around 10% in comparison to the wall application. In this regard, insulating materials with higher thermal capacity offer better performance during the summer time, affecting positively the periodic thermal transmittance Y mn (W/(m2∙K)) and thermal In this regard, insulating materials with higher thermal capacity offer better performance during 2 the summer time, affecting positively the periodic thermal transmittance Ymn (W/(m ·K)) and thermal time shift (h) of the building envelope components. Although no information about these two the summer time, affecting positively the periodic thermal transmittance Y mn (W/(m2∙K)) and thermal time shift (h) of the building envelope components. Although no information about these two parameters have been collected for the nZEB sample, we investigated which materials are used in time shift (h) of the components. Although no information about are these two parameters have beenbuilding collectedenvelope for the nZEB sample, we investigated which materials used in parameters have been collected for the nZEB sample, we investigated which materials are used in 3 different climatic conditions, according to the mass (kg) and density (kg/m ) of the insulating materials. Figure 10 shows the use of low and high density insulating materials in walls and roofs according to the HDD and CDD. Buildings 2017, 7, x FOR PEER REVIEW 11 of 22 different climatic conditions, according to the mass (kg) and density (kg/m3) of the insulating materials. Figure 10 shows the use of low and high density insulating materials in walls and roofs Buildings 2017, 7, 43 11 of 22 according to the HDD and CDD. (a) (b) Figure 10. Typology of the most common insulating material used in the walls (a) and in the roofs (b) Figure 10. Typology of the most common insulating material used in the walls (a) and in the roofs of noted data nZEBs collected, in relation to the HDD and CDD and according to low and high density (b) of noted data nZEBs collected, in relation to the HDD and CDD and according to low and high of insulating materials. density of insulating materials. From a technical point of view, we expected a higher use of insulating materials with high Frommass a technical point of view, we expected a higher use of insulating with high thermal thermal in warm climates [23]. Nevertheless, the insulation adopted materials in both cold and warm mass inresults warm climates [23]. Nevertheless, adopted inno both cold andinfluences warm zones results zones in being quite homogeneous the in insulation walls and roofs, and significant of the inclimate being quite homogeneous in walls and roofs, and no significant climate conditions conditions on the insulation density can be observed. It is influences important of to the point out that the building envelopes are composed by various layers of different materials that play together a relevant on the insulation density can be observed. It is important to point out that the building envelopes are role, and, by in most of layers the cases, the higher contribution to the thermal inertia from composed various of different materials that play together a relevantcomes role, and, inmassive most of the layers (e.g., bricks, stone, etc.). Therefore, choice of an insulating seems to be more etc.). cases, the higher contribution to the thermalthe inertia comes from massivematerial layers (e.g., bricks, stone, influenced by other factors than by their performance in the cooling period. Therefore, the choice of an insulating material seems to be more influenced by other factors than by Considering the characteristics of the windows, despite the expectations, we observed that their performance in the cooling period. “triple glazing” systems are also applied on buildings located in cooling dominated climates, as Considering the characteristics of the windows, despite the expectations, we observed that “triple shown in Figure 11. glazing” systems are also applied on buildings located in cooling dominated climates, as shown in Figure 11. Buildings 2017, 7, x FOR PEER REVIEW Buildings 2017, 7, x FOR PEER REVIEW Buildings 2017, 7, 43 12 of 22 12 of 22 12 of 22 Figure 11. Typology of the most common glass typologies of windows in nZEBs collected, in relation Figure 11. Typology of the most common glass typologies of windows in nZEBs collected, in relation Figure 11. Typology of the most common glass typologies of windows in nZEBs collected, in relation to the HDD and CDD. to the HDD and CDD. to the HDD and CDD. Due to to the the lack lack of of more more specific specific information information concerning concerning the the double double glass glass coating coating (e.g., (e.g., low low Due Due to the lack of more specific information concerning the double glass coating (e.g., low emission, selective…), it is difficult to add further considerations. In fact, these glazing systems have emission, selective…), it is difficult to add further considerations. In fact, these glazing systems have emission, selective . . . ), it is difficult to add further considerations. In fact, these glazing systems similar thermal transmittance, but but different windows’ proprieties (e.g., glass emissivity) that can can similar thermal transmittance, but different windows’ proprieties (e.g., glass have similar thermal transmittance, different windows’ proprieties (e.g., glassemissivity) emissivity)that that can influence the choice of one or other glass according to the building context (orientation, dimension of influence the choice of one or other glass according to the building context (orientation, dimension of influence the choice of one or other glass according to the building context (orientation, dimension of the windows, building use, etc.). In addition, the lack of reliability of the specific data hinders a more the windows, building use, etc.). In addition, the lack of reliability of the specific data hinders a more the windows, building use, etc.). In addition, the lack of reliability of the specific data hinders a more detailed analysis. As it can be seen in Figure 12, the thermal transmittances of triple glass windows detailed analysis. As it can be seen in Figure 12, the thermal transmittances of triple glass windows detailed analysis. As it can be seen in Figure 12, the thermal transmittances of triple glass windows are clearly lower in comparison to double and low‐e glazing typologies. However, in the case of low are clearly lower in comparison to double and low‐e glazing typologies. However, in the case of low are clearly lower in comparison to double and low-e glazing typologies. However, in the case of low emission double double glasses, the median of the the thermal thermal transmittance is just slightly slightly lower than the emission double glasses, the median of transmittance just lower the emission glasses, the median of the thermal transmittance is justis slightly lower than thethan median median in the simple double glass. For this reason, it can be deduced that, during the data collection, median in the simple double glass. For this reason, it can be deduced that, during the data collection, in the simple double glass. For this reason, it can be deduced that, during the data collection, some some double‐glazing with low emissivity properties were wrongly identified as a simple double glass. some double‐glazing with low emissivity properties were wrongly identified as a simple double glass. double-glazing with low emissivity properties were wrongly identified as a simple double glass. Figure 12. Thermal transmittance according to the type of window glass. Figure 12. Thermal transmittance according to the type of window glass. Figure 12. Thermal transmittance according to the type of window glass. 4.3. Mechanical Ventilation 4.3. Mechanical Ventilation Buildings 2017, 7, 43 Buildings 2017, 7, x FOR PEER REVIEW 13 of 22 13 of 22 Buildings 2017, 7, x FOR PEER REVIEW 13 of 22 4.3. Mechanical Ventilation The use of mechanical ventilation in buildings ensure air exchange at a certain rate. It reduces the indoor carbon dioxide concertation, moisture, smoke or other possible contaminants. In addition, The use of mechanical ventilation in buildings ensure air exchange at a certain rate. It reduces The use of mechanical ventilation in buildings ensure air exchange at a certain rate. It reduces the the air‐movement improves the comfort of the occupants. the indoor carbon dioxide concertation, moisture, smoke or other possible contaminants. In addition, indoor carbon dioxide concertation, moisture, smoke or other possible contaminants. In addition, the From the improves results of the the comfort analysis, be noticed that mechanical ventilation is a recurrent the air‐movement improves the comfort of the occupants. air-movement of it thecan occupants. technical solution in new and renovated nZEBs (share of 89%), as shown in Figure 13. This technology From the the results results of of the the analysis, analysis, it it can can be be noticed noticed that that mechanical mechanical ventilation ventilation is recurrent From is aa recurrent is used without any relevant difference in warm, mild and cold climates. Only in 11% of the selected technical solution in new and renovated nZEBs (share of 89%), as shown in Figure 13. This technology technical solution in new and renovated nZEBs (share of 89%), as shown in Figure 13. This technology nZEBs, the data any information was not declared not and defined during the data collection, for this is used without any relevant difference in warm, mild and cold climates. Only in 11% of the selected is used without relevant difference in warm,or mild cold climates. Only in 11% of the selected reason in these cases the results are defined as “unknown”. nZEBs, the data information was not declared or not defined during the data collection, this nZEBs, the data information was not declared or not defined during the data collection, for thisfor reason reason in these cases the results are defined as “unknown”. in these cases the results are defined as “unknown”. Figure 13. Mechanical ventilation systems declared. Figure 13. Mechanical ventilation systems declared. Figure 13. Mechanical ventilation systems declared. In order to reduce the increasing heating and cooling demands due to the replacement of the indoor air with the outside air, most of the mechanical ventilation systems include heat recovery. In order to reduce the increasing heating and cooling demands due to the replacement of the In order to reduce the increasing heating and cooling demands due to the replacement of the These permit recovering heat or cold from the outgoing air to pre‐heat or pre‐cool the indoor systems air most of indoor air with with the the outside air, outside air, most of the the mechanical mechanical ventilation ventilation systems systems include include heat heat recovery. recovery. incoming fresh air. The high efficiencies of the heat recovery systems (over 80%), as declared in data These systems systems permit permit recovering heat or cold the outgoing air to pre‐heat or the pre‐cool the These recovering heat or cold fromfrom the outgoing air to pre-heat or pre-cool incoming collected, make their use very frequent in ventilation systems in new and renovated buildings, and incoming fresh air. The high efficiencies of the heat recovery systems (over 80%), as declared in data fresh air. The high efficiencies of the heat recovery systems (over 80%), as declared in data collected, make they are commonly used (84%), as the Figure 13. This is also in line with the results of the survey collected, make their use very frequent in ventilation systems in new and renovated buildings, and their use very frequent in ventilation systems in new and renovated buildings, and they are commonly carried out within EU IEE ZEBRA2020 project to building professionals, in which 92% of the they are commonly used (84%), as the Figure 13. This is also in line with the results of the survey used (84%), as the Figure 13. This is also in line with the results of the survey carried out within EU IEE respondents adopt “sometimes” or “often” heat recovery systems in ventilation when constructing carried out project within to EU IEE ZEBRA2020 project to building professionals, which 92% of the ZEBRA2020 building professionals, in which 92% of the respondents in adopt “sometimes” or high‐energy efficient buildings [2]. respondents adopt “sometimes” or “often” heat recovery systems in ventilation when constructing “often” heat recovery systems in ventilation when constructing high-energy efficient buildings [2]. high‐energy efficient buildings [2]. 4.4. Heating System 4.4. Heating System 4.4. Heating System Concerning the different boiler configurations (i.e., combined and separate generation of heating Concerning the different boiler configurations (i.e., combined and separate generation of heating and DHW), around 60% of analyzed nZEBs use one single system for both needs (heating + DHW). Concerning the different boiler configurations (i.e., combined and separate generation of heating and DHW), around 60% of analyzed nZEBs use one single system for both needs (heating + DHW). On the other hand, 26% use separated thermal systems for heating and DHW, and, for the rest of the and DHW), around 60% of analyzed nZEBs use one single system for both needs (heating + DHW). On the other hand, 26% use separated thermal systems for heating and DHW, and, for the rest of the sample (14%), there is no information about the used systems (i.e., unknown), as shown in Figure 14. On the other hand, 26% use separated thermal systems for heating and DHW, and, for the rest of the sample (14%), there is no information about the used systems (i.e., unknown), as shown in Figure 14. sample (14%), there is no information about the used systems (i.e., unknown), as shown in Figure 14. Figure 14. Heating and DHW systems used in nZEBs collected. Figure 14. Heating and DHW systems used in nZEBs collected. Figure 14. Heating and DHW systems used in nZEBs collected. Buildings 2017, 7, 43 Buildings 2017, 7, x FOR PEER REVIEW Buildings 2017, 7, x FOR PEER REVIEW 14 of 22 14 of 22 14 of 22 The most commonly used used system system to to produce heating and DHW is the the the “heat pump”, with with a The most commonly used system DHW is “heat pump”, with a The most commonly to produce produceheating heatingand and DHW is “heat pump”, presence of 32%, followed by “boiler” (23%) and “district heating” (14%), as shown in Figure 15. presence of 32%, followed by “boiler” (23%) and “district heating” (14%), as shown in Figure 15. a presence of 32%, followed by “boiler” (23%) and “district heating” (14%), as shown in Figure 15. Figure 15. Share of systems to produce heating and DHW in the selected nZEBs. Figure 15. Share of systems to produce heating and DHW in the selected nZEBs. Figure 15. Share of systems to produce heating and DHW in the selected nZEBs. Figure 16 shows the share of the most used heating systems according to the climatic zone. Figure 16 shows the share of the most used heating systems according to the climatic zone. The Figure 16 shows the share of the most used heating systems according to the climatic zone. The reduced number of buildings in the sample could affect the representativeness of the technologies The reduced number of buildings in the sample could affect the representativeness of the technologies reduced number of buildings in the sample could affect the representativeness of the technologies used for the warm climates. Nevertheless, Figure 16 reports the share of heating systems of the three used for the warm climates. Nevertheless, Figure 16 reports the share of heating systems of the three used for the warm climates. Nevertheless, Figure 16 reports the share of heating systems of the three climatic zones. The “heat “heat pump” pump” is is the the most most used used technology, technology, with a alower lower penetration in in a cold cold climatic zones. The “heat pump” is the most in a climatic zones. The used technology,with witha lowerpenetration penetration a cold climatic zone (31%). This technology is widely adopted in warm‐mild climates (42%), since it allow climatic zone (31%). This technology is widely adopted in warm‐mild climates (42%), since it allow climatic zone (31%). This technology is widely adopted in warm-mild climates (42%), since it allow for for achieving high performance levels with mild external temperature, and it is commonly used to for achieving high performance levels with mild external temperature, and it is commonly used to achieving high performance levels with mild external temperature, and it is commonly used to also also satisfy the cooling needs in summer periods. also satisfy the cooling needs in summer periods. satisfy the cooling needs in summer periods. Figure 16. Share of heating systems according to climatic zones. Figure 16. Share of heating systems according to climatic zones. Figure 16. Share of heating systems according to climatic zones. The survey implemented within EU IEE ZEBRA2020 project to building professionals confirmed The survey implemented within EU IEE ZEBRA2020 project to building professionals confirmed The survey implemented within EU IEE ZEBRA2020 project to building professionals confirmed that “heat pumps” and “condensing boilers” are the most used heating systems, as shown in Figure 17. that “heat pumps” and “condensing boilers” are the most used heating systems, as shown in Figure that “heat pumps” and “condensing boilers” are the most used heating systems, as shown in Figure 17. 17. Buildings 2017, 7, 43 Buildings 2017, 7, x FOR PEER REVIEW Buildings 2017, 7, x FOR PEER REVIEW 15 of 22 15 of 22 15 of 22 Figure 17. Percentage of active solutions used Source: survey implemented to building Figure in nZEBs. Figure 17. 17. Percentage Percentage of of active active solutions solutions used used in in nZEBs. nZEBs. Source: Source: survey survey implemented implemented to to building building professionals [2]. professionals [2]. professionals [2]. By analyzing the technology adopted during the last years, the trends for the heating systems in By analyzing the technology adopted during the last years, the trends for the heating systems in By analyzing the technology adopted during the last years, the trends for the heating systems in different climates highlight a constant use of heat pump systems in mild climates, and a reduction of different climates highlight a constant use of heat pump systems in mild climates, and a reduction of different climates highlight a constant use of heat pump systems in mild climates, and a reduction a boiler system with an increment of stove systems (Figure 18). In addition, it can be noticed that a boiler system with an increment of stove systems (Figure 18). In addition, it can be noticed that of a boiler system with an increment of stove systems (Figure 18). In addition, it can be noticed that “district heating” is very common in cold climates (normally in North and East Europe), probably “district heating” is very common in cold climates (normally in North and East Europe), probably “district heating” is very common in cold climates (normally in North and East Europe), probably because of the longer period, thus investing in this type of infrastructure is more profitable [24,25]. because of the longer period, thus investing in this type of infrastructure is more profitable [24,25]. because of the longer period, thus investing in this type of infrastructure is more profitable [24,25]. Nevertheless, political reasons and national strategies could be also behind the high use of district Nevertheless, political reasons and national strategies could be also behind the high use of district Nevertheless, political reasons and national strategies could be also behind the high use of district heating in these countries. heating in these countries. heating in these countries. Figure 18. Heating systems technologies trend according to climatic zones. Note: the heating systems Figure 18. Heating systems technologies trend according to climatic zones. Note: the heating systems Figure 18. Heating systems technologies trend according to climatic zones. Note: the heating systems technology trend in warm climates has too few nZEBs to be presented. technology trend in warm climates has too few nZEBs to be presented. technology trend in warm climates has too few nZEBs to be presented. The energy carriers used by thermal systems in the collected buildings can be gathered in four The energy carriers used by thermal systems in the collected buildings can be gathered in four The energy carriers used by thermal systems in the collected buildings can be gathered in four groups: “natural gas”, “district heating”, “electricity” and “RES” (e.g., firewood, wood pellets, wood groups: “natural gas”, “district heating”, “electricity” and “RES” (e.g., firewood, wood pellets, wood groups: “natural gas”, “district heating”, “electricity” and “RES” (e.g., firewood, wood pellets, wood chips, solar thermal . . . ), as shown in Figure 19. chips, solar thermal…), as shown in Figure 19. chips, solar thermal…), as shown in Figure 19. Electricity is the most used source for thermal systems (share of 28%) such as air, water, soil heat Electricity is the most used source for thermal systems (share of 28%) such as air, water, soil heat Electricity is the most used source for thermal systems (share of 28%) such as air, water, soil heat pumps and direct electric technologies. pumps and direct electric technologies. pumps and direct electric technologies. Buildings 2017, 7, 43 Buildings 2017, 7, x FOR PEER REVIEW Buildings 2017, 7, x FOR PEER REVIEW 16 of 22 16 of 22 16 of 22 Figure 19. Share of energy carriers used by thermal plants. Figure 19. Share of energy carriers used by thermal plants. Figure 19. Share of energy carriers used by thermal plants. 4.5. Cooling System 4.5. Cooling System 4.5. Cooling System As previously said, the cooling needs to depend on several aspects like external climate As previously said, said, the the cooling cooling needs needs to to depend depend on on several several aspects aspects like like external external climate climate As previously conditions, use of the building (use profile, internal gains, etc.), building construction features (such conditions, use of the building (use profile, internal gains, etc.), building construction features (such conditions, use of the building (use profile, internal gains, etc.), building construction features (such as as window‐to‐wall ratio, etc.) and shading system, among others. as window‐to‐wall ratio, etc.) and shading system, among others. window-to-wall ratio, etc.) and shading system, among others. In addition, 25% of the selected nZEBs use a cooling system, divided between residential (46.5%) In addition, 25% of the selected nZEBs use a cooling system, divided between residential (46.5%) and non‐residential The box plot diagrams in system, Figure 20 shows the CDD values of the In addition, 25% of(53.5%). the selected nZEBs use a cooling divided between residential (46.5%) and non‐residential (53.5%). The box plot diagrams in Figure 20 shows the CDD values of the locations where the cooling system is installed both for residential and non‐residential buildings in and non-residential (53.5%). The box plot diagrams in Figure 20 shows the CDD values of the locations locations where the cooling system is installed both for residential and non‐residential buildings in the sample. where the cooling system is installed both for residential and non-residential buildings in the sample. the sample. Figure 20. Distribution of CDD of residential and non-residential buildings with cooling systems. Figure 20. Distribution of CDD of residential and non‐residential buildings with cooling systems. In In 75% of the residential buildings collected, the CDD results are equal to or higher than 510 CDD, while, 75% of the residential buildings collected, the CDD results are equal to or higher than 510 CDD, in the non‐residential buildings, results are equal to or higher than 240 CDD. Figure 20. Distribution of CDD of residential and non‐residential buildings with cooling systems. In while, in the non-residential buildings, results are equal to or higher than 240 CDD. 75% of the residential buildings collected, the CDD results are equal to or higher than 510 CDD, while, The results showed in Figure 20 highlights in most the cases (75%—first quartile), a in the non‐residential buildings, results are equal to or higher than 240 CDD. The results showed in Figure 20 highlights that,that, in most of theof cases (75%—first quartile), a cooling cooling system in new nZEB is installed if the CDD are higher than 238 for non‐residential buildings system in new nZEB is installed if the CDD are higher than 238 for non-residential buildings and for and for CDD higher than 507 for residential buildings. The results in Figure 20 highlights that, in most of the cases (75%—first quartile), a CDD higher thanshowed 507 for residential buildings. This difference confirms that the cooling energy consumption in non‐residential buildings is cooling system in new nZEB is installed if the CDD are higher than 238 for non‐residential buildings This difference confirms that the cooling energy consumption in non-residential buildings is higher than in residential ones [26]. In fact, non‐residential buildings have higher internal loads due and for CDD higher than 507 for residential buildings. higher than in residential ones [26]. In fact, non-residential buildings have higher internal loads due to to the considerable use of appliances and lighting [27], and they are mainly occupied during daytime This difference that and the cooling consumption in non‐residential buildings is the considerable use confirms of appliances lightingenergy [27], and they are mainly occupied during daytime hours, i.e., when the radiation and temperatures are higher. Missed information, like wall‐window higher than in residential ones [26]. In fact, non‐residential buildings have higher internal loads due hours, i.e., when the radiation and temperatures are higher. Missed information, like wall-window ratio (WWR) or orientation, reduce the possibility to go deeply in the nZEB features’ analysis of their to the considerable use of appliances and lighting [27], and they are mainly occupied during daytime ratio (WWR) influence. or orientation, reduce the possibility to go deeply in the nZEB features’ analysis of hours, i.e., when the radiation and temperatures are higher. Missed information, like wall‐window their influence. ratio (WWR) or orientation, reduce the possibility to go deeply in the nZEB features’ analysis of their influence. Buildings 2017, 7, 43 Buildings 2017, 7, x FOR PEER REVIEW 17 of 22 17 of 22 The most used cooling systems are “heat pumps” with a share of 75% and in particular the “heat The most used cooling systems are “heat pumps” with a share of 75% and in particular the “heat pumps using the outside air as heat source” (share of 13%), as shown in Figure 21. The advantages pumps using the outside air as heat source” (share of 13%), as shown in Figure 21. The advantages originated from this kind of technology, such as the satisfaction of the heating and cooling demands, originated from this kind of technology, such as the satisfaction of the heating and cooling demands, the the energy low energy costs the environmental friendliness of this system (for the reduced carbon low costs and theand environmental friendliness of this system (for the reduced carbon emissions), emissions), foster their implementation in nZEBs. foster their implementation in nZEBs. Figure 21. Share of cooling system typologies used in selected nZEBs (a total of 101 buildings with Figure 21. Share of cooling system typologies used in selected nZEBs (a total of 101 buildings with cooling systems). cooling systems). 4.6. Passive Solutions 4.6. Passive Solutions Passive Passive solutions solutions in in buildings buildings are are climate-based climate‐based design design measures measures used used to to reduce reduce the the energy energy demand of the building by exploiting the natural resources available in the context (e.g., daylighting, demand of the building by exploiting the natural resources available in the context (e.g., daylighting, natural ventilation, night cooling, etc.). natural ventilation, night cooling, etc.). The use of these strategies result in being very important in high-energy efficient buildings, as their The use of these strategies result in being very important in high‐energy efficient buildings, as implementation can produce an important decreasedecrease of the energy demand. potential their implementation can produce an important of the energy This demand. This reduction potential depends on the set of passive solutions applied and on the climate context. In cold climates, highly reduction depends on the set of passive solutions applied and on the climate context. In cold climates, insulated and airtight have to face high risk [28], which bewhich significantly highly insulated and buildings airtight buildings have to overheating face high overheating risk can [28], can be reduced by means of natural ventilation [29]. In warm climates, a reduction of internal and solar loads significantly reduced by means of natural ventilation [29]. In warm climates, a reduction of internal implies energy savings due to a reduction in the utilization of air conditioning. and solar loads implies energy savings due to a reduction in the utilization of air conditioning. In this regard, the lack of information concerning the usage of passive strategies in the collected In this regard, the lack of information concerning the usage of passive strategies in the collected nZEBs is a weak point of this investigation. From one side, the missing data depend on the lack of nZEBs is a weak point of this investigation. From one side, the missing data depend on the lack of answers due to the answers due to the open open questions questions used used to to outline outline the the passive passive solutions. solutions. On On the the other other side, side, some some passive are mandatory in some countries, suchsuch as shading systems or green hence, passive strategies strategies are mandatory in some countries, as shading systems or roofs, green and, roofs, and, they could not be identified as additional passive solutions in the data sources. Although the high hence, they could not be identified as additional passive solutions in the data sources. Although the importance for the reduction of the energy demand, only 36% of the collected buildings (150 nZBEs) high importance for the reduction of the energy demand, only 36% of the collected buildings (150 declared the use of passive strategies, as shown in Figure 22. nZBEs) declared the use of passive strategies, as shown in Figure 22. Nevertheless, we can also deduce significant results from the reduced sample: in particular, the most mentioned passive strategies are the sunshade (80%), natural ventilation (63%), night cooling (59%) and thermal mass (57%). Buildings 2017, 7, x FOR PEER REVIEW 18 of 22 Buildings 2017, 7, 43 Buildings 2017, 7, x FOR PEER REVIEW 18 of 22 18 of 22 Figure 22. Share of known passive strategies used in nZEBs. Nevertheless, we can also deduce significant results from the reduced sample: in particular, the most mentioned passive strategies are the sunshade (80%), natural ventilation (63%), night cooling (59%) and thermal mass (57%). Figure 22. Share of known passive strategies used in nZEBs. Figure 22. Share of known passive strategies used in nZEBs. 4.7. Renewable Energy 4.7. Renewable Energy Nevertheless, we can also deduce significant results from the reduced sample: in particular, the In this part, the RE production systems were analyzed. In particular, the focus of the most mentioned passive strategies are the sunshade (80%), natural ventilation (63%), night cooling In this part, the RE production systems were analyzed. In particular, the focus of the investigation investigation was on Solar Thermal (ST) and Photovoltaic (PV) Systems installed. (59%) and thermal mass (57%). was on Solar Thermal (ST) and Photovoltaic (PV) Systems installed. It is apparent that the integration of renewables is crucial in an nZEB; in fact, it occurs in 81% of It is apparent that the integration of renewables is crucial in an nZEB; in fact, it occurs in 81% of 4.7. Renewable Energy the cases in the sample, since most of the national definitions require a minimum amount of energy the cases in the sample, since most of the national definitions require a minimum amount of energy produced from RES according to the indications of the EPBD. In particular, the installation of PV In this part, RE production systems of were In particular, the focus of the produced from RESthe according to the indications the analyzed. EPBD. In particular, the installation of PV accounts for 29% of the sample, and ST systems is around 28%, as shown in Error! Reference source investigation was on Solar Thermal (ST) and Photovoltaic (PV) Systems installed. accounts for 29% of the sample, and ST systems is around 28%, as shown in Figure 23. Finally, the 24% not found.. Finally, the 24% of nZEBs collected uses both systems (PV and ST systems), while, in 19% It is apparent that the integration of renewables is crucial in an nZEB; in fact, it occurs in 81% of of nZEBs collected uses both systems (PV and ST systems), while, in 19% of the cases, the detailed of the cases, the detailed information is missed. the cases in the sample, since most of the national definitions require a minimum amount of energy information is missed. produced from RES according to the indications of the EPBD. In particular, the installation of PV accounts for 29% of the sample, and ST systems is around 28%, as shown in Error! Reference source not found.. Finally, the 24% of nZEBs collected uses both systems (PV and ST systems), while, in 19% of the cases, the detailed information is missed. Figure 23. Share of installation of PV and solar thermal systems. Figure 23. Share of installation of PV and solar thermal systems. Error! 24 Reference not the share of exploitation different technologies RES Figure presents source the share of found. differentpresents technologies for RES in the three for defined exploitation in the three defined climatic zones. It is possible to underline a reduced integration of climatic zones. It is possible to underline a reduced integration of PV and ST in nZEBs located in PV and ST in nZEBs located in cold climates zone than in mild climates (44% vs. 60%), mainly due to cold climates zone than in mild climates (44% vs. 60%), mainly due to less sunlight availability in Figure 23. Share of installation of PV and solar thermal systems. less sunlight availability in higher latitudes. In particular, the cold climate zone does not higher latitudes. In particular, while the cold climate zone doeswhile not present a significant wide diffusion present a significant wide diffusion of a specific technology, the mild climate zone shows a high share of a specific technology,source the mild climate zone shows the a high share photovoltaic system installed Error! Reference not found. presents share of ofdifferent technologies for RES of photovoltaic system installed with (45% considering plants coupled with ST). Finally, the in number the warm (45% considering plants coupled ST). Finally, in the warm climate zone, although of exploitation in the three defined climatic zones. It is possible to underline a reduced integration of buildings in the sample reduced and the representativeness of the sample is lower, a higher share of PV and ST in nZEBs located in cold climates zone than in mild climates (44% vs. 60%), mainly due to nZEBs with STavailability is observedin (41% considering plants coupled with PV). less sunlight higher latitudes. In particular, while the cold climate zone does not present a significant wide diffusion of a specific technology, the mild climate zone shows a high share of photovoltaic system installed (45% considering plants coupled with ST). Finally, in the warm Buildings 2017, 7, x FOR PEER REVIEW Buildings 2017, 7, x FOR PEER REVIEW 19 of 22 19 of 22 climate zone, although the number of buildings in the sample reduced and the representativeness of climate zone, although the number of buildings in the sample reduced and the representativeness of the sample is lower, a higher share of nZEBs with ST is observed (41% considering plants coupled the sample is lower, a higher share of nZEBs with ST is observed (41% considering plants coupled Buildings 2017, 7, 43 19 of 22 with PV). with PV). Figure 24. Share of PV and ST systems installed according to climatic zones. Figure 24. Share of PV and ST systems installed according to climatic zones. Figure 24. Share of PV and ST systems installed according to climatic zones. Figure 25 shows the share of buildings with one or more renewable energy systems installed, also Figure 25 shows the share of buildings with one or more renewable energy systems installed, Figure 25 shows the share of buildings with one or more renewable energy systems installed, also including the heat pumps in the considered technologies. also including the heat pumps in the considered technologies. including the heat pumps in the considered technologies. Figure 25. Share of renewable energy systems installed (heat pumps, PV and ST) in the nZEBs analyzed. Figure 25. 25. Share Share of of renewable renewable energy energy systems systems installed installed (heat (heat pumps, pumps, PV PV and and ST) ST) in in the the nZEBs nZEBs Figure analyzed. analyzed. It is important also to point out that, for cold climates, six percent of the buildings (26 buildings) It is important also to point out that, for cold climates, six percent of the buildings (26 buildings) It is important also to point out that, for cold climates, six percent of the buildings (26 buildings) declared no renewable energy system (heat pumps, PV or ST) installed. This share results in being declared no renewable energy system (heat pumps, PV or ST) installed. This share results in being declared no renewable energy system (heat pumps, PV or ST) installed. This share results in being very low in relation to the previous outcome of Figure 24, where 41% of cases declared no PV or ST very low in relation to the previous outcome of Error! Reference source not found., where 41% of very low in relation to the previous outcome of Error! Reference source not found., where 41% of systems installed. This information further highlights the large use of heat pumps in cold climates. cases declared no PV or ST systems installed. This information further highlights the large use of heat cases declared no PV or ST systems installed. This information further highlights the large use of heat Similar considerations are valuable also for mild and warm climates. The thermal system used in all pumps in cold climates. Similar considerations are valuable also for mild and warm climates. The pumps in cold climates. Similar considerations are valuable also for mild and warm climates. The these buildings for heating and DHW are traditional or condensing boiler fuelled mainly by natural thermal system used in all these buildings for heating and DHW are traditional or condensing boiler gasthermal system used in all these buildings for heating and DHW are traditional or condensing boiler (96%) and direct electric technologies (4%), without any photovoltaic, thermal panels, heat pumps fuelled mainly by natural gas (96%) and direct electric technologies (4%), without any photovoltaic, or fuelled mainly by natural gas (96%) and direct electric technologies (4%), without any photovoltaic, other bio-fuel system installed. Furthermore, these buildings are located in mild-cold climates where heating during the winter is necessary. The lack of use of renewable energy systems in some nZEBs is mainly due to the construction period of these buildings, since, in some cases, they were built before the EPBD implementation at the national level, and due to the lack of information during the data collection. Buildings 2017, 7, 43 20 of 22 5. Conclusions This paper aims to identify the main technologies adopted across Europe in the construction as well as in the renovation of buildings towards the target nZEBs. In particular, we evaluated to which extent the adoption of the technologies is influenced by the climate conditions. The analysis was based on a sample of 411 representative European high energy performance buildings (new and renovated, residential and non-residential) mainly located in mild-cold climates, whose features have been collected within the EU IEE ZEBRA2020 project. As a general outcome, we can deduce that the climate conditions do not represent the main parameter affecting the definition of the technology package to achieve the nZEB target. Nevertheless, we can highlight that the availability of natural sources in the zones (i.e., solar irradiation) affects the use of renewable technologies. In fact, we observed a reduced share of PV and ST in cold climates and an increased share in mild and warm climates, due to the higher irradiation and production potential that enhance the cost-effectiveness of the technologies. This result was confirmed by the survey to building professionals carried out within EU IEE ZEBRA2020 project [2]. In fact, only 3.5% of the respondents selected “the adaptability to climatic context” as an important criteria for adopting a specific technology, while the “investment costs” (27%), “energy performance” (16%) and “operational cost” (14%) were the preferred ones. The heating demand analysis shows that energy efficiency technological solutions are selected independently to the climate condition. The heating demand values of the buildings are similar in all climates, as well as the thermal transmittance of the envelope components (both transparent and opaque). This is mainly influenced by the similar national envelope minimum requirements defined across Europe. Moreover, the HDD and CDD do not even influence so strongly the choice of the insulating materials and their associated properties (high or low thermal inertia). Concerning the active solutions, the recurrent technologies are the mechanical ventilation, with a share of 89% in the sample and a high penetration of heat recovery systems (able to supply heating, DHW and cooling demand). In cold climate zones, the district heating systems is widely used, accounting for 25%. Within the analyzed sample, the cooling system is installed in 25% of the buildings, and we identified the thresholds for the installation of such systems around 240 CDD for non-residential buildings, and 510 CDD for residential ones. As a general remark, it is important to point out that the building data collection was carried out from EPCs, building databases and reports on energy efficiency buildings. The size of the analyzed buildings sample is relatively small (411 buildings) due to the reduced amount of available data, and the lack of existing nZEB information; moreover, it has different levels of accuracy as a result of the heterogeneous collection process (EPCs, building databases and reports on energy efficiency buildings). In some cases, the limited level of detail of the data reduced the possibilities to investigate deeply the technology market penetration and its relation to the climate conditions. Moreover, one of the most critical issues across Europe is the heterogeneous calculation approach for the energy performance indicators. The EPBD introduced the general nZEB concept to the European Member States, while national and regional regulations defined tailored calculation methods and targets in terms of both primary energy and share of renewable energy. This means that performance indicators are evaluated with different calculation methods, boundary conditions (i.e., base internal temperature), and conversion factors. At the European level, more efforts should be made to harmonize the calculation methods and the boundary conditions, and to make building energy consumption data available. Moreover, an open accessible European EPC cadaster, also including construction costs and actual energy consumption data, would represent a strategic tool to define the nZEB learning curve, assess the relative rate of penetration in the building stock, and give meaningful information to manage decision process of relevant stakeholders (developers, designers, builders, and manufacturers). Further analysis should be performed increasing the number of case studies, especially in warm climates, and investing more efforts during the data collection phase, raising the detail level and Buildings 2017, 7, 43 21 of 22 taking into account the local specificities, as well as the minimum requirements provided by law and incentives as the main drivers for the technologies. Future studies should include the analysis of the costs and the influence on the adoption of the technologies, also considering that the nZEB requirements should be set according to cost-optimal levels and Life Cycle Assessment (LCA) as requested in the EPBD recast. Nevertheless, this work is a pioneering study on European nZEB stock and the results of the analysis present an overview of the main technologies adopted in new and renovated nZEBs in Europe, and represent an important step for the definition of design guidelines with the most effective solutions. Furthermore, the identification of the most used technology solutions in relation to the climate condition should be used from building manufactories in order to identify the building market needs and address the efforts. Acknowledgments: This work was supported by EU IEE ZEBRA2020 project that has financed the investigation. We thank to the efforts invested by the EU IEE ZEBRA2020 project partners, especially to the project coordinator Raphael Bointner, who recently passed away, and to our colleagues Annamaria Belleri, Giuseppe De Michele and Sofia Rioli for the feedback during the works. Author Contributions: Ramón Pascual Pascuas contributed with the collection of nZEBs data, Giulia Paoletti carried out the analysis concept, and together interpreted the data and wrote the paper. Roberta Pernetti supervised the data analysis and composition of the paper. Roberto Lollini revised the article. Conflicts of Interest: The authors declare no conflict of interest. References 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. Recast, E.P.B.D. Directive 2010/31/EU of the European Parliament and of the Council of 19 May 2010 on the energy performance of buildings (recast). Off. J. Eur. Union 2010, 18, 21. Pascual, R.; Paoletti, G. Deliverable 5.1: Nearly Zero-Energy Building (nZEB) Technology Solutions, Cost Assessment and Performance. Available online: http://zebra2020.eu/publications/nzeb-technologysolutions-cost-assessment-and-performance/ (accessed on 16 February 2017). D’Agostino, D.; Zangheri, P. Development of the NZEBs Concept in Member States. Towards Nearly Zero Energy Buildings in Europe; Publications Office of the European Union: Luxembourg, 2016. D’Agostino, D. Assessment of the progress towards the establishment of definitions of nearly Zero Energy Buildings (nZEBs) in European Member States. J. Build. Eng. 2015, 1, 20–30. [CrossRef] Becchio, C.; Bottero, M.C.; Corgnati, S.P.; Ghiglione, C. nZEB design: Challenging between energy and economic targets. Energy Procedia 2015, 78, 2070–2075. [CrossRef] Buonomano, A.; Montanaro, U.; Palombo, A.; Vicidomini, M. NZEBs in Mediterranean climates: Energy design and optimization for a non-residential building. Energy Procedia 2015, 82, 458–464. [CrossRef] Charisi, S. The role of the building envelope in achieving nearly-zero energy buildings (nZEBs). Procedia Environ. Sci. 2017, 38, 115–120. Loukaidou, K.; Michopoulos, A.; Zachariadis, T. Nearly-zero energy buildings: Cost-optimal analysis of building envelope characteristics. Procedia Environ. Sci. 2017, 38, 20–27. [CrossRef] Guillén-Lambea, S.; Rodríguez-Soria, B.; Marín, J.M. Control strategies for energy recovery ventilators in the South of Europe for residential nZEB—Quantitative analysis of the air conditioning demand. Energy Build. 2017, 146, 271–282. [CrossRef] Ascione, F.; D’Agostino, D.; Marino, C.; Minichiello, F. Earth-to-air heat exchanger for NZEB in Mediterranean climate. Renew. Energy 2016, 99, 553–563. [CrossRef] Mohamed, A.; Hasan, A.; Sirén, K. Fulfillment of net-zero energy building (NZEB) with four metrics in a single family house with different heating alternatives. Appl. Energy 2014, 114, 385–399. [CrossRef] Garde, F.; Ayoub, J.; Aelenei, D.; Aelenei, L.; Scongnamiglio, A. Solution Sets for Net Zero Energy Buildings: Feedback from 30 Net ZEBs Worldwide; Ernst & Sohn: A Wiley Brand: Berlin, Germany, 2017; ISBN 978-3-433-03072-1. EU IEE TABULA-EPISCOPE Project. Available online: http://www.episcope.eu/iee-project/tabula/ (accessed on 20 April 2017). Buildings 2017, 7, 43 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 22 of 22 EU H2020 ODYSSE-MURE. Available online: http://www.indicators.odyssee-mure.eu/ (accessed on 20 April 2017). EU IEE ENTRANZE Data Tool. Available online: http://www.entranze.eu/tools/interactive-data-tool (accessed on 9 February 2017). EU IEE ENTRANZE Cost Tool. Available online: http://www.entranze.eu/tools/cost-tool (accessed on 20 April 2017). Becchio, C.; Guala, C.; Orlieti, L. A harmonized database to share nZEBs good practices. Rehva J. 2015, 52, 12–16. Tsikaloudaki, K.; Laskos, K.; Bikas, D. On the Establishment of Climatic Zones in Europe with regard to the Energy Performance of Buildings. Energies 2011, 5, 32–44. [CrossRef] EN ISO 13790: Energy Performance of Buildings—Calculation of Energy Use for Space Heating and Cooling; International Organization for Standardization: Milan, Italy, 2008. UNI CEN/TR 15615:2008 Explanation of the General Relationship between Various European Standards and the Energy Performance of Buildings Directive (EPBD)—Umbrella Document. Available online: http://deep.iclei-europe.org/fileadmin/user_upload/Procurement/DEEP/Project_Results/DEEP_ WPIII_report_-_annex_01.pdf (accessed on 17 February 2017). Laustsen, J.; Ruyssevelt, P.; Staniaszek, D.; Strong, D.; Zinetti, S. Europe’s Building under the Microscope; Buildings Performance Institute Europe (BPIE): Brussels, Belgium, 2011; ISBN 978949114301. Fedrizzi, R.; Dipasquale, C.; Bellini, A. D6.5—Position Paper on Systemic Energy Renovation. Available online: http://inspirefp7.eu/wp-content/uploads/2017/01/WP6_D6.5_20161201_P1_Position-Paper-onSystemic-Energy-Renovation.pdf (accessed on 17 February 2017). Rossia, M.; Roccoba, V.M. External walls design: The role of periodic thermal transmittance and internalareal heat capacity. Energy Build. 2014, 68, 732–740. [CrossRef] Andrews, D.; Krook-Riekkola, A.; Tzimas, E.; Serpa, J.; Carlsson, J.; Pardo-Garcia, N.; Papaioannou, I. Background Report on EU-27 District Heating and Cooling Potentials, Barriers, Best Practice and Measures of Promotion; Joint Research Centre of the European Commission: Luxembourg, 2012. Department of Development and Planning; Aalborg University. Heat Roadmap Europe. Available online: http://www.heatroadmap.eu/maps.php (accessed on 24 January 2017). Moretti, E.; Bonamente, E.; Buratti, C.; Cotana, F. Development of innovative heating and cooling systems using renewable energy sources for non-residential buildings. Energies 2013, 6, 5114–5129. [CrossRef] Kalz, D.; Pfafferott, J. Thermal Comfort and Energy-Efficient Cooling of Nonresidential Buildings; Springer: New York, NY, USA, 2014. Mlakar, J.; Štrancar, J. Overheating in residential passive house: Solution strategies revealed and confirmed through data analysis and simulations. Energy Build. 2011, 6, 1443–1451. [CrossRef] Psomas, T.; Heiselberg, P.; Duer, K.; Bjørn, E. Overheating risk barriers to energy renovations of single family houses: Multicriteria analysis and assessment. Energy Build. 2016, 4, 138–148. [CrossRef] © 2017 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).
© Copyright 2026 Paperzz