Nuaire Residential Catalogue - MVHR - Acoustic Solution

MVHR
ACOUSTIC SOLUTION FOR MRXBOX95-WH1
TECHNIC AL INFORMATION
ACOUSTIC SOLUTION FOR MRXBOX95-WH1
DESIGNED TO REDUCE NOISE LEVELS
AND INSTALLATION ISSUES WHEN WALL OR
CUPBOARD MOUNTING MRXBOX95-WH1.
42
029 2085 8500
MVHR
ACOUSTIC SOLUTION FOR MRXBOX95-WH1
TECHNIC AL INFORMATION
BENEFITS
Nuaire’s First Fix and Acoustic Solution are designed to not only reduce noise but to improve the installation when wall or cupboard mounting the
MRXBOX95-WH1 MVHR Units. Offering the only complete MVHR acoustic and first fix solution to overcome both noise and ease the installation of heat
recovery units; Nuaire’s solution addresses both duct and breakout noise; provides an aesthetically pleasing cupboard installation for the home occupant and
reduces installation errors and time.
EASY INSTALLATION
Significantly reduces overall installation time.
DESIGN SERVICE AVAILABLE - FULL VENTILATION, NOISE ANALYSIS AS PART
OF YOUR DESIGN.
SIMPLE SET-UP
No banding of ducts from spigots.
EASE OF POSITIONING
Prevents issues associated with lining up of spigots
to units.
NEGATES THE NEED FOR FLEXIBLE DUCTS
To overcome lining issues and adding additional
resistance/noise to the system.
Nuaire’s full acoustic analysis software will
calculate anticipated room NR levels from the
ventilation system and will provide you with
accurate noise levels both with and without our
acoustic attenuation.
Nuaire’s complete ventilation design will provide
a breakdown of all the information, allowing you
to confidently make a decision regarding noise
levels preventing costly and timely issues before
it’s too late.
PROMOTES BEST PRACTICE INSTALLATION
Peace of mind.
FIRST FIX SOLUTION MRXBOX-FF-WH1
Nuaire’s First Fix box is fixed to the underside of the floor slab at first fix
stage of the build. The box has four airflow chambers pre-fitted with
204x60mm spigots. Ceilings can then be boarded within the cupboard
space far easier and quicker without any risk of not lining up the spigots
to the fan unit.
ACOUSTIC BOX MRXBOX-AB-WH1
Nuaire have created a unique solution that is not only designed to
reduce noise significantly, addressing duct and breakout noise but is
visibly appealing for the home occupant.
MRXBOX95B-WH1
Nuaire’s WH1 heat recovery system is designed for medium to large
new build properties. This system uses the latest technology of low watt
DC fans providing extremely quiet running and long life motors.
DC fans will also reduce power consumption, operating costs and the
life cycle costs.
Download specification from www.nuaire.co.uk/specifications
nuaire.co.uk
43
MVHR
ACOUSTIC SOLUTION FOR MRXBOX95-WH1
TECHNIC AL INFORMATION
MRXBOX95-WH1 ACOUSTIC SOLUTION - DIMENSIONS (mm)
MRXBOX95-AB-WH1
Top view
Side view
655
505
458 CRS
=
=
=
432
MRXBOX95-FF-WH1
227 CRS
=
Front view
400
=
=
=
=
666
Top view
Side view
458 CRS
Face to be mounted
nearest to wall
=
=
=
=
=
242 CRS
227 CRS
155
489
107
=
110
Front view
Side view
1180
635
1158
1013
524
Wall mounting
bracket.
30
30
167
COMPLETED SYSTEM
Cross brace &
angle brackets.
=
=
672
44
029 2085 8500
M8 Fixings.
Patress.
MVHR
ACOUSTIC SOLUTION FOR MRXBOX95-WH1
TECHNIC AL INFORMATION
CONSULTA NTS SPECIFIC ATION
MRXBOX-FF-WH1
The unit shall be supplied with 204mm x 60mm rectangular spigots to connect
to the duct run, with the ability to be fitted in eight separate positions reducing
the requirement for bends in the system.
The unit offers the facility to be fitted directly to the mating sections without
the need for spigots reducing breakout noise, additional 150mm circular spigots
to be supplied as an alternative option.
MRXBOX-AB-WH1
The unit offers the facility to be fitted directly to the MVHR unit and plenum
chamber without the need for spigots reducing breakout noise, however, there
is the capability to fit 150mm circular spigots as an alternative option.
The unit shall be fully lined with acoustic material offering excellent noise
reduction.
Wall mounting brackets are to be supplied as part of the system to allow the
MVHR unit to be raised after other system components are installed to form
an airtight seal and enable the installation to be levelled.
The unit shall be clamped to the MRXBOX95-WH1 unit to provide an efficient
seal and ensure correct alignment.
The unit shall be fixed in position during installation as a standalone section
without relying on other system elements.
Download specification from www.nuaire.co.uk/specifications
nuaire.co.uk
45