CIRCULATION SYSTEM www.dabpumps.com 1 CIRCULATION SYSTEM: HEATING & AIR CONDITIONING Wet rotor circulators for heating and air conditioning system EVOSTA (only heating) EVOTRON APPLICATIONS: Circulate water in a closed circuit in both heating and air conditioning system Used also in solar heating circuits www.dabpumps.com 2 CIRCULATION SYSTEM: HEATING & AIR CONDITIONING Wet rotor circulators for heating and air conditioning system EVOSTA EVOTRON EVOPLUS SMALL VS (only heating) Main features: Flow rates from 1 to 9,6 m3/h and with maximum differential pressure head of 11m, depending of the model for domestic and residential application. Temperature range from -10°C to +110°C The pumped liquid must be clean, free of oily substances and chemically neutral. Motor casing in die cast aluminum impeller in engineering polymer ULTEM Threaded or flanged unions depending on the model www.dabpumps.com 3 MAIN COMPONENTS OF A HEATING SYSTEM www.dabpumps.com 4 MAIN COMPONENTS OF A HEATING SYSTEM Generation: Converting the energy carrier Accumulation: Temporal decoupling of generation and use of heat Distribution: Transport of heat in the building Emission: Heat transfer in environment Regulation: Decide when, where and how much heat issue in environment It has nothing to do with the regulation of the generator www.dabpumps.com/d.training 5 HYDRAULIC CIRCUIT To transport the heat it’s necessary to spin the water along delivery and return BOILER For each lap, the water carries a quantity of heat proportional to the difference between the supply temperature and the return temperature If the temperature difference between supply and return is high enough to run a little water BOILER To spin the water in a circuit must be a push (pressure) sufficient to overcome the resistance (pressure losses of pipes and devices) To adjust the power output of the system we will have to adjust the water flow and water temperatures or heat exchange to the radiators BOILER (fan) www.dabpumps.com/d.training 6 HYDRAULIC CIRCUIT Pressure Pressure losses Pressure losses Pressure losses Pressure losses www.dabpumps.com/d.training 7 SYSTEM FLOW RATE CALCULATION www.dabpumps.com 8 SYSTEM FLOW RATE CALCULATION 𝑷 ∙ 𝟎, 𝟖𝟔 𝑸= ∆𝑻 Q : water flow rate [m3/h] P : demanding heat [kW] 0,86 : factor for conversion from kW to kcal/h ΔT : temperature difference between delivery and return [°C] Temperature delta Legislation stipulates that for every building it has to be assigned a “heat-loss factor”; the law establishes also a maximum room temperature of 20°C. To ensure the room temperature is kept at 20°C, a balance must be established between the “heat-loss factor” and the building overall heat-drop. www.dabpumps.com 9 SYSTEM HEAD CALCULATION The system head is calculated by adding together the localized friction loss in the heating system. Example: H = Hed ∙ K • Hed = building height of 9 m • K = let’s assume this is 25% - 30% of the building’s height 1. H = 9 x 0.30 = 2.7 m 2. H = 9 x 0.25 = 2.25 m www.dabpumps.com 10 SYSTEM HEAD CALCULATION www.dabpumps.com 11 THE HYDRAULIC PROBLEM When the flow rate decreases, the pressure losses decrease dramatically Flow rate = 1000 l/h Pressure losses = 30 mm.w.c. Flow rate = 500 l/h Pressure losses = 7,5 mm.w.c. The pressure losses depend on the square of the flow www.dabpumps.com 12 MAIN REGULATION MODES WITH ELECTRONIC CIRCULATORS CONSTANT differential pressure ΔP-c PROPORTIONAL differential pressure ΔP-c CONSTANT curve speed www.dabpumps.com 13 CONSTANT DIFFERENTIAL PRESSURE Q = Variable H = Constant This control mode is particularly useful in: heating and conditioning systems with low pressure loss two-pipe central heating systems with thermostatic valves and head ≤ 2 m single-pipe central heating systems with thermostatic valves systems with natural circulation installations having primary circuit pumps with low pressure loss sanitary recirculation systems with thermostatic valves Set by scrolling through the Evoplus menu or with the external signal (0-10V or PWM)* *MULTIFUNCTION module requested for this application on EVOPLUS SMALL www.dabpumps.com 14 PROPOTIONAL DIFFERENTIAL PRESSURE Q = Variable H = Variable This control mode is particularly useful in: heating and air conditioning systems with high pressure loss double-pipes central heating systems with thermostatic valves and head ≥ 4 m heating systems with secondary differential pressure regulators installations having primary circuit pumps with high pressure loss sanitary recirculation systems with thermostatic valves Set by scrolling through the Evoplus menu or with the external signal (0-10V or PWM)* *MULTIFUNCTION module requested for this application on EVOPLUS SMALL www.dabpumps.com 15 PROPOTIONAL DIFFERENTIAL PRESSURE Q = Variable H = Variable www.dabpumps.com 16 CONSTANT CURVE H Curve limit Constant speed The operating curve can be adjusted manually Q setting the percentage reduction factor. The value 100% indicates the “Curve Limit” . This control mode is particularly useful in: heating and air-conditioning systems with constant flow Set by scrolling through the Evoplus menu or with the external signal (0-10V or PWM)* *MULTIFUNCTION module requested for this application on EVOPLUS SMALL www.dabpumps.com 17 CONSTANT CURVE www.dabpumps.com 18 CONSTANT DIFFERENTIAL PRESSURE DIFFERENTIAL PRESSURE CONTROL MODE ELIMINATED THE NOISE THANKS TO AUTOMATIC ADJUSTMENT OF THE CIRCULATION www.dabpumps.com 19 PROPOTIONAL DIFFERENTIAL PRESSURE ELIMINATED THE NOISE THANKS TO AUTOMATIC ADJUSTMENT OF THE CIRCULATION www.dabpumps.com 20 SYSTEM DESIGN EXAMPLES 1 SINGLE-PIPE HEATING SYSTEM (RADIATORS IN SERIES) www.dabpumps.com 21 SYSTEM DESIGN EXAMPLES 2 TWO-PIPE HEATING SYSTEM (RADIATORS IN PARALLEL) www.dabpumps.com 22 SYSTEM DESIGN EXAMPLES 3 UNDER-FLOOR HEATING SYSTEM www.dabpumps.com 23 ELECTRONIC CIRCULATORS MODELS www.dabpumps.com Flow rate → 0,6 – 3,5 m3/h Head max → 7 m Flow rate → 0,6 – 4,2 m3/h Head max → 4 – 8 m Flow rate → 4,2 – 9,6 m3/h Head max → 4 – 11 m 24 ELECTRONIC CIRCULATORS MODELS TWIN TWIN www.dabpumps.com Flow rate → 4,2 – 72 m3/h Head max → 4 – 18 m Flow rate → 2,4 – 9,6 m3/h Head max → 4 – 11 m Flow rate → 4,2 – 72 m3/h Head max → 4 – 18 m 25 CIRCULATORS MODELS FOR SANITARY WATER VS SAN SAN www.dabpumps.com Flow rate → 0,6 – 5,4 m3/h Head max → 0,8 – 6,5 m Flow rate → 0,6 – 4,2 m3/h Head max → 4 – 8 m Flow rate → 1,8 – 42 m3/h Head max → 4 – 15 m 26 FLOW RATE CALCULATION Example: Assume you need a circulator for a standard heating system. We know that the boiler heating capacity is 10000 kcal/h and that system pressure drop is about 4 m. Data : System pressure drop = 4 m Boiler capacity = 10000 kcal/h Considering a temperature difference between delivery and return = 20°C 1. Apply the formula for the flow rate: 𝑄 𝑙 = 𝑠 𝑘𝑐𝑎𝑙 𝑘𝑐𝑎𝑙 10000 𝑙 𝑚3 ℎ ℎ = = 0,41 ⇒ 0,5 ∆𝑇 [°𝐶] ∙ 3600 20 °𝐶 ∙ 3600 𝑠 ℎ 𝐵𝑜𝑖𝑙𝑒𝑟 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦 Suitable circulator = EVOTRON 40/130 or EVOSTA 40/70 www.dabpumps.com 27 IMPORTANT INFORMATION FOR THE INSTALLATION We recommend: Install check valves in both the suction line and the delivery line The terminal box must never be below the pump 30% maximum glycol contents In case of heat insulation, ensure the motor casing condensate discharge nozzles are not clogged The circulator is maintenance free The unit can be supplied complete with unions and other accessories www.dabpumps.com 28
© Copyright 2026 Paperzz