Transformer and Circuit Breaker Monitoring in Substations PATAKI, ANDRÁS M.Sc PhD Student DÁN, ANDRÁS PhD, Associate professor Department of Power Engineering Budapest University of Technology and Economics Budapest 1117 Egry József utca 18 HUNGARY Abstract: - The paper deals with the introduction of the comparative method of the state estimation of transformers and circuit breakers using continuous monitoring of voltage, current, oil-tank vibration and displacement of breaker contacts if function of time. The paper gives details of the hardware and software of the measuring equipment Key-Words: - Monitoring, Test on site, Vibration, Displacement, Harmonics, Special hardware 1 Introduction 2 Problem Formulation The privatisation of the electric sector brought a profit oriented thinking in the whole area of the electrical energy bussiness. It means that not only the production and delivery of electrical energy must be kept on the lowest price, but the cost of maintenance must be decreased as well. In order to decrease the cost of maintenance, instead of the periodically predefined planned maintenance, the necessity of maintenance is introduced. It means that e.g. a transformer- circuit breakerdisconnector unit of a substation will be in operation until the weekest element needs the maintenance. However this policy requires a sophisticated monitoring system and a CAM (Computer Aided Maintenance software) which is able to make decision on time of necessity of maintenance. If the system works well, the cost of maintenance can decrease while the quality of supply remains on the desired level. The paper is focusing on the transformer oil-tank vibration and on the movement of circuit breaker contacts. These data are suitable to develop a softwarebased comparison of the sequenced time functions- for decision making. There are known methods [1],[2] to measure transformer oil-tank vibration, but without measuring the current simutaneously with vibration, the decision can be false. Below the suggested method will be discussed. Regarding circuit breakers, the new type of breakers are equipped optionally with monitoring. However the older breakers need monitoring as well. Below a cheep and rigid solution will be introduced, suitable to maintain the old type breakers as well. 2.1 Transformer Because power transformers are expensive machines, thus the number of maintenances should be the possible minimal over its lifetime. To reach this goal two main parts must be examined (windings and core) by making tests on the site. Vibration analysis extended with the measurement of currents and voltages offers a robust method to plan maintenance. The task is to find correlation between current and vibration which represents correctly the state of the transformer winding. While vibration generated by the windings caused by the electrodynamic forces, the magnetostriction effect[1],[3] makes the core to vibrate. Separation of these sources would be advantageous, but it is essential to find out if they are correlated or not? This method hopefully gives an important benefit, after an accurate state estimation the transformer may be repaired on site if it is needed. With more than one accelerometer, it is possible to predict which winding should be repaired in case of three phase transformer. In this case repairment on the site is enough. To remove a transformer from a substation, and to transport it for maintenance is a complex and very expensive process and requires a lot of time too. 2.2 Circuit breaker Circuit breakers are very important elements in the power transmission line so monitoring the events gives a knowledgebase to determine time to the next maintenance. In contrast with transformers, the measurement of vibration is not the appropriate method for state estimation, instead of that displacement-time function of the breaker contacts must be recorded. 3 Problem Solution 3.1 Transformer Whilst in the previous section the problem was described, this section gives the details and answers regarding the minimum number of accelerometers, their placement on the transformer tank, the role of the harmonic currents and vibrations and hardware solution for the measurement. This method compares previous results carried out on the same transformer with the actual ones. Since the initial vibration spectrum is unknown for older transformers, the first series of measurement serves as a reference for later tests. Information is resulted partly from the appearance of such harmonics which were not relevant in the previous spectrum and from the relative changes of the spectrum. Two main types of vibration tests are possible: Switching measurement may be separated into subtasks. (By using synchronous switch, two measurements on the transformer have taken in different times become comparable.) Characterising the vibration spectrum generated by the core (Magnetostrictive effect) can be decided after transients having dumped. In Fig. 1 a 400/120kV power transformer can be seen. There are three points which indicate where to place the accelerometers to capture the vibrations. The vibration measurement requires a special equipment, and a remote unit, because the vibration can be captured only in the vicinity of the transformer, but currents and voltages are measured in the control room. To solve this problem a dedicated remote vibration measurement unit was developed to the existing TR-16 equipment. The TR-16 (Fig. 2) is a 16 channel portable Class A power system analyzer[4]. It can be used with various configurations of input signal conditioners for different measurement tasks. It is capable to perform both short or longterm monitoring functions or the evaluation of voltages, currents, active and reactive powers, impedances, voltage outages, flicker harmonics on 16 channels simultaneously . Localising a virtual vibration source for the transformer is calculated from the time delay of the accelerometer’s transient signals.(There are more than one accelerometer) Since not only the vibration is recorded but currents and voltages too, more accurate results are expected. The other type of test is the load current and vibration measurement at high currents. In this case estimation can be made regarding the state of the winding. Fig. 1 Marked points on the power transformer Fig. 2 Picture of TR-16 equipment There are often 200-300 meter distance (in a larger substation) between the transformer where vibrations are picked up, and the control room where the secondary of the current and voltage transformers are accessible. On the other hand voltage output accelerometers can not be used with cables longer than 100 meters, but charge output ones can be used with just not longer than 10 meters of cables [1]. To resolve this difficulty a special fiber based communication line has been adopted to avoid disturbances resulted by electromagnetic fields. This hardware ensures the galvanic isolation from high potential parts as well. Fig. 3 Schematic diagram of TR-16 remote unit In Fig. 3 the principle of the remote unit is shown. There are four input channels in TR-16 to retrieve power transformer-sensor-remote unit signals. There is also a reverse directioned communication between the daisychained input cards and the remote unit. The master card collects the range setting from the slaves and transmits to the remote unit. The measurement range can be changed by software before the measurement. Fig. 4 Shows the to be taken into account at the hardware design phase. An other requirement –equipment separation from high potential parts- involves the problem. In Fig. 5 there is the simplified schematic diagram of the breaker monitoring equipment. Two light sources emit 10m light ray which are interrupted by the rotating disc. Size of 10 mil width holes are manufactured to the disk to chop the light. This pattern secures the appropriate resolution of speed. Receivers sense square pulse which carries the velocity. In this figure only one phase is shown. It must be mentioned that at high voltage breakers three set of sensor unit needed, but for medium voltage breakers one set is enough. The capture circuit may be connected to a PC to Fig. 5 Schematic diagram of circuit breaker realisation of an input card. download the stored data, and with a special software further analysis can be made. The capture circuit has the responsibility to communicate with the SCADA system if any kind of problem concerning the circuit breakers would begin to develop. Breaker trigger signal are connected into the capture circuit to act as a start signal for the measurement Fig. 6 shows a solution for the communication. Fig. 4 Realisation of the input card 3.2 Circuit breaker There are numerous methods to examine circuit breakers, but now, just two from them being covered here. A low current test and a high current one. The given results show significant difference in the shape of the displacement-time function of the breaker. While in case of low current test, there is no swing in the displacement-time diagram, in the high one a swing might be observed which means that (because of electrodynamic forces) the breaker contacts are slowing down or reverses their movement direction for a short time in an open-close sequence. This phenomenom has Fig. 6 Capture unit PC communication 4 Measurement results 4.1 Transformer test results In order to test the method mentioned above, measurements have been made in Encs substation on a single phase 2MVA, 26/0.7kV transformer supplying thyristor switched static VAr compensation. The compensation serves 3rd, 5th 7th harmonic filter as well. Fig. 7 shows the time function of the primary current (black line) in which more than 80A current changes can be observed. These changes are sudden and rapid according the railway’s demand. Below in Fig. 8 and Fig. 9 the switching transient and the corresponding vibration-time function is shown. There are three relevant peaks in the vibration RMS time function, which is correlated with the current of secondary side. This means that the amplitude of vibration is mostly determined by the electrodynamic force. Fig. 10 Harmonics of u25 The next step is to find special patterns which may be useful. First let us take a closer look to the time function and FFT spectrum of vibration and current. Fig. 7 Iszk Current RMS–time function The switching measurement must be done by applying the synchronous switch because the needed worst case can be ensured. In this case just small transient resulted since the prviously mentioned switch has missed. Fig. 11 Time function of vibration In Fig. 11 and Fig. 12 that is shown. It is interesting that the most significant harmonic of the vibration is the 200Hz component. The even order harmonics must originate from the core because the exciting current has no such kind order of component (just odd order) as shown in Fig. 13 and Fig. 14. Only u25 has 200Hz component in the frequency specturm. (Fig. 10) Fig. 8 vibration RMS-time function Fig. 12 Harmonics of vibration Fig. 9 Primary voltage RMS-time function Fig. 13 Time function of iszk Fig. 16 Graph vibration(3)-iszk(3) Fig. 14 Harmonics of iszk Just based on this information accurate decision is impossible to make, therfore further signs must be find. A possible solution is to draw the current harmonic in the function of –vibration harmonic. The following diagrams show interesting patterns. The practical meaning of these patterns is not understood yet, but they must be investigated further. One approach may be if the correlation ratio changes test by test is should mean that somekind of problem has beggun to develop. Fig. 17 Graph vibration(5)-iszk(5) 4.2 Breaker test results Fig. 15 Graph vibration(1)-iszk(2) Each graph has is own special shape, thus one idea could be the monitoring of the changes of this pattern. In Fig. 15 an almost straight line can be observed, but in Fig. 16 the shape is loop like. In Fig. 18 an open-close sequence of a circuit breaker is drawn. The closing time approximatly 57 msec while the opening time is 49msec. This experiment carried out by ICMET High Power Laboratory in Craiova. It can ce seen that this trial was made at 50A which is relative low current. At high currents if there is a swing in the displacement-time function of the breaker contacts, that predicts the blowing up of the breaker. Therefore if this kind of swing begins to develop, the monitoring system has to send an alarm signal to the SCADA system. That is why it is necessary to make direction sesnsitive hardware. [4] RST Ltd, Transanal-16 user’s manual, Budapest, 2001 Fig. 18 Laboratory test of circuit breaker at low current (making and breaking) 5 Conclusion 5.1 Transformer This paper tried to introduce such kind of monitoring methods which are suitable to predict time to the next mintenance both for power transformers and circuit breakers. Hardware solutions were proposed too. It is seen that state estimation is a very difficult and complex task. For transformers not only the minimum number of sensors must be determined, but the locations on the transformer’s oil-tank where by placing them the most informative results can be extracted. Measurement results show an interesting correlation between current and vibration harmonics that worth for further analysis. In this state of the research is is seen that for transformer monitoring a physical modell is essential to be able interpreting the results. Furthermore a comparative knowledgebase is also very important to recognize the individual errors. 5.1 Circuit breaker At circuit breakers the displacement- time function represents the mechanical state. If a swing begins to develop actions have to be made to avoid the blowing up of the circuit breaker. References: [1] Timár P. L., Fazekas A., Kiss L., Miklós A., S.J. Yang, Villamos gépek zaja és rezgése. Műszaki Könyvkiadó, Budapest, 1968. [2] L. Tóth, T. Tóth, „Short-circuit tests on power transformers with pressure measurements,” Powertech 99, pp, Budapest [3] S. L. Foster, E. Reiplinger „Characteristics and control of transformer sound,” IEEE Transactions on Power Apparatus and Systems, Vol. PAS-100, No.3, March 1981
© Copyright 2026 Paperzz