Apeks Supercritical Setup and Operating Instructions for 1500-5L and 1500-20L with Automatic CO2 Makeup Recirculating Subcritical/Supercritical CO2 Extraction Systems Apeks Fabrication 14381 Blamer Rd Johnstown OH 43031 www.apekssupercritical.com Updated 6-17-14 1 Copyright Apeks Fabrication 2014 Operating Instructions for CO2 Extraction Systems Throughout these instructions, this symbol is used to indicate that high pressure is in the system and failure to follow the instructions as written can result in a rapid release of pressure potentially causing equipment or personnel damage. DANGER – Subcritical and Supercritical CO2 systems operate under high pressure. Operators must be fully trained and familiar with the system. Failure to operate the system properly can result in equipment damage and/or bodily injury. DANGER – Opening a vessel under pressure can result in a rapid release of pressure and ejection of the material inside the vessel. DO NOT ATTEMPT TO OPEN A VESSEL UNDER PRESSURE! Always make sure a vent path for the vessel is opened and the corresponding pressure gage reads zero prior to loosening the vessel closure bolts. 1. System Setup and Installation The Apeks Fabrication 1500-5L and 1500-20L subcritical/supercritical CO2 systems come fully assembled and require only facility hookup and installation. 1.1. System Requirements and Connections for Installation The following instructions are recommended for connecting the 1500-5L or 1500-20L subcritical/supercritical CO2 systems to your facility. Variations in utilities and available space may require modifications to these recommendations. Contact Apeks Supercritical to insure installation modifications will not be detrimental to the system. 1.1.1. Location CAUTION - The system stores CO2 during use. A suitable location with adequate ventilation is required to prevent buildup of CO2 which can cause asphyxiation. Use of a CO2 monitor is recommended for indoor or low lying applications. CAUTION – The 1500-5L system weighs approximately 550 pounds, and the 1500-20L system weighs approximately 750 pounds. Appropriate rigging equipment and methods should be used to move the system. Use the supplied leveling feet to provide adequate clearance below the system and to keep the system from sliding when being operated. Use caution to ensure the leveling feet bolts are not touching the frame. There should be at least 1/8” clearance between the top of the leveling feet bolt and the bottom of the frame. Updated 6-17-14 2 Copyright Apeks Fabrication 2014 1.1.2. Electrical CAUTION - Do not modify the power connections or attempt to use a higher or lower voltage than is specified. Electrical connections are to be made using the supplied power cords. CO2 system control box – 110V, 15A, 50-60Hz, 1 phase. Plug is NEMA 5-15 male. Chiller/heater unit – 220V, 15A, 60Hz, 1 phase. Plug is NEMA 6-15 male. 1.1.3. Air Compressed air must be non-lubricated and should be filtered to between 5μ and 40μ and have a dew point between 0°F and 50°F Max pressure – 150psi. No regulator or lubricator is required. Minimum pressure – 100psi. Minimum flow – 30 SCFM Maximum flow – 120 SCFM NOTE: CO2 flowrate (and subsequently extraction time) is proportional to air flow CO2 system air connection is ½” NPT female. Connection to facility compressed air should be made through a minimum ½” inner diameter pipe or flexible hose. Runs longer than 50 feet should be ¾” minimum inner diameter. Always follow the air compressor manufacturer’s operating instructions to insure proper performance of the compressed air system. 1.1.4. Water Chiller/Heater Chiller/heater unit is designed for use in an area where room temperature is less than 85F. Higher temperatures will adversely affect the cooling capacity of the chiller. Circulating fluid - Recirculating chiller/heater fluid should be a mixture of 50/50 water and propylene glycol to prevent freezing and improve heat transfer. Plain distilled water can be used for temperatures above 32F if propylene glycol is not available. – DO NOT USE DEIONIZED WATER. Volume – Total volume of fluid in the cooling/heating water jackets on the vessels and chiller/heater reservoir is approximately 4 gallons for the 1500-5L, and 12 gallons for the 1500-20L. Outlet connection - Connect the chiller/heater “OUTLET” to the back connection (inlet) of the temperature control heat exchanger. Inlet connection – Connect the chiller/heater “INLET” to the top (outlet) of the 2nd separator jacket. Remote Probe - With the chiller/heater power off, connect remote temperature sensor to the “REMOTE PROBE” connection on the back of the chiller. CAUTION – DO NOT CONNECT/DISCONNECT THE TEMPERATURE PROBE WHILE THE CHILLER IS UNDER POWER. Updated 6-17-14 3 Copyright Apeks Fabrication 2014 It may be necessary to adjust the chiller settings for Remote Probe Control mode: 1. To verify chiller is in Remote Probe Control mode, press “Menu” button until the left display shows “P1” or “P2” 2. If left display shows “P1”, then chiller is in Remote Probe Control mode and no other adjustments are necessary. Press menu 1 time so the left display shows water pressure in “psi”. NOTE: When “P1” is displayed on the left screen, the chiller’s internal temperature probe reading is displayed on the right screen. 3. If left display shows “P2”, then press and hold menu button for 3 seconds, press menu button until “rP” is displayed on the left, and use the temperature control knob to adjust the right setting to “rPC”. Wait for 10 seconds for the chiller to reset out of the menu mode, then repeat step 1 and 2 to verify changes. Circulating fluid is added to the system through the reservoir cap on the top of the chiller/heater while the chiller/heater is running. Maintain a visible level of fluid in the chiller/heater reservoir during operation. More detailed operating instructions for the heater/chiller can be found in the manufacturer’s operating instructions. 1.1.5. CO2 CO2 should be beverage grade or better for operations that come in contact with food product. 1500-5L system holds 8-12# of liquid CO2 while operating. A minimum 50# CO2 cylinder is recommended for this system 1500-20L holds approximately 30-40# of liquid CO2 while operating. A minimum 75# CO2 cylinder is recommended for this system CO2 system connection is CGA-320. The supplied hose should be connected directly to the CO2 bottle valve. No regulator is required. A supplied CGA-320 plastic gasket is required to seal the connection between the hose and the CO2 bottle. CO2 cylinder should be high pressure gas feed with no check valves. Siphon tube or dip tube bottles can cause system blockages during startup and should not be used. NOTE: a liquid CO2 dewar is not recommended due to the limited amount of CO2 lost during the extraction process. Updated 6-17-14 4 Copyright Apeks Fabrication 2014 2. Theory of Operation The 1500-5L and 1500-20L systems perform botanical oil extractions using CO2 as a solvent. When CO2 is a supercritical fluid or a subcritical liquid it has the ability to dissolve and carry certain oils, waxes and other soluble compounds from botanical plant materials. When the supercritical/liquid CO2 with suspended oils and waxes is subsequently decompressed, the CO2 loses its ability to hold the suspended oils and waxes in solution and drops them out of solution at the point of decompression. In addition to the oil and wax extraction, the 1500-5L and 1500-20L systems also recirculate the CO2 during operation and recover the CO2 at the end of the extraction to minimize CO2 loss. The extraction process begins in the Extraction Vessel. CO2 in either a liquid state (Figure 2) or supercritical state (Figure 3) enters the Extraction Vessel where it will dissolve oils/waxes from the botanical plant material and carry it over to the Valveless Expansion Technology (VET) mechanism in the separator vessel. The supercritical/liquid CO2 is decompressed through the VET mechanism which causes it to change phase into a gas and subsequently drop the suspended oil/wax into the separator vessel. The heavier oil and wax will collect in the bottom of the separator vessel. After oil and wax separation, the cold, gaseous CO2 is directed to the inlet of the pump where it is recompressed. The pump discharge is cooled in the regenerative heat exchanger by the water cooling circuit, and then is cooled/heated to the appropriate temperature by the temperature control heat exchanger and water chiller/heater. The liquid or supercritical CO2 then enters the Extraction Vessel to extract more oils and waxes again. Updated 6-17-14 5 Copyright Apeks Fabrication 2014 Figure 1 – Subcritical CO2 System Dynamics During Operation Figure 2 - Supercritical CO2 System Dynamics During Operation Updated 6-17-14 6 Copyright Apeks Fabrication 2014 3. System Operation These operating instructions are for 1500-5L and 1500-20L systems with Valveless Expansion Technology mechanism and automatic CO2 makeup installed. 3.1. Orifice Selection The size of the orifice must be chosen such that the flow of CO2 into the separators matches the flow of CO2 from the gas booster. The following are recommended settings for choosing the correct orifice: 3.1.1. Supercritical CO2 NOTE: external cooling for the CO2 pump must be applied for supercritical parameters Chiller/heater temperature – 110F to 120F Extraction pressure – 1200-1300psi Orifice size: 30CFM air flow (~7.5 HP air compressor) – #15 orifice 60CFM air flow (~15 HP air compressor) – #20 orifice 100CFM air flow (~25 HP air compressor) – #25 orifice Weight of CO2 in system – 6-8 pounds for the 5L systems, 20-25 pounds for the 20L systems Separator pressure – 250-300psi Separator temperature – 50F to 80F 3.1.2. Subcritical CO2 Chiller/heater temperature – 60F to 65F Extraction pressure – 1200-1300psi Orifice size: 30CFM air flow (~7.5 HP air compressor) – #10 orifice 60CFM air flow (~15 HP air compressor) – #15 orifice 100CFM air flow (~25 HP air compressor) – #20 orifice Weight of CO2 in system – 8-12 pounds for the 5L systems, 30-40 pounds for the 20L systems Separator pressure – 250psi to 300psi Separator temperature – 20F to 30F 3.2. Loading Material into the Extraction Vessel DANGER – Opening a vessel under pressure can result in a rapid release of pressure and ejection of the material inside the vessel. DO NOT ATTEMPT TO OPEN A VESSEL UNDER PRESSURE! Always make sure a vent path for the vessel is opened and the corresponding pressure gage reads zero prior to loosening the vessel closure bolts. Updated 6-17-14 7 Copyright Apeks Fabrication 2014 3.2.1. Opening the Extraction Vessel NOTE: This operation cannot be performed during an extraction. The extraction must be stopped prior to opening the Extraction vessel Shut valves 1 and 2. Open valves 3 and 4. Remove the bolts on the top of the vessel using a 1.5” impact socket and impact wrench. Lift the flange and allow it to rest in the open position on the stops. Use caution not to scratch or otherwise damage the o-ring sealing surfaces on the flanges. 3.2.2. Loading the Extraction Vessel The system scale can be used to weigh the amount of material loaded. Tare the scale by pushing the “tare/reset” key. Media to be extracted can be loaded directly into the Extraction Vessel. The supplied funnel can help minimize spillage. Media can be ground to a particle size as small as 50 micron, but particles about the size of coffee grounds generally works well. Any amount of material can be loaded into the Extraction Vessel – it does not have to be full in order to operate correctly Gentle compression can be used to increase the amount of material loaded in the vessel, however heavy compaction should be avoided to prevent CO2 channeling through the material upon startup. 3.2.3. Sealing the Extraction Vessel Once the desired amount of material is loaded into the Extraction Vessel the vessel can be closed and sealed Ensure all sealing surfaces are clean and free of debris Check the o-ring for any visible damage or defects. Replace as necessary The o-ring does not require any lubrication Close the vessel flange and install each of the closure bolts hand tight Using the supplied impact wrench and socket, tighten the bolts in a star pattern. Use the supplied impact wrench with 1-2 second bursts to deliver approximately 50 ft-lbs of torque to each bolt. Heavy torqueing of the bolts is not required. 3.3. Evacuating entire system To remove any moisture from the system the entire system must be evacuated. Evacuate using these steps: 3.3.1. Open all valves on system except CO2 bottle valve and valve 4. 3.3.2. Connect vacuum pump to valve 10, open valve 10, and turn vacuum pump on to vacuum system down to 20-25 in.Hg. 3.3.3. Hold vacuum for several minutes to ensure no gross leaks and to remove moisture. Updated 6-17-14 8 Copyright Apeks Fabrication 2014 3.3.4. 3.4. Shut all valves and disconnect vacuum pump and vacuum gage from valve 10. Fill system with CO2 and start extraction Filling the system with CO2 is accomplished with the following steps: 3.4.1. Tare the scale by pushing the “tare/reset” key. 3.4.2. Open CO2 bottle valve. 3.4.3. Open valves 1, 3, 5, and 7. 3.4.4. Pressurize and fill Extractor by slowly opening valve 13. Allow Extractor pressure to equalize with the CO2 bottle pressure. 3.4.5. Once Extractor pressure has equalized with the CO2 bottle pressure, shut valves 5 and 13. 3.4.6. Pressurize separators to 300psi by opening valves 11 and 12. Adjustment of the green handled regulating valve may be necessary to set the separators to approximately 300psi. 3.4.7. Close valve 11. 3.4.8. Open valve 14. 3.4.9. Turn the start/stop switch on control panel to “START” to start the CO2 pump. 3.4.10. Once Extractor pressure has reached approximately 1200psi, close valve 14, and open valves 6 and 11. 3.4.11. If necessary, adjust the green handled regulating valve to maintain 300psi in the separators and a corresponding1200psi in the extraction vessel. NOTE: changes may take several minutes to stabilize – make changes in small increments and allow at least 5 minutes between changes. 3.5. Removing CO2 to Maintain Pressure The system is now circulating CO2 and extracting. In the event that the system is overfilled with CO2 due to ambient temperature variations the system may shut down on Extractor over pressure. Decrease the Extractor pressure as follows: 3.5.1. Turn the green handled regulating valve in the “decrease” direction approximately ¼ turn to avoid overloading the CO2 again. 3.5.2. Shut valves 1 and 5 (or check that they are both shut) and QUICKLY open and shut valve 13, then QUICKLY reopen valve 1 or 5 (whichever was previously opened). 3.5.3. Allow system to stabilize for 5 minutes and repeat as necessary 3.6. Setting extraction timer The control system is equipped with a timer that will automatically shut down the system after a set amount of time has elapsed. The timer can be adjusted at any time during the extraction. Actual time elapsed is displayed as red text. To set the timer: Updated 6-17-14 9 Copyright Apeks Fabrication 2014 3.7. Use the up or down arrow keys on the timer controller to set the desired run time (green text) Use the left arrow to adjust the place setting (HH:MM) Press “MODE” to lock in the new time Flow Reversal It may be necessary to reverse the flow in the Extraction Vessel during operation to either back flush a clogged filter, to prevent channeling through the media, or both. The Extractor vessel filter may need back flushed if a differential pressure greater than 300 psi exists between the Extractor pressure and either the inlet or outlet pressure for the Extractor. Note: these instructions assume the valves are in the original positions. If a reversal has already been performed, use the valves in parenthesis 3.7.1. Extractor Flow Reversal 3.7.1.1. Open valve 5 (valve 1) 3.7.1.2. Open valve 2 (valve 6) 3.7.1.3. Shut valve 1 (valve 5) 3.7.1.4. Shut valve 6 (valve 2). 3.8. Orifice clog On rare occasions it may be necessary to clean the orifice during operation. The orifice is clogged when separation pressure continually decreases with a corresponding increase in extraction pressure. To clear a clogged orifice filter: 3.8.1. Shut valve 2 and valve 6 (only one of them will be open). 3.8.2. Shut valve 12. 3.8.3. Allow the pump to draw the CO2 out of the separators and transfer the CO2 to the Extraction vessel. 3.8.4. When Extraction Vessel pressure reaches 1400psi, shut valves 1 and 5 (only one of them will be open), then quickly open valve 13 to direct the remaining CO2 in the separators back to the storage bottle. 3.8.5. When the separators reach approximately 70 psi, the pump will automatically turn off. 3.8.6. Shut valve 13 3.8.7. Open valve 1 or 5 (whichever was previously opened). 3.8.8. Shut valve 11. 3.8.9. Open valve 10 to relieve any residual pressure in the separators. Leave valve 10 open to allow any residual pressure to vent. Updated 6-17-14 10 Copyright Apeks Fabrication 2014 3.8.10. 3.8.11. 3.8.12. 3.8.13. 3.8.14. 3.9. Remove the 1st separator cap and remove the orifice. Clean the orifice by removing it and soaking it in acetone or ethanol and blowing it out with compressed air. Verify the orifice is clear by looking through it. Reassemble the orifice using the provided Teflon tape. Use caution to prevent excess Teflon tape from getting into the orifice. Tighten the orifice assembly such that the orifice points toward the separator wall. Replace the 1st separator cap and tighten the clamp bolts to 20 ft-lbs Shut valve 10 Open valve 11, valve 12 and valve 2 or 6 (whichever was previously open). The pump will automatically re-start when separator pressure reaches 70psi. CO2 Recovery Once the extraction is complete, recover the CO2 as follows. NOTE: if the system shut down with the timer, it will be necessary to switch the system to “STOP” to reset the timer, then returning the system to “START” to start the pump. 3.9.1. To recover the CO2 from the system: 3.9.1.1. Increase the temperature of the chiller/heater to 110F. 3.9.1.2. Open valve 6 and shut valve 2 (they may already be in this position). 3.9.1.3. Shut valves 1 and valve 5 (only one of them will be open). 3.9.1.4. Quickly open valve 13 to allow flow into the CO2 bottle. 3.9.1.5. Shut valve 12 3.9.1.6. When Extractor pressure is below 700psi, shut valve 6 and open valves 2 and 8. 3.9.1.7. The pump will shut down automatically when separator pressure reaches 70psi. 3.9.1.8. Shut CO2 bottle valve. 3.9.1.9. Vent remaining CO2 in system by opening valves 10, 1 and 4. NOTE: LEAVE VALVES 10, 3 and 4 OPEN TO ALLOW ANY RESIDUAL PRESSURE IN THE SYSTEM TO VENT The system can now be powered down, or new extraction media can be reloaded and the extraction process and be started again. 4. System Error Messages The 1500-5L and 1500-20L control system will monitor and attempt to protect the system in the event of an overpressure or underpressure condition. There are 4 system errors: High Separator Pressure - Pressure in the Separator Vessels is higher than 500psi. High Extractor Pressure – Pressure in the Extraction Vessel is higher than 1500psi. Updated 6-17-14 11 Copyright Apeks Fabrication 2014 Low Separator Pressure – Pressure in the Separator Vessels is less than 70psi. Air Pressure Fault – Air Pressure is greater than 140psi or less than 40psi. 5. System Maintenance Maintenance on the system is critical to proper operation. Failure to follow these maintenance items can cause premature system failure. The maintenance items below pertain to the CO2 system only. Follow the manufacturer’s recommended maintenance plan for the chiller/heater unit and the compressed air system. This maintenance schedule assumes an 8 hour daily operating schedule. More frequent operation will require more frequent maintenance operations. Frequency After Each Extraction Weekly Bi-Weekly Updated 6-17-14 Maintenance Item Extraction vessel – remove spent material from the extraction vessel by either vacuuming it out through the top flange, or by opening the bottom flange and catching the material in a receptacle. Verify the extractor filters are clear and free of debris Check extraction vessel oring and oring groove sealing surfaces for damage – replace if necessary Separator vessels – remove extracted oil from separator vessels and clean with alcohol or other acceptable solvent. Remove any oil carryover from the flow line between the separators with alcohol and compressed air. Check separator vessel gaskets for damage – replace if necessary Pump Inlet Line Disconnect the flexible line connecting the outlet of Separator #2 to the CO2 pump and disconnect the stainless tubing from the inlet side of the CO2 pump. Open valve 11, clean flexible line and tubing with acetone or alcohol, then blow out with compressed air. Lubricate CO2 pump spool valve orings. Replace if necessary. Clean CO2 flow lines from separator #2 to the CO2 pump with alcohol and compressed air. Disassembly of the flowlines may be necessary. Check chiller/heater water level is between min and max Check CO2 pump seals for wear - While system is operating, remove piston vent filters (4 total) and verify no flow for compressed air piston vents (point toward front of system), and intermittent suction/pressure for CO2 piston vents (point toward back of system) 12 Copyright Apeks Fabrication 2014 Monthly Updated 6-17-14 Check air operated safety valve operation – during operation, turn start/stop switch to stop and verify valve coupling rotates 90 degrees quickly and without hesitation. “Ext Out” gage reading should drop to match separator pressure. Restart process and verify valve coupling rotates 90 degrees in the opposite direction. Contact Apeks immediately if valve is not operating properly. 13 Copyright Apeks Fabrication 2014 Figure 4 - PID drawing for 1500-5L and 1500-20L CO2 systems. Updated 6-17-14 14 Copyright Apeks Fabrication 2014 Figure 5 – Extraction Vessel for 1500-20L Supercritical CO2 system. Updated 6-17-14 15 Copyright Apeks Fabrication 2014 Figure 6 – Extraction Vessel for 1500-5L Supercritical CO2 system. Updated 6-17-14 16 Copyright Apeks Fabrication 2014 Figure 7 – Separator Vessels for 1500-20L and 1500-5L Supercritical CO2 system. Updated 6-17-14 17 Copyright Apeks Fabrication 2014 Updated 6-17-14 18 Copyright Apeks Fabrication 2014 Updated 6-17-14 19 Copyright Apeks Fabrication 2014
© Copyright 2026 Paperzz