b-lux classic - B

B-LUX CLASSIC – BR 545 030
Emergency Exit SigBR545030-engn with aluminium frame in exclusive design, as self-contained light fitting with AUTOTESTFunction according to DIN EN 60598-1, DIN EN 60598-2-22 and DIN EN 1838 for installations according to DIN VDE 0108 / 10.89
for separate operation.
- Duration 3 hours
- Maintained and non maintained version
- Viewing distance 24 meter
- Wall mounted
- Housing made of aluminium
- Polycarbonate cover, transparent, unbreakable
- Aluminium reflector for perfect light distribution
- Aluminium frame for pictogram
- Inlay PVC-film pictogram
- inclusive 1x standard set pictograms (emergency exit / above door, emergency way left, emergency way right)
- Test results with fault analysis (light source, charging circuit, battery circuit) as well as status display (operation, AUTOTEST) with
three coloured LED’s
- Automatically function test (AUTOTEST type A) weekly
- Automatically duration test (AUTOTEST type B) every 3 months
- Operating temperature 5°C to 35°C
- Supply voltage 230V AC
- Including bulb T5 – 8W
- Output 8 W
- Protection degree IP 40
- Insulation class I
- NI-MH-battery 4.8 V / 4000 mAH
- Dimensions (A x B x C) 355 x 167 x 78 mm
Manufacturer: B-SAFETY or equal
Article No.:
BR 545 030
B-LUX CLASSIC – BR 545 032
Emergency Exit Sign with aluminium frame in exclusive design, as self-contained light fitting with AUTOTEST-Function according
to DIN EN 60598-1, DIN EN 60598-2-22 and DIN EN 1838 for installations according to DIN VDE 0108 / 10.89 for separate
operation.
- Duration 3 hours
- Maintained and non maintained version
- Viewing distance 24 meter
- Wall mounted, recessed version
- Housing made of aluminium
- Polycarbonate cover, transparent, unbreakable
- Aluminium reflector for perfect light distribution
- Aluminium frame for pictogram
- Inlay PVC-film pictogram
- inclusive 1x standard set pictograms (emergency exit / above door, emergency way left, emergency way right)
- Test results with fault analysis (light source, charging circuit, battery circuit) as well as status display (operation, AUTOTEST) with
three coloured LED’s
- Automatically function test (AUTOTEST type A) weekly
- Automatically duration test (AUTOTEST type B) every 3 months
- Operating temperature 5°C to 35°C
- Supply voltage 230V AC
- Including bulb T5 – 8W
- Output 8 W
- Protection degree IP 40
- Insulation class I
- NI-MH-battery 4.8 V / 4000 mAH
- Dimensions (A x B x C) 355 x 167 x 78 mm
- Mounting hole dimensions 319 x 123 mm
Manufacturer: B-SAFETY or equal
Article No.:
BR 545 032
B-LUX CLASSIC – BR 545 090
Emergency Exit Sign with aluminium frame in exclusive design, as Emergency Light according to DIN EN 60598-1, DIN EN 605982-22 and DIN EN 1838 for installations according to DIN VDE 0108 / 10.89 for central supply systems.
- Maintained and non maintained version, freely programmable with suitable central supply systems
- Viewing distance 24 meter
- Wall mounted
- Housing made of aluminium
- Polycarbonate cover, transparent, unbreakable
- Aluminium reflector for perfect light distribution
- Aluminium frame for pictogram
- Inlay PVC-film pictogram
- inclusive 1x standard set pictograms (emergency exit / above door, emergency way left, emergency way right)
- Operating temperature 5°C to 35°C
- Supply voltage 230V AC / DC
- Including bulb T5 – 8W
- Output 8 W
- Protection degree IP 40
- Insulation class I
- Dimensions (A x B x C) 355 x 167 x 78 mm
Manufacturer: B-SAFETY or equal
Article-No : BR 545 090
B-LUX CLASSIC – BR 545 092
Emergency Exit Sign with aluminium frame in exclusive design, as Emergency Light according to DIN EN 60598-1, DIN EN 605982-22 and DIN EN 1838 for installations according to DIN VDE 0108 / 10.89 for central supply systems.
- Maintained and non maintained version, freely programmable with suitable central supply systems
- Viewing distance 24 meter
- Wall mounted, recessed version
- Housing made of aluminium
- Polycarbonate cover, transparent, unbreakable
- Aluminium reflector for perfect light distribution
- Aluminium frame for pictogram
- Inlay PVC-film pictogram
- inclusive 1x standard set pictograms (emergency exit / above door, emergency way left, emergency way right)
- Operating temperature 5°C to 35°C
- Supply voltage 230V AC / DC
- Including bulb T5 – 8W
- Output 8 W
- Protection degree IP 40
- Insulation class I
- Dimensions (A x B x C) 355 x 167 x 78 mm
- Mounting hole dimensions 319 x 123 mm
Manufacturer: B-SAFETY or equal
Article No:
BR 545 092
B-LUX CLASSIC – BR 547 010
Emergency Exit Sign with aluminium frame in exclusive design with high-power-LED’s, as self-contained light fitting with
AUTOTEST-Function according to DIN EN 60598-1, DIN EN 60598-2-22 and DIN EN 1838 for installations according to DIN VDE
0108 / 10.89 for separate operation.
- Duration 1 hour
- Maintained and non maintained version
- Viewing distance 24 meter
- Wall mounted
- Housing made of aluminium
- Polycarbonate cover, transparent, unbreakable
- Aluminium reflector for perfect light distribution
- Aluminium frame for pictogram
- Inlay PVC-film pictogram
- inclusive 1x standard set pictograms (emergency exit / above door, emergency way left, emergency way right)
- Test results with fault analysis (light source, charging circuit, battery circuit) as well as status display (operation, AUTOTEST) with
three coloured LED’s
- Automatically function test (AUTOTEST type A) weekly
- Automatically duration test (AUTOTEST type B) every 3 months
- Operating temperature 5°C to 35°C
- Supply voltage 230V AC
- Including 5x High-Power-LED’s
- Output 15 W
- Protection degree IP 40
- Insulation class I
- NI-MH-battery 4.8 V / 4000 mAH
- Dimensions (A x B x C) 355 x 167 x 78 mm
Manufacturer: B-SAFETY or equal
Article No.: BR 547 010
B-LUX CLASSIC – BR 547 012
Emergency Exit Sign with aluminium frame in exclusive design with high-power-LED’s, as self-contained light fitting with
AUTOTEST-Function according to DIN EN 60598-1, DIN EN 60598-2-22 and DIN EN 1838 for installations according to DIN VDE
0108 / 10.89 for separate operation.
- Duration 1 hour
- Maintained and non maintained version
- Viewing distance 24 meter
- Wall mounted, recessed version
- Housing made of aluminium
- Polycarbonate cover, transparent, unbreakable
- Aluminium reflector for perfect light distribution
- Aluminium frame for pictogram
- Inlay PVC-film pictogram
- inclusive 1x standard set pictograms (emergency exit / above door, emergency way left, emergency way right)
- Test results with fault analysis (light source, charging circuit, battery circuit) as well as status display (operation, AUTOTEST) with
three coloured LED’s
- Automatically function test (AUTOTEST type A) weekly
- Automatically duration test (AUTOTEST type B) every 3 months
- Operating temperature 5°C to 35°C
- Supply voltage 230V AC
- Including 5x High-Power-LED’s
- Output 15 W
- Protection degree IP 40
- Insulation class I
- NI-MH-battery 4.8 V / 4000 mAH
- Dimensions (A x B x C) 355 x 167 x 78 mm
- Mounting hole dimensions 319 x 123 mm
Manufacturer: B-SAFETY or equal
Article No.: BR 547 012
B-LUX CLASSIC – BR 547 090
Emergency Exit Sign with aluminium frame in exclusive design with high-power-LED’s, as Emergency Light according to DIN EN
60598-1, DIN EN 60598-2-22 and DIN EN 1838 for installations according to DIN VDE 0108 / 10.89 for central supply systems.
- Maintained and non maintained version, freely programmable with suitable central supply systems
- Viewing distance 24 meter
- Wall mounted
- Housing made of aluminium
- Polycarbonate cover, transparent, unbreakable
- Aluminium reflector for perfect light distribution
- Aluminium frame for pictogram
- Inlay PVC-film pictogram
- inclusive 1x standard set pictograms (emergency exit / above door, emergency way left, emergency way right)
- Operating temperature 5°C to 35°C
- Supply voltage 230V AC / DC
- Including 5x High-Power-LED’s
- Output 15 W
- Protection degree IP 40
- Insulation class I
- Dimensions (A x B x C) 355 x 167 x 78 mm
Manufacturer: B-SAFETY or equal
Article No.: BR 547 090
B-LUX CLASSIC – BR 547 092
Emergency Exit Sign with aluminium frame in exclusive design with high-power-LED’s, as Emergency Light according to DIN EN
60598-1, DIN EN 60598-2-22 and DIN EN 1838 for installations according to DIN VDE 0108 / 10.89 for central supply systems.
- Maintained and non maintained version, freely programmable with suitable central supply systems
- Viewing distance 24 meter
- Wall mounted, recessed version
- Housing made of aluminium
- Polycarbonate cover, transparent, unbreakable
- Aluminium reflector for perfect light distribution
- Aluminium frame for pictogram
- Inlay PVC-film pictogram
- inclusive 1x standard set pictograms (emergency exit / above door, emergency way left, emergency way right)
- Operating temperature 5°C to 35°C
- Supply voltage 230V AC / DC
- Including 5x High-Power-LED’s
- Output 15 W
- Protection degree IP 40
- Insulation class I
- Dimensions (A x B x C) 355 x 167 x 78 mm
- Mounting hole dimensions 319 x 123 mm
Manufacturer: B-SAFETY or equal
Article No.: BR 547 092