Product Data - Refricenter Group

FX4D
Comfortt Series Fan Coil
Sizes 019 thru 061
Product Data
AIR HANDLER TECHNOLOGY
AT ITS FINEST
The FX4D fan coils combine the proven technology of Carrier fan
coil units with Puron®, the environmentally sound refrigerant.
These fan coils are loaded with popular features. Factory--installed,
refrigerant--specific thermostatic expansion valves (TXV) are
standard with these fan coil designs. The designs feature contoured
condensate pans with rugged, drain connections, ensuring that little
water is left in the unit at the end of the cooling duty cycle. The
lack of standing condensate and corrosion free pans improves IAQ
and product life, features homeowners appreciate.
Standard features include grooved copper tubing and louvered
aluminum fins. The large face areas of the refrigerant coils provide
superior efficiency for high SEER and HSPF performance. Coil
circuiting has also been updated to make the most of all Carrier
heat pumps and air conditioners. Also units come with solid state
fan controls, 1--in (25mm) thick insulation with R--value of 4.2,
multi--speed motors, and fully--wettable coils. Units can
accommodate factory-- and/or field--installed heaters from 3 to 30
kW.
It also should be noted that the unique cabinet design of these fan
coils meet new stringent regulations for cabinet air leakage -- a
requirement of 2% cabinet leakage rate when tested at 1.0 inches of
static pressure.
The FX4D fan coil is the Puron® refrigeration design loaded with
popular features. It comes in a pre--painted (taupe metallic)
galvanized steel casing and is shipped with a cleanable, permanent
framed filter, and a factory--supplied power plug. ArmorCoatt
provides a tin plating of the indoor coil’s copper hairpins. This
creates a barrier between the corrosion--causing elements and the
coil. These fan coils utilize the latest in electronic commutation
motor (ECM) technology through the use of high efficiency, X13,
blower motors.
A10009
FX4D
STANDARD FEATURES
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
High efficiency ECM (electronic commutating motor) X--13 motors -- all sizes
Integrated motor controls have replaced integrated circuit board
Large, grooved tube, louvered fin coils
Efficient, quiet, time--tested blower housings and diffusers
Sturdy, drainable condensate pans
Cabinet construction features innovations designed to prevent cabinet sweating
Tested for condensate disposal in much tougher conditions than Air Conditioning and Refrigeration Institute requirements
Super--thick R--4.2 insulation with vapor barrier
Pre--painted galvanized steel cabinet (taupe metallic)
Cabinet design meets stringent regulations for 2% cabinet leakage rate when tested at 1.0 inches static pressure
Installation--flexible, multipoise units
Horizontal hanging provisions on cabinet
No tools required to service filter
Factory--supplied, cleanable and reusable filter
Newly improved filter rack area filter door insulation added for improved air seal
Factory--installed heater packages available (5-- through 15--kW)
3-- through 30--kW accessory heaters -- field installed
Factory--supplied power plug
Easy plug--in provisions for heater installation
Entry options for high and low voltage wiring hook--up
Simple, 5--amp blade fuse (and a spare) to protect 40 VA transformer
Easy coil inspection (removable, snap--in plug on A--coil models)
Leak--preventing sweat connections
Modular cabinets available on 037 through 061 sizes.
Designed for manufactured housing applications.
ADDITIONAL FEATURES
FX4D
S
S
S
S
Puron®, environmentally sound refrigerant
Factory--installed Puron® refrigerant thermostatic expansion valves (TXV)
Factory--installed heater packages available
ArmorCoatt coil protection available
2
MODEL NUMBER NOMENCLATURE
CARRIER FAN COILS
1
F
2
X
3
4
4
D
5
N
6
B
7
0
8
1
9
9
10
0
Product Type
Fan Coil, Multipoise with Puron
11
0
12
0
Heating Size
000 = No Heat
005 = 5kW
008 = 8 kW
010 = 10kW
015 = 15kW
Electrical
N -- 208/230v, 1 ph, 60 Hz
Cabinet Style
B -- Modular
F -- Single Piece
Coil Coating
0 = Standard
T = ArmorCoatt
FX4D
Capacity
019 = 18,000
025 = 24,000
031 = 30,000
037 = 36,000
043 = 42,000
049 = 48,000
061 = 60,000
ISO 9001:2000
the environmentally sound refrigerant
Use of the AHRI Certified TM
Mark indicates a manufacturer’s
participation in the program For
verification of certification for
individual products, go to
www.ahridirectory.org.
REGISTERED
3
DIMENSIONS
UNIT
A
B
C
D
E
F
G
H
J
COIL
CONFIGURATION
SLOPE
"A"
SHIPPING WT
(LBS)
NON TIN-COATED
SHIPPING WT
(LBS)
TIN-COATED
FX4DNF019
49 5/8"
17 5/8"
15 3/4"
15 5/8"
15 3/8"
23 1/8"
23 5/8"
-
17"
X
-
122
122
FX4DNF025
49 5/8"
17 5/8"
15 3/4"
15 5/8"
15 3/8"
23 1/8"
23 5/8"
-
17"
X
-
122
122
X
-
FX4DNF031
53 7/16"
21 1/8"
19 1/4"
19 1/8"
19 3/16"
26 15/16"
27 1/2"
-
19"
146
146
FX4DNF037
49 5/8"
21 1/8"
19 1/4"
19 1/8"
15 11/16"
23 7/16"
23 1/8"
-
-
-
X
157
157
FX4DNF043
49 5/8"
21 1/8"
19 1/4"
19 1/8"
15 11/16"
23 7/16"
23 1/8"
-
-
-
X
157
157
FX4DNF049
53 7/16"
24 11/16"
22 3/4"
22 11/16"
19 1/2"
27 1/4"
26 15/16"
-
-
-
X
185
185
FX4DNF061
59 3/16"
24 11/16"
22 3/4"
22 11/16"
25 1/4"
32 15/16"
32 5/8"
-
-
-
X
201
201
NOTE:
NOTE: ALLOW 21" FROM FRONT
FOR SERVICE
1. SERIES DESIGNATION IS THE 14TH POSITION
OF UNIT PRODUCT NUMBER
2. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED.
UNIT CONNECTION SIZES
SUCTION: 018 THRU 025 - 5/8" I.D. SWEAT
030 THRU 037 - 3/4" I.D. SWEAT
042 THRU 061 - 7/8" I.D. SWEAT
LIQUID: 3/8" I.D. SWEAT
CONDENSATE: 3/4" FPT
22 1/16"
10 3/16"
FX4D
2 1/8"
7/8", 1 3/32"
2" DIA. K.O.'S
FOR HIGH VOLTAGE
POWER WIRING
1 7/8"
11"
1"
K.O.'S
1 1/2"
1"
1 15/16"
TOP VIEW
1 3/8"
J
1 3/16"
MAX
DISCONNECT OR
CIRCUIT BREAKER
LOCATION
H
FOR
MODULAR UNITS
19"
B
C
15/16"
NOTE: MODULAR
UNITS WILL HAVE
A TWO-PIECE
CABINET
OPTIONAL FIELD CONVERTED
RIGHT SIDE RETURN OPENING
(SLOPE COIL UNITS ONLY)
A
7/8"DIA. K.O.
FOR LOW VOLTAGE
CONTROL WIRING
3/4"
OUTLET AIR
ALTERNATE
7/8",1 3/32",2"DIA.
FOR HIGH VOLTAGE
POWER WIRING
OPPOSITE SIDE
ALTERNATE
7/8"DIA. K.O.
FOR LOW VOLTAGE
CONTROL WIRING
7/8"
1 3/4"
BLOWER, CONTROL,
& ELECTRIC HEATER
ACCESS PANEL
OPENING
19 13/16"
1 1/4"
2 1/2"
RIGHT SIDE VIEW
INLET AIR
COIL ACCESS
PANEL
INLET AIR
2 5/8"
4 11/16"
FITTING
PANEL
LIQUID LINE CONNECTION
SUCTION LINE CONNECTION
LIQUID LINE
CONNECTION
3 1/16"
E
LIQUID LINE
CONNECTION
10 7/16"
SUCTION LINE
CONNECTION
10 3/4"
6 3/16"
5"
OPENING
1"
9 1/2"
FILTER ACCESS
PANEL
D
SLOPE COIL DETAILS
INLET AIR
CONNECTION LOCATIONS SHOWN
FOR UPFLOW OR HORIZ.
LEFT APPLICATIONS
FRONT VIEW
ACCESS PANEL CONFIG. FOR
SLOPE COILS
DOWNFLOW OR HORIZ.
RIGHT APPLICATIONS
AND
"A" COILS
SHOWN WITH "A" COIL DETAILS CONNECTION
LOCATIONS FOR UPFLOW OR HORIZ. APPLICATIONS
DOWNFLOW APPLICATIONS
A10032
Fig. 1 -- FX4D -- English
4
DIMENSIONS (cont.)
NOTES:
1. CONDENSATE PAN DRAIN CAPS NOT SHOWN FOR CLARITY.
SLOPE COIL
2. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED.
AIRFLOW
2 3/16" TYP.
(2 PLACES)*
7/16" TYP.
(2 PLACES)*
AIRFLOW
3 1/4"
F
G
1" TYP.
(2 PLACES)*
PRIMARY DRAIN
1 1/4"
SECONDARY DRAIN
SECONDARY DRAIN
PRIMARY DRAIN
2 7/8"
1 1/4"
DOWNFLOW
(FIELD CONVERTED)
FX4D
7/16" TYP.
(4 PLACES)*
1" TYP.
(2 PLACES)*
2 9/16"
3 1/4"
2 3/16"
TYP.
(2 PLACES)*
UPFLOW
(AS SHIPPED)
PRIMARY DRAIN
SECONDARY DRAIN
5/16"
TYP.*
PRIMARY DRAIN
1 13/16"
TYP.*
SECONDARY DRAIN
1 1/4"
1 5/8"
5/16"
TYP.*
2 1/8"
1 13/16"
TYP.
1/2"
TYP.*
1 1/4"
7/8"
TYP.*
F
1/2"
TYP.*
7/8"
TYP.*
HORIZ. RIGHT
(FIELD CONVERTED)
PRIMARY DRAIN
2 3/16" TYP.
(2 PLACES)*
3 1/16"
1 1/2"
5/16"
TYP*
5 7/8"
1 3/16"
7/8"
TYP*
G
5"
AIRFLOW
1/2"
TYP*
4 3/4"
HORIZ. LEFT
(AS SHIPPED)
1 13/16"
TYP*
SECONDARY DRAIN
F
1 5/8"
2 7/8"
A-COIL
* HORIZONTAL MOUNT LOCATIONS - DIMPLES PROVIDED IN TOP PANEL,
AND BACK OF CABINET. IN CABINET BOTTOM. HOLES PROVIDED
AIRFLOW
5/16"
TYP.*
1" TYP.
(2 PLACES)
7 7/8"
HORIZ. LEFT
(AS SHIPPED)
SECONDARY DRAIN
7/16" TYP.
(4 PLACES)
SECONDARY DRAIN
PRIMARY DRAIN
PRIMARY DRAIN
PRIMARY DRAIN
5/16"
TYP.*
SECONDARY DRAIN
1" TYP.
(2 PLACES)*
3" 1/8
1 1/2"
7/16" TYP,
(4 PLACES)*
DOWNFLOW
(FIELD CONVERTED)
3 1/16"
5 7/8"
7 7/8"
1 13/16"
TYP.
1 3/16"
1/2"
TYP.*
HORIZ. RIGHT
(FIELD CONVERTED)
7/8"
TYP.*
2 3/16"
TYP.
(2 PLACES)*
4 3/4"
2 11/16"
UPFLOW
(AS SHIPPED)
A10033
Fig. 2 -- FX4D -- English
5
DIMENSIONS (cont.)
UNIT
A
B
C
D
E
F
G
H
COIL
CONFIGURATION
J
SLOPE
"A"
SHIPPING WT
(Kgs)
NON TIN-COATED
SHIPPING WT
(Kgs)
TIN-COATED
FX4DNF019
1260.5
447.7
400.0
396.9
390.5
587.4
600.1
-
431.8
X
-
55.3
55.3
FX4DNF025
1260.5
447.7
400.0
396.9
390.5
587.4
600.1
-
431.8
X
-
55.3
55.3
FX4DNF031
1357.3
536.6
489.0
485.8
487.4
684.2
698.5
-
482.6
X
-
66.2
66.2
FX4DNF037
1260.5
536.6
489.0
485.8
398.5
595.3
587.4
-
-
-
X
71.2
71.2
FX4DNF043
1260.5
536.6
489.0
485.8
398.5
595.3
587.4
-
-
-
X
71.2
71.2
FX4DNF049
1357.3
627.1
577.8
576.3
495.3
692.2
684.2
-
-
-
X
84.1
84.1
FX4DNF061
1503.4
627.1
577.8
576.3
641.4
836.6
828.7
-
-
-
X
91.2
91.2
NOTE:
1. SERIES DESIGNATION IS THE 14TH POSITION
OF UNIT PRODUCT NUMBER
NOTE: ALLOW 533.4 FROM FRONT
FOR SERVICE
UNIT CONNECTION SIZES
2. ALL DIMENSIONS ARE IN "MM" UNLESS NOTED.
SUCTION: 018 THRU 025 - 15.88 I.D. SWEAT
030 THRU 037 - 19.05 I.D. SWEAT
042 THRU 061 - 22.23 I.D. SWEAT
LIQUID: 9.53 I.D. SWEAT
CONDENSATE: 19.0 FPT
560.4
258.8
FX4D
19.0
OUTLET AIR
NOTE: MODULAR
UNITS WILL HAVE
A TWO-PIECE
CABINET
OPTIONAL FIELD CONVERTED
RIGHT SIDE RETURN OPENING
(SLOPE COIL UNITS ONLY)
A
47.6
22.2
ALTERNATE
22.23, 27.78, 50.80 DIA. K.O.'S
FOR HIGH VOLTAGE
POWER WIRING
OPPOSITE SIDE
ALTERNATE
22.23 DIA. K.O.
FOR LOW VOLTAGE
CONTROL WIRING
22.23, 27.78
50.80 DIA. K.O.'S
FOR HIGH VOLTAGE
POWER WIRING
279.4
25.4
54.0
38.1
22.23 DIA. K.O.
FOR LOW VOLTAGE
CONTROL WIRING
J
30.2
MAX
25.4
49.2
TOP VIEW
H
FOR
MODULAR UNITS
482.6
34.9
44.4
B
C
23.8
OPENING
503.2
31.8
DISCONNECT OR
CIRCUIT BREAKER
LOCATION
63.5
RIGHT SIDE VIEW
INLET AIR
BLOWER, CONTROL,
& ELECTRIC HEATER
ACCESS PANEL
COIL ACCESS
PANEL
INLET AIR
66.7
119.1
FITTING
PANEL
LIQUID LINE CONNECTION
SUCTION LINE CONNECTION
LIQUID LINE
CONNECTION
77.8
E
LIQUID LINE
CONNECTION
265.1
SUCTION LINE
CONNECTION
273.0
157.2
127.0
OPENING
25.4
241.3
FILTER ACCESS
PANEL
D
SLOPE COIL DETAILS
CONNECTION LOCATIONS SHOWN
FOR UPFLOW OR HORIZ.
LEFT APPLICATIONS
INLET AIR
FRONT VIEW
ACCESS PANEL CONFIG. FOR
SLOPE COILS
DOWNFLOW OR HORIZ.
RIGHT APPLICATIONS
AND
"A" COILS
SHOWN WITH "A" COIL DETAILS CONNECTION
LOCATIONS FOR UPFLOW OR HORIZ. APPLICATIONS
DOWNFLOW APPLICATIONS
A10034
Fig. 3 -- FX4D -- Metric
6
DIMENSIONS (cont.)
NOTES:
1. CONDENSATE PAN DRAIN CAPS NOT SHOWN FOR CLARITY.
SLOPE COIL
2. ALL DIMENSIONS ARE IN "MM" UNLESS NOTED.
11.1 TYP.
(2 PLACES)*
AIRFLOW
AIRFLOW
55.6 TYP.
(2 PLACES)*
25.4 TYP.
(2 PLACES)*
PRIMARY DRAIN
82.6
F
G
SECONDARY DRAIN
31.8
SECONDARY DRAIN
PRIMARY DRAIN
73.0
31.8
82.6
55.6
TYP.
(2 PLACES)*
DOWNFLOW
(FIELD CONVERTED)
65.1
FX4D
11.1 TYP.
(4 PLACES)*
25.4 TYP.
(2 PLACES)*
UPFLOW
(AS SHIPPED)
PRIMARY DRAIN
SECONDARY DRAIN
PRIMARY DRAIN
8.0
TYP.*
46.0
TYP.*
SECONDARY DRAIN
31.8
41.3
54.0
46.0
TYP.*
31.8
8.0
TYP.*
12.7
TYP.*
12.7
TYP.*
22.2
TYP.*
F
41.3
73.0
22.2
TYP.*
HORIZ. RIGHT
(FIELD CONVERTED)
HORIZ. LEFT
(AS SHIPPED)
127.0
A-COIL
* HORIZONTAL MOUNT LOCATIONS - DIMPLES PROVIDED IN TOP PANEL,
AND BACK OF CABINET. IN CABINET BOTTOM. HOLES PROVIDED
3.45 DIA. HORIZONTAL HANGING HARDWARE TO BE FIELD SUPPLIED.
PRIMARY DRAIN
46.0
TYP*
SECONDARY DRAIN
AIRFLOW
55.6 TYP.
(2 PLACES)*
AIRFLOW
12.7
TYP*
F
22.2
TYP*
G
120.6
77.8
38.1
8.0
TYP*
149.2
30.2
25.4 TYP.
(2 PLACES)
200.0
HORIZ. LEFT
(AS SHIPPED)
SECONDARY DRAIN
11.1 TYP.
(4 PLACES)
SECONDARY DRAIN
PRIMARY DRAIN
PRIMARY DRAIN
PRIMARY DRAIN
8.0
TYP.*
SECONDARY DRAIN
25.4 TYP.
(2 PLACES)*
79.4
11.1 TYP,
(4 PLACES)*
38.1
DOWNFLOW
(FIELD CONVERTED)
149.2
200.0
46.0
TYP.
30.2
77.8
12.7
TYP.*
HORIZ. RIGHT
(FIELD CONVERTED)
22.2
TYP.*
55.6
TYP.
(2 PLACES)*
120.6
68.3
UPFLOW
(AS SHIPPED)
A10035
Fig. 4 -- FX4D -- Metric
7
PHYSICAL DATA
FX4D
ORDERING NO.
FX4DNF0190,T)00
FX4DNF019005
FX4DNF025(0,T)00
FX4DNF025005
FX4DNF031(0,T)00
FX4DNF031008
FX4DNF037(0,T)00
FX4DNF037010
FX4DNF043(0,T)00
FX4DNF043010
FX4DNF049(0,T)00
FX4DNF049010
FX4DNF061(0,T)00
FX4DNF061010
FX4DNF061015
FACTORY
INSTALLED
HEAT (kW)
--5
--5
--8
--10
--10
--10
--10
15
NOMINAL COOLING
CAPACITY (Btuh)
18,000
24,000
30,000
36,000
42,000
48,000
60,000
FX4DNB031T00
---
30,000
FX4DNB037T00
---
36,000
FX4DNB043T00
---
42,000
FX4DNB049T00
---
48,000
FX4DNB061T00
---
60,000
DIMENSIONS
Height
Width
Depth
SHIPPING
WEIGHT
49 5/8--- in
1261mm
49 5/8--- in
1261mm
53 7/16--- in
1357mm
49 5/8--- in
1261mm
49 5/8--- in
1260mm
53 7/16--- in
1357mm
17 5/8--- in
447mm
17 5/8--- in
447mm
21 1/8--- in
536mm
21 1/8--- in
536mm
21 1/8--- in
536mm
24 11/16--- in
627mm
22--- 1/16--- in
560mm
22--- 1/16--- in
560mm
22--- 1/16--- in
560mm
22--- 1/16--- in
560mm
22--- 1/16--- in
560mm
22--- 1/16--- in
560mm
122 lb
55 kg
122 lb
55 kg
146 lb
66 kg
157 lb
71 kg
157 lb
71 kg
185 lb
84 kg
59 3/16--- in
1503mm
24 11/16--- in
627mm
22--- 1/16--- in
560mm
201 lb
91 kg
53 7/16--- in
1357mm
53 7/16--- in
1357mm
53 7/16--- in
1357mm
53 7/16--- in
1357mm
59 3/16--- in
1503mm
21 1/8--- in
536mm
21 1/8--- in
536mm
21 1/8--- in
536mm
24 11/16--- in
627mm
24 11/16--- in
627mm
22--- 1/16--- in
560mm
22--- 1/16--- in
560mm
22--- 1/16--- in
560mm
22--- 1/16--- in
560mm
22--- 1/16--- in
560mm
146 lb
66 kg
175 lb
79kg
175 lb
79kg
185 lb
84 kg
201 lb
91 kg
6th digit: B --- Modular cabinet, F --- Single piece cabinet
10th digit: 0 --- Standard copper coil, T --- ArmorCoatt
SPECIFICATIONS
MODEL FX4D
019
025
031
037
043
049
061
COIL
Puronr Refrigerant
TXV --- factory installed hard --- shutoff, bi--- flow type for heat pump application
Metering Device
TXV
2 ton
3 ton
4 ton
Rows/Fins Per In.
3 / 14.5
Face Area (Sq. Ft.)
2.97
3.46
4.45
5.93
7.42
Configuration
Slope
A
FAN
CFM (Nominal)
600
800
1000
1200
1400
1600
2000
Motor Type (ECM)
X--- 13
X--- 13
X--- 13
X--- 13
X--- 13
X--- 13
X--- 13
Motor Hp
1/3
1/3
1/2
1/2
1/2
3/4
3/4
FILTER
21--- 1/2--- in / 546 mm X
16--- 3/8--- in / 417 mm
19--- 7/8--- in / 505 mm
23--- 5/16--- in / 585 mm
CABINET CONFIGURATION OPTIONS
1--- pc
1--- pc / Modular
8
PERFORMANCE DATA
MODEL &
SIZE
FX4D 019
FX4D 025
FX4D 031
FX4D 037
FX4D 043
FX4D 049
FX4D 061
BLOWER
SPEED
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
0.10
0.20
0.30
0.40
0.50
0.60
776
683
683
631
625
956
825
825
726
631
1189
1041
1041
924
779
1363
1237
1237
1095
1014
1519
1437
1437
1257
1237
1757
1664
1664
1459
1301
2030
1811
1811
1665
1462
745
644
644
563
524
920
795
795
695
563
1151
998
998
876
693
1332
1206
1206
1058
885
1490
1403
1403
1226
1206
1725
1626
1626
1420
1241
1995
1775
1775
1632
1418
696
589
589
500
457
891
757
757
635
500
1104
944
944
817
628
1294
1160
1160
1007
773
1454
1366
1366
1191
1160
1693
1593
1593
1379
1195
1961
1740
1740
1593
1371
660
548
548
443
417
851
722
722
598
443
1050
886
886
752
571
1253
1121
1121
951
673
1419
1333
1333
1141
1121
1653
1552
1552
1336
1150
1927
1703
1703
1556
1327
609
494
494
409
367
816
674
674
543
409
1003
837
837
704
526
1207
1070
1070
888
609
1379
1294
1294
1090
1070
1614
1517
1517
1298
1102
1888
1664
1664
1507
1278
572
461
461
361
319
780
634
634
509
361
959
772
772
660
476
1157
1013
1013
824
549
1332
1245
1245
1033
1013
1576
1477
1477
1259
1039
1842
1613
1613
1453
1228
--- Airflow outside 450 cfm/ton.
NOTES:
1. Airflow based upon dry coil at 230v with factory--approved filter and electric heater (2 element heater sizes 018 through 037, 3 element
heater sizes 043 through 061).
2. Airflow at 208 volts is approximately the same as 230 volts because the X--13 motor is a constant torque motor. The torque doesn’t drop
off at the speeds the motor operates.
3. To avoid potential for condensate blowing out of drain pan prior to making drain trap:
Return static pressure must be less than 0.40 in wc.
Horizontal applications of 043 -- 061 sizes must have supply static greater than 0.20 in wc.
4. Airflow above 400 cfm/ton on 049--061 size could result in condensate blowing off coil or splashing out of drain pan.
9
FX4D
AIRFLOW PERFORMANCE (CFM)
PERFORMANCE DATA (cont.)
GROSS COOLING CAPACITIES (MBH) -- PURONr REFRIGERANT
UNIT
SIZE
FX4D
FX4D
019
FX4D
025
FX4D
031
FX4D
037
FX4D
043
FX4D
049
FX4D
061
INDOOR COIL
AIR
CFM
EWB
72 / 22
67 / 19
525
62 / 17
72 / 22
67 / 19
600
62 / 17
72 / 22
67 / 19
675
62 / 17
72 / 22
67 / 19
700
62 / 17
72 / 22
67 / 19
800
62 / 17
72 / 22
67 / 19
900
62 / 17
72 / 22
67 / 19
875
62 / 17
72 / 22
67 / 19
1000
62 / 17
72 / 22
67 / 19
1125
62 / 17
72 / 22
67 / 19
1050
62 / 17
72 / 22
67 / 19
1200
62 / 17
72 / 22
67 / 19
1350
62 / 17
72 / 22
67 / 19
1225
62 / 17
72 / 22
67 / 19
1400
62 / 17
72 / 22
67 / 19
1575
62 / 17
72 / 22
67 / 19
1400
62 / 17
72 / 22
67 / 19
1600
62 / 17
72 / 22
67 / 19
1800
62 / 17
72 / 22
67 / 19
1600
62 / 17
72 / 22
67 / 19
1750
62 / 17
72 / 22
67 / 19
2000
62 / 17
TC
36
29
23
40
33
26
44
36
29
48
39
31
53
43
34
57
47
37
59
48
38
65
53
42
71
58
46
67
54
43
74
60
48
81
66
52
79
64
51
87
71
56
95
77
61
90
73
58
100
81
65
109
89
70
109
89
71
117
95
76
129
105
84
35 / 2
SHC
19
19
19
21
21
21
23
23
24
25
25
25
27
28
28
30
30
31
30
31
31
33
34
35
36
37
38
36
37
37
40
41
41
43
45
46
41
42
43
46
47
48
50
51
52
48
49
49
53
54
55
58
59
60
57
58
59
61
62
63
67
69
70
BF
0.00
0.01
0.02
0.00
0.02
0.02
0.00
0.02
0.03
0.00
0.03
0.03
0.00
0.04
0.04
0.00
0.05
0.05
0.00
0.03
0.04
0.00
0.04
0.05
0.00
0.05
0.06
0.00
0.03
0.03
0.00
0.04
0.04
0.00
0.05
0.05
0.00
0.04
0.04
0.00
0.05
0.06
0.00
0.06
0.07
0.00
0.03
0.03
0.00
0.04
0.04
0.00
0.05
0.05
0.00
0.02
0.03
0.00
0.03
0.03
0.00
0.04
0.04
SATURATED TEMPERATURE LEAVING EVAPORATOR (_F / °C)
40 / 4
45 / 7
50 / 10
TC
SHC
BF
TC
SHC
BF
TC SHC
BF
33
17
0.00
28
15
0.00
24
13
0.00
26
17
0.01
22
15
0.02
17
13
0.02
20
17
0.02
16
15
0.02
12
12
0.07
36
19
0.00
32
17
0.00
27
14
0.01
29
19
0.02
24
17
0.02
19
14
0.02
22
19
0.02
17
17
0.03
13
13
0.08
40
21
0.00
35
18
0.00
29
16
0.02
32
21
0.03
26
18
0.03
21
16
0.03
24
21
0.03
19
19
0.04
15
15
0.10
43
22
0.00
37
19
0.00
31
17
0.02
34
22
0.03
28
20
0.03
22
17
0.03
26
23
0.03
20
20
0.04
16
16
0.10
47
24
0.00
41
21
0.01
35
18
0.03
37
25
0.04
31
22
0.04
25
19
0.04
29
25
0.04
23
22
0.05
18
18
0.12
51
27
0.00
45
23
0.03
38
20
0.04
41
27
0.05
34
24
0.05
27
21
0.05
31
28
0.05
25
24
0.06
20
20
0.14
53
27
0.00
46
24
0.01
38
20
0.02
42
28
0.03
35
24
0.04
27
21
0.04
32
28
0.04
25
24
0.04
20
20
0.11
58
30
0.00
51
26
0.02
42
23
0.04
46
31
0.04
38
27
0.05
30
23
0.05
35
31
0.05
28
27
0.06
22
22
0.13
63
33
0.00
55
29
0.03
46
25
0.05
50
33
0.05
42
29
0.06
33
25
0.06
38
34
0.06
30
30
0.07
24
24
0.15
60
32
0.00
52
28
0.00
44
24
0.02
47
33
0.03
40
29
0.03
31
25
0.03
36
33
0.03
29
29
0.04
22
22
0.10
66
36
0.00
58
31
0.01
48
27
0.03
52
36
0.04
44
32
0.04
35
27
0.04
40
37
0.04
32
32
0.05
25
25
0.12
72
39
0.00
63
34
0.03
53
30
0.04
57
40
0.05
48
35
0.05
38
30
0.05
44
41
0.05
35
36
0.06
28
28
0.14
71
37
0.00
62
33
0.02
52
28
0.03
56
38
0.04
47
33
0.04
37
29
0.04
43
38
0.04
34
34
0.05
27
27
0.12
78
41
0.00
68
36
0.03
57
31
0.04
62
42
0.05
52
37
0.05
41
32
0.05
47
43
0.06
38
38
0.06
30
30
0.14
85
45
0.00
74
39
0.04
62
34
0.05
67
46
0.06
56
40
0.06
44
35
0.07
51
47
0.07
41
41
0.08
33
33
0.17
81
43
0.00
71
38
0.00
59
32
0.02
64
44
0.03
54
38
0.03
42
33
0.03
49
44
0.03
39
39
0.04
30
30
0.10
89
48
0.00
78
42
0.01
65
36
0.03
71
48
0.04
59
43
0.04
47
36
0.04
54
49
0.04
43
43
0.05
34
34
0.12
97
52
0.00
85
46
0.03
71
39
0.04
77
53
0.05
65
47
0.05
51
40
0.05
59
54
0.05
47
48
0.06
37
37
0.14
98
51
0.00
86
45
0.00
73
39
0.01
78
52
0.02
66
46
0.02
52
39
0.03
60
52
0.03
48
46
0.03
37
37
0.09
105
55
0.00
92
48
0.01
78
41
0.02
84
56
0.03
70
49
0.03
56
42
0.03
64
56
0.03
51
50
0.04
40
40
0.10
116
60
0.00
102
53
0.02
86
46
0.03
92
62
0.04
78
54
0.04
62
47
0.04
71
63
0.04
57
55
0.05
45
45
0.12
See Notes following table.
10
TC
19
12
10
21
13
11
23
15
12
25
16
13
27
17
15
30
19
16
30
19
16
33
21
18
36
23
20
35
22
18
38
24
21
41
27
23
41
26
22
45
29
25
48
31
27
47
30
25
51
33
28
56
36
31
58
37
31
62
40
33
68
44
37
55 / 13
SHC
11
10
10
12
12
11
13
13
12
14
14
13
15
16
15
17
17
16
17
17
16
19
19
18
20
21
20
20
20
18
22
23
21
25
25
23
23
24
22
26
26
25
28
29
27
27
27
25
30
30
28
33
33
31
32
33
31
35
35
33
38
39
37
BF
0.01
0.02
0.24
0.02
0.03
0.25
0.02
0.03
0.26
0.03
0.04
0.26
0.04
0.05
0.28
0.05
0.06
0.29
0.03
0.04
0.27
0.04
0.05
0.29
0.05
0.07
0.30
0.03
0.04
0.26
0.04
0.05
0.28
0.05
0.06
0.29
0.04
0.05
0.28
0.05
0.06
0.29
0.06
0.07
0.31
0.03
0.04
0.26
0.04
0.05
0.28
0.05
0.06
0.29
0.02
0.03
0.24
0.02
0.03
0.25
0.03
0.05
0.27
PERFORMANCE DATA (cont)
EWB --- Entering Wet Bulb _F (_C)
BF --- Bypass Factor
LWB --- Leaving Wet Bulb _F (_C)
MBH --- 1000 Btuh
NOTES:
TC --- Gross Cooling Capacity 1000 Btuh
SHC CORRECTION FACTOR
1. Contact manufacturer for cooling capacities at conditions
other than shown in table.
2. Formulas:
Leaving db = entering db --sensible heat cap.
1.09 x CFM
Leaving wb = wb corresponding to enthalpy of air leaving
coil (hlwb)
hlwb = hewb --total capacity (Btuh)
4.5 x CFM
where hewb = enthalpy of air entering coil. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 80_F (27_C) db temperature of air entering coil. Below 80_F (27_C) db, subtract (Correction Factor x CFM) from SHC. Above 80_F (27_C) db, add (Correction Factor x CFM) to SHC.
4. Bypass Factor = 0 indicates no psychometric solution. Use
bypass factor of next lower EWB for approximation.
ENTERING AIR DRY-- BULB TEMPERATURE (_F)
BYPASS
FACTOR
79
78
77
76
75
Under 75
81
82
83
84
85
Over 85
ENTERING AIR DRY-- BULB TEMPERATURE (_C)
26
25
25
24
24
Under 75
27
28
28
29
29
Over 85
Use
formula
shown
below
Correction Factor
0.10
.098
1.96
2.94
3.92
4.91
0.20
0.87
1.74
2.62
3.49
4.36
0.30
0.76
1.53
2.29
3.05
3.82
Interpolation is permissible.
Correction Factor = 1.09 x (1 --- BF) x (db --- 80)
FX4D
CFM --- Cubic Ft per Minute
SHC --- Gross Sensible Capacity 1000
Btuh
MINIMUM CFM AND MOTOR SPEED SELECTION
FAN COIL SIZES
FX
019
025
031
037
043
049
061
*
3
525
700
—
—
—
—
—
5
525
700
875
1050
—
—
—
8
525
700
875
970
1225
1400
1750
9
—
—
—
970
1225
1400
1750
HEATER kW
10
15
600*
—
700
775*
875
875
970
920
1225
1225
1400
1400
1750
1750
18
—
—
—
—
1225
1400
1750
20
—
—
1060*
1040
1225
1400
1750
24
—
—
—
—
—
1400
1750
30
—
—
—
—
—
1400
1750
Indicates medium speed (blue). All other motor speeds at low tap.
AIR DELIVERY PERFORMANCE CORRECTION COMPONENT PRESSURE DROP (in wc)
AT INDICATED AIRFLOW (DRY--TO--WET COIL)
FX
SIZE
019
025
031
037
043
049
061
500
0.034
0.016
--- ----- ----- ----- ----- ---
600
0.049
0.027
--- ----- ----- ----- ----- ---
700
0.063
0.038
--- ----- ----- ----- ----- ---
800
--- --0.049
0.049
--- ----- ----- ----- ---
900
--- --0.059
0.059
--- ----- ----- ----- ---
1000
--- ----- --0.070
0.055
--- ----- ----- ---
1100
--- ----- --0.080
0.064
--- ----- ----- ---
CFM
1200 1300
--- ----- ----- ----- ----- ----- --0.073 0.081
0.049 0.056
--- ----- ----- ----- ---
11
1400
--- ----- ----- ----- --0.063
0.038
--- ---
1500
--- ----- ----- ----- --0.070
0.043
--- ---
1600
--- ----- ----- ----- ----- --0.049
0.027
1700
--- ----- ----- ----- ----- --0.054
0.031
1800
--- ----- ----- ----- ----- --0.059
0.035
1900
--- ----- ----- ----- ----- ----- --0.039
2000
--- ----- ----- ----- ----- ----- --0.043
PERFORMANCE DATA (cont)
FACTORY--INSTALLED FILTER STATIC PRESSURE DROP (in wc)
UNIT SIZE
FX4D
019, 025
031, 037, 043
049, 061
400
0.012
-----
600
0.022
-----
800
0.048
0.036
---
CFM
1200
--0.07
---
1000
0.072
0.051
---
1400
--0.092
0.073
1600
--0.12
0.086
1800
----0.105
2000
----0.13
ELECTRIC HEATER STATIC PRESSURE DROP (in wc)
FX4D
019 --- 037
HEATER
ELEMENTS
kW
0
1
2
3
4
0
3, 5
8, 10
9, 15
20
EXTERNAL STATIC
PRESSURE
CORRECTION
+.02
+.01
0
–.02
–.04
043 --- 061
HEATER
ELEMENTS
KW
0
2
3
4
6
0
8, 10
9, 15
20
18, 24, 30
EXTERNAL STATIC
PRESSURE
CORRECTION
+.04
+.02
0
–.02
–.10
The airflow performance data was developed using fan coils with 10 ---kW electric heaters (2 elements) in the 019 through 037 size units and 15 ---kW heaters (3
elements) in the 043through 061 size units. For fan coils with heaters of a different number of elements, the external available static at a given CFM from the
curve may be corrected by adding or subtracting available external static pressure as indicated above.
ACCESSORY ELECTRIC HEATERS
*
HEATER
PART NO.
kW @
240V
VOLTS/
PH
STAGES (kW
OPERATING)
KFCEH0401N03
KFCEH0501N05
KFCEH0801N08
KFCEH0901N10
KFCEH3201F20
KFCEH1601315
KFCEH2001318
KFCEH3401F24
KFCEH3501F30
KFCEH2401C05
KFCEH2501C08
KFCEH2601C10
KFCEH3301C20
KFCEH2901N09
KFCEH3001F15
KFCEH3101C15
3
5
8
10
20
15
18
24
30
5
8
10
20
9
15
15
230/1
230/1
230/1
230/1
230/1
230/3
230/3
230/3*
230/3*
230/1
230/1
230/1
230/1
230/1{
230/1
230/1
3
5
8
10
5, 20
5, 15
6, 12, 18
8, 16, 24
10, 20, 30
5
8
10
5, 20
3, 9
5, 15
5, 15
INTERNAL
CIRCUIT
PROTECTION
None
None
None
None
Fuse}
None
None
Fuse
Fuse
Circuit Breaker
Circuit Breaker
Circuit Breaker
Circuit Breaker
None
Fuse}
Circuit Breaker
FAN COIL SIZE
USED WITH
HEATING CAP.**
@ 230V
018–024
018–060
018–060
018–060
030–060
036–060
042–060
048, 060
048, 060
018–060
018–060
018–060
030–060
036–060
024–060
024–060
9,400
15,700
25,100
31,400
62,800
47,100
56,500
78,300
94,100
15,700
25,100
31,400
62,800
28,200
47,100
47,100
Field convertible to 1 phase.
{ Field convertible to 3 phase.
} Single point wiring kit required for these heaters in Canada.
** Blower Motor heat not included.
ESTIMATED SOUND POWER LEVEL (dBA)
*
UNIT SIZE
FX
CONDITIONS
OCTAVE BAND CENTER FREQUENCY*
CFM
Ext Static
Pressure
63
125
250
500
1000
2000
4000
019
600
0.25
64.7
60.7
56.7
53.7
51.7
49.7
45.7
025
800
0.25
66.0
62.0
58.0
55.0
53.0
51.0
47.0
031
1000
0.25
67.0
63.0
59.0
56.0
54.0
52.0
48.0
037
1200
0.25
67.8
63.8
59.8
56.8
54.8
52.8
48.8
043
1400
0.25
68.4
64.4
60.4
57.4
55.4
53.4
49.4
049
1600
0.25
69.0
65.0
61.0
58.0
56.0
54.0
50.0
061
2000
0.25
70.0
66.0
62.0
59.0
57.0
55.0
51.0
Estimated sound power levels have been derived using the method described in the 1987 ASHRAE HVAC Systems & Applications Handbook, Chapter 52,
p. 52.7.
12
ELECTRICAL DATA FOR UNITS WITH FACTORY--INSTALLED HEAT
SINGLE CIRCUIT
HEAT PACK
FX4DNF
MTR MTR VOLTS/PH/
INSTALLED Heater
MODEL NO. HP FLA
HZ
MCA
MOCP
MKFCEH
Amps
019005
025005
031008
037010
043010
049010
061010
061(0,T)015
1/3
1/3
1/2
1/2
1/2
3/4
3/4
3/4
2.8
2.8
4.1
4.1
4.1
6.0
6.0
6.0
208/230/1/60
208/230/1/60
208/230/1/60
208/230/1/60
208/230/1/60
208/230/1/60
208/230/1/60
208/230/1/60
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
0501N05
0501N05
0801N08
0901N10
0901N10
0901N10
0901N10
1501F15
18.1/20.0
18.1/20.0
28.9/32.0
36.2/40.0
36.2/40.0
36.2/40.0
36.2/40.0
54.2/59.9
26.1/28.5
26.1/28.5
41.3/45.2
50.4/55.1
50.4/55.1
52.8/57.5
52.8/57.5
75.3/82.4
30/30
30/30
45/50
60/60
60/60
60/60
60/60
80/90
DUAL CIRCUIT
Htr.
Htr.
MCA
MOCP
MCA
MOCP
Amps
Amps
L1/L2
L1/L2
L1/L2
L3/L4
L3/L4
L3/L4
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
36.2/40.0 52.8/57.5 60/60 18.1/20.0 22.6/25.0 25/25
MODEL NO.
MTR
HP
MTR
FLA
VOLTS/PH/HZ
FX4DNF019(0,T)00
FX4DNF025(0,T)00
FX4DNF031(0,T)00
FX4DNF037(0,T)00
FX4DNF043(0,T)00
FX4DNF049(0,T)00
FX4DNF061(0,T)00
FX4DNB031T00
FX4DNB037T00
FX4DNB043T00
FX4DNB049T00
FX4DNB061T00
1/3
1/3
1/2
1/2
1/2
3/4
3/4
1/2
1/2
1/2
3/4
3/4
2.8
2.8
4.1
4.1
4.1
6.0
6.0
4.1
4.1
4.1
6.0
6.0
208/230/1/60
208/230/1/60
208/230/1/60
208/230/1/60
208/230/1/60
208/230/1/60
208/230/1/60
208/230/1/60
208/230/1/60
208/230/1/60
208/230/1/60
208/230/1/60
SINGLE CIRCUIT
MAXIMUM
OVERCURRENT
MCA
PROTECTION
3.5
15
3.5
15
5.1
15
5.1
15
5.1
15
7.5
15
7.5
15
5.1
15
5.1
15
5.1
15
7.5
15
7.5
15
*
BRANCH CIRCUIT
MIN WIRE SIZE*
AWG
14
14
14
14
14
14
14
14
14
14
14
14
Use copper wire only. Use 75_C only in this application. When using non ---metallic (NM) sheathed cable, wire size required should be based on that of 60_C
conductors, instead of wire sizes shown in table above per NEC Article 336 ---26.
NOTE: If branch circuit wire length exceeds 100 ft (30 m), consult NEC 215 ---2 to determine maximum wire length. Use 2% voltage drop.
FLA --- Full Load Amps
13
FX4D
ELECTRICAL DATA FOR UNITS WITHOUT ELECTRICAL HEAT
14
18.0
18.0
22.5
22.5
5
5
8
8
9
9
10
10
15
15
15
18
20
20
24
24
30
30
KFCEH2401C051
KFCEH2401C052
KFCEH0801N08
KFCEH2501C08
KFCEH2901N09
KFCEH2901N09**
KFCEH0901N10
KFCEH2601C10
KFCEH3001F15
KFCEH3101C15
KFCEH1601315
KFCEH2001318
KFCEH3201F20
KFCEH3301C20
15.0
13.5
11.3
11.3
11.3
7.5
7.5
6.8
6.8
6.0
6.0
3.8
3.8
3.8
1
3
1
3
1
1
3
3
1
1
1
1
3
1
1
1
1
1
1
1
1
P
H
A
S
E
Fuse
Fuse
Fuse
Fuse
Ckt Bkr
Fuse
None
None
Ckt Bkr
Fuse
Ckt Bkr
None
None
None
Ckt Bkr
None
Ckt Bkr
Ckt Bkr
None
None
None
INTERNAL
CIRCUIT
PROTECTION
109.0/120.0
62.6/69.2
86.7/95.5
50.1/55.4
—
72.3/79.9
37.6/41.5
31.3/34.6
—
54.2/59.9
36.2/40.0
36.2/40.0
18.8/20.8
32.8/36.0
28.9/32.0
28.9/32.0
18.1/20.0
18.1/20.0
18.1/20.0
18.1/20.0
10.9/12.0
Single
Circuit
—
—
—
—
36.2/40.0
36.2/40.0
—
—
36.2/40.0
36.2/40.0
—
—
—
—
—
—
—
—
—
—
—
L1,l2
—
—
—
—
36.2/40.0
36.2/40.0
—
—
18.1/20.0
18.1/20.0
—
—
—
—
—
—
—
—
—
—
—
L3,L4
Dual Circuit
HEATER AMPS
208/230V
144.8/158.5
86.8/95.0
116.9/127.9
71.2/77.8
—
98.9/108.4
55.5/60.4
47.7/51.8
—
76.3/83.4
53.8/58.5
53.8/58.5
32.0/34.5
49.5/53.5
44.7/48.5
44.7/48.5
31.2/33.5
26.0/28.4
31.2/33.5
26.0/28.4
15.9/17.3
Single
Circuit
—
—
—
—
53.8/58.5
53.8/58.5
—
—
53.8/58.5
53.8/58.5
—
—
—
—
—
—
—
—
—
—
—
L1,L2
—
—
—
—
45.3/50.0
45.3/50.0
—
—
22.7/25.0
22.7/25.0
—
—
—
—
—
—
—
—
—
—
—
L3,L4
Dual Circuit
Min Ampacity
208/230V*
kW
22.5
18.0
208V
1
1
P
H
A
S
E
L1,L2
36.2/40.0
28.9/32.0
36.2/40.0
28.9/32.0
L3,L4
HEATER AMPS
208/230V
L5,L6
36.2/40.0
28.9/32.0
L1,L2
53.8/58.5
44.7/48.5
45.3/50.0
36.2/40.0
L3,L4
MIN AMPACITY
208/230V*
L5,L6
45.3/50.0
36.2/40.0
—
—
—
—
8/8
8/8
—
—
10/10
10/10
—
—
—
—
—
—
—
—
—
—
—
6/6
8/8
L1,L2
8/8
8/8
L3,L4
8/8
8/8
L5,L6
—
—
—
—
10/10
10/10
—
—
10/10
10/10
—
—
—
—
—
—
—
—
—
—
—
10/10
10/10
150/175
90/100
125/150
80/80
—
100/110
60/70
50/60
—
80/90
60/60
60/60
35/35
50/60
45/50
45/50
35/35
30/30
35/35
30/30
20/20
Single
Circuit
60/60
45/50
L1,L2
50/50
40/40
L3,L4
50/50
40/40
L5,L6
—
—
—
—
60/60
60/60
—
—
60/60
60/60
—
—
—
—
—
—
—
—
—
—
—
L1,L2
117/150
97/98
115/116
94/95
—
85/109
76/77
56/90
—
88/89
78/80
78/80
83/85
54/87
59/60
59/60
85/88
66/66
85/88
66/66
67/68
Single
Circuit
78/80
59/60
L1,L2
59/59
73/73
L3,L4
59/59
73/73
L5,L6
—
—
—
—
78/80
78/80
—
—
78/80
78/80
—
—
—
—
—
—
—
—
—
—
—
L1,L2
—
—
—
—
59/59
59/59
—
—
75/76
75/76
—
—
—
—
—
—
—
—
—
—
—
L3,L4
Dual Circuit
Max Wire Length
208/230V (Ft)‡
MAX WIRE LENGTH
208/230V (FT)‡
—
—
—
—
50/50
50/50
—
—
25/25
25/25
—
—
—
—
—
—
—
—
—
—
—
L3,L4
Dual Circuit
Max Fuse/Ckt Bkr Amps
208/230V
MAX FUSE/CKT BKR
AMPS
208/230V
—
—
—
—
10/10
10/10
—
—
10/10
10/10
—
—
—
—
—
—
—
—
—
—
—
L3,L4
Dual Circuit
L1, L2
MIN GND
WIRE SIZE
208/230V
6/6
8/8
6/6
8/8
—
8/6
10/8
10/10
—
8/8
10/10
10/10
10/10
10/10
10/10
10/10
10/10
10/10
10/10
10/10
12/12
Single
Circuit
Min Gnd Wire Size
208/230V
BRANCH CIRCUIT
Includes blower motor amps of largest fan coil used with heater.
Copper wire must be used. If other than uncoated (non ---plated), 75_C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of
the National Electric Code (ANSI/NFPA 70).
} Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.
** Field convertible to 3 phase.
{{ Field convertible to 1 phase, single or multiple supply circuit.
NOTES:
1. For fan coil sizes 018 ---037.
2. For fan coil sizes 042 ---061.
3. Single circuit application of F15 and F20 heaters requires single ---point wiring kit accessory.
30
KFCEH3501F30††
*
{
24
240V
KFCEH3401F24††
HEATER PART
NO.
—
—
—
—
6/6
6/6
—
—
6/6
6/6
—
—
—
—
—
—
—
—
—
—
—
L3, L4
MIN WIRE SIZE (AWG)
208/230V†
0/00
3/3
1/1
4/4
—
3/2
6/6
8/6
—
4/4
6/6
6/6
8/8
8/6
8/8
8/8
8/8
10/10
8/8
10/10
12/12
L1, L2
Dual Circuit
Min Wire Size (AWG)
208/230V†
Single
Circuit
FIELD MULTIPOINT WIRING OF 24--AND 30--kW SINGLE PHASE
KFCEH3501F30††
KFCEH3401F24††
15.0
5
KFCEH0501N052
3.8
5
KFCEH0501N051
2.3
208v
3
240v
KFCEH0401N03
HEATER
PART NO.
kW
ACCESSORY ELECTRIC HEATER ELECTRICAL DATA
FX4D
HEATER ELECTRICAL DATA
FACTORY--INSTALLED HEATER OPTIONS*
MODEL
FX4DNF
*
019
5
025
5
031
8
037
10
043
10
049
10
061
10, 15
For field---installed heater/fan coil combinations, see Accessory Electric Heaters.
*
HEATER kW
PHASE
5
8
9
10
15
15
18
20
24
30
1
1
1/3
1
1
3
3
1
1/3
1/3
FUSE
QTY/SIZE
—
—
—
—
2/30–2/60
—
—
4/60
6/60
6/60
CKT BKR*
QTY/SIZE
1/60
1/60
—
1/60
2/60
—
—
2/60
—
—
All circuit breakers are 2 pole.
When using units with 20--, 24--, and 30--kW electric heaters, maintain a 1--in. (25 mm) clearance from combustible materials to discharge
plenum and ductwork and maintain a distance of 36 in. (914mm) from the unit. Use an accessory downflow base to maintain proper clearance
on downflow installations. Use flexible connectors between ductwork and unit to prevent transmission of vibration. When electric heater is
installed, use heat resistant material for flexible connector between ductwork and unit at discharge connection. Ductwork passing through
unconditioned space must be insulated and covered with vapor barrier
ACCESSORIES
1.
ITEM
Disconnect Kit
2.
Downflow Base Kit
3.
Downflow Conversion Kit {
4.
5.
6.
Downflow/Horizontal Conversion Gasket Kit
Horizontal Water Management Kit (25 pack) }
Single--- Point Wiring Kit
7.
Filter Kit (12 Pack)
8.
9.
10.
Fan Coil Filter Cabinet
(Fan Coil Filter Media)
PVC Condensate Trap Kit (50 pack)
Air Cleaner 240--- volt Conversion Kit
ACCESSORY PART NO.*
KFADK0201DSC
KFACB0201CFB
KFACB0301CFB
KFACB0401CFB
KFADC0201SLP
KFADC0401ACL
KFAHD0101SLP
KFAHC0125AAA
KFASP0101SPK
KFAFK0112SML
KFAFK0212MED
KFAFK0312LRG
KFAFK0412XXL
FNCCABCC0014
(FILXXFNC0014)
FNCCABCC0017
(FILXXFNC0017)
FNCCABCC0021
(FILXXFNC0021)
FNCCABCC0024
(FILXXFNC0024)
KFAET0150ETK
KEAVC0201240
* Factory authorized and listed, field---installed.
{ KFAHD0101SLP must also be purchased for downflow applications.
} KFAHD0101SLP must also be purchased for downflow or horizontal applications.
15
FAN COIL SIZE USED WITH
Cooling controls and heaters 3--- through 10--- kW
019, 025
031, 037, 043
049, 061
Slope Coil Units — 019, 024, 031
A--- Coil Units — 037, 043, 049, 061
All
All
Only with 15--- and 20--- kW Fused Heaters
NA
019, 025
031 037, 043
049, 061
NA
019, 025
031, 037, 043
049, 061
All
All
FX4D
ELECTRIC HEATER INTERNAL PROTECTION
FX4D
ACCESSORY KITS DESCRIPTION SUGGESTED AND REQUIRED USE
1. Disconnect Kit
The kit is used to disconnect electrical power to the fan coil so service or maintenance may be performed safely.
SUGGESTED USE: Units for 3-- through 10--kW electric resistance heaters and cooling controls.
2. Downflow Base Kit
This kit is designed to provide a 1--in. minimum clearance between unit discharge plenum, ductwork, and combustible materials. It
also provides a gap--free seal with the floor.
REQUIRED USE: This kit must be used whenever fan coils are used in downflow applications.
3. Downflow Conversion Kit
Fan coils are shipped from the factory for upflow or horizontal--left applications. Downflow conversion kits provide proper condensate
water drainage and support for the coil when used in downflow applications. Separate kits are available for slope coils and A--coils.
REQUIRED USE: This kit must be used whenever fan coils are used in downflow applications.
4. Downflow/Horizontal Conversion Gasket Kit
This kit provides the proper gasketing of units when applied in either a downflow or horizontal application.
REQUIRED USE: Fan coils in either downflow or horizontal applications.
5. Horizontal Applications -- Water Management Kit
This kit provides proper installation of fan coils under conditions of high static pressure and high relative humidity.
SUGGESTED USE: All fan coils.
6. Single Point Wiring Kit
The single point wiring kit acts as a jumper between L1 and L3 lugs, and between the L2 and L4 lugs. This allows the installer to run
two heavy--gauge, high--voltage wires into the fan coil rather than 4 light--gauge, high--voltage wires.
SUGGESTED USE: Fan coils with 15-- and 20--kW fused heaters only.
7. Filter Kit (12 pack)
The kit consists of 12 fan coil framed filters. These filters collect large dust particles from the return air entering the fan coil and
prevents them from collecting on the coil. This process helps to keep the coil clean, which increases heat transfer and, in turn, the
efficiency of the system.
SUGGESTED USE: To replace filters in fan coils.
REQUIRED USE: All units unless a filter grille is used.
8. Fan Coil Filter Cabinet
This cabinet is mounted to the fan coil on the return air end and designed to slip over the outer fan coil casing. The cabinets are
insulated using the same insulation as production fan coils. They are designed for the removal of particulates from indoor air using
FILXXFNC00(14, 17, 21, 24) media filter cartridges. These fan coil media filter cartridge kits are designed for the removal of particles
from indoor air. The cartridge is installed in the return air duct next to the air handler or further upstream.
SUGGESTED USE: All fan coils.
9. Condensate Drain Trap Kit
This kit consists of 50 PVC condensate traps. Each trap is pre--formed and ready for field installation. This deep trap helps the system
make and hold proper condensate flow even during blower initiation.
SUGGESTED USE: All fan coils.
10. Air Cleaner 240--volt Conversion Kit
The AIRA electronic air cleaner comes ready for 115--v operation.
REQUIRED USE: This kit is required when running 240--volt circuit to air cleaner.
Edition Date: 01/10
Catalog No: FX4D---01PD
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Replaces: NEW
Copyright 2010 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Printed in U.S.A.
16