Make CENTO™ Part of your Lighting Control Strategy

Wall-Switch Sensors
Ceiling Sensors
Power Packs
Make CENTO™ Part of your
Lighting Control Strategy
Universal Lighting Technologies, an industry leader in high efficiency
ballasts and other lighting control equipment, offers a full line of wallswitch and ceiling sensors plus power packs. Sensors can provide
substantial energy savings by turning lights on when needed and
off when not needed. These products leverage our extensive control
experience to set the new industry standard. CENTO™ products are
Title 24 and ASHRAE compliant.
CENTO™ sensors can be specified for energy saving control
strategies in spaces having intermittent lighting requirements including
office, commercial and industrial applications. When combined with
other controllable lighting measures, these sensors can enhance
savings provided by an already efficient system.
Functional options are diverse, from basic to feature-rich. Voltage
options include line-voltage (120/277VAC & 347VAC) and low-voltage
(24VAC pulse). Power Packs contain a power supply to convert line
voltage to low voltage, and are designed to work seamlessly with
our CENTO™ low voltage sensor line.
PIR technology breaks the “field of view” into narrow segments.
When a heat producing body enters a segment, or passes from
one segment and into another, occupancy is detected. Lenses
and detectors are carefully matched to optimize recognition of
human presence and motion within the target coverage area.
Features and Benefits:
• Occupancy control provides substantial
energy savings
• Self-adapting technology (user configurable)
tracks occupancy patterns and adjusts the turnoff delay to achieve optimal energy savings.
• Switch mount sensors provide 180º coverage
and include a hardened lens to resist damage
from vandalism.
• Ceiling mount sensors provide 360º coverage
and have an adjustable lens for fine tuning the
covered area.
• Vacancy Sensors (permanently configured
for manual-ON /auto-OFF) ensure additional
savings, and are mandated by some energy
codes.
• Photocells on some models eliminate “ON”
when ambient light is plentiful
51 Century Blvd., Suite 230 • Nashville, TN 37214 • 615-316-5100 • (TES) 1-800-BALLAST • www.unvlt.com
Switch Mounts, Passive Infrared (PIR)
Single-pole
Two-Pole
Single-pole
Two-Pole
Single-pole
Manual ON / Auto OFF
(non-configurable)
Item
Color
Coverage
Voltage
OSRUS1-W
White
180°
Fine-motion: 350sqft
Large-motion: 1050sqft
120/277VAC
OSR3S1-W
White
180°
Fine-motion: 350sqft
Large-motion: 1050sqft
347VAC
OSRUS2-P-W
White
OSRUS2-P-G
Gray
120/277VAC
OSRUS2-P-I
Ivory
180°
Fine-motion: 350sqft
Large-motion: 1050sqft
OSR3S2-P-W
White
OSR3S2-P-G
Gray
347VAC
OSR3S2-P-I
Ivory
180°
Fine-motion: 350sqft
Large-motion: 1050sqft
VSRUS1-W
White
180°
Fine-motion: 350sqft
Large-motion: 1050sqft
120/277VAC
VSRUS2-P-W
White
VSRUS2-P-G
Gray
120/277VAC
VSRUS2-P-I
Ivory
180°
Fine-motion: 350sqft
Large-motion: 1050sqft
180°
Fine-motion: 350sqft
Large-motion: 1050sqft
24VAC
Rectified Pulse
Output
OSRPS1-P-W
Two-Pole
Auto ON / Auto OFF
(configurable)
Switch-Mount,
Line Voltage
Vacancy Sensor
Switch-Mount, Low-Voltage
Occupancy Sensor
Poles
Auto ON / Auto OFF
(configurable)
Switch-Mount, Line-Voltage
Ocupancy Sensor
Description
White
OSRPS2-DP-W
White
OSRPS2-DP-G
Gray
OSRPS2-DP-I
Ivory
180°
Fine-motion: 350sqft
Large-motion: 1050sqft
Power Packs
24VAC
Rectified Pulse
Output
Description
Item Number
Power Input
Single-pole
120/277V
Power Pack
PPK1-PLS25C
120/277VAC
Two-pole
120/277V
Power Pack
PPK2-PLS25C
120/277VAC
Single-pole
347V
Power Pack
PPK1-347-PLS25C
347VAC
Ceiling Mounts, Passive Infrared (PIR)
Poles
Item
Lens Type
Coverage
OCRUS2-P-N
Standard-range lens
360º / 500sqft
OCRUX2-P-N
Extended-range lens
360º / 2200sqft
OCR3S2-P-N
Standard-range lens
360º / 500sqft
OCR3X2-P-N
Extended-range lens
360º / 2200sqft
OCRPS1-N
Standard-range lens
360º / 500sqft
OCRPX1-N
Extended-range lens
360º / 2200sqft
OCRPS2-DPR-L
Standard-range lens
360º / 500sqft
OCRPX2-DPR-L
Extended-range lens
360º / 2200sqft
OCRPB2-DPR-L
Hi-Bay Range, High Mounting, Narrow Angle
360° / 40ft radius at 40ft mtg.
Voltage
Two-Pole
120/277VAC
Single-Pole
347VAC
Two-Pole
Auto ON / Auto OFF
(configurable)
Auto ON / Auto OFF
(configurable)
Ceiling-Mount, Low-Voltage
Occupancy Sensor
Ceiling-Mount, Line-Voltage
Occupancy Sensor
Description
24VAC
Rectified Pulse Output
24VAC
Rectified Pulse Output
Select models have photo sensors with a 0-10V dimming function for daylight harvesting. The diverse
options of our CENTO™ line make them perfect for a variety of applications, from hallways to offices
and from closets to warehouse aisle. Make CENTO™ part of your lighting control strategy today!
All specification information is subject to change without notification.
CENTOFLYER0914
51 Century Blvd., Suite 230 • Nashville, TN 37214 • 615-316-5100 • (TES) 1-800-BALLAST • www.unvlt.com