QUARTER TURN ELECTRIC ACTUATOR STANDARD WIRING DIAGRAMS FOR BASIC MODEL 20 CODING SYSTEM FOR AV ACTUATOR WIRING DIAGRAMS There are 3 elements to the wiring codes used in AVA electric actuators: CONTROL WIRING CODE 1 2 X FEEDBACK TYPE CODE 1 2 3 X ALARM CODE 0 A C AVA CODE SYSTEM 1 1 2 1 CONTROL WIRING TYPE 3 Wire system, single pole double throw, switching the live 3 Wire system, single pole single throw, make or break switch Other factory special wiring SPDT SPST FEEDBACK TYPE 3 Wire system, cam driven volt free single pole double throw switch 2 Wire system connected to motor switches to give powered output 3 Wire system, 10kΩ potentiometer Other factory special feedback SPDT ALARM No alarm (not available in Basic Series) 0 0 WIRING CREATED BY THE AVA CODE 3 Wire, SPDT control with cam driven volt free SPDT feedback [Standard stock in UK] 3 Wire, SPST control with cam driven volt free SPDT feedback ACCESSORIES: ANTI-CONDENSATION HEATER AVA REFERENCE Heater CONTROL TYPE 2 wire permanent supply NOTES Unless otherwise stated UK stock is fitted with an anti-condensation heater as standard. Success results from our continual pursuit of perfection, details therefore subject to change without notice in the interests of product development and improvement. www.avactuators.co.uk QUARTER TURN ELECTRIC ACTUATOR WIRING DIAGRAMS FOR BASIC MODEL 20 Note: All AVA Basic Model 20 actuators are supplied pre-wired with a cable approximately 0.8m long ON-OFF [OPEN / CLOSE] WIRING DIAGRAM: A AVA REFERENCE A (Code 1-1-0) CONTROL TYPE SPDT (Single pole, double throw) TO OPEN Connect live / +ve to BK (black cable) TO CLOSE Disconnect from BK, connect to RD (red cable) END OF TRAVEL CONFIRMATION Yes, volt free, switch is made just ahead of final motor stop position. Do not cut motor power on receipt of end of travel confirmation. FAULT ALARM Not available in this version NOTES Cam operated mechanical limit switches . End of travel confirmation circuit can be a different voltage to motor voltage circuit. AVA REFERENCE Code 1-2-0 CONTROL TYPE SPDT (Single pole, double throw) TO OPEN Connect live / +ve to BK (black cable) TO CLOSE Disconnect from BK, connect to RD (red cable) END OF TRAVEL CONFIRMATION Uses motor control switches for simultaneous position confirmation. Motor and end of travel confirmation circuits carry the same voltage. FAULT ALARM Not available in this version Note: Standard UK stock wiring configuration WIRING DIAGRAM: FACTORY OPTION NOTES WIRING DIAGRAM: FACTORY OPTION AVA REFERENCE Code 1-3-0 CONTROL TYPE SPDT (Single pole, double throw) TO OPEN Connect live / +ve to BK (black cable) TO CLOSE Disconnect from BK, connect to RD (red cable) END OF TRAVEL CONFIRMATION 10k potentiometer FAULT ALARM Not available in this version NOTES Success results from our continual pursuit of perfection, details therefore subject to change without notice in the interests of product development and improvement. www.avactuators.co.uk QUARTER TURN ELECTRIC ACTUATOR WIRING DIAGRAMS FOR BASIC MODEL 20 Note: All AVA Basic Model 20 actuators are supplied pre-wired with a cable approximately 0.8m long ON-OFF [OPEN / CLOSE] WIRING DIAGRAM: C WIRING DIAGRAM: A - Failsafe AVA REFERENCE C (Code 2-1-0) CONTROL TYPE SPST (Single pole, single throw) TO OPEN Connect live / +ve to RD (red cable) TO CLOSE Disconnect live / +ve from RD (red cable) END OF TRAVEL CONFIRMATION Yes, volt free, switch is made just ahead of final motor stop position. Do not cut motor power on receipt of end of travel confirmation. FAULT ALARM Not available in this version NOTES Cam operated mechanical limit switches . End of travel confirmation circuit can be a different voltage to motor voltage circuit. AVA REFERENCE Code A Failsafe (1-1-0-Fail [close or open]) CONTROL TYPE SPDT (Single pole, double throw) TO OPEN Connect L/ +ve to RED cable TO CLOSE Disconnect from RED, connect to BLACK cable END OF TRAVEL CONFIRMATION Yes, volt free, switch is made just ahead of final motor stop position. Do not cut motor power on receipt of end of travel confirmation. FAULT ALARM Not available in this version NOTES Cam operated mechanical limit switches . End of travel confirmation circuit can be a different AVA REFERENCE Code C Failsafe (2-1-0-Fail [close or open]) CONTROL TYPE SPDT (Single pole, double throw) TO OPEN Connect L/ +ve to RED cable TO CLOSE Disconnect from RED, connect to BLACK cable END OF TRAVEL CONFIRMATION Yes, volt free, switch is made just ahead of final motor stop position. Do not cut motor power on receipt of end of travel confirmation. FAULT ALARM Not available in this version NOTES Cam operated mechanical limit switches . End of travel confirmation circuit can be a different voltage to motor voltage circuit. Note: Standard UK stock wiring configuration WIRING DIAGRAM: C - Failsafe Success results from our continual pursuit of perfection, details therefore subject to change without notice in the interests of product development and improvement. www.avactuators.co.uk
© Copyright 2026 Paperzz