XGP 2L - Sauter Controls

69.310/1
XGP 2L: Heavy-duty, pneumatic control-pressure adjuster
Areas of application
Remote adjuster for setpoint adjustment of pneumatic controllers (e.g. Centair) with large capacity.
Manual control of pneumatic control units.
Features
•
Integrated minimum or maximum limiting of control pressures
•
Setting knob with interchangeable scales and 2 stops for limiting the setting range or locking
the setting
•
Suitable for fitting into panels or for recessed mounting
•
Complies with directive 97/23/EC Art. 3.3 on pressure equipment
Technical description
•
Supply pressure 1.3 bar ± 0.1
Type
XGP 2L F001
Supply pressure 2)
Air consumption 3)
Output pressure
Setting range 1)
bar
Air capacity
In/h
Weight
kg
0...1,2
400
0,09
1,3 ± 0,1 bar
7 In/h
0...1,2 bar
Permissible ambient temp.
0...55 °C
Connection diagram
Dimension drawing
Fitting instructions
A03466
M297370
MV 7321
Y03461
bar
1,2
Output pressure
Accessories
0296936 000*
0296937 000*
0296218 000*
0296990 000*
Bracket for EN 60715, 35 × 7,5 and 35 × 15 rail
Bracket for C EN 60715-C20 rail and for wall mounting
Buckle-proof connector-adaptor for push-on installation
Buckle-proof connector-adaptor for screw-type installation; MV 7322
0
*)
Dimension drawing or wiring diagram are available under the same number
1)
Scale: 0...1,2 bar, ‘tail' increasing in thickness. Rear scale: 0...1,2 bar, ‘tail' decreasing.
Inscribable scale (0...100%) is included underneath the normal scale.
See Section 60 on regulations concerning the quality of supply air, especially at low ambient temperature.
40 ln/h when measuring connection is open (provides greater response sensitivity).
2)
3)
0
Set value
1,2 bar
Pressure adjustment
B03463
bar
1,2
Output pressure
Operation
The transmitter's functions can be split up as follows:min.
Pressure adjustment
The output pressure increases when the adjuster knob is turned in a clockwise direction. If greater
response sensitivity is required, the measuring connection (M4 sealing screw) must be loosened by
one or two turns.
0
0
Input pressure 1,2 bar
Minimum limitation
B03464
Minimum limitation
The minimum value increases when the adjuster knob is turned in a clockwise direction. The setting of
the minimum value is protected by an in-built diode. The M4 sealing screw is closed for both bleed-off
and non-bleed-off systems.
Maximum limitation
The maximum value increases when the adjuster knob is turned in a clockwise direction. The M4 sealing screw is closed for bleed-off systems; for non-bleed-off systems, the M4 sealing screw must be
loosened by one or two turns.
bar
1,2
Output pressure
max.
0
0
Input pressure 1,2 bar
Maximum limitation
B03465
Connection diagram
1,3 bar
2
1
6
P
F
A03466
Sauter Components
7169310003 04
69.310/2 XGP 2L
Dimension drawing
Ø5
48
6
44
1
0,2
1,0 0
,8
2
0,6 0,
4
1,
2
0
M4
bar
Ø40
18
2
~57
6
max.12
8,4
1
4,5
41
48
45
°
M297370c
min.46
Accessories
296936
296937
5
25
13
40
32
30
4,5
13
18
5,5 1,5
4,5
5,5
25
13
18
12
18
5
0,
13
46
120
120
M00563
Sauter Components
Ø4
Ø6
Ø4
Ø6
M00129
296990
296218
Printed in Switzerland
Right of amendment reserved
N.B.: A comma between cardinal
numbers denotes a decimal point
© Fr. Sauter AG, CH-4016 Basle
7169310003 04
60
M00166
M00564