FMC‑210‑SM Single Action Call Points

Fire Alarm Systems | FMC‑210‑SM Single Action Call Points
FMC‑210‑SM Single Action Call Points
▶ Alarm triggering by breaking of the glass pane
▶ Variable labeling possible with foil sets
▶ Indicator LED for alarm or for inspection evaluation
▶ Call point query routines with evaluation and multiple
transmission
▶ Individual call point identification
The FMC‑210‑SM Single Action Call Points are used to
trigger the alarm manually, and can be used in the Local
SecurityNetwork LSN and LSN improved. The FMC‑210‑SM
Single Action Call Points are designed for indoor
deployment.
Individual call point identification with display of the call
point address on the fire panel ensures the quick location
of the triggered call point.
Certifications and Approvals
Functions
Region
Certification
Germany
VdS
G 207008 FMC-210-SM-G-R
Installation/Configuration Notes
•
•
With single action call points, the alarm is triggered when
the glass plate (2) is broken and the button (3) springs up.
This activates the microswitch for alarm triggering and the
indicator LED (4) blinks.
The call point (3) can be reset after inserting a new glass
pane (2) and closing the door of the single action call point
(1). The indicator LED (4) goes out.
This does not reset the alarm on the fire panel.
•
•
Manual call points must be mounted visibly along
escape and rescue routes (e. g. exits, passageways,
stairwells) and be easily accessible.
An installation height of 1400 mm ±200 mm, measured
from the middle of the manual call point to the floor,
must be maintained.
Manual call points must be adequately illuminated by
sunlight or another light source (including emergency
lighting if present).
The maximum number of LSN elements that may be
connected depends on their current consumption from
the LSN data line. The limit values should be taken from
the product information supplied with the fire panel
used.
www.boschsecurity.com
2 | FMC‑210‑SM Single Action Call Points
•
Further standards, guidelines and planning
recommendations regarding the installation location
etc., should also be taken into consideration (see Fire
Detection manual).
The regulations of the local fire services must be
observed.
Parts Included
TypeNumber.
Component
FMC‑210‑SM‑G‑B
Form G, Blue
Single Action Call Point for indoor use, direct triggering (type A)
Installation notes in accordance with VdS/VDE
• The distance between manual call points should not be
more than 100 m according to DIN 14675 or 80 m
according to VdS.
• In high risk areas, manual call points should be installed
at a distance of max. 40 m (VDE 0833 Part 2,
Point 7.2.6).
FMC‑210‑SM‑G‑R
Form G, Red
Single Action Call Point for indoor use, direct triggering (type A
Installation
• The cable duct can be surface-mounted or flushmounted.
Electrical
•
Note
The key must be ordered separately.
Technical Specifications
Operating voltage
15 V DC . . . 33 V DC
Current consumption
0.4 mA
Mechanics
Dimensions (H x W x D)
135 x 135 x 40 mm
Housing material
Plastic, ASA
Colors
•
•
FMC-210-SM-G-R
Red, RAL 3001
FMC-210-SM-G-B
Blue, RAL 5005
Weight
•
Installation in fire hose cabinets is possible in three
ways:
Approx. 235 g
Environmental Considerations
Protection class as per EN 60529
IP 52
Permissible operating temperature -10 °C. . . +55 °
Ordering Information
FMC‑210‑SM‑G‑B Form G, Blue
Single Action Call Point for indoor use, direct
triggering (type A)
FMC-210-SM-G-B
FMC‑210‑SM‑G‑R Form G, Red
Single Action Call Point for indoor use, direct
triggering (type A)
FMC-210-SM-G-R
Accessories
Pos.
Description
1
Installation depth version 1: ca. 40 mm
2
Installation depth version 2: 14 mm
3
Installation depth version 3: min. 30 mm
FMX‑FSO‑LSN Punched, Self-adhesive Foil
Sets (Blank)
For the labeling field of manual call points of
the Series FMC‑210.
1 unit = 10 sheets
FMX-FSO-LSN
FMC‑FST‑DE Printed Labeling Foils for the
Upper Label Field
For yellow and blue manual call points of Series
FMC‑120 and FMC‑210, 1 unit = 5 sheets
FMC-FST-DE
FMC‑SPGL‑DEIL Spare Glasses
For manual call points of Series DM, DKM, SKM,
FMC‑120 and FMC‑210.
1 unit = 5 spare glasses
FMC-SPGL-DEIL
Key for Fire Detectors Types G and H
made of red plastic (ASA)
FMM-KEY-Form G/H
FMC‑210‑SM Single Action Call Points | 3
Ordering Information
Sign with label "Nicht in Betrieb"
Metal sign for fire detectors form G or H
FMM-SIGN
www.boschsecurity.com
4 | FMC‑210‑SM Single Action Call Points
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
[email protected]
www.boschsecurity.com
Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
[email protected]
www.boschsecurity.us
© Bosch Security Systems B.V. 2007 | Data subject to change without notice