Light Oil Burners RL 70/M - 100/M - 130/M Low - High or

Installation, use and maintenance instructions
Light Oil Burners
RL 70/M - 100/M - 130/M
Low - High or Modulating Operation
C6505053 - 2916050 (3) - 10/2008
CONTENTS
TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
Burner models designations. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Burner description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Packaging - Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Max. dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standard equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Firing rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Minimum furnace dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . .
WARNING
3
3
3
4
4
4
4
5
5
Do not store flammable or hazardous materials in the vicinity
of fuel burning appliances.
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Boiler plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Blast tube length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Securing the burner to the boiler . . . . . . . . . . . . . . . . . . . . . . . . . 6
Choice of nozzle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Nozzle assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Combustion head setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Fuel supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Hydraulic connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Air pressure switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Servomotor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Burner calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Burner starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Burner operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Oil pressure switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Final checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Procedure to refer burner operating condition
in high altitude plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Flame signal measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Siemens LAL control sequence of operations . . . . . . . . . . . . . . 16
Siemens LAL control troubleshooting guide. . . . . . . . . . . . . . . . 17
Factory wiring diagram - burner mounted LAL . . . . . . . . . . . . . . 18
Field wiring diagram- burner mounted LAL . . . . . . . . . . . . . . . . 19
Factory wiring diagram - remote panel . . . . . . . . . . . . . . . . . . . . 20
Spare parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Start up reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Burner shall be installed in accordance with manufacturers
requirements as outlined in this manual, local codes and authorities having jurisdiction.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or
death. Refer to this manual for instructional or additional information. Consult a certified installer, service representative
or the gas supplier for further assistance.
N.B.
Figures mentioned in the text are identified as follows:
1)(A)
= part 1 of figure A, same page as text;
1)(A)p.4 = part 1 of figure A, page number 4.
2
TECHNICAL DATA
MODEL
RL 70/M
Output (1)
High
MBtu/hr (3)
GPH
MBtu/hr (3)
GPH
Low
Fuel
Operation
Nozzle
Standard applications
Ambient temperature
Combustion air temperature
Main power supply (+/- 10%)
Fan motor
number
°F
°F max
V/Ph/Hz
rpm
W - HP
V
A
V1 - V2
I1 - I2
GPH
PSI
° F max
W max
Ignition transformer
Pump
delivery (at 290 PSI)
pressure range
fuel temperature
Electrical power consumption
Electrical protection
Noise levels (2)
dBA
RL 100/M
RL 130/M
1792 - 3136
12.8 - 22.4
756 - 1792
5.4 - 12.8
2688 - 4480
3564 - 5824
19.2 - 32
25.6 - 41.6
1260 - 2688
1568 - 3584
9 - 19.2
11.2 - 25.6
# 2 fuel oil
Low - high or modulating
1 (return flow nozzle)
Boilers: water, steam, thermal oil
32 - 104 (0 - 40 °C)
140 (60 °C)
208 - 230 / 460 / 575 / 3 / 60
3400
3400
3400
1100 - 1.5
1800 - 2.5
2200 - 3
208 - 230 / 460 / 575
208 - 230 / 460 / 575
208 - 230 / 460 / 575
4.8 / 2.8 / 2
6.7 / 3.9 / 2.8
8.8 / 5.1 / 3.7
120 V - 2 x 5 kV
3.7 A - 35 mA
60.8
145 - 304.5
194 (90 °C)
1400
2200
2600
NEMA 1
75
77
78.5
Reference conditions: Ambient temperature 68 °F (20 °C) - Barometric pressure 394” WC - Altitude 329 ft a.s.l.
Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated output.
(3) Equivalent Btu values based on 1 USGPH = 140,000 Btu/hr.
(1)
(2)
Burner models designations:
Model
RL 70/M
RL 100/M
RL 130/M
Code
C9514300 (3477070)
C9514301 (3477075)
C9714300 (3477073)
C9714301 (3477073)
C9515300 (3477270)
C9515301 (3477275)
C9715300 (3477273)
C9715301 (3477273)
C9516300 (3477470)
C9516301 (3477475)
C9716300 (3477473)
C9716301 (3477473)
VOLTAGE
208-230/460/3/60
575/3/60
208-230/460/3/60
575/3/60
208-230/460/3/60
575/3/60
208-230/460/3/60
575/3/60
208-230/460/3/60
575/3/60
208-230/460/3/60
575/3/60
Flame safeguard
Burner mounted
Burner mounted
In an auxiliary panel (see Accessories)
In an auxiliary panel (see Accessories)
Burner mounted
Burner mounted
In an auxiliary panel (see Accessories)
In an auxiliary panel (see Accessories)
Burner mounted
Burner mounted
In an auxiliary panel (see Accessories)
In an auxiliary panel (see Accessories)
ACCESSORIES (optional):
• Available auxiliary panels
Auxiliary panel code
Flame safeguard type
3010330
Fireye
3010334
Landis
• Kit for lengthening the combustion head
L
= Standard length
L1 = Length obtainable with the kit
COD. 3010280
L = 10 23/32 ”
COD. 3010281
L = 10 23/32 ”
COD. 3010282
L = 10 23/32 ”
L1 = 15 5/32 ”
L1 = 15 5/32 ”
L1 = 15 5/32 ”
• RL 70/M
• RL 100/M
• RL 130/M
• Flame inversion boiler kit
COD. 3010180
• RL 70/M - RL 100/M
COD. 3010183
• RL 130/M
Important:
The installer is responsible for the supply and installation of any safety device(s) not indicated in this manual.
3
BURNER DESCRIPTION (A)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Ignition electrodes
Combustion head
Screw for combustion head adjustment
Screw for fixing fan to flange
Pressure gauge for pressure on nozzle return
Pump
Non-drip nozzle holder
Air damper
Fan pressure test point
Boiler mounting flange
Flame stability disk
Servomotor, provides adjustment of fuel delivery regulator and of air damper.
When the burner is not operating the air damper is
fully closed in order to reduce to a minimum heat dispersion from the boiler.
Slide bars for opening the burner and inspecting the
combustion head
Photocell (cad cell)
High oil pressure switch
Extensions for slide bars 14) (with kit)
Ignition transformer
Motor contactor and thermal overload with reset button
Power switch for different operations:
automatic - manual - off.
Button for:
power increase - power reduction.
Valve assembly with pressure regulator on nozzle
return
Terminal strip
Knockouts for electrical connections by installer
Flame safeguard with lock-out pilot light and lock-out
reset button
Flame inspection window
Two types of burner failure may occur:
(A)
D2349
inch
A
B
C
lbs
RL 70/M
459/32“
235/8“
313/16“
143
RL 100/M
459/32“
235/8“
313/16“
150
RL 130/M
459/32“
235/8“
313/16“
157
Flame safeguard Lock-out: if the Flame relay 23)(A)
pushbutton lights up, it indicates that the burner is in
lock-out.
To reset, press the pushbutton.
Motor trip: release by pressing the pushbutton on thermal overload 18)(A).
PACKAGING - WEIGHT (B) - Approximate meas-
(B)
D36
urements
• The burners is supplied skid mounted. Outer dimensions of packaging are indicated in (B).
• The weight of the burner complete with packaging is
indicated in Table (B).
MAX. DIMENSIONS (C) - Approximate measurements
The maximum dimensions of the burners are given in
(C).
Keep in mind that inspection of the combustion head
requires the burner to be opened and the rear part withdrawn on the slide bars.
The maximum dimension of the burner when open, without casing, is given in measurement I.
D1217
RL
70
A
B
C
D
E
F (1)
G
H
STANDARD EQUIPMENT
I (1)
26 1/8 ” 11 21/32 ” 14 15/32 ” 21 27/32 ” 26 25/32 ” 10 23/32 ” - 15 5/32 ” 7 1/16 ” 16 15/16 ” 37 7/16 ” - 42 3/4 ”
100 26 1/8 ”
12 9/32 ” 14 15/32 ” 21 27/32 ” 26 25/32 ” 10 23/32 ” - 15 5/32 ” 7 1/16 ” 16 15/16 ” 37 7/16 ” - 42 3/4 ”
130 27 3/4 ”
13 5/16 ” 14 15/32 ” 21 27/32 ” 26 25/32 ” 10 23/32 ” - 15 5/32 ” 7 7/16 ” 16 15/16 ” 37 7/16 ” - 42 3/4 ”
(1) Blast tube: short - long (obtainable with the kit)
(C)
4
2
2
1
4
-
Flexible hoses
Gaskets for flexible hoses
Burner head gasket
Screws to secure the burner flange to the boiler
1/2 W
1 - Adaptor G 1/8“ / 1/8“ NPT
1 - Instruction booklet
1 - Spare parts list
FIRING RATES (A)
Comb. chamb. “ WC
During operation, burner output varies between:
• MINIMUM OUTPUT: area A;
• MAXIMUM OUTPUT: area B (and C for model RL 130/
M).
Graphs (A):
Horizontal axis
Vertical axis
: Burner output
: Combustion chamber pressure
The firing rate may be found by plotting a vertical line
from the desired delivery and a horizontal line from the
pressure in the combustion chamber. The intersection of
these two lines is the firing rate which must lie within
area A, for MIN output, and within area B, for MAX output.
In order to utilize also area C (RL 130/M) it is necessary
to perform the calibration of the combustion head as
explained on page 6.
Comb. chamb. “ WC
Note:
The FIRING RATE areas given in figure (A) have been
reduced by 10% with respect to the maximum range that
can be reached.
Important:
The FIRING RATE area values have been obtained considering an ambient temperature of 68 °F (20°C), and an
atmospheric pressure of 394” WC and with the combustion head adjusted as shown on page 7.
Consult Procedure on page 15 to refer burner operating
condition in high altitude plants.
MINIMUM FURNACE DIMENSIONS (B)
The firing rates were set in relation to certified test boilers.
Figure (B) indicates the diameter and length of the test
combustion chamber.
Comb. chamb. “ WC
Example
Output 2579 MBtu/hr:
diameter 24 inch - length 6.6 ft.
(A)
D2350
Furnace dimensions
Length (ft)
Diameter (inches)
(B)
D2919
5
INSTALLATION
inch
A
B
C
RL 70/M
7 9/32 “
10 27/32 “ - 12 13/16 “
1/2 W
RL 100/M
7 9/32 “
10 27/32 “ - 12 13/16 “
1/2 W
RL 130/M
7 21/32 “
10 27/32 “ - 12 13/16 “
1/2 W
BOILER PLATE (A)
Drill the combustion chamber mounting plate as shown
in (A). The position of the threaded holes can be marked
using the head gasket supplied with the burner.
BLAST TUBE LENGTH (B)
D455
(A)
The length of the blast tube must be selected according
to the indications provided by the manufacturer of the
boiler, and it must be greater than the thickness of the
boiler door complete with its insulation. The range of
lengths available, L (inch), is as follows:
Blast tube 9):
• short
• long
RL 70/M
10 23/32 ”
15 5/32 ”
RL 100/M
10 23/32 ”
15 5/32 ”
RL 130/M
10 23/32 ”
15 5/32 ”
For boilers with front flue passes 12) or flame inversion
chambers, protective insulaton material 10) must be
inserted between the boiler refractory 11) and the blast
tube 9).
This protective insulation must not compromise the
extraction of the blast tube.
For boilers having a water-cooled front the insulation
10)-11)(B) is not required unless it is required by the
boiler manufacturer.
SECURING THE BURNER TO THE BOILER (B)
D1219
(B)
Disassemble the blast tube 9) from the burner 6) by proceeding as follows:
- Loosen the four screws 3) and remove the cover 1).
- Remove the screws 2) from the two slide bars 5).
- Remove the two screws 4) fixing the burner 6) to the
flange 7).
- Withdraw the blast tube 9) complete with flange 7) and
slide bars 5).
COMBUSTION HEAD CALIBRATION
At this point check, for model RL 130/M, whether the
maximum delivery of the burner is contained in area B or
in area C of the firing rate. See page 5.
If it is in area B then no operation is required.
If, on the other hand, it is in area C:
- Unscrew the screws 1)(C) and disassemble the blast
tube 5);
- Unscrew the screws 3) and remove the shutter 4);
- Tighten the screws 3) on the rod 2);
- Now refit the blast tube 5) and the screws 1).
Once this operation has been carried out (if required),
secure flange 7)(B) to the boiler plate inserting the supplied gasket 8)(B). Use the 4 screws provided after having protected the thread with an anti-seize product.
The burner-boiler seal must be airtight.
D690
(C)
6
CHOICE OF NOZZLE (A)
See diagrams (B)page 11.
In case an intermediate delivery between the two values
indicated in the diagrams (B) page 11 is required, a nozzle with higher delivery must be chosen. Delivery reduction will be obtained by means of the pressure regulator.
RECOMMENDED NOZZLES:
Type A4 return flow nozzles - 45° angle
NOZZLE ASSEMBLY
At this stage of installation the burner is still disassembled from the blast tube; it is therefore possible to fit the
nozzle with the box wrench 1)(A), inserting the wrench
through the central hole in the flame stability disk. Do
not use any sealing products such as gaskets, sealing
compound, or tape. Be careful to avoid damaging the
nozzle sealing seat.
D1220
(A)
Make sure that the electrodes are positioned as shown
in Figure (B).
Finally remount the burner 3)(C) on the slide bars 2) and
slide it up to the flange 5), keeping it slightly raised to
prevent the flame stability disk from pressing against the
blast tube.
Tighten the screws 1) on the slide bars 2) and screws 4)
fixing the burner to the flange.
If it proves necessary to change a nozzle with the burner
already fitted to the boiler, proceed as outlined below:
- Pull back the burner on its slide bars as shown in fig.
(B)p.6.
- Remove the nuts 1)(D) and the disk 2).
- Use wrench 3)(D) to change the nozzles.
D1221
D2528
(B)
(C)
COMBUSTION HEAD SETTING
The setting of the combustion head depends exclusively
on the maximum burner delivery at which it will be operating.
Turn screw 4)(E) until the notch shown in diagram (F) is
level with the front surface of flange 5)(E).
Example:
RL 70/M, maximum light oil delivery = 16 GPH
Diagram (F) indicates that for a delivery of 16 GPH the
RL 70/M Model requires the combustion head to be set
to approx. three notches, as shown in Figure (E).
(D)
D1222
(E)
D462
N° Notches
(F)
Max Fuel oil delivery
USGPH
D2351
7
HYDRAULIC SYSTEM
FUEL SUPPLY
5
A
P
V
7
1
315/16”
+H
6
2
4
5
3
D737
7
The loop circuit
A loop circuit consists of a loop of piping exiting and
returning to the tank with an auxiliary pump that circulates the fuel under pressure. A branch connection from
the loop goes to feed the burner. This circuit is extremely
useful whenever the burner pump does not succeed in
self-priming because the tank distance and/or height difference are higher than the values listed in the Table.
-H
B
6
+H
-H
(ft)
+ 13
+ 10
+ 6.6
+ 3.3
+ 1.6
0
- 1.6
- 3.3
- 6.6
- 10
- 13
3/8”
234
204
174
145
132
118
105
92
63
33
–
L (ft)
Ø (inch)
1/2”
454
401
399
296
270
243
217
191
138
86
33
Double-pipe circuit (A)
The burner is equipped with a self-priming pump which
is capable of feeding itself within the limits listed in the
table at the side.
The tank higher than the burner A
Distance "P" must not exceed 33 ft in order to avoid subjecting the pump's seal to excessive strain; distance "V"
must not exceed 13 ft in order to permit pump self-priming even when the tank is almost completely empty.
The tank lower than the burner B
Pump suction values higher than 13 “Hg must not be
exceeded because at higher levels gas is released from
the fuel, the pump starts making noise and its working
life-span decreases.
It is good practice to ensure that the return and suction
lines enter the burner from the same height; in this way it
will be less probable that the suction line fails to prime or
stops priming.
Key
H =
L =
Ø =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
5/8”
493
493
493
493
493
451
405
359
266
174
82
Pump/foot valve height difference
Piping length
Inside pipe diameter
Burner
Pump
Filter
Manual on/off valve
Suction line
Foot valve
Return line
HYDRAULIC CONNECTIONS (B)
(A)
D1224
(B)
8
The pumps are equipped with a by-pass that connects
the return line and suction line. The pumps are installed
on the burner with the by-pass closed by screw
6)(A)p.13.
It is therefore necessary to connect both hoses to the
pump.
The pump seal will be dammaged immediately if it is
run with the return line closed and the by-pass
screw inserted.
Remove the plugs from the suction and return connections of the pump.
Insert the hose connections with the supplied seals into
the connections and screw them down.
Take care that the hoses are not stretched or twisted
during installation.
Install the hoses where they cannot be stepped on or
come into contact with hot surfaces of the boiler.
Now connect the other end of the hoses to the suction
and return lines.
PUMP (A)
PUMP SUNTEC J7 C
1
2
3
4
5
6
- Suction
- Return
- Pressure gauge attachment
- Vacuum gauge attachment
- Pressure adjustment screw
- By-pass screw
1/2" NPT
1/2" NPT
G 1/8"
G 1/8"
A - Min. delivery rate at 290 PSI pressure
B - Delivery pressure range
C - Max. suction pressure
D - Viscosity range
E - Max light oil temperature
F - Max. suction and return pressure
G - Pressure calibration in the factory
H - Filter mesh width
PUMP PRIMING
- Before starting the burner, make sure that the tank
return line is not clogged. Obstructions in the line
could cause the seal located on the pump shaft to
break.
The time required for this operation depends upon the
diameter and length of the suction tubing. If the pump
fails to prime at the first starting of the burner and the
burner locks out, wait approx. 15 seconds, reset the
burner, and then repeat the starting operation as often
as required. After 5 or 6 starting operations allow 2 or 3
minutes for the transformer to cool.
J7 C
A
B
C
D
E
F
G
H
GPH
PSI
“Hg
cSt
°F
PSI
PSI
inch
Important: the priming operation is possible because
the pump is already full of fuel when it leaves the factory.
If the pump has been drained, fill it with fuel through the
opening on the vacuum meter prior to starting; otherwise, the pump will seize. Whenever the length of the
suction piping exceeds 66 - 98 ft, the supply line must be
filled using a separate pump.
60.8
145 - 304.5
13
2,8 - 200
194 (90 °C)
21.8
290
0,006
AIR PRESSURE SWITCH (B)
(A)
D2352
AIR PRESSURE SWITCH
(B)
9
Adjust the air pressure switch after having performed all
other burner adjustments with the air pressure switch set
to the start of the scale (B).
With the burner operating at min. output, increase adjustment pressure by slowly turning the relative dial clockwise until the burner locks out.
Then turn the dial anti-clockwise by about 20% of the set
point and repeat burner starting to ensure it is correct.
If the burner locks out again, turn the dial anti-clockwise
a little bit more.
SERVOMOTOR (A)
The servomotor gives simultaneous regulation of the air
damper through the adjustable profile cam 2)(F) and the
pressure controller (A) pag. 11.
It rotates by 130° in approx. 35 s.
The factory settings must not be changed for the first firing, just check that they comply with the details below.
To open the servomotor, remove the screws and pull the
cover outward, fig. (A).
CAMS AND TRIM POTENTIOMETERS FUNCTIONS
(A)
Cam 1:
130°
Limits rotation towards maximum.
D2277
YES
NO
Cam 2:
0°
Limits rotation towards minimum, air damper closed on
stand by.
Cam 3:
20°
Limits ignition position.
Cams 4 - 5 - 6 - 7 - 8: not used
Trim potentiometer MAX
Limits maximum modulation.
It must be set near the stroke end (cam 1) to exploit as
far as possible the variable profile cam.
Don’t release the button indicated in this figure: the syncronization of the cams
made in factory would be
changed.
D2585
Figure above shows how the servomotor is released to manually check
(B) there is no binding though its motion.
Position jumpers
Trim potentiometers
Slide switch
Trim potentiometer MIN
Limits minimum modulation.
It must be set near the stroke end (cam 2) to exploit as
far as possible the variable profile cam.
Trim potentiometer POS
Limits an intermediate operating position between MAX
and MIN, supplying power to the "P" terminal in the servomotor (through an external command). This function
cuts out any external signals.
Note
Using the slide switch to select MAX or MIN, the servomotor goes into the position for the respective settings of
the MAX and MIN TRIM POTENTIOMETERS.
When the settings are complete, place the slide switch
on OPE.(operate)
(C)
(D)
(E)
1 Servomotor
2 Adjustable profile cam
3 Adjustment screws for cam
starting profile
4 Adjustment fixing screws
5 Adjustment screws for cam
and profile
D1229
(F)
10
BURNER CALIBRATION
PRESSURE CONTROLLER
The optimum calibration of the burner requires an analysis of the flue gases at the boiler outlet.
The following settings that have already been made do
not require modification under normal circumstances:
• Combustion head;
• Servomotor, cams I - II - III
ADJUSTING THE NOZZLE FLOW RATE
The nozzle flow rate varies according to the fuel pressure on the nozzle return.
Diagram (B) indicates this relationship for type A4 return
flow nozzles with pump delivery pressure of 290 PSI.
Diagrams (B):
Horizontal axis
Vertical axis
NOTE: with a pump delivery pressure of 290 PSI, the
pressure on the nozzle return must not exceed 246.5
PSI.
The pressure difference between pump delivery and
nozzle return must be at least 43.5 PSI. With smaller
pressure differences, the pressure on the nozzle return
can be unstable.
D1227
(A)
1
2
3
4
5
6
7
-
Gauge for pressure in return line
Oil pressure switch
Ring for piston stop
Nut and lock-nut for piston setting
Eccentric adjusting screw
Variable eccentric
Eccentric locking screws
The nozzle return pressure value is indicated by the
pressure gauge 1)(A).
The output and the pressure of the nozzle are at maximum when the servomotor is positioned on maximum.
The fine adjustment of the pressure in the return line
may be carried out by changing the setting of the eccentric 6)(A), of the nut and lock-nut 4)(A).
The eccentric setting should be carried out by loosening
screws 7), and turning the screw 5) to obtain the desired
eccentricity. Turn clockwise, screw 5) to increase the
eccentricity, increasing the difference between the min.
and max. capacity of the nozzle; turn counter-clockwise,
screw 5) to decrease the eccentricity and, consequently
the difference between the min. and max. capacity of the
nozzle.
Delivery pressure 290 PSI
NOTE
• The proper setting of the eccentric 6) is possible when
its operation field follows the servomotor operation
field (20° ÷ 130°): so, that every variation of the servomotor position corresponds to a pressure variation.
• Do not let the piston bottom out repeatedly: the
stop ring 3)(A) determines the max. stroke.
• When the setting is carried out, verify manually that no
slow-down occurs between 0° and 130° and that the
maximum and minimum pressures correspond to
those chosen as per diagrams (B).
• If you wish to check the delivery capacity of the nozzle,
open the burner, attach the nozzle, simulate the startup and then proceed with observing of the maximum
and minimum pressures of the fuel.
• If at the maximum capacity of the nozzle (maximum
pressure in the return line) pressure fluctuations are
detected on the gauge 1), slightly decrease the pressure in the return line until they are completely eliminated.
Nozzle flow rate
Type A4 return flow nozzle (45°)
: PSI, nozzle return pressure
: GPH, nozzle flow rate
Return pressure
The values indicated in the right side of the diagram, refer to the data printed
on the nozzle.
(B)
D2355
11
BURNER STARTING
Position jumpers
Close the control circuit, with the switches in fig. (C) and
(E) in the AUTO position.
On firing turn the switch (C) to MAN.
Trim potentiometers
Slide switch
(A)
(B)
(C)
D2593
MAXIMUM OUTPUT
Using button (B), "increase output" until it stops at app.
130° (cam 1).
Place the slide switch on MAX and set the relative MAX
trim potentiometer (setting must be very near to 130°) to
exploit as far as possible the variable profile cam 2)(D).
The setting of the oil delivery must be made on the variable eccentric 6)(A) page 11 by turning the screw 5)(A)
page. 11.
The air setting must be made on the variable profile cam
2)(D) after loosening the screws 4) by turning the screws
3).
MINIMUM OUTPUT
With the slide switch on the OPE position, use button (B)
"decrease output" until it stops at app. 20° (cam 3).
Put the slide switch in the MIN position and set the modulation minimum using the relative MIN trim potentiometer.
The setting of the oil delivery must be made on the nut
and lock-nut 4)(A)page.11 and, if necessary, on the variable eccentric 6)(A) page 11.
Important
When the eccentricity is modified, it is necessary to bring
back to MAX and check the setting again.
The setting must be made on the adjustable profile cam
2)(D).
INTERMEDIATE OUTPUTS
With the switch (C) in the AUTO position, the slide switch
in the OPE position and the switch 1)(E) in the MAN position, move the button 2)(E) in various intermediate levels between maximum and minimum and set the variable
profile cam 2)(D) to achieve optimum combustion, by
turning the screws 3).
If possible, do not change the previously set maximum
and minimum levels.
Do not change the eccentric, already adjusted for MAX
and MIN.
Check the various setting levels with a combustion analysis.
D1229
1
2
3
4
5
Servomotor
Adjustable profile cam
Adjustment screws for cam starting profile
Adjustment fixing screws
Adjustment screws for cam and profile
Important
Make a progressive setting of the profile, without sharp
changes.
When the setting is complete, lock the cam profile using
screws 4)(D).
(D)
1
(E)
2
D791
12
BURNER OPERATION
BURNER STARTING (A) - (B)
• Operating control closes, the motor starts.
The pump 3) draws the fuel from the tank through the
piping 1) and pumps it under pressure for delivery. The
piston 4) rises and the fuel returns to the tank through
the piping 5) - 7). The screw 6) closes the by-pass
heading towards suction and the de-energized solenoid valves 8) - 9) - 2) close the passage to the nozzle.
• Servomotor starts: 130° rotation to right, until contact is
made on cam 1. The air damper is positioned on MAX.
output.
• Pre-purge stage with air delivery at MAX. output.
• Servomotor rotates to left until contact is made on cam
3.
• Air damper and pressure regulator are positioned on
MIN output.
• Ignition electrode strikes a spark.
• Solenoid valves 8) - 9) - 2) open; the fuel passes
through the piping 10) and filter 11), and enters the
nozzle.
A part of the fuel is then sprayed out through the nozzle, igniting when it comes into contact with the spark:
flame at a low output level; the rest of the fuel passes
through piping 12 at the pressure adjusted by the regulator 13, then, through piping 7), it goes back into the
tank.
• The spark goes out.
• The starting cycle ends.
STEADY STATE OPERATION
At the end of the starting cycle, the servo-motor control
then passes to load control for boiler pressure or temperature.
• If the temperature or pressure is low (and the load control is consequently closed), the burner progressively
increases output up to MAX.
• If subsequently the temperature or pressure increases
until the load control opens, the burner progressively
decreases output down to MIN.
• The burner shuts off when demand for heat is less
than the heat supplied by the burner in the MIN output.
The servomotor returns to the 0° angle limited by contact with cam 2. The air damper closes completely to
reduce thermal dispersion to a minimum.
Every time output is changed, the servomotor automatically modifies oil delivery (pressure regulator) and air
delivery (fan damper).
D2444
(A)
FIRING FAILURE
If the burner does not fire, it goes into lock-out within 5 s
of the opening of the light oil valve.
FIRING FAILURE
If the flame should go out for accidental reasons during
operation, the burner will lock out in 1 s.
OIL PRESSURE SWITCH
The oil pressure switch 15)(A) page 4 is factory set to
43.5 PSI (3 bar). If the oil pressure goes above this
value in the return piping, the pressure switch stops the
burner. Burner starts again automatically if the pressure
goes down under 43.5 PSI (3 bar) after burner shut
down. If a loop circuit with Px pressure feeds the burner,
the pressure switch should be adjusted to Px + 43.5
PSI.
13
FINAL CHECKS
• Obscure the photocell and switch on the control
devices: the burner should start and then lock-out
about 5 s after starting.
• Illuminate the photocell and switch on the control
devices: burner should go into lock-out.
• Obscure the photocell while the burner is operating:
flame should go out and burner lock out within 1 s.
• Switch off control devices while the burner is operating: the burner should stop.
MAINTENANCE
(A)
D707
D709
(B)
(D)
(C)
D1232
D1233
Combustion
An analysis of the flue gases at the boiler outlet is
required . Significant differences with respect to the previous measurements indicate the points where more
care should be exercised during maintenance.
Pump
The pump delivery pressure must be stable at 290 PSI.
The suction must be less than 6.5 PSI.
Unusual noise must not be evident during pump operation.
If the pressure is found to be unstable or if the pump
runs noisily, the flexible hose must be detached from the
line filter and the fuel must be sucked from a tank
located near the burner. This measure permits the
cause of the anomaly to be traced to either the suction
line or the pump.
If the pump is found to be responsible, check to make
sure that the filter is not dirty. The vacuum gauge is
installed up-line from the filter and consequently will not
indicate whether the filter is clogged or not. If the problem lies in the suction line, check to make sure that the
filter is clean and that air is not entering the piping.
Servomotor
Disengage the cam 4)(A)p.10 from the servomotor and
turn it backwards and forwards by hand to make sure it
moves freely.
Filters (A)
Check the following filters:
• on line 1) • in pump 2) • at nozzle 3), and clean or
replace as required.
If rust or other impurities are observed inside the pump,
use a separate pump to suck out any water and other
impurities that may have deposited on the bottom of the
tank.
Combustion head
Check to make sure that all the parts of the combustion
head are in good condition, positioned correctly, free of
all impurities, and that no deformation has been caused
by operation at high temperatures.
Nozzle
Do not clean the nozzle orifices.
Replace the nozzles every 2-3 years or whenever necessary. Combustion must be checked after the nozzles
have been changed.
Photocell (cad cell) (B)
Clean the glass cover from any dust that may have
accumulated. Photocell 1) can be removed by pulling it
outward forcefully.
Flame inspection window (C)
Clean the glass.
Flexible hoses
Check to make sure that the flexible hoses are still in
good condition.
Fuel tank
Every 5 years, or whenever necessary, suck out any
water or other impurities present on the bottom of the
tank using a separate pump.
Burner
Make sure that the screws are fully tightened.
TO OPEN THE BURNER (D)
- Switch off the electrical power
- Loosen screws 1) and withdraw the cover 2)
- Unscrew screws 3)
- Fit the two extensions 4) supplied with a kit on request
onto the slide bars 5) (models with long blast tube)
- Pull part A backward keeping it slightly raised to avoid
damaging the disk 6) on blast tube 7).
FUEL PUMP AND/OR COUPLINGS REPLACEMENT
(E)
As per fig. (E), dimension X should set as follows:
RL70/M - 1/2 ”
RL100/M - 5/16 ”
RL130/M - 7/16 ”
X
dimension
(E)
D2854
14
PROCEDURE TO REFER BURNER OPERATING CONDITION IN HIGH ALTITUDE PLANTS
-
Find the corrected burner capacity for the plant’s altitude in chart 1 and the corrected pressure in chart 2.
Check in the firing rate graph of the burner (page 5), if the working point defined by the values above is within the range limits.
If not, higher burner size is needed.
Note
Charts are based only on altitude variation
(reference temperature = 68°F , 20°C)
To get the combined correction in case of different
air temperature, a compensation of 1000 ft each
20°F (305 m each 11°C) is applicable.
1
Rated Capacity
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
5500
6000
6500
7000
7500
8000
8500
9000
9500
10000
Average barometric
Pressure (20°C)
Average barometric
Pressure (68°F)
2
Rated Pressure
0,50
1,00
1,50
2,00
2,50
3,00
3,50
4,00
4,50
5,00
5,50
6,00
6,50
7,00
7,50
8,00
8,50
9,00
9,50
10,00
Average barometric
Pressure (20°C)
Average barometric
Pressure (68°F)
Example
Rated capacity = 3000 MBtu/hr - Rated air pressure = 1.5”w.c.
Real altitude = 5000 ft - Real temperature = 108°F
Δ = 108°F - 68°F (reference temp.) = 40°F (equivalent 2000 ft variation)
Proceeding as descripted above and considering a “virtual altitude” of (5000 + 2000) ft:
- the corrected capacity is 3847 MBtu/hr;
Burner RL 100/M is OK
- the corrected burner air pressure is 1.92.
CORRECTED BURNER CAPACITY ACCORDING TO ALTITUDE
m. a.s.l.
ft a.s.l
0
0
494
987
1481
1974
2468
2962
3455
3949
4442
4936
5429
5923
6417
6910
7404
7897
8391
8885
9378
9872
100
328
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
5500
6000
6500
7000
7500
8000
8500
9000
9500
10000
305
1000
512
1023
1535
2046
2558
3069
3581
4092
4604
5116
5627
6139
6650
7162
7673
8185
8697
9208
9720
10231
610
2000
530
1061
1591
2121
2652
3182
3712
4243
4773
5303
5834
6364
6894
7425
7955
8485
9016
9546
10076
10607
Altitude
915
3000
551
1101
1652
2202
2753
3303
3854
4404
4955
5505
6056
6606
7157
7708
8258
8809
9359
9910
10460
11011
1220
4000
571
1142
1713
2284
2855
3425
3996
4567
5138
5709
6280
6851
7422
7993
8564
9135
9705
10276
10847
11418
1525
5000
593
1186
1778
2371
2964
3557
4149
4742
5335
5928
6520
7113
7706
8299
8892
9484
10077
10670
11263
11855
1830
6000
616
1232
1848
2464
3079
3695
4311
4927
5543
6159
6775
7391
8006
8622
9238
9854
10470
11086
11702
12318
2135
7000
641
1282
1924
2565
3206
3847
4488
5130
5771
6412
7053
7694
8335
8977
9618
10259
10900
11541
12183
12824
2440
8000
669
1337
2006
2675
3343
4012
4680
5349
6018
6686
7355
8024
8692
9361
10029
10698
11367
12035
12704
13373
mbar
1013
1000
977,4
942,8
908,2
875,8
843,5
811,85
779,8
747,8
"w.c.
399
394
385
371
358
345
332
320
307
294
CORRECTED BURNER AIR PRESSURE ACCORDING TO ALTITUDE
m. a.s.l.
ft a.s.l
0
0
0,49
0,99
1,48
1,97
2,47
2,96
3,46
3,95
4,44
4,94
5,43
5,92
6,42
6,91
7,40
7,90
8,39
8,88
9,38
9,87
100
328
0,50
1,00
1,50
2,00
2,50
3,00
3,50
4,00
4,50
5,00
5,50
6,00
6,50
7,00
7,50
8,00
8,50
9,00
9,50
10,00
305
1000
0,51
1,02
1,53
2,05
2,56
3,07
3,58
4,09
4,60
5,12
5,63
6,14
6,65
7,16
7,67
8,18
8,70
9,21
9,72
10,23
610
2000
0,53
1,06
1,59
2,12
2,65
3,18
3,71
4,24
4,77
5,30
5,83
6,36
6,89
7,42
7,96
8,49
9,02
9,55
10,08
10,61
Altitude
915
3000
0,55
1,10
1,65
2,20
2,75
3,30
3,85
4,40
4,95
5,51
6,06
6,61
7,16
7,71
8,26
8,81
9,36
9,91
10,46
11,01
1220
4000
0,57
1,14
1,71
2,28
2,85
3,43
4,00
4,57
5,14
5,71
6,28
6,85
7,42
7,99
8,56
9,13
9,71
10,28
10,85
11,42
1525
5000
0,59
1,19
1,78
2,37
2,96
3,56
4,15
4,74
5,33
5,93
6,52
7,11
7,71
8,30
8,89
9,48
10,08
10,67
11,26
11,86
1830
6000
0,62
1,23
1,85
2,46
3,08
3,70
4,31
4,93
5,54
6,16
6,77
7,39
8,01
8,62
9,24
9,85
10,47
11,09
11,70
12,32
2135
7000
0,64
1,28
1,92
2,56
3,21
3,85
4,49
5,13
5,77
6,41
7,05
7,69
8,34
8,98
9,62
10,26
10,90
11,54
12,18
12,82
2440
8000
0,67
1,34
2,01
2,67
3,34
4,01
4,68
5,35
6,02
6,69
7,35
8,02
8,69
9,36
10,03
10,70
11,37
12,04
12,70
13,37
mbar
1013
1000
977,4
942,8
908,2
875,8
843,5
811,85
779,8
747,8
"w.c.
399
394
385
371
358
345
332
320
307
294
Reference conditions (Charts 1-2): Ambient temperature 68 °F (20 °C) - Barometric pressure 394” WC (1000 mbar) - Altitude 328 ft a.s.l. (100 m a.s.l.)
15
FLAME SIGNAL MEASUREMENT (A)
Min value for a good signal: 8 μA.
If the value is lower, it can be due to:
• Worn photocell;
• Low current;
• Bad set up of the burner.
In order to measure the current, use a microammeter of
100 μA c.c., connected to the scanner, as in the diagram.
LAL2... Sub-base
Min. detector current required at AC 230 V
D3206
(A)
8 μA
Max. detector current required without
flame
0.8 μA
Max. detector current that can occur
35 μA
Instrument’s + pole
to term. 22
Length of detector line
In the same cable as the control lines
Full modulation
Separate cable in the cable duct
not perm.
20 m
Three-wire cable
---
Two-wire cable for the detector line (bl,
sw); separate single-wire cable for the line
(br)
---
Shielded cable (e.g. RG62, shielding insulated)
200 m
Shielding
to term. 23
SEQUENCE OF OPERATION - LAL CONTROL
See fig. (B) - (C).
Switching times are given in seconds, in the burner startup sequence.
LAL 2.25
t1
t2
t3
t4
(B)
D2871
High - low
(C)
D2883
16
18
4
2
12
t5
t6
t7
t8
optional
optional
12
4
Legend for the times
t1
Pre-purge time with air damper open
t2
Safety time
t3
Pre-ignition time, short (“Z” connected to
terminal “16”)
t4
Interval between voltage at terminals “18” and
“20”
t5
Air damper running time to OPEN position
t6
Air damper running time to low-flame position
(MIN)
t7
Permissible after-burn time
t8
Interval to the OPEN command for the air damper
BURNER FAULTS
SYMBOL (1)
FAULT
The burner does not start
The burner does not start and a
function lock-out occurs
1
2
-
8
9
10
11
12
13
14
-
SUGGESTED REMEDY
A limit or safety control device is open . . . . . . . . . . . . . . . . Adjust or replace
Control box lock-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reset control box
Oil pressure switch tripped . . . . . . . . . . . . . . . . . . . . . . . . . Adjust pressure switch or eliminate pressure
Motor protection tripped . . . . . . . . . . . . . . . . . . . . . . . . . . . Reset thermal cut-out
No electrical power supply . . . . . . . . . . . . . . . . . . . . . . . . . Close all switches - Check connections
Flame safeguard fuse blown . . . . . . . . . . . . . . . . . . . . . . . . Replace
Contact II of servomotor does not operate, . . . . . . . . . . . . . Adjust cam II or replace servomotor
flame safeguard terminals 11 - 8
Pump is jammed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
Defective motor command control device . . . . . . . . . . . . . . Replace
Defective Flame safeguard . . . . . . . . . . . . . . . . . . . . . . . . . Replace
Defective electrical motor . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
Flame simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace control box
Photocell short-circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace photocell
Missing phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reset thermal cut-out
thermal cut-out trips
when third phase is re-connected
Contact I of servomotor does not operate, . . . . . . . . . . . . . Adjust cam I or replace servomotor
flame safeguard terminals 9-8
Fault in flame detection circuit. . . . . . . . . . . . . . . . . . . . . . . Replace flame safeguard
The burner starts but stops at
maximum air damper setting
The burner starts and then goes
into lock-out
The burner remains in pre-purging
phase
After pre-purge and the safety
time, the burner goes to lock-out
and the flame does not appear
15 -
Uneven fuel supply
45 - Check if cause is in pump or . . . . . . . . . . . . . . . . . . . . . . . . Feed burner from tank
fuel supply system
located near burner
46 - Water in tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Remove water from tank bottom with separate pump
47 - Air has entered the suction line . . . . . . . . . . . . . . . . . . . . . Tighten connectors
- Depression value too high (higher than 35 cm Hg):
48 - Tank/burner height difference too great . . . . . . . . . . . . . . . Feed burner with loop circuit
49 - Piping diameter too small . . . . . . . . . . . . . . . . . . . . . . . . . . Increase
50 - Suction filters clogged . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clean
51 - Suction valves closed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Open
52 - Paraffin solidified due to low temperature . . . . . . . . . . . . . . Add additive to light oil
53 - Return pipe not immersed in fuel . . . . . . . . . . . . . . . . . . . . Bring to same height as suction pipe
54 - Air enters suction piping . . . . . . . . . . . . . . . . . . . . . . . . . . . Tighten connectors
55 - Leakage from sealing organ . . . . . . . . . . . . . . . . . . . . . . . . Replace pump
56 - Not enough air. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjust head and fan damper
57 - Nozzle worn or dirty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
58 - Nozzle filter clogged . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clean or replace
59 - Erroneous pump pressure. . . . . . . . . . . . . . . . . . . . . . . . . . Adjust
60 - Flame stability disk dirty, loose, or deformed . . . . . . . . . . . Clean, tighten in place, or replace
61 - Boiler room air vents insufficient . . . . . . . . . . . . . . . . . . . . . Increase
62 - Too much air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjust head and fan damper
63 - Nozzle or filter dirty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
64 - Unsuitable nozzle delivery or angle . . . . . . . . . . . . . . . . . . See recommended nozzles
65 - Loose nozzle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tighten
66 - Impurities on flame stability disk . . . . . . . . . . . . . . . . . . . . . Clean
67 - Wrong head adjustment or not enough air . . . . . . . . . . . . . Adjust, open air damper
68 - Blast tube length unsuited to boiler . . . . . . . . . . . . . . . . . . . Contact boiler manufacturer
69 - Dirty or defective photocell . . . . . . . . . . . . . . . . . . . . . . . . . Clean or replace
16 -
17 - Contact III of servomotor does not operate, . . . . . . . . . . . . Adjust cam III or replace servomotor
flame safeguard terminals 10-8
18 - No fuel in tank; water on tank bottom . . . . . . . . . . . . . . . . . Top up fuel level or suck up water
19 - Inappropriate head and air damper adjustments . . . . . . . . Adjust
20 - Light oil solenoid valves fail to open . . . . . . . . . . . . . . . . . . Check connections; replace coil
21 - Nozzle clogged, dirty, or deformed . . . . . . . . . . . . . . . . . . . Replace
22 - Dirty or poorly adjusted firing electrodes. . . . . . . . . . . . . . . Adjust or clean
23 - Grounded electrode due to broken insulation . . . . . . . . . . . Replace
24 - High voltage cable defective or grounded . . . . . . . . . . . . . . Replace
25 - High voltage cable deformed by high temperature . . . . . . . Replace and protect
26 - Ignition transformer defective . . . . . . . . . . . . . . . . . . . . . . . Replace
27 - Poor electrical connections of valves or transformer . . . . . Check
28 - Defective flame safeguard . . . . . . . . . . . . . . . . . . . . . . . . . Replace
29 - Pump unprimed. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Prime pump and see "Pump unprimes”
30 - Pump/motor coupling broken . . . . . . . . . . . . . . . . . . . . . . . Replace
31 - Pump suction line connected to return line . . . . . . . . . . . . . Correct connection
32 - Valves up-line from pump closed . . . . . . . . . . . . . . . . . . . . Open
33 - Filters dirty: line - pump - nozzle . . . . . . . . . . . . . . . . . . . . . Clean
34 - Incorrect motor rotation direction . . . . . . . . . . . . . . . . . . . . Change motor electrical connections
The flame ignites normally but the 35 - Defective photocell or flame safeguard. . . . . . . . . . . . . . . . Replace photocell or flame safeguard
burner locks out when the safety 36 - Dirty photocell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clean
time has elapsed
Firing with pulsations or flame
37 - Poorly adjusted head . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjust
detachment, (lift off) delayed firing 38 - Poorly adjusted or dirty firing electrodes . . . . . . . . . . . . . . . Adjust
39 - Poorly adjusted fan air gate: too much air . . . . . . . . . . . . . Adjust
40 - Nozzle unsuited for burner or boiler . . . . . . . . . . . . . . . . . . See Nozzle Table
41 - Defective nozzle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
42 - Inappropriate pump pressure . . . . . . . . . . . . . . . . . . . . . . . Adjust
The burner does not pass to 2nd 43 - Control device TR does not close . . . . . . . . . . . . . . . . . . . . Adjust or replace
stage
44 - Defective control box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
Internally rusted pump
Noisy pump, unstable pressure
Pump loses prime after prolonged
pause
Pump leaks light oil
Smoke in flame - dark Bacharach
- yellow Bacharach
Dirty combustion head
I
PROBABLE CAUSE
1
2
3
4
5
6
7
During operation, the burner stops
in lock out
(1) When the burner does not fire or stops following a fault, the symbol which appears on control box after lockout indicates type of problem.
(2) The fuse is located in the rear part of the control box. A spare fuse is also available located under a break off tang.
17
Factory Wiring Diagram
RL70 - 100 - 130/M with burner mounted Siemens LAL control
D2815
Continuous fan operation
Change the wire connection from terminal 7 to terminal 1, move the jumper from terminals 12-13 to terminals 4-12 and
remove the wire from terminal 13 of control box.
D2873
(A)
LAYOUT (A)
Burners RL 70/M - RL 100/M - RL 130/M
S2
Key to Layout (A)
CMV
- Motor contactor
DA
- Control box
FR
- Photocell
MB
- Terminal strip
MV
- Fan motor
PA
- Air pressure switch
PO
- High oil pressure switch
RT
- Thermal overload
S1
- Switch for following operations :
MAN = manual
AUT = automatic
SM
TA
TB
VM
VS
VR
18
OFF
- Button for :
- = power reduction
+ = power increase
- Servomotor
- Ignition transformer
- Burner ground (earth) connection
- Delivery pump valve
- Delivery pump valve (safety valve)
- Valve on nozzle return
Field Wiring Diagram
RL 70 - 100 - 130/M with burner mounted LAL flame safeguard
D2291
Motor Connection
RL 70/M
RL 100/M
RL 130/M
208 208 460 V 575 V 230 V 460 V 575 V
460 V 575 V
230 V
230 V
F
A
T10
T6
T6
T15
T10
T6
T15
T10
T10
S
AWG
14
14
14
14
14
14
14
14
14
D3686
(A)
FIELD WIRING CONNECTIONS
set by installer
Use flexible cables according to local regulation.
LAYOUT (A)
RL 70-100-130/M electrical connection three-phase 208 - 230/460 V power supply
Key to wiring layouts (A)
H1
- Remote lock-out signal
H2
- Burner on signal
H4
- Power on signal
H5
- Limit satisfied
IN
- Manual burner stop switch
MB - Terminal strip
PS
- Remote lock-out reset
OC - Operating control.
HL
- High limit control.
N.B.
• The setting of the thermal overload must be according to the total burner amperage draw.
• The RL 70-100-130/M burners leave the factory preset for:
- 208-230 V power supply: only in this case, if 460 V power supply is required, change the fan and the pump motor connection from delta to star
and change the setting of the thermal overload as well;
- or 575 V power supply;
depending on the burner model (see page 3).
• The RL 70/M - RL 100/M - RL 130/M burners have been type-approved for intermittent operation. This means they should be stopped at least once
every 24 hours to enable the control box to perform self checks at start-up. Burner halts are normally provided for automatically by the boiler load
control system.
19
Factory Wiring Diagram RL 70 - 100 - 130/M
With auxiliary panel
20
(A)
Factory Wiring Diagram RL 70 - 100 - 130/M
With auxiliary panel
21
(B)
LAYOUT (A) - (B) page 20 - 21
Burners RL 70 - 100 - 130/M
The flame safeguard is in an auxiliary panel.
See the internal electrical systems of the auxiliary panel in order to have the complete wiring diagram.
Key to Layouts (A) - (B)
B2
- Photocell
BB
-
F1
-
Fan motor thermal overload
K1
-
Fan motor contactor
M1
-
Fan motor
SM
-
Servomotor
S10
-
Air pressure switch
S14
-
High oil pressure switch
TB
-
Burner ground (earth) connection
T1
-
Ignition transformer
XMB -
On the burner
Burner terminal strip
XMQ -
Auxiliary panel terminal strip
XQ1 -
3-pin plug-socket
XQ2 -
12-pin plug-socket
XQ3 -
12-pin plug-socket
XQ4 -
12-pin plug-socket
Y20
-
Safety oil valve
Y21
-
Oil valve on delivery
Y24
-
Oil valve on return
22
23
39
SPARE PARTS LIST
19
10
9
8
17
17
62
9
8
7
6
5
4
3
2
1
0
16
49
30
72
46
30
36
44
18
84
35
4
85
29
18
C5830009
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
• • • •
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
• •
•
• • •
•
• • •
• • •
•
•
•
•
•
•
•
C9716301 (3477473) *
• •
•
•
• • • •
•
•
• • • •
• • • •
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
C9516301 (3477475)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
C9716300 (3477473) *
C9715301 (3477273) *
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
C9516300 (3477470)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
• •
•
•
• • • •
•
•
• • • •
• • • •
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
C9714300 (3477273) *
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
C9515300 (3477270)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
C9515301 (3477275)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
C9714300 (3477073) *
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
C9714301 (3477073) *
3012454
3003948
3003949
3007079
3003006
3012455
3009081
3012949
3012948
3012622
3012458
3006292
3006787
3003055
3006184
3007164
3012932
3012384
3012957
3000805
3013127
3013205
3012933
3012343
3012080
3007627
3012934
3012935
3012936
3012937
3012991
3013124
3013125
3012938
3006140
3012357
3003952
3003763
3012939
3012403
3012940
3003954
3013056
3012476
C9514301 (3477075)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
21
22
23
24
25
26
27
27
27
27
27
27
28
29
30
31
32
33
33
33
34
34
35
C9514300 (3477070)
N. CODE
•
•
•
•
•
• • • •
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
• • • •
• • • • • • • •
• • • • • • • • • • • •
DESCRIPTION
DESCRIZIONE
BURNER SERIAL NUMBER
MATRICOLA BRUCIATORE
AIR INTAKE
AIR DAMPER ASSEMBLY
GRID
SEAL
CONNECTOR
CONNECTOR
CONNECTOR
CONNECTOR
AIR PRESSURE SWITCH
DRIVE DISC
TUBE
SEAL
FILTER
CONNECTOR
BAR
SEAL
PLUG
OIL PRESSURE SWITCH
ANCHOR PLATE
PUMP SEAL
BASE PLATE
BASE PLATE
CONTROL BOX LAL 2.25
SUPPORT
SWITCH
MEMBRAN
COVER
OVERLOAD+CONTACTOR 208-230/460V
OVERLOAD+CONTACTOR 208-230/460V
OVERLOAD+CONTACTOR 208-230/460V
OVERLOAD+CONTACTOR 575V
OVERLOAD+CONTACTOR 575V
OVERLOAD+CONTACTOR 575V
TRANSFORMER
PRESSURE GAUGE
BEARING
SOUND DAMPING
INSPECTION WINDOW
FAN
FAN
FAN
DRIVE COUPLING
DRIVE COUPLING
NEEDLE VALVE
BOCCA D'ASPIRAZIONE
GRUPPO SERRANDA
PROTEZIONE
GUARNIZIONE
RACCORDO
RACCORDO
RACCORDO
RACCORDO
PRESSOSTATO ARIA
DISCO ELASTICO
TUBO
GUARNIZIONE
FILTRO
RACCORDO
PERNO
GUARNIZIONE
TAPPO
PRESSOSTATO OLIO
PIASTRA
ORGANO DI TENUTA
MENSOLA
MENSOLA
APPARECCHIATURA LAL 2.25
SUPPORTO
INTERRUTTORE
MEMBRANA
COFANO
RELE' TERMICO+CONTATTORE 208-230/460V
RELE' TERMICO+CONTATTORE 208-230/460V
RELE' TERMICO+CONTATTORE 208-230/460V
RELE' TERMICO+CONTATTORE 575V
RELE' TERMICO+CONTATTORE 575V
RELE' TERMICO+CONTATTORE 575V
TRASFORMATORE
MANOMETRO
CUSCINETTO
FONOASSORBENTE
VISORE
GIRANTE
GIRANTE
GIRANTE
GRUPPO GIUNZIONE
GRUPPO GIUNZIONE
VALVOLA DI SCARICO
C5360001
C9715301 (3477273) *
C9714300 (3477273) *
C9714301 (3477073) *
• • • • • • • • •
• • • • • • • •
•
• • • •
• • • •
•
• • • • • • • •
•
• • • •
• • • •
•
• • • • • • • • •
• • • • • • • • •
• • • • • • • • •
• • • • • • • • •
• • • • • • • • •
• • • • • • • • •
• • • • • • • • •
C9514300 (3477070)
C9516301 (3477475)
3003974
3003975
3003976
3012464
3012465
3012466
3003983
3003984
3012467
3012468
3012469
3003322
3012950
3012354
3012353
3012352
3006098
3003841
C9516300 (3477470)
•
•
C9515301 (3477275)
• • • • • • • • • • •
• • • • • • • • • • •
•
•
•
•
•
•
•
•
•
•
•
• • • • • • • • • • •
• • • • • • • • • • •
• • • • • • • • • • •
• •
• •
• •
• • • • • • • • • • •
• • • • • • • • • • •
• • • • • • • • • • •
• • • • • • • • • • •
• • • • • • • • • • •
• • • • • • • • • • •
• • • • • • • • • • •
• • • • • • • • • • •
• • • • • • • • • • •
• • • • • • • • • • •
• • • •
• • • • • • •
• • • • • • • • • • •
C9515300 (3477270)
C9716301 (3477473) *
C5360027
C9714300 (3477073) *
C9716300 (3477473) *
36
37
38
38
38
38
38
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
53
54
55
56
57
57
58
58
58
59
59
60
60
60
61
62
63
64
65
66
67
C9514301 (3477075)
3007169
3012012
3012941
3012942
3012943
3013059
3013060
3013061
3012944
3003481
3003970
3006216
3003996
3006369
3012092
3012475
3012959
3003796
3003495
3012461
3012095
3012096
3012462
3012463
3012127
N. CODE
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
• • •
• • •
• • •
• • •
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
DESCRIPTION
DESCRIZIONE
BURNER SERIAL NUMBER
MATRICOLA BRUCIATORE
O RING
HALF-SHELL
MOTOR 208-230/460V
MOTOR 208-230/460V
MOTOR 208-230/460V
MOTOR 575V
MOTOR 575V
MOTOR 575V
SERVOMOTOR
SCREW
BAR
P.E. CELL
PLUG
PUMP
SUPPORT
TUBE
H.T. LEAD
ELECTRODE
U BOLT
SUPPORT
NUT
NOZZLE HOLDER ASSEMNLY
DIFFUSER DISC
DIFFUSER DISC
SPACER
ANELLO OR
GUSCIO
MOTORE 208-230/460V
MOTORE 208-230/460V
MOTORE 208-230/460V
MOTORE 575V
MOTORE 575V
MOTORE 575V
SERVOMOTORE
VITE
PERNO
FOTORESISTENZA
TAPPO
POMPA
SUPPORTO
TUBO
COLLEGAMENTO
ELETTRODO
CAVALLOTTO
SUPPORTO
DADO
GRUPPO PORTAUGELLO
ELICA
ELICA
DISTANZIALE
CONTROL DEVICE
FRONT PIECE
FRONT PIECE
SQUARE
SQUARE
SQUARE
SHUTTER
SHUTTER
END CONE
END CONE
END CONE
CONNECTOR
CONTROL BOX BASE
LEVER
BAR
BAR
PIN JOINT
BEARING
GRUPPO REGOLATORE
FRONTONE
FRONTONE
SQUADRETTA
SQUADRETTA
SQUADRETTA
OTTURATORE
OTTURATORE
IMBUTO FIAMMA
IMBUTO FIAMMA
IMBUTO FIAMMA
RACCORDO
ZOCCOLO
LEVA
PERNO
PERNO
SNODO SFERICO
CUSCINETTO
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
C9716301 (3477473)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
C9516301 (3477475)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
C9716300 (3477473)
C9715301 (3477273) *
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
C9516300 (3477470)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
C9714300 (3477273) *
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
C9515300 (3477270)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
C9515301 (3477275)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
C9714300 (3477073) *
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
C9714301 (3477073) *
3012470
3012471
3003005
3012351
3006723
3012359
3012472
3006097
3012358
3012356
3012945
3006767
3007150
3003204
3003200
3012474
3013065
3009075
3013231
C9514301 (3477075)
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
C9514300 (3477070)
N. CODE
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
DESCRIPTION
DESCRIZIONE
BURNER SERIAL NUMBER
MATRICOLA BRUCIATORE
TUBE
TUBE
CONNECTOR
TIE ROD
CONNECTOR
LEVER
BEARING
FLAT SPRING
CAM ASSEMBLY
SPRING
SHAFT
COIL
O RING
SEAL
NUT
MODULATOR
CONNECTOR
CONNECTOR
PLUG
TUBO
TUBO
RACCORDO
TIRANTE
RACCORDO
LEVA
CUSCINETTO
MOLLA
CAMMA COMPLETA
MOLLA
ALBERO
BOBINA
ANELLO OR
GUARNIZIONE
DADO
MODULATORE
RACCORDO
RACCORDO
SPINA
BURNER START UP REPORT
Model number:
Serial number:
Project name:
Start-up date:
Installing contractor:
Phone number:
GAS OPERATION
Gas Supply Pressure:
CO2: Low Fire
High Fire
Main Power Supply:
O2: Low Fire
High Fire
Control Power Supply:
CO: Low Fire
High Fire
Burner Firing Rate:
NOX: Low Fire
High Fire
Manifold Pressure:
Net Stack Temp - Low Fire:
High Fire:
Pilot Flame Signal:
Comb. Efficiency - Low Fire:
High Fire:
Low Fire Flame Signal:
Overfire Draft:
High Fire Flame Signal:
OIL OPERATION
Oil supply pressure:
CO2: Low Fire
High Fire
Oil suction pressure:
O2: Low Fire
High Fire
Control Power Supply:
CO: Low Fire
High Fire
Burner Firing Rate:
NOX: Low Fire
High Fire
Low Fire Flame Signal:
Net Stack Temp - Low Fire:
High Fire:
High Fire Flame Signal:
Comb. Efficiency - Low Fire:
High Fire:
Low Fire Nozzle Size:
Overfire Draft:
High Fire Nozzle Size:
Smoke number:
CONTROL SETTINGS
Operating Setpoint:
Low Oil Pressure:
High Limit Setpoint:
High Oil Pressure:
Low Gas Pressure:
Flame Safeguard Model Number:
High Gas Pressure:
Modulating Signal Type:
NOTES
27
RIELLO S.p.A.
Via degli Alpini 1
I - 37045 Legnago (VR)
Tel.: +39.0442.630111 Fax: +39.0442.630375
http:// www.rielloburners.com
RIELLO BURNERS NORTH AMERICA
1-800-4-RIELLO
35 Pond Park Road
Hingham, Massachusetts,
1-800-474-3556
U.S.A. 02043
2165 Meadowpine Blvd.
Mississauga, Ontario,
Canada L5N 6H6
http://www.riello-burners.com
Subject to modifications