Coal Authority Downbrook MWTS Specification Coal Authority Downbrook MWTS Specification Coal Authority Downbrook MWTS Specification PART C WORKS INFORMATION Date: 21/11/2011 Page 2 of 26 Issue:03 Coal Authority Downbrook MWTS Specification SECTION 1 – DESCRIPTION OF THE WORKS 1.1 Introduction Covered in CA Documentation 1.2 Description of the project Covered in CA Documentation 1.3 Site Location Covered in CA Documentation 1.4 Extent of Works 1.4.1 Work under this Contract The works at Downbrook Minewater Treatment Scheme shall include but not be limited to the following: Factory Acceptance Testing (FAT). Delivery to site, off loading and handling on site. Construction of a headworks surround, hardstanding area, Motor Control Centre Slab and false flooring and installation of interconnecting duct work. Supply and installation of all headworks steel work. Supply and Installation of Motor Control Centre, including supply and programming of site controller (PLC). Supply and installation of Steel Kiosk. Supply and installation of borehole pump, riser pipes, headplate, above ground pipework, valves and instrumentation. Supply and installation of discharge range, intermediate chambers, valves and other defined fittings. Cabling and installation work associated with all pumping plant and services as above. Instrumentation as required to control and monitor the plant. Commissioning and putting into service. Record drawings in paper and electronic (CAD) form. Operating and Maintenance manuals in paper and electronic format. Training of Purchaser’s staff. Installation of ‘free-issue’ telemetry equipment. The Works shall include all items necessary for the complete execution of the Contract whether expressly listed or not. In respect of the site installation and modification works in the Contractor’s scope the Contractor shall survey the site to determine the exact requirements. All equipment shall be installed and connected in accordance with the manufacturer’s recommendations. The Contractor shall not degrade the performance, reliability or robustness of the systems to be modified in any way. Date: 21/11/2011 Page 3 of 26 Issue:03 Coal Authority Downbrook MWTS Specification 1.4.2 Work by Others The work to be undertaken by others shall include the following: 1.4.3 Provision of power supply to the site (client to manage) Provision of telecommunication to the site (client to manage) Telemetry configuration Variations and Deviations from Specification Where the Contractor identifies an alternative means of delivering the works, the Contractor will submit for approval the details and any associated cost increase or saving to the Coal Authority for review. Any deviations from the specification will not be implemented without written acceptance or approval from the Coal Authority or their nominated representative. Date: 21/11/2011 Page 4 of 26 Issue:03 Coal Authority Downbrook MWTS Specification SECTION 2 – PARTICULAR SPECIFICATION 2.1 Introduction 2.2 Construction (Design & Management) Regulations 2007 The Contractor shall be appointed Principal Contractor, following assessment for competence, and shall carry out the duties of Principal Contractor as defined in the Construction (Design and Management) Regulations 2007. In addition, the Contractor shall carry out the duties of Designer as defined in the Construction (Design and Management) Regulations 2007 for all aspects of design the Contractor carries out. The Contractor shall ensure a Designer’s Risk Assessment is produced for the design work he is responsible for and submit it to the CDM Co-ordinator for acceptance at least 14 days before construction starts. 2.3 Programme of Works The Contractor shall submit a detailed Programme of Works for review by the Client. The programme shall be detailed sufficiently to allow the Project manager to assess its validity. The Programme shall as a minimum include the following work: Design and submission of drawings Procurement Works Testing and Factory Acceptance Testing (FAT) Construction Site installation Commissioning Site Acceptance Testing (SAT) Submission of manuals Training The contractor will include a 2 week review period of any proposed plant and equipment, prior to placing orders for any such plant or equipment. Similarly any plant which requires further design development, e.g. the MCC, drawings and Functional Design Specification will be submitted for review prior to progressing the manufacture of any such items. 2.4 General Technical The Contractor shall adopt the initial design and develop it to construct a fully equipped and operational pumping station. The installed pumping installation shall be automatically controlled by a PLC system, the software for which will be developed by the Contractor or appointed sub contractor. 2.5 Design Within this specification, Appendix A, the Contractor is provided with drawings and information. The Contractor shall recognise that such drawings and/or information shall in no way diminish or negate the Contractors design responsibility to provide a fully functional pumping station. The content of all drawings / information provided shall be verified by the Contractor as correct. Where not explicitly stated within this specification, standards for plant; equipment and installation will be in accordance with the standards referred to in Appendix C. The details of all plant being supplied by the Contractor, will be submitted to The Coal Authority, or nominated representative, for review and approval, prior to orders being placed by the Contractor. Date: 21/11/2011 Page 5 of 26 Issue:03 Coal Authority Downbrook MWTS Specification 2.6 Plant Performance The Contractor shall guarantee the BH pump performance as declared in his submission. This will include the submission of at least 3 options for the borehole pump, which meet the operating criteria specified in section 2.10.1, including full performance curves, guaranteed work test values and comparative costs. This will enable the Coal Authority to choose the optimum pump performance, following a Capital and Operating expenditure analysis. 2.7 Plant Access 2.7.1 General As far as practicable within this design, the Contractor shall ensure all plant, valves and equipment are fully accessible for maintenance and removal in a safe manner. 2.7.2 Craneage The Contractor shall make his own arrangements in regard to any offloading and lifting during the works. 2.7.3 Free Issue Items For this site the following items will be “free issued”: 2.8 Radio Telemetry Unit (Opus) GSM Modem and SIM Card. Commissioning FAT & SAT documents shall be provided at least 2 weeks prior to the commencement of commissioning. The MCC shall undergo tests at the factory, including but not limited to: high voltage “flash” tests, visual inspections and checks, and functional tests including PLC I/O signals, instrument transmitters and control equipment. The Employer shall be given opportunity to witness the tests at the factory. A test procedure shall be submitted for approval at least two weeks before the tests are due to take place. A record of the tests shall be submitted immediately after the tests are concluded. The Contractor shall undertake such pre-commissioning tests as are necessary to ensure that the plant is ready for commissioning with the Client’s representative. 2.9 Training The Contractor shall include 2 training sessions, duration not exceeding 4 hours each. The training sessions shall be designed to complement the Operating & Maintenance manuals and shall prepare the Coal Authority’s appointed Operations and Maintenance Contract staff for routine operations and detailed maintenance of the plant supplied. A process overview will be required with detailed training on equipment maintenance procedures, including the type and frequency of maintenance. Date: 21/11/2011 Page 6 of 26 Issue:03 Coal Authority Downbrook MWTS Specification 2.10 Mechanical Works 2.10.1 Borehole 2.10.1.1 Borehole Pump Specification The Contractor shall supply and install within the Borehole, a single submersible pump-set operating at variable speed from an AC inverter drive mounted in a remote MCC, generally in accordance with WIMES 1.05. Borehole Details: Top of Borehole Level Bottom of Casing Level Proposed Minimum Pump Level Bottom of Borehole Level ID of Casing ID of Open Hole Casing Note: ~90.5mAOD 70.5mAOD 71.0mAOD 67.0mAOD 380mm 250mm Actual Pump installation depth will ensure that NPSH requirements of the pump are met at the proposed Pumping Level of 71.0mAOD. This will be determined following a review of the pump performance curves provided under Section 2.6. Pumping Borehole Water Levels: At Rest Level – Discharge Control Level – Proposed Pumping Level – ~84.9mAOD 82.4mAOD 79.4mAOD Pump Duties: Normal duty (At target level) Flow – Head - 15 l/s 18.5 m Maximum flow (Initial drawdown) Flow – Head - 30 l/s 15 m The borehole pump, including all internal and external components, will be suitable for the long term operation whilst pumping water of the quality contained within the borehole. A detailed water analysis is provided in Appendix B. The Contractor shall provide full characteristic curves, including pump/motor combined overall efficiency and NPSH requirements at maximum (duty) speed and at the minimum speed recommended by the motor manufacturer. Pump curves will offer guarantee points to BS EN ISO 9906 Class 1 tolerances, with no negatives on pump efficiency. Pumps will be works tested and curves provided for review prior to despatch. The Client or nominated representative, will be given the opportunity to witness any such performance tests. Each pump motor is to be appropriately rated for operation with a frequency inverter to provide variable speed control. The motor shall be suitably rated to deliver the maximum absorbed power across the complete available operating range specified by the pump manufacturer, plus a margin of 10%. Where there is a non overloading power curve characteristic, the motor will be rated to the maximum possible power plus a margin of 10%. This will be verified by the Coal Authority’s nominated representative prior to an order being placed. Date: 21/11/2011 Page 7 of 26 Issue:03 Coal Authority Downbrook MWTS Specification Pump motors will be wound with high temperature windings and include temperature monitoring sensors (PT100s). The temperature monitoring sensors will be provided with sufficient cable to enable the signals to be presented to a temperature monitoring unit housed within the new MCC, this does not preclude the use of a local junction box at the head works. The Contractor shall ensure that all electric cables are suitable for the operating conditions under which they will operate. The length of cable attached to the motor will be sufficient to reach the headwork’s junction box, plus 5m, to enable the cable to be cut and re-used on subsequent pump changes. 2.10.1.2 Borehole Rising Main The Contractor shall supply a 150mm diameter rising main of total length to suit the pump position when the intake level is set as specified in clause 2.10.1.1. Each pipe section shall be a maximum of 3m in length and connected with flange joints. The contractor will provide a starter pipe, 500mm long, to provide a means of clamping the pumpset for installation; this pipe will also be used, where necessary, to make the transition from the pump discharge flange to the rising main flange. The pressure rating of the column pipe shall safely withstand the closed valve delivery pressure of the pump, plus the combined weight of the pump set and column pipe. All pipework shall be fabricated in carbon steel using tubes conforming to BS3601, API 5L Grade B, HFS or equivalent, rated for 16 bar working pressure, with a minimum wall thickness of 9mm. All flanges shall be raised face steel plate type to BS EN 1092-1:2002, PN16 with continuous internal and external fillet welds. Welding shall comply with BS 2971:1001. Flange fixing holes shall be sized so that the correct diameter bolts can be fitted without damaging the protective coating. Flange fixings shall be in grade A2 stainless steel with a flat washer located under each bolt head and each nut. The nut will be manufactured in grade A4 stainless steel, to prevent ‘pick-up’, whilst assembling and removing the bolts during installation and future removal. Flange gaskets shall be full faced, to BS 2494, manufactured in EPDM rubber. If required, a double flanged or similar adaptor shall be supplied to connect the pump set to the column pipe. On completion of fabrication the column pipe sections shall be grit blasted to SA 2.5 and coated internally and externally with a fusion bonded epoxy resin. The coating material shall be 100% solid thermosetting fusion bonded epoxy resin as ‘ScotchKote 206 N’; Rilsan; or an approved equivalent. The thickness of the finished coating shall be not less than 0.3mm. During installation the motor cables and temperature monitoring cables, shall be securely supported at the pump flanges using non-corrodible clamps as detailed in the drawings held in the appendices of this specification. The contractor shall supply a set of certified lifting clamps for the purpose of installing the rising main and pump-set, they shall be left on site for future use by the Coal Authority. The lifting clamps will be manufactured in mild steel, before being hot dip galvanised. They shall be load tested to 150% of the maximum possible load in service. Test certificates shall be provided. 2.10.1.3 Borehole Headworks The contractor shall provide a borehole extension piece, with integral dip tube mounting plates, cable way and cable cover with access plate. This will enable the motor and instrument cables to be directed into the cable trench adjacent to the headworks, for connection into remote junction boxes. The configuration of the borehole extension will generally be in accordance with the drawings provided in the appendices. Date: 21/11/2011 Page 8 of 26 Issue:03 Coal Authority Downbrook MWTS Specification The headworks will include a headplate, which will be bolted to the borehole extension and act as the support for the rising mains, and the transition point to the headworks discharge pipework. The headplate will generally be in accordance with the drawings provided in the appendices and include a ½” bsp tapping below the headplate for the connection of a pressure transducer, which will be accessible from above. 2.10.1.4 Borehole Headworks Pipework and Valves The Contractor shall supply and install a range of 200mm NB pump delivery pipework from head plate to below ground, where the transition will be made to a 225 SDR17 MDPE (PE80) discharge range. Each delivery pipe shall be fitted with all necessary isolation valves and branches to comply with the proposed layout drawing held in the appendices. The scope of borehole pump pipework shall include but not be limited to; all pipe, fittings, valves, flange jointing, pipe supports/straps, cleaning access points & small bore tappings for instrumentation etc. The Contractor shall include the following within the scope of delivery pipework: 1 No. connection for automatic air valve located on crown of pipe, at least 2 diameters downstream of the headplate bend. Supply with isolating valve. Butterfly valves shall be the double flanged type, manually operated by a hand wheel and a gearbox, the hand wheel will be removable. Face to face dimensions will be in accordance with EN 558, Series 14. Gate valves will be double flanged and manually operated by a hand wheel, which will be removable. The gates will be resilient seated to provide a full bore aperture within the valve and will conform to BS 5163. The first 90o bend bolted to the head plate/clamp shall have sufficient horizontal straight length, such that disconnection at the first joint allows unrestricted lift of the borehole pump or head plate/clamp. All pipework shall be fabricated in carbon steel using tubes conforming to BS3601, API 5L Grade B, HFS or equivalent, rated for 16 bar working pressure. All bends will have a long radius to allow cleaning pigs to pass through easily. Upon completion of fabrication the pipework shall be grit blasted to SA 2.5 and coated externally and internally with fusion bonded epoxy resin, as 'Skotchkote 206 N'; or Rilsan; or an approved equivalent. The thickness of the finished coating shall be checked with a calibrated thickness tester and shall not be less than 0.3mm. Flange adaptors shall be nylon coated or fusion bonded epoxy coated. All flange adaptors shall be tied to the pipework to resist thrust. Flange fixings shall be to BS 4190 grade 8.8 or equivalent, hot dip galvanised to BS EN ISO 1461 with a washer located under both bolt head and nut. Flange gaskets shall be full faced to BS 2454 manufactured in EPDM. Where pipework is damaged or modified on site, the affected areas will be repairs in accordance with the coating suppliers recommendations using materials, supplied or approved by the coating manufacturer/applier. 2.10.2 Borehole Instrumentation The Contractor shall supply and install the following instrumentation at the borehole: Date: 21/11/2011 Page 9 of 26 Issue:03 Coal Authority Downbrook MWTS Specification (a) (b) (b) A Borehole level transducer terminated at a local junction box, housed beneath the headworks steel work. A discharge pressure transducer. A 200 NB electro magnetic flow meter. See Section 2.11 for details. The contractor shall supply and install 3 off dip tubes suspended from the dip tube support plate detailed on the enclosed drawings, the dip tubes will be of a trapezoidal thread design to provide a smooth external and internal wall, include an end cap to prevent instruments from dropping into the well area and a screened casing at the top and bottom to allow water in and air to vent within the dip tube, the dip tubes will finish with a bsp adapter, suitable for screwing into the support plate and a suitable cap for glanding and supporting any instruments installed within the dip tubes. 2.10.3 Discharge Range 2.10.3.1 Pipework The contractor shall be responsible for the supply and installation of a 225OD SDR 17 MDPE PE80 discharge range from the headworks, below ground to each of the cascades; this will include all intermediate inspection chambers, cross connection and valve chambers as detailed on the supplied drawings. The nominal depth of lay will be 900mm to crown, with imported backfill in accordance with Coal Authority Standards Specifications and CESWI specifications/guidelines. The pipework will be installed using butt fusion techniques with electro-fusion couplers acceptable at transitions in materials in conjunction with stub flanges. The line of the discharge range is to be a straight as possible, where bends need to be used, they will have a long radius to ensure cleaning ‘pigs’ can pass unobstructed through the full length of the discharge range. Pipework entering and exiting chambers will be mild steel and include puddle flanges as detailed on the drawings provided. All pipework shall be fabricated in carbon steel using tubes conforming to BS3601, API 5L Grade B, HFS or equivalent, rated for 16 bar working pressure. Upon completion of fabrication the pipework shall be grit blasted to SA 2.5 and coated externally and internally with fusion bonded epoxy resin, as 'Skotchkote 206 N' or an approved equivalent. The thickness of the finished coating shall be checked with a calibrated thickness tester and shall not be less than 0.3mm. Flange adaptors shall be nylon coated or fusion bonded epoxy coated. All flange adaptors shall be tied to the pipework to resist thrust. Flange fixings shall be to BS 4190 grade 8.8 or equivalent, hot dip galvanised to BS EN ISO 1461 with a washer located under both bolt head and nut. Flange gaskets shall be full faced to BS 2454 manufactured in EPDM. All bolting exposed to ground conditions on flanges and couplings shall be suitably protected by wrapping with an appropriate proprietary tape protection system. Details of the proposed system shall be submitted to the Project Manager for approval before use. Pipework shall be designed and installed to allow removal of any valve requiring replacement or maintenance without the need to dismantle large sections of pipework, i.e. with the use of tied flange adaptors. Upon completion the pipework will be tested in accordance with the Water Research Council test method Type 2 or Type 1, to a pressure of 1.5 x the rated pressure of the lowest rated component on the system. Date: 21/11/2011 Page 10 of 26 Issue:03 Coal Authority Downbrook MWTS Specification Detailed Method Statements and Risk Assessments will be issued at least 2 weeks prior to any testing for review by the Coal Authority or nominated representative. 2.10.3.2 Valves The Contractor shall provide all valves necessary to provide a complete installation and to enable operation and maintenance to be carried out on pumps rising, main and the discharge range, without the need for a complete system shutdown and drain. Gate valves installed below ground will be double flanged, c/w a cap top for operation with a bar and key, the gates will be resilient seated to provide a full bore aperture within the valve, to enable any cleaning pigs to pass through easily. 2.10.3.3 Inspection chambers Due to the relative short length of the rising main/range, it is not envisaged that any intermediate inspection or hatch box chambers will be required. Date: 21/11/2011 Page 11 of 26 Issue:03 Coal Authority Downbrook MWTS Specification 2.11 EICA Works 2.11.1 Introduction The EICA Works shall include but not be limited to design, manufacture, supply, witnessed tests at the factory, installation, tests at site, training for the Employer’s operatives, operating and maintenance instructions, record drawings, diagrams and other documentation, commissioning and setting to work. 2.11.2 Electrical installation design The Contractor shall provide a complete electrical installation design, in accordance with IEE 17th Edition Wiring Regulations, including calculations, diagrams, schedules, drawings and all other documentation required to demonstrate a satisfactory design. 2.11.3 Electrical single line diagram The Contractor shall prepare a detailed single line diagram for the new pumping station. 2.11.4 Main electricity supply The Client will arrange for a new electricity supply to be provided to the proposed Scheme by the energy provider. The contractor shall ensure that a suitable meterbox is included in the booster kiosk design complete with locking arrangement to allow access for both energy provider and the Employer. The meterbox requirements are provided by the Energy provider and these will be forwarded once the provider’s quotation is received. 2.11.5 Motor Control Centre Whilst the pump-set duty is likely to require an 18.5kW drive, there may be a requirement to increase the output from the borehole to achieve the required drawdown, therefore the inverter drive rating is to be increased to 30kW and the incomers oversized accordingly. The Contractor shall provide a Form 4 motor control centre (MCC) with front only access and bottom cable entry, it shall be constructed, generally in accordance with WIMES 3.01, and shall have the following compartments: Main incoming supply, with door mounted multi-function digital power meter (reading V, A, kW, kVA, PF, kWh, etc.) and a phase failure relay with front panel indication and voltfree contact for PLC Generator incoming supply, with a phase failure relay with front panel indication and voltfree contact for PLC, with Castell key interlock with the main incoming supply circuit breaker to prevent simultaneous closure, generator connection facilities and access for generator cables Borehole Pump Variable speed drive Small power distribution section. PLC control system, including UPS and telemetry system All terminals will be of a disconnect type, e.g. knife. A full-length electrical insulation rubber mat will be supplied for in front of the MCC 9.5mm thick, compliant with BS921 Electrical Safety Matting. Date: 21/11/2011 Page 12 of 26 Issue:03 Coal Authority Downbrook MWTS Specification Main Incoming Supply 100 Amp four pole ‘Mains Supply’ moulded case circuit breaker, with adjustable overload and short circuit protection module fitted with door interlocked handle and Castell key switch. An earth leakage detection module, with adjustable trip setting, nominally 100mA. Set of mains monitoring unit current transformers and H.R.C. fuse protection, as required. Phase failure relay. Set of engraved designation labels to complete. Multi Function Kwhr meter with pulsed contact output for remote monitoring. Generator Supply (Temporary): 100 Amp four pole generator moulded case circuit breaker with adjustable overload and short circuit protection module fitted with door interlocked handle and Castell key switch. Set of mains monitoring unit current transformers and H.R.C. fuse protection, as required. Phase failure relay. Set of engraved designation labels to complete. 30kW Borehole Pump Drive – Variable Speed Triple pole door interlocked moulded case circuit breaker with door interlocked handle. Triple pole 30kW. Motor rated 'Line' contactor. 30K.w. ACS 550 VSD complete with Keypad. Set of Instrument protection fuses. Anti-condensation heater. Current transformers. Set of control circuit relays to give the required sequence of operation. Set of electronic timers to give the required sequence of operation. 415/110V A.C. Control transformer. Temperature monitoring unit, recording motor winding temperature and generating a 420mA signal to the PLC. Set of Klippon polyamide control circuit terminals for all incoming and outgoing connections. Set of main motor terminals. Mounted on the Front of the Panel door: Multi-function digital power meter (reading V, A, kW, kVA, PF, kWh, etc.) Temperature display for Motor Winding Temperature Hours Run indicator. 'Hand/Off/Auto' selector switch. 'Start/Stop' pushbuttons for use in the 'Hand' position. Pilot lamps to indicate pump status. Lamp Test pushbutton. Mushroom headed stay put pattern 'Emergency Stop' pushbutton unit. Ventilation fan and filter unit. Set of engraved designation labels. PLC and Control and Instrumentation Date: 21/11/2011 Internal isolator. Allen Bradley P.L.C. system type Compact Logix and comprising:o CPU o RS232 connection to telemetry. o Additional Ethernet connection to telemetry. o Power supply. o Set of digital input cards (16 Inputs). Page 13 of 26 Issue:03 Coal Authority Downbrook MWTS Specification o Set of digital output cards (8 Outputs). o Set of Analogue input cards (16 Inputs). o Set of Analogue output cards (4 Outputs). Door mounted HMI. 5A 24V D.C. Power supply. PT100 to analogue converter. UPS unit with capacity of supporting the above P.L.C. and telemetry unit for 20 minutes. Set of MCB’s. 240V Socket outlet. Internal light fitting with door operated switch. Indicator lamps. Fault Reset pushbutton. Free Issue Telemetry Unit and Modem Distribution Internal mounted 63A moulded case circuit breaker 3 Phase Merlin Gerin Pan Assembly fitted with a selection of miniature circuit breakers. 230V Socket outlet. 110V Tool socket transformer. 110V Tool socket. 24V Tool socket transformer. 24V Tool socket. 2.11.6 Control, HMI & Telemetry Control A new Allen Bradley CompactLogix PLC system shall be supplied and installed in the MCC to control the borehole pump and monitor site parameters. A Functional Design Specification (FDS) for the control of the pumping plant will be developed by the contractor for review by the Client. The software will be capable of automatically starting and stopping the pump to maintain a water level within the borehole, which can be input through the HMI, this will be combined with an ability to enter a set point flow rate, to ensure the pump-set operates at or near it’s best efficiency point. An internal time clock, will enable certain periods of operation to be inhibited, when the electricity tariffs are particularly high, this inhibit function will be overridden if the water level rises to an unacceptably high level, irrespective of the time of day or tariff. In addition the PLC will monitor and record the pump performance and power used to generate a real time pump efficiency, which will be displayed on the HMI. The following PLC signals for the new booster installation shall include: Analogue inputs Main Input Power Borehole Level Pump delivery pressure Pump delivery flow Pump power (prior to inverter) Pump speed (from inverter) Pump Motor Temperature (PT100) Analogue outputs Pump required speed Digital inputs Date: 21/11/2011 Page 14 of 26 Issue:03 Coal Authority Downbrook MWTS Specification Kiosk intruder (doors open) Mains supply healthy Generator supply healthy Pump available Pump running Pump tripped kWhr Pulse from Main Incomer kWhr Pulse from pump starter section Flow pulse from flow meter UPS Status (Healthy/by-pass) Digital outputs Pump start HMI A HMI Panel will be fitted to the door of the PLC compartment and act as an operator interface to; display the status and values of all signals being monitored; enable set points such as pump flow and borehole level to be input. Telemetry Telemetry equipment will be free-issued for incorporation within the ICA section of the new MCC, details of the telemetry equipment is held in the appendices. 2.11.7 Instrumentation The Contractor shall provide all instrumentation including: Borehole Water Level transducer Pump delivery pressure transducer Pump delivery flowmeter Motor temperature PT100s – (Pump manufacturer supply) Borehole Level Transmitter The transducers shall be of the two wire type, provide a 4-20mA signal manufactured by Trafag or equivalent and have the provision to detach the transducer head from the vented cable. The transmitter will be terminated at a control junction box sited at the borehole headworks below the galvanised steel framework. Pressure Transducers These shall be installed on the delivery pipework of the borehole rising main as described previously and fitted with an isolation valve. The pressure transducer shall be of the two wire type and provide a 4-20mA signal, manufactured by Trafag or equivalent. The transmitter will be terminated at a control junction box sited at the borehole headworks below the galvanised steel framework. Flow Meters The Contractor shall supply and install ABB flow meters to monitor the common borehole flows. The flow meters shall be manufactured and tested in accordance with EN ISO 9001 QA system and comply with the following requirements: Date: 21/11/2011 Page 15 of 26 Issue:03 Coal Authority Downbrook MWTS Specification Size: Medium: Pressure: Flanges: Protection sensor: Cable: Transmitter: Display: Flowrate range: Working temp: Option: 200mm Minewater 16 bar maximum BS 4504 PN16 IP68 SWA Remote (240V ac power supply) 3 line with keypad Abstraction 0 - 50 l/s -10deg C to +50deg C Calmaster card & fingerprint The Contractor shall install the flowmeter transmitter head, cable and duct as necessary to complete the installation. A 4-20mA analogue output and flow pulse signal will be connected from the flow transmitter to the PLC. 2.11.8 Building Services for Control Kiosk 2.11.8.1 Lighting Internal fluorescent lighting shall be installed to provide an area illumination of 500lux. Corrosion resistant luminaires shall be provided. The luminaires shall provide maintained emergency lighting for a minimum of 3 hours on main electricity supply failure. 2.11.8.2 Heating The kiosk shall be provided with heaters to maintain an internal temperature of 5ºC with an external temperature of -10ºC. The heaters shall be controlled by a single room thermostat. 2.11.8.3 Ventilation Fan assisted ventilation shall be provided to limit the pumping station internal temperature to a maximum value suitable for the equipment installed within. The ventilation system shall be controlled by a tamperproof thermostat, set to activate the system at 20ºC. The kiosk shall be provided with fixed air inlet and outlet louvres. 2.11.8.4 Earthing and Bonding Compliance with Earthing and Bonding Regulations and Standards shall include bonding across pipe work joints and couplings, provision of main equipotential bonding of entry and exit points of pipe work to the local earth bar. 2.11.8.5 Earthing The Contractor shall provide an independent earthing system designed for full earth fault current and with a maximum resistance to earth of 1 ohm. The independent earth shall be connected by a disconnection link to the Booster Kiosk earth bar. Provision will also be made for the connection of a mobile generator earth point. Proprietary inspection pits shall be provided for inspection of all terminations. 2.11.8.6 Cabling The Contractor shall provide a complete electrical and wiring installation design, in accordance with IEE 17th Edition Wiring Regulations, including calculations, diagrams, schedules, drawings and all other documentation required to demonstrate a satisfactory design. Date: 21/11/2011 Page 16 of 26 Issue:03 Coal Authority Downbrook MWTS Specification The installation shall comprise all cables, cable containment and supports, wiring accessories and all other plant required to provide a complete functional installation. Cabling Power The Contractor shall include within the price for all necessary power cabling to produce a complete and operational site. Preference shall be given to the use of multicore XLPE insulated armoured cables to BS 5467. Other types of cable may be used with the Client’s approval. Cabling Control The Contractor shall include within the price for all necessary control and instrumentation cabling to produce a complete and operational site. All analogue signals shall be cabled using screened twisted-pair cable. All spare cores/pairs in multicore/multipair cables shall be connected to individual disconnect type terminals. Adequate terminals shall be provided for terminating individual and overall screens, and connection to signal earth where appropriate. Date: 21/11/2011 Page 17 of 26 Issue:03 Coal Authority Downbrook MWTS Specification 2.12 Civil & Building Works (ATKINS TO EXPAND ON CIVILS REQUIREMENTS) 2.12.1 General Nominal cover to all steel reinforcement including links shall be not less than 40mm. A blinding layer of minimum thickness 75mm and minimum grade C16/20 concrete, shall be used under all foundations. The minimum grade of concrete to be used in the building foundation shall be grade C28/35. The structural requirements for all structures will be calculated and details of calculations and results will be sent to the Client for review as part of the detailed design process. 2.12.2 Borehole Headworks Slab The Contractor shall design and construct a reinforced concrete foundation around the existing borehole liner flange, generally in accordance with the drawings held in the appendices. The ground preparation and slab will be designed to support the weight of the pump-set, cable, rising main full of water and the head works, which will be transmitted onto the slab directly and through the support beams bolted to the slab. There will be provisions within the slab for 3 off ducts from the GRP Kiosk foundation, 2 off to the borehole head works support steel work and one adjacent to the flow meter. 2.12.3 Kiosk Foundation The Contractor shall design and construct a reinforced concrete foundation to support the new Control Kiosk and the plant installed within it. The construction of the foundation will generally be in accordance with the detail provided in the drawings, the final dimensions will be determined by the size of the proposed Motor Control Centre and associated equipment offered by the contractor. The foundation shall include all cable ducts/drawpits as required to accommodate the installed equipment and will include: 2 No. Ducts to the Borehole Headworks Slab 1 No. Duct to beneath the flow meter 1 No. 150mm Long Radius duct (Black) for the new main incoming supply. 1 No. Duct to the external earthing arrangement. The profile of the slab will enable the Kiosk to be positioned and bolted down, and the area flooded with a free flowing concrete mix to fill the void, thus covering holding down bolts and providing a sealed base. 2.12.4 Kiosk Steel Work The contractor will supply and install all necessary steel work to support the MCC and open mesh flooring, as well as the open mesh flooring. All steel work is to be suitably sized for the anticipated loads and will be hot dip galvanised after manufacture. Date: 21/11/2011 Page 18 of 26 Issue:03 Coal Authority Downbrook MWTS Specification 2.12.5 Kiosk/Control Building The Contractor shall provide and install a building, manufactured from steel, to house the new Motor Control Centre and associated equipment for the operation and monitoring of the borehole pump. The building will generally be in accordance with the drawings provided, the final dimensions will be determined by the size of the Motor Control Centre provided, and will have a minimum internal height of 2500mm. The kiosk will be supplied with a detachable roof, to enable the MCC to be installed and removed, without disturbing the building. The Kiosk will have an access door and a second door for access to the REC incoming fuses and metering, housed in the segregated section of the Kiosk, within the metering section, a flame retardant mounting board will be required. The building shall include an emergency generator cable entry point consisting of a ‘cat flap’ type access door, which can be locked in both closed and open positions. The building shall be fully weather proof, finished to provide a matt gloss finish. Colour Green, 14 C 39 to BS 4800. The kiosk will be manufactured from steel range and meet the requirements of Loss Prevention Certification Board (LPCB) level 4. The building will be of an insulated construction giving a U Value of 0.3w/m2/oC. The Internal finishes will be painted white or any BS4800 colour, fully boarded options are endless see above photos for some examples. Doors are also to be certified to LPCB level 4 insulated, preference is for a single point padlockable system with an internal override. Details of the proposed locking system are to be submitted to the Coal Authority or nominated representative for approval prior to manufacture. The kiosk shall be supplied with the following additional facilities and fixtures. Doors shall have stainless steel hinges and a restraining open mechanism. Thermostatically controlled heating to maintain temperature at 10 o C. High and low level natural ventilation panels with fly / vermin guards. Thermostatically controlled ventilation. Internal fluorescent lights to IP55 switched at inside of doorway, one unit with emergency light facility and test switch, lights will have a means of disconnecting/unplugging to facilitate the removal of the roof without extensive wiring alterations. 1 double socket (BS4343) RCD protected outlet. SP and N Distribution board c/w MCBs and isolator for above electrics plus at least 2 spare ways. Wiring for 230v 50 hertz operation. Wiring to 17th edition of IEE regulations. Security – Door Open contacts. 2.12.6 Chambers It is not envisaged that any additional chambers will be required. . Date: 21/11/2011 Page 19 of 26 Issue:03 Coal Authority Downbrook MWTS Specification APPENDICES Date: 21/11/2011 Page 20 of 26 Issue:03 Coal Authority Downbrook MWTS Specification APPENDIX A DRAWINGS Date: 21/11/2011 Page 21 of 26 Issue:03 Coal Authority Downbrook MWTS Specification Title Drawing No. Rev Site Layout Proposed Site Layout IWK278_100 Sht 1 of 1 0 IWK278_110 Sht 1 of 7 IWK278_111 Sht 2 of 7 IWK278_112 Sht 3 of 7 IWK278_113 Sht 4 of 7 IWK278_114 Sht 5 of 7 IWK278_116 Sht 6 of 7 IWK278_117 Sht 7 of 7 0 0 0 0 0 0 0 Headworks Arrangement and Detail Drawings Headworks Configuration Headworks Concrete Borehole Extension Headplate Detail Pipework Detail Proposed kiosk slab Proposed kiosk layout Date: 21/11/2011 Page 22 of 26 Issue:03 Coal Authority Downbrook MWTS Specification APPENDIX B WATER QUALITY ANALYSIS Date: 21/11/2011 Page 23 of 26 Issue:03 Coal Authority Downbrook MWTS Specification APPENDIX C SPECIFICATIONS AND STANDARDS Date: 21/11/2011 Page 24 of 26 Issue:03 Coal Authority Downbrook MWTS Specification WIMES SPECIFICATIONS 1.05 Submersible Borehole Pump Units. 2: 1 May 2010 This Specification defines the requirements for the performance, design and testing of submersible borehole pump units in the Water Industry in the form of text and DATA SHEETS. The pump unit shall be of centrifugal, multistage, closed impeller design and be driven by an integral, direct coupled, squirrel cage, induction motor. 3.01 Low Voltage Switchgear and Controlgear Assemblies. 4: 1 Jan 2011 This Specification defines the requirements for the design, construction, inspection and testing of lowvoltage switchgear and controlgear assemblies for use in the Water Industry in the form of text and DATA SHEETS. 3.02 Low Voltage Electrical Installations. 3: 1 Jul 2008 This Specification defines the requirements for the design, construction, and initial inspection and testing of low voltage electrical installations (hereafter termed the 'installation') associated with plant, equipment and ancillary services in the Water Industry. 3.02(A) Profibus and Optical Fibre Network Design. 1: 1 Jul 2008 This Specification defines the requirements for the design of Profibus DP, Profibus PA and optical fibre networks in the Water Industry. The installation of Profibus DP, Profibus PA and optical fibre networks is covered by Section 9.4 of WIMES 3.02 (Issue 3). 3.04 Low Voltage Electrical Specification for Package Plant. 4: 1 Jan 2011 This Specification defines the requirements for electrical equipment forming part of package plant (hereafter termed ‘electrical equipment’) for use in the Water Industry in the form of text and DATA SHEETS (refer to Guidance Notes). The package plant will typically be designed to deliver a defined functional performance based on a proven solution. Usually, this solution will not vary significantly from site to site or application to application, other than by the adjustment of operating levels or set points. The electrical equipment shall typically comprise a low voltage switchgear and controlgear assembly (hereafter termed the ‘Assembly’) and a number of local control stations and items of control and monitoring instrumentation, incorporating electrical components or equipment specific to the package plant, together with all associated interconnecting cabling and wiring systems. The total incoming supply to the electrical equipment shall be generally limited to a maximum of 100 A and be protected by a fuse. If the total incoming supply is greater than 100 A, short circuit withstand tests are required and the electrical equipment is outside the scope of this Specification. In this case, WIMES 3.01 (Low Voltage Switchgear and Controlgear Assemblies for use in the Water Industry) and WIMES 3.02 (Low Voltage Electrical Installations) shall apply. 3.05 Electrical Components (For Use in LV Assemblies). 3: 1 Jan 2011 This Specification defines the requirements for the performance, construction, design and testing of electrical components (for use in LV Assemblies) for use in the Water Industry. Date: 21/11/2011 Page 25 of 26 Issue:03 Coal Authority Downbrook MWTS Specification 3.07 Uninterruptible Power Supplies. 3: 1 Feb 2011 This Specification defines the requirements for the performance, design and testing of static, on-line (double conversion) uninterruptible power supplies (UPS) in the form of text and DATA SHEETS. The UPS shall incorporate a bypass facility that shall automatically transfer the load to the bypass circuit, by means of a transfer switch, in the event of a UPS fault or overload. 4.01 Paints & Polymeric Coatings for Corrosion Protection. 3: 1 Sep 2005 This Specification defines the requirements for the corrosion protection of mild steel structures and assemblies, items of machinery and ductile and cast iron pipework (incorporating pipes, valves and fittings) for use in the Water Industry by paints and polymeric coatings (hereafter termed 'coatings'). Typical application areas shall include: a) Machinery and package plant support structures (e.g. baseplates, pedestals and/or support frames); b) Sludge separation equipment (e.g. sludge scraper assemblies); c) Grit separation and removal equipment (e.g. settlement tanks, grit scraper and separator assemblies, and/or rake classifiers); d) Screens (e.g. screen curtain support structures); e) Machinery items (e.g. pumps and gearbox casings); f) The exterior and/or interior surfaces of storage tanks or vessels; and g) The exterior and/or interior surfaces of pipework (incorporating pipes, valves and fittings). 8.03 Mechanical Installation. 2: 1 Aug 2006 This Specification defines the requirements for the mechanical installation of equipment in the Water Industry in the form of text and DATA SHEETS. Additional specification clauses relating to the installation of specific types of equipment (e.g. pumpsets, screens etc.) may be given in the appropriate WIMES for these items of equipment, where such WIMES exist. Date: 21/11/2011 Page 26 of 26 Issue:03
© Copyright 2026 Paperzz