ASTM F1936 Test Report This test is performed in accordance with ASTM F1936-10, a Standard Specification for Shock-Absorbing Properties of North American Football Field Playing Systems as Measured in the Field. The results reported herein reflect the performance of the tested playing field surface at the time of testing and the temperature and ambient conditions reported. Performance will vary with the temperature, moisture content and other factors. The test is performed using a Clegg Impact Tester manufactured by Turf Tec International, in conformance with the technical requirements of ASTM F355 procedure A. ASTM Standards are available from www.astm.org Agency requesting the tests Name: Ball State University - Soccer Address: 2000 W. University Ave City: Muncie State: Indiana Zip: 47306 Country: USA Contact name: Phil Clay Contact phone: 765-730-7209 Date of test: June 2nd, 2014 Manufacturer/Supplier/Installer of Name: AstroTurf Year Installed: N/A Description of surface(s): Warm Product name: Astroturf Date installed: N/A Thickness of surface material: 2” Site Orientation: End A: SOUTH Sideline C: WEST End B: NORTH Sideline D: EAST Evenness (comment on wear patterns and disruption): Rubber was even and there was minimal debris on the playing surface Weather condition of test Sunny Temperature: ambient air 72 Degrees Surface condition: frozen______ dry ___ X ____ damp ______ surface temperature taken ½” depth 70 Degrees The drop height each test location is 2’ and the velocity at the point of impact shall be 11.35 ±0.56 ft/s. The drop height is physically measured. The drops are performed from the same drop height to the same point on the surface. The ASTM F1936 requires that the average Gmax of the second and third drops at a single test point shall not exceed 200 average Gmax. If a turf system is tested in accordance with the Test Method ASTM F355, Procedure C, as specified, and the average Gmax of 1 or more of the tested points reported is in excess of 200 average Gmax, the surface system should be replaced in full or in part. Drop # 1 2 3 Drop height 2’ 2’ 2’ 4 5 6 2’ 2’ 2’ Drop location: Velocity Calibration Drop 1 Calibration Drop 2 Calibration Drop 3 Point 1 – Goal Line, End A, Center Field. Infill Depth 140 141 140 11.2 11.2 11,2 Av. 5&6 7 8 9 Gmax 145 156 153 1.1” 151 2’ 2’ 2’ Point 2 – 10 Yard Line, End A, 63 ft from center of field to Side C. 11.2 11.3 11.2 Av. 8&9 137 139 165 1 ¼” 147 10 11 12 Av. 11&12 2’ 2’ 2’ 13 14 15 Av. 14&15 2’ 2’ 2’ 16 17 18 Av. 17&18 2’ 2’ 2’ 19 20 21 Av. 20&21 2’ 2’ 2’ 22 23 24 Av. 23&24 2’ 2’ 2’ 2’ Point 3 – 25 Yard Line, End A, 40 ft from center of field Side C. 11.2 11.2 11.3 133 143 155 1.3” 144 Point 4 – Center Field. 11.2 11.2 11.2 128 142 146 1 ¼” 139 Point 5 – 25 Yard Line, End B, 63 ft from center of field Side D. 11.2 11.3 11.3 131 150 145 1.25” 142 Point 6 – 12 Yard Line, End B, center of the field. 11.2 11.2 11.2 127 143 146 1.3” 139 Point 7 – NW 40 – Just Out of Bounds 11.2 11.2 11.2 145 166 170 160 1 ¼” 25 26 27 Av. 26&28 2’ 2’ 2’ 2’ 29 30 31 Av. 30&31 2’ 2’ 2’ 2’ 32 33 34 Av. 33&34 2’ 2’ 2’ 2’ Point 8- SW 40 – 10’ in From Sideline 11.2 11.2 11.2 140 162 170 1.1” 157 Point 9 – 6 ft from Goal Line to back of the End Zone, End A, center of field. 11.2 11.2 11.2 138 156 159 1.1” 151 Point 10 – 6 ft from the back of the End Zone to the Goal Line, End B, center of field. Test Performed by: Bruce Heldt 11.3 11.3 11.2 130 148 143 140 1 ¼”
© Copyright 2026 Paperzz