1 New Method to Determine Optimum Impedance of Fault Current Limiters for symmetrical and/or asymmetrical faults in Power Systems Seyed Mahmoud Modaresi1* and Hamid Lesani2 1 Department of Electrical Engineering, Science and Research Branch, Islamic Azad University, Tehran, Iran. 2 The School of Electrical and Computer Engineering, University of Tehran, Tehran, Iran. Abstract—The selection of type and value of Fault Current Limiters (FCLs) impedance is a problem for power network designers. This paper introduces a new method to calculate the optimum value for FCL impedance considering its position in the network. Due to the complexity of this impedance, the costs of both real and imaginary parts of FCL impedance are considered. The optimization of FCL impedance is based on a goal function that while minimizes the cost of FCL impedance; it maximizes the fault current reduction. The FCL position in the network has an effect on calculating the optimum impedance value however; the selection of the FCL location is not the purpose of this paper. The proposed method can be used for every network with symmetrical and asymmetrical faults. However, for the purpose of demonstration a 14-bus IEEE network is used to explain the process. The optimum FCL impedance used in the above mentioned network is calculated by taking into account the vast range of costs for real and imaginary parts of FCL impedance. Index Terms—Fault Current Limiter (FCL), FCL impedance, Short circuit current, Fault Current, Power System. I. INTRODUCTION I NCREASING the fault currents has been a big challenge in power system [1]–[8]. To decrease the fault current level, in one method, Thevenin’s equivalent impedance is increased by splitting Bus Ties of substations or adding series reactors to network. These methods increase the system loss, and also can decrease the voltage and the stability of the network [4]–[10]. In another method, a Fault Current Limiter (FCL) is used to reduce the fault current as a result of adding impedance to the system. The FCL impedance in a normal condition is nearly zero. However, when a fault occurs in the network, the impedance changes to ZFCL [4]–[13]. Fig. 1 shows the FCL configuration before and after the fault occurrence. Fig. 1. Circuital representation of the FCL at pre and post fault periods. Depending on the mechanism and the time of adding or removing FCL impedance, there are many FCL type such as superconductor FCL (SFCL) [2]–[5], [9], [14]–[16], series or parallel resonance FCL [8], [10], magnetic FCL [11], [12] and solid state FCL [6], [13], [17]. In these types of FCL, the *Corresponding author: (e-mail: [email protected]) impedance can be resistance (RFCL), inductive reactance (XFCLL), capacitive reactance (XFCLC) or complex value that is a combination of any or all of them [17]. During the fault occurrence, the FCL impedance can be either a fixed value or a variable value. For the FCLs with variable impedance, such as SFCLs, the impedance increases rapidly until reaches its maximum value [3], [4], [9], [16], [18]. In such cases, the maximum value of FCL impedance is important for calculating optimum impedance [3], [16]. The FCL impedance increases when, the cost of FCL rises [1]–[3] and the level of fault current decreases until it levels off [9], [14], [15], [19]. In the power network, the fault current of buses should be less than the maximum allowable current (Im) of circuit breakers and other components of the network [1]–[3], [20]. The selection of the value and the type of FCL impedance is a big challenge for network designers. In references [1]–[3], the impedance of FCL is selected based on the lower value of FCL impedance, provided that, the fault current of all buses of network be equal or less than Im however, this approach cannot necessarily be an optimized option because, if the fault current reduces further, it can cause some positive effect on the network. For example it can reduce the failure probability of the network components and increases the system reliability [20]–[27]. It can also reduce the level of electro mechanical and thermal tensions on network components [2], [6], [7], [12]. Therefore more reduction of fault current can be an important criterion in the selection of FCL impedance. In references [1]–[4], [28] the FCL impedance has been simply chosen to be purely RFCL or purely XFCLL and then the optimum value of FCL impedance is determined. The FCL impedance can be generally a complex value, consisting of real and imaginary parts [29], [30]. Therefore different prices of the real and imaginary parts of FCL impedance can affect the selection of the value and the type of FCL impedance. In this paper, an approach is proposed to calculate optimum FCL impedance for power network. To be neutral, the FCL impedance can be assumed to be a complex value consisting RFCL, XFCLL and XFCLC. Depending on the network data and the type of faults three phase symmetrical (3ph) and single line to ground (1ph), the fault current is calculated. By considering both the higher fault current reduction and the lower cost of FCL, the optimum value of FCL impedance is determined at certain location of the network. The results are then verified 2 using a computer program developed for 14-bus IEEE system. It should be mentioned that the FCL positioning is not the main goal of this paper and it can be taken into account in the future studies. In addition, the mechanism for FCL operation is not the objective of this paper and only FCL impedance value after the fault occurrence is considered. This paper is organized as follows. Section II discusses the fault current before and after installation FCL. In Section III, locus of FCL impedance for decreasing the fault current equal or less than Im is calculated and cost function of FCL is defined. Method of FCL impedance optimization is probed in Section IV. Numerical studies are examined in Section V. Conclusions are given in Section VI. II. Fault current before and after FCL installation Generally, different kinds of faults in a system include 3ph, line to line, double line to ground and 1ph faults. But 3ph and 1ph fault are of great importance in network study [14], [20]. A. Fault current before FCL installation Assuming that the fault impedance is Zf, 3ph fault current (If3ph) and 1ph fault current (If1ph) are calculated by the following equations [31]. I 3f ph I 1f ph Vf Z Bus Z11 Zi 1 A ZiB 1 Z n1 new Z11 Z new new A1 Z Bus inew ZiB 1 Z nnew 1 Z new jk Z jk Z ff Z f 3V f (2) Z 0ff Z ff Z ff 3Z f zero sequence, positive sequence and negative sequence to be achieved from the impedance matrix of the network. To calculate the worst fault current, Zf is assumed to be zero. Fault current after FCL installation If there is a need to install a FCL in bus i of a power network, the bus i is divided into two parts as buses iA and iB and then the FCL is placed between them. This concept is shown in Fig. 2 where Comps. A and Comps. B are equivalent of components connected to buses iA and iB. Bus (i ) Comps. A Comps. B (a) Bus (iA) Bus (iB) Comps. A Comps. B (b) Bus (iA) Comps. A FCL Bus (iB) Comps. B (c) Fig. 2. Bus (i), (a): before separating the bus, (b): after separating the bus and before installation FCL, (c): after FCL installation. In this case, the impedance matrix for n bus network after separating buses and before FCL installation is represented by Eq. (3), and the impedance matrix after the FCL installation is represented by Eq. (4). Each matrix element in Eq. (4) is Z1i A Z1i B Z i Ai A Z i Ai B ZiB i A ZiB iB Z ni B Z ni A Z1new iA Z inew Ai A Z inew BiA Z ninew A Z ji A Z1n Zi An ZiB n Z nn Z1new Z1new iB n new new Z i Ai B Z i A n Z inew Z inew B iB Bn new Z ninew Z nn B Z ji B Z i A k Z i B k Zi Ai A Z i B i B 2 Z i Ai B Z FCL . (3) (4) (5) If bus f is the goal of fault current calculation and a FCL is installed between buses iA and iB, therefore a general form of If3ph and If1ph for bus f-th, is represented by Eqs. (6) and (7). I 3f ph A Z FCL B Z FCL C I 1f ph D (1) In the above equations Vf is voltage of bus f before the fault occurrence, Z 0ff , Z ff and Z ff are Thevenin’s impedance of B. calculated by Eq. (5) [31]. (6) 2 Z FCL EZ FCL F (7) 2 Z FCL GZ FCL H Where, the variables A, B, C, D, E, F, G and H are calculated by Eqs. (8) to (15) using the elements driven from the impedance matrix of zero, positive sequence and negative sequence and with j being equal to 1 . A Vf A1 jA2 A A Z ff (8) B Z iAi A Z iBiB 2Z iAiB B1 jB 2 C B 2Z D 3V f Z 0ff fi A Z fi B 2 Z ff Z fi A Z Z ff iA f Z fi B Z iB f D1 jD2 D D E L N E1 jE2 (9) C1 jC 2 (10) (11) (12) (13) F L N F1 jF2 GE (K M ) G1 jG2 ( Z 0ff 2Z ff ) (14) H F ( K N M L) H1 jH 2 ( Z 0ff 2 Z ff ) (15) In equations (12) to (15), the elements of K, L, M and N are expressed by (16) to (19). K (Z 0fi A Z 0fi B ) (Zi0A f Zi0B f ) (16) L Zi0Ai A Zi0B iB 2Zi0AiB (17) M 2 ( Z fi A Z fi B ) ( ZiA f ZiB f ) (18) N ZiAi A ZiB iB 2ZiAiB . (19) The ZFCL is called FCL Impedance and according to Eq. (20), it includes real part that is RFCL and imaginary part (XFCL). The RFCL is FCL resistance and always positive but the XFCL is FCL reactance and can be either positive or negative 3 depending on XFCLL or XFCLC. (20) Z FCL RFCL jX FCL 3ph The current magnitude of 3ph fault (|If |) and the current magnitude of 1ph fault (|If1ph|) for bus f-th can be calculated by Eqs. (21) and (22) where O, P, T and U are expressed by Eqs. (23) to (26). I 3f ph A RFCL B1 2 X FCL B2 2 RFCL C1 2 X FCL C2 2 (21) I 1f ph D O 2 P 2 T 2 U 2 (22) O RFCL 2 X FCL 2 RFCL E1 X FCL E2 F1 (23) (24) P 2RFCL X FCL RFCL E2 X FCL E1 F2 T RFCL 2 X FCL 2 RFCL G1 X FCL G2 H1 (25) (26) U 2RFCL X FCL RFCL G2 X FCL G1 H 2 FCL Impedance locus regarding Im of network buses 2 M 2 C1 B1 X M 2 1 FCL where, M M 2 C 2 B2 M 2 1 2 M M 1 2 Eq. (27) represents a circle that is shown in Fig. 3 for a test system. If M>1, the locus of RFCL and XFCL are outside of the circle area and if M<1 they are inside of the circle area. In this figure, RC is the radius of circle and DC is the distance from the center to the origin. Note that RFCL is resistance and actually cannot be a negative value. (R-0.25)2+(X+0.5)2-1 = 0 1.5 0.5 0 X RC -1 -1.5 -1.5 -1 -0.5 0 0.5 R 1 C (28) Cost RFCL Dividing both sides of Eq. (28) by produces the cost function of FCL (Z′) as shown in Eq. (29) and cost factors wL and wC are calculated by Eqs (30) and (31). L C (29) Z RFCL wL X FCL wC X FCL Z FCL Costeq (30) CostRFCL wL wC Cost XFCL L (31) Cost RFCL Cost XFCL C Cost RFCL (32) Network designers can select the proper wL or wC depending on their design priorities and not the cost of each parts of FCL impedance. Simultaneous using of XFCLL and XFCLC is not suitable because they cancel out each other’s effect. Hence, the expression Z′ is modified and defined as Eq. (33). L L wL X FCL If ZFCL includes the RFCL and X FCL R (33) Z FCL C C RFCL wC X FCL If ZFCL includes the RFCL and X FCL IV. Optimization of FCL impedance F 3 ph -2 -2.5 -2 C Selection of FCL impedance based on the fault current of buses is equal to Im does not necessarily produce optimized results. It is possible to have impedance that greatly reduces the fault current and be economically viable. Therefore depending on |If3ph| and |If1ph|, functions F3ph and F1ph are defined by Eqs. (34) and (35) that achieves FCL impedance based on maximum reduction of fault current and minimum cost of FCL. 1 DC L Per Unit (pu) for the RFCL, XFCLL and XFCLC and |RFCL|, |XFCLL| and |XFCLC| are absolute value of the RFCL, XFCLL and XFCLC respectively in Ω or pu, then the equivalent cost of a FCL ( FCL ) is obtained by Eq. (28). Costeq 2 C1 B1 2 C 2 B2 2 (27) Im . A -0.5 The selection of FCL without considering the type and cost of FCL impedance cannot produce the optimal results. For example regarding to the Fig. 3, if the costs of RFCL, XFCLL and XFCLC are the same, the purely XFCLL is the best selection due to the lower impedance value compared to other types of FCL impedance. But if the cost of XFCLL is three times the RFCL or more, the RFCL is a better choice due to the lower cost of FCL. The cost of a FCL includes both the cost of real and imaginary parts of FCL impedance. Besides, the cost of each part rises as the value of the impedance increases [1]–[3]. If Cost RFCL , Cost XFCL and Cost XFCL are the costs of each ohm (Ω) or L The fault current passing through components of the network should be less than or equal of the maximum allowable current (Im) of the network components. The FCL impedance locus is the acceptable ranges of FCL impedance which causes the fault current magnitude of a specific bus to be equal or less than Im for the same bus on that network. The FCL impedance locus, for the 3ph fault is calculated by |If3ph|=Im, which is shown by Eq. (27) R FCL The cost function of FCL impedance FCL Costeq RFCL Cost RFCL X FCL Cost XFCL X FCL Cost XFCL L C III. FCL impedance locus and its cost function A. B. 1.5 2 2.5 3 I 3f ph 0 I 3f ph Z I 1f ph 0 I 1f ph (34) Fig. 3. The FCL impedance locus for fault current equal to Im in a test system. F 1 ph The FCL impedance locus for 1ph fault can be mathematically calculated by |If1ph|=Im, however, to avoid complicating this paper those calculations are not shown here. Where the |If3ph0| and |If3ph| are the fault current absolute value of bus f-th before and after FCL installation that are expressed by Eq. (21) and the |If1ph0| and |If1ph| are the fault Z (35) 4 current absolute value of bus f-th before and after FCL installation that are expressed by Eq. (22). The functions F3ph and F1ph are including variables RFCL and XFCL that can be different value, therefore assuming |Z| is the absolute value of FCL impedance and Ɵ is its angle, the RFCL and XFCL can be expressed by Eqs. (36) and (37). RFCL Z cos (36) X FCL Z sin . X FCL Z cos (39) Z sin (40) cos wL sin , 0 90 cos wC sin , 90 0 (41) Let be noted that the function F1ph can be mathematically calculated using Eq. (35), however, to avoid complicating this paper, the process of further expanding related equations are only shown for 3ph Fault that shown in Eq. (42). F 3 ph A B12 B2 2 Z C12 C 2 2 Start Z 2 2Z B1 cos B2 sin 2 B12 B2 2 2 2 Z 2 2Z C1 cos C 2 sin 2 C1 C 2 (42) The extreme points of function F3ph can be calculated when Ɵ and α determined a fix value and the derivative of F3ph with respect to Z′ is set to zero. The number of extreme points (Z′) for the Eq. (42) is 8. Among the calculated values of Z′, when F3ph is higher it means that the FCL impedance is best. But the maximum F3ph is not necessarily the optimum option, because that impedance may not resolve the Im limitation of buses. If none of the selected Z′ can decrease the fault current equal or less than Im, therefore, in accordance with the FCL impedance locus, this problem can be solved by increasing the Z′. In order to find the new Z′ (Z′new) one must use Eq. (43) below, where according to Fig. 3, the RC and DC are defined. 2 2Z new DC cos DC2 RC2 0 Z new (43) So far, the achieved Z′ is calculated by using the specific Ɵ however, in order to use various Ɵ values, one can change Ɵ at the range of 90 90 and repeating the FCL impedance optimization using the new Ɵ. By doing so, the various values of Z′ are calculated. Therefore, the optimal Z′ can be selected by comparing the value of F3ph for all Z′ (See Eq. (42). It should be noted that the selection of proper Ɵ can be done by genetic algorithm or other methods, however in this paper to simplify, the Ɵ is changed by steps ∆Ɵ=0.1 degree. The smaller the ∆Ɵ increases, the more accurate will be the calculations of optimum FCL impedance but this can impact the computational time. Finally, with the obtained values of Z′ and Ɵ, the real and imaginary parts of optimal FCL impedance are calculated using Eqs. (39) and (40). The computer algorithm (flowchart) Z'=maximum valid point of F. Input a location for FCL instalation on network. No Input the Im and the cost factors wL and wC. No Yes FinalF=max (FinalF , F(Z',)) Yes |If1ph|>|If3ph| Fault Current(Z') > Im Z'=Z'New (from Eq. (43)) Calculate the variables of A, B, C, D, E, F and H by Eqs. (8) to (15). (37) In above equations, Ɵ can be varied from -90 to 90 degrees. If Ɵ is greater than zero XFCL is equal to XFCLL and if Ɵ is less than zero XFCL is equal to XFCLC. By uses the Eqs. (33), (36) and (37), the Z′, RFCL and XFCL are expressed by Eqs. (38), (39) and (40) respectively where, α is shown by Eq. (41). Z Z (38) RFCL for proposed FCL impedance optimization is shown in Fig. 4. =+0.1 F=F1ph F=F3ph No >90 Yes =-90 End Fig. 4. Flowchart of the proposed FCL impedance optimization. If with respect to Eq. (38) and by replacing α|Z| instead Z′ in Eq. (42), the Eq. (44) below are created. F 3 ph A B1 2 B2 2 Z C1 2 C 2 2 Z Z sin C 2 2 Z B1 cos B2 sin B1 B2 2 2 2 Z C1 cos C 2 2 2 2 1 C2 (44) The extreme points of function F3ph in Eq. (44), are calculated when Ɵ is a fix value and the derivative of the function F3ph with respect to |Z| is set to zero. With comparing the extreme points of the function F3ph for Eq. (42) and Eq. (44), it appears that the values of |Z| and Z′/α in extreme point of the function F3ph are both equal. The |Z| is independent of the wL and wC therefore, changing wL and wC doesn’t affect the |Z| for optimum FCL impedance when Ɵ is a fix value. It means that the value of Z′/α is unchanged within a specific range of wL and wC in a fix Ɵ. This is an interesting result that shows, although it is possible that different range of wL and wC affect the type of optimal FCL impedance but doesn’t affect the optimal value of impedance in each case. V. A. NUMERICAL STUDIES Test system description To achieve optimal FCL impedance, the proposed algorithm can uses for each power network. For our purposes the IEEE 14 bus system as shown in Fig. 5 is used for calculating the FCL impedance optimization [32]. The impedance data (Ra , X’d) of the Generators and Compensators are shown in Table I. TABLE I IMPEDANCE DATA OF GENERATORS AND COMPENSATORS IN PU Component Type Gen. Bus No. 1 TType Ra 0 X’d 0.23 Gen. 2 0.0031 0.23 Com. 3 0.0031 0.13 Com. 6 0.0014 0.12 Com. 8 0.0041 0.12 The |If3ph| before FCL installation are calculated for all buses. Bus 2 has the highest value of |If3ph| that is equal to 15.37pu. Thus, according to Fig. 5, a FCL is placed on the bus 2. The variables |A|, B1, B2, C1 and C2 considering 3ph fault occurrence in the bus 2 are calculated by Eqs. (8) to (10) and recorded at Table II. TABLE II THE VARIABLES |A|, B1, B2, C1 AND C2. |A| 10.84 B1 0.0145 B2 0.3257 C1 0.0031 C2 0.23 5 scenarios. In first scenario, the Im=11 pu and the acceptable FCL impedance locus is shown in Fig. 8. In second scenario, the Im=14 pu and its acceptable FCL impedance locus is shown in Fig. 9. Different colors in those Figures shown different fault current magnitude in pu. Fig. 5. IEEE 14 bus test system Fig. 6 shows the |If3ph| for bus 2 versus the different range of FCL impedance including RFCL and XFCLL. It shows that for FCL impedance with RFCL and XFCLL, the |If3ph| is decreased as a homographic function. Such that, the minimum value for fault current that is equal to |A| will occur at infinite value for FCL impedance. Fig. 8. The FCL impedance locus for Im=11 pu 16 15 f |I3ph| 14 13 12 11 0 1 0.2 0.8 0.4 0.6 0.6 0.4 0.8 0.2 1 XFCLL 0 RFCL XFCL Fig. 9. The FCL impedance locus for Im=14 pu 3ph Fig. 6. Differentiation of |If | versus to FCL impedance (RFCL and XFCLL). Fig. 7 shows the |If3ph| for bus 2 versus the different range of FCL impedance including RFCL and XFCLC. It is shows that for FCL impedance with RFCL and XFCLC, the |If3ph| first reaches a pick and then decreases to a minimum. It then rises to level off and reaches |A| at infinite value for FCL impedance. 120 100 f |I3ph| 80 60 40 20 1 0 -1 -0.8 0.5 -0.6 -0.4 -0.2 XFCLC 0 0 RFCL XFCL 3ph Fig. 7. Differentiation of |If | versus to FCL impedance (RFCL and XFCLC). B. Test result and discussion Depending on Im, the acceptable FCL impedance locus is different. The FCL impedance optimization calculates for two The costs of real and imaginary parts of impedance for different types of FCL can be different. The optimal FCL impedance for different ranges of wL and wC is calculated. The values of optimal RFCL, XFCL and |If3ph| for Im=11 pu is shown in Figs. 10 to12 and for Im=14 pu is shown in Figs. 13 to 15. Table III summarizes all related values used in Figs. 10 to 15. TABLE III THE OPTIMAL VALUE OF FCL IMPEDANCE AND |IF3PH| FOR IM=11PU AND IM=14PU ACCORDING TO DIFFERENT RANGE OF WL AND WC. Im=11 pu wL wL>0.2795 wL<0.2795 wL>(0.0165wC) wC wC>16.965 wC>(60.7wL) wC<16.965 ZFCL 1.752 pu 6.258 i pu -0.3227 i pu |If3ph| 11 pu 11 pu 1.725 pu Im=14 pu wL wL>1.6604 wL<1.6604 wL>(0.3255wC) wC wC>5.1012 wC>(3.0723wL) wC<5.1012 ZFCL 0.266 pu 0.0992 i pu -0.3227 i pu |If3ph| 13.16 pu 14 pu 1.725 pu Figs. 10 to 15 and the Table III show the following results: 1- At the optimal level of FCL Impedance for both RFCL and XFCL, the |If3ph| is equal to Im where Im=11pu. But when Im=14pu the |If3ph| for optimal resistive FCL (RFCL) is less than Im. It shows that, the selection of FCL impedance solely based on Im limitation is not necessarily the optimum solution. 6 2- The most decreasing of fault current for both Im=11pu and Im=14pu are occurred when a XFCLC is selected for FCL. However it is not necessarily the optimum solution due to different ranges of wL and wC. It should be noted that using the XFCLC might cause some problems such as sub synchronous resonance and instability in the power systems. Therefore in choosing the capacitive FCL, one should study the power system stability that is out of the scope of this paper and can be a base for future studies. 3- The optimal FCL impedance for different ranges of wL and wC are only one of the cases of RFCL, XFCLL or XFCLC. Thus, the combination of RFCL and XFCLL or RFCL and XFCLC for this network is not optimized. 4- The optimum impedance value for pure RFCL, pure XFCLL and pure XFCLC is a fix value for each of the above cases but a different value among all of those cases. It means that different range of wL and wC affect the type of optimal FCL impedance but doesn’t affect the optimal value of impedance in each case. 0.266 pu 0 pu 0 pu Fig. 13. The value of RFCL for different range of wL and wC, when Im=14pu 0.0992 pu 0 pu -0.3227 pu 1.752 pu 0 pu 0 pu Fig. 14. The value of XFCL for different range of wL and wC, when Im=14pu 14 pu 13.16 pu Fig. 10. The value of RFCL for different range of wL and wC, when Im=11pu 1.725 pu 6.258 pu 0 pu -0.3227 pu Fig. 11. The value of XFCL for different range of wL and wC, when Im=11pu 11 pu Fig. 15. The value of |If3ph| for different range of wL and wC, when Im=14pu Figs. 16 to 19 is shown the value of Z′ and Z′/α for various range of wL and wC for both cases including Im=11 pu and Im=14 pu. They show the value of Z′ varies but the value of Z′/α is definite for different ranges of wL and wC. Thus, the optimal FCL impedance is a fix value when Ɵ is a fix value. 11 pu 1.725 pu Fig. 12. The value of |If3ph| for different range of wL and wC, when Im=11pu Fig. 16.Value of Z′ for different range of wL and wC when Im=11kA 7 6.258 pu 1.752 pu 0.3227Ω Fig. 17. Value of Z′/α for different range of wL and wC when Im=11kA the fault current reaches the Im. The cost of the FCL impedance includes the costs of RFCL, XFCLL and XFCLC that can vary for different types of FCL. Thus, the FCL impedance optimization in the 14 bus IEEE system is calculated based on those cost variations. The results show that the optimum FCL impedance for different range of costs (including wL and wC) are different and the FCL impedance can be any of the pure RFCL, pure XFCLL or pure XFCLC depending of the range of costs. Be noted that in the test system, the combination of RFCL, XFCLL and XFCLC does not produce optimize results. Because the Z′/α is a fix value for various costs of FCL when the Ɵ is a fix value, the changes in the costs can only affect the FCL impedance type and has no influence on the optimum value of that FCL impedance. As a result, one can select the optimum FCL impedance value without concerning the costs of FCL impedance. REFERENCES [1] [2] [3] Fig. 18. Value of Z′ for a different range of wL and wC when Im=14kA [4] 0.266 pu 0.3227 pu [5] 0.0992 pu [6] [7] [8] Fig. 19. Value of Z′/α for a different range of wL and wC when Im=14kA VI. Conclusion In this paper, the importance of FCL impedance optimization in a power network has been pointed out. Generally speaking the FCL impedance is a complex value and the FCL cost function is defined based on the cost of real and imaginary parts of FCL impedance. The fault current for each bus should be lower than Im. The locus of FCL impedance is defined by the fault current being equal or less than Im. By increasing the value of FCL impedance, the magnitude of fault current is reduced and the cost of FCL is increased. To determine the optimized value of FCL impedance, an objecttive function is defined that calculates the FCL impedance by using the maximum reduction of fault current over a minimum cost of FCL. If the calculated FCL impedance cannot reduce the fault current to/or below Im, therefore according to the FCL impedance locus for Im, the FCL impedance is changed until [9] [10] [11] [12] [13] [14] [15] J.-H. Teng and C.-N. Lu, “Optimum fault current limiter placement with search space reduction technique,” IET Generation, Transmission & Distribution, vol. 4, no. 4. p. 485, 2010. K. Hongesombut, Y. Mitani, and K. Tsuji, “Optimal location assignment and design of superconducting fault current limiters applied to loop power systems,” IEEE Trans. Appl. Supercond., vol. 13, no. 2, pp. 1828–1831, Jun. 2003. M. Nagata, K. Tanaka, and H. Taniguchi, “FCL location selection in large scale power system,” in IEEE Transactions on Applied Superconductivity, 2001, vol. 11, no. 1, pp. 2489–2494. S. Alaraifi, M. S. El Moursi, and H. H. Zeineldin, “Optimal allocation of HTS-FCL for power system security and stability enhancement,” IEEE Trans. Power Syst., vol. 28, no. 4, pp. 4702–4711, Nov. 2013. L. Kovalsky, X. Yuan, K. Tekletsadik, a. Keri, J. Bock, and F. Breuer, “Applications of Superconducting Fault Current Limiters in Electric Power Transmission Systems,” IEEE Trans. Appiled Supercond., vol. 15, no. 2, pp. 2130–2133, Jun. 2005. A. Abramovitz and K. Ma Smedley, “Survey of solid-state fault current limiters,” IEEE Trans. Power Electron., vol. 27, no. 6, pp. 2770–2782, Jun. 2012. M. Fotuhi-Firuzabad, F. Aminifar, and I. Rahmati, “Reliability Study of HV Substations Equipped With the Fault Current Limiter,” IEEE Trans. Power Deliv., vol. 27, no. 2, pp. 610–617, Apr. 2012. H. Javadi, “Fault current limiter using a series impedance combined with bus sectionalizing circuit breaker,” Int. J. Electr. Power Energy Syst., vol. 33, no. 3, pp. 731–736, Mar. 2011. M. S. El Moursi and R. Hegazy, “Novel technique for reducing the high fault currents and enhancing the security of ADWEA power system,” IEEE Trans. Power Syst., vol. 28, no. 1, pp. 140–148, Feb. 2013. S. B. Naderi, M. Jafari, and M. Tarafdar Hagh, “Parallel-resonance-type fault current limiter,” IEEE Trans. Ind. Electron., vol. 60, no. 7, pp. 2538–2546, Jul. 2013. S. C. Mukhopadhyay, M. Iwahara, S. Yamada, and F. P. Dawson, “Investigation of the performances of a permanent magnet biased fault current limiting reactor with a steel core,” IEEE Trans. Magn., vol. 34, no. 4, pp. 2150–2152, Jul. 1998. D. Cvoric, S. W. H. de Haan, J. A. Ferreira, Z. Yuan, M. van Riet, and J. Bozelie, “New Three-Phase Inductive FCL With Common Core and Trifilar Windings,” IEEE Trans. Power Deliv., vol. 25, no. 4, pp. 2246– 2254, Oct. 2010. S. A. A. Shahriari, A. Y. Varjani, and M. R. Haghifam, “Cost reduction of distribution network protection in presence of distributed generation using optimized fault current limiter allocation,” Int. J. Electr. Power Energy Syst., vol. 43, no. 1, pp. 1453–1459, Dec. 2012. M. Stemmle et al., “Analysis of Unsymmetrical Faults in High Voltage Power Systems With Superconducting Fault Current Limiters,” IEEE Trans. Appl. Supercond., vol. 17, no. 2, pp. 2347–2350, Jun. 2007. H. Yamaguchi and T. Kataoka, “Current Limiting Characteristics of Transformer Type Superconducting Fault Current Limiter With Shunt 8 [16] [17] [18] [19] [20] [21] [22] [23] [24] [25] [26] [27] [28] [29] [30] [31] [32] Impedance,” IEEE Trans. Appl. Supercond., vol. 17, no. 2, pp. 1919– 1922, Jun. 2007. G. Didier and J. Lévêque, “Influence of fault type on the optimal location of superconducting fault current limiter in electrical power grid,” Int. J. Electr. Power Energy Syst., vol. 56, pp. 279–285, Mar. 2014. A. HEIDARY and H. RADMANESH, “Series transformer based diodebridge-type solid state fault current limiter,” Front. Inf. Technol. Electron. Eng., vol. 16, pp. 769–784, Sep. 2015. A. Abramovitz and K. Ma Smedley, “Survey of Solid-State Fault Current Limiters,” IEEE Trans. Power Electron., vol. 27, no. 6, pp. 2770–2782, Jun. 2012. G. Didier, C. H. Bonnard, T. Lubin, and J. Lévêque, “Comparison between inductive and resistive SFCL in terms of current limitation and power system transient stability,” Electr. Power Syst. Res., vol. 125, pp. 150–158, 2015. Q. B. Dam, A. P. S. Meliopoulos, and G. J. Cokkinides, “A breakeroriented fault analysis methodology,” Int. Trans. Electr. Energy Syst., vol. 23, no. 7, pp. 1071–1082, Oct. 2013. S.-Y. Kim, W.-W. Kim, and J.-O. Kim, “Determining the location of superconducting fault current limiter considering distribution reliability,” IET Generation, Transmission & Distribution, vol. 6, no. 3. p. 240, 2012. S.-Y. Kim, W.-W. Kim, and J.-O. Kim, “Evaluation of distribution reliability with superconducting fault current limiter,” in 2011 10th International Conference on Environment and Electrical Engineering, 2011, pp. 1–5. S.-Y. K. S.-Y. Kim, I.-S. B. I.-S. Bae, and J.-O. K. J.-O. Kim, “An optimal location for superconducting fault current limiter considering distribution reliability,” Power Energy Soc. Gen. Meet. 2010 IEEE, pp. 1–5, Jul. 2010. Q. B. Dam and A. P. S. Meliopoulos, “Failure Probability Methodology for Overdutied Circuit Breakers,” in 2006 38th North American Power Symposium, 2006, pp. 667–672. Q. B. Dam and A. P. S. Meliopoulos, “Reliability implications of increased fault currents and breaker failures,” in 2007 iREP Symposium Bulk Power System Dynamics and Control - VII. Revitalizing Operational Reliability, 2007, pp. 1–8. M. R. Haghifam, A. Ghaderi, and M. Abapour, “Enhancement circuit breaker reliability by using fault current limiter,” in 2009 IEEE Power & Energy Society General Meeting, 2009, pp. 1–5. H. Yousefi, F. Aminifar, and M. Mirzaie, “Reliability assessment of HV substations equipped with fault current limiter considering changes of failure rate of components,” IET Gener. Transm. Distrib., vol. 10, no. 7, pp. 1504–1509, May 2016. H.-C. Seo, C.-H. Kim, S.-B. Rhee, J.-C. Kim, and O.-B. Hyun, “Superconducting Fault Current Limiter Application for Reduction of the Transformer Inrush Current: A Decision Scheme of the Optimal Insertion Resistance,” IEEE Trans. Appl. Supercond., vol. 20, no. 4, pp. 2255–2264, Aug. 2010. Y. Guo, Y. Yokomizu, and T. Matsumura, “Design guidelines of a fluxlock superconducting fault current limiter with ac magnetic field coil for a 6.6-kV distribution system,” Electr. Eng. Japan, vol. 135, no. 4, pp. 17–25, Jun. 2001. T. Matsumura, H. Shimizu, and Y. Yokomizu, “Design guideline of flux-lock type HTS fault current limiter for power system application,” IEEE Trans. Appiled Supercond., vol. 11, no. 1, pp. 1956–1959, Mar. 2001. H. Saadat, Power System Analysis. 1998. University of Washington, “Power System Test Case Archive,” 2012. [Online]. Available: https://www.ee.washington.edu/research/pstca/pf14/pg_tca14bus.htm.
© Copyright 2026 Paperzz