End Fault in Bus Protection Contr. Question 15 Pref. Subject 1 Jorge Cardenas (GE Multilin Presented at the 2007 CIGRE-Madrid Conference 2007-PS1-15-ES01-Cardenas End Fault Protection Breakers: Bus-side CTs CT Blind spot for bus protection CB • Blind spot exists between the CB and CT • CB is going to be tripped by line protection • After the CB gets opened, the current shall be removed from differential calculations (expanding the differential zone up to the opened CB) • Relay configuration required: identical as for the Single-CT TieBreaker 2007-PS1-15-ES01-Cardenas End Fault Protection Breakers: Line-side CTs CB “Over-trip” spot for bus protection CT • “Over-trip” spot between the CB and CT when the CB is opened • When the CB gets opened, the current shall be removed from differential calculations (contracting the differential zone up to the opened CB) • Relay configuration required: identical as for a Single-CT TieBreaker, but…. 2007-PS1-15-ES01-Cardenas End Fault Protection Breakers: Line-side CTs contract CB Blind spot for bus protection CT • but…. • A blind spot created by contracting the bus differential zone • End Fault Protection required to trip the remote end 2007-PS1-15-ES01-Cardenas