Customer-owned tank pre-inspection guidelines To save time and costs, please review the following information prior to Air Products inspecting your tank. Any liquid bulk tank not installed by Air Products must pass an extensive inspection process conducted by an Air Products' technician. The inspection is done to ensure that the tank has been installed and equipped to meet all requirements associated with the storage of cryogenic or gaseous products, enabling safe delivery, storage and product use. Our ultimate goals are safety and that all inspections pass during our technician's initial visit. Our experience tells us that the items listed on the next page are the most probable (but not only) causes why your tank system may fail our inspection. In an effort to help pass the inspection on the initial visit, please review these guidelines prior to scheduling our technician for the inspection. Feel free to contact your Air Products sales representative if you are unsure about the status or intent of any items listed. Primary reasons tanks fail inspection • The tank is not installed, anchored to the foundation and system piping is not completed • The tank’s Maximum Allowable Working Pressure (MAWP) is =/< 150 psig – If the tank’s MAWP is =/<150 psig, please contact us to purchase a Fill Line Closure Device (FLCD). This is a requirement before the tank can be filled to protect from overpressure scenarios. • The tank’s fill line is > 15 feet long – If so, please contact your Air Products sales representative for guidance. • Tank vents are directed such that they discharge toward the driver during delivery – Redirect vents so they will not discharge toward the driver. • The tank does not have proper safety relief valve and rupture discs – Must have full flow device for safety relief and not thermal relief. – Is the device able to lift freely (not bolted or wired down)? – The relief valve must have a set point equal to or lower than the MAWP of the tank. – All relief discharges must be to the outdoors. – Must have at least one rupture disc, in addition to, at least one safety relief valve. • The tank was manufactured by Linde, Taylor Wharton or UCAR between 1964-1985 and still has the original brass tee between the stainless steel liquid fill penetration and the pressure build inlet – Contact your sales representative and send a picture(s) of the fill line penetration and surrounding piping, if easily visible, to Air Products. Please make sure not to disturb the area around this joint, especially if the area is covered in ice, because if the joint has not been fixed, the ice could be holding it together. • Oxygen tank is too close to flammables – Minimum of 50’ required from flammable liquids and gas storage (see diagram). • For oxygen deliveries, the required 8' x 12' unloading pad, made of concrete or gravel, is not present •T he site cannot be accessed by a tanker truck •T ank pad greater than 12” above grade with no steps/railing – I nstall steps and railing. • Fill connection greater than 2’ to 3’ from grade – I nstall steps and railing or re-pipe to lower fill connection. • For tanks already in service, excessive ice and/or snow blocking relief, discharge or driver access to offloading valves –D e-ice system and/or remove snow. Figure 1: Gaseous or Liquid Oxygen Distance Requirements Structures Buildings of Wood 50' Frame Construction Oxygen Vessel 17' with firewall 50' Air Intake: General 10' Wall Openings 5,000 scfh or less 20' Air Intake: Small Air Compressors (Consult Safety for large compressors) Sewer - from Fill Connection Including Delivery Trailer 8' 3' Buildings Other than Wood Frame Construction 0 3 5 8 10 15 17 20 255 50' Miscellaneous 50' Places of Public Assembly 50' 25' Open Flames or Welding Oxygen Vessel Property Lines which 5' may be built upon 10' 3' with firewall 3' with firewall Overhead Power Lines for Electric Trolly Train or Bus (Distance measured in plan view) Overhead Power Lines (Distance measured in plan view) 10' Parked Vehicles Public Sidewalk 10' 3' Protective Structures/ Fire Wall 0 3 5 8 10 15 17 20 255 50' Flammables, Combustibles, and Oxidizers 25' with firewall 17' with firewall 50' 17' with firewall 50' 15' to welded joints Oxygen Vessel 75' 25' to mechanical joints Flammable Pipelines 8.5' with firewall 25' Non-liquefied or Dissolved Gases (25,000 scf or less) Flammable Gas 8.5' with firewall 25' Slow-burning Combustible Solids (i.e. coal) 8.5' with firewall 25' Above-ground Storage 5' with firewall 15' 15' 5' with firewall Non-liquefied or Dissolved Gases (More than 25,000 scf) Flammable Gas (more than 1,000 gal.) Liquefied Gas Flammable and Combustible Liquid 25' Vent or Fill Connection Underground Tank Rapidly-burning Combustible Solids 50' Above-ground Storage (less than 1,000 gal.) 8.5' with firewall Flammable and Combustible Liquid Brush or Dry Vegetation Class III B Combustible Liquids 15' 3' Non-flammable Cryogens 0 3 5 8 10 15 17 20 255 distance in feet LHY Tank 50' 75' Figure 2: Tanker Truck Access o 90 8' o 45 Path of right rear tire 28' 22' 26' 24' 2'- 4" Optimum manuvering area: Road width: 25' o 90 turn: 50' radius (internal) 75' radius (external) o 180 turn: 2x vehicle length 100' normal 50' R 28' Path of overhang 22' o 50 minimum practical turning radius Air Products delivery tanker o 45 2'- 4'' Path of left front tire 68' For more information, please contact us at: Corporate Headquarters Air Products and Chemicals, Inc. 7201 Hamilton Boulevard Allentown, PA 18195-1501 T 800-654-4567 T 610-706-4730 F 800-272-4449 F 610-706- 6980 [email protected] tell me more airproducts.com © Air Products and Chemicals, Inc., 2014 (37497) 320-14-002-US
© Copyright 2026 Paperzz