Installation Instructions for TAS Temperature Switches
Adjusting the Set Point:

For DIN Models, remove DIN securing screw, leave DIN adaptor
in place.
Insert a 5/64” allen key into hole for the adjustment screw.
For FL and SPADE models remove adjustment plug at top and
insert allen key
For Integral Deutsch, insert allen key through adjustment hole



All TAS switches are shipped set to the high side of the temperature range.
For proper adjustment, the TAS temperature switch must be brought to the
required set point temperature either in the application or a temperature
bath. If using a temperature bath, the sensing bulb, threaded connection
and one half to three quarters of the hex must be submerged in the fluid.
After soaking unit at temperature, rotate the adjustment screw counterclockwise until the switch sets (signals) Then rotate the adjustment screw
clockwise until the unit resets, noting the amount of rotation. Again rotate
the adjustment screw counter-clockwise until the switch signals, then turn it
back ½ the amount of the noted rotation
Check for set point accuracy. Make minor adjustments as required.
NOTE: The amount of rotation required to fine tune the set point is minimal.
Contact
Spades
(Fig 1)
Flying
Leads
DIN
HC/HN
(Fig 2)
Integral
Deutsch
(Fig 3)
Common
C
Black
Pin 1
Pin 1
N.Closed
NC
Green
Pin 2
Pin 2
N. Open
NO
Red
Pin 3
Pin 2
OPERATING CHARACTERISTICS
ADJUSTMENT RANGE (°F / °C) TAS ‐ 1 70° ‐ 128° F (21°‐53°C) AVERAGE Max DIFFERENTIAL Working (°F / °C) Pressure(PSI)
50°F (10°C) 175 TAS – 2 129° ‐ 187° F (54°‐86°C) 50°F (10°C) 175 TAS ‐ 3 188° ‐ 285° F (87°‐141°C) 50°F (10°C) 175