AMTRON® S2 - Aquametro

Text for tenders
AMTRON S2
Compact mechanical heat and cooling meter
Heating, mounting on Return line
95162
AMTRON S2+ 15 1.5_110_G3/4 B10
Compact mechanical heat meter
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95163
15 ... 90°C
5 … 55°C
PN 16
DN 15
1.5 m3/h
3.0 m3/h
30 l/h
7 l/h
110 mm
G3/4"
0.200 bar
3.35 m3/h
Return line
AMTRON S2+ 20 2.5_130_G1 B10
Compact mechanical heat meter
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
81919489
12.2014
1/18
Text for tenders
Optical interface (M-bus protocol)
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95164
1 ... 90°C
5 … 55°C
PN 16
DN 20
2.5 m3/h
5.0 m3/h
50 l/h
10 l/h
130 mm
G1"
0.170 bar
6.06 m3/h
Return line
AMTRON S2+ 15 1.5_110_G3/4 B10M
Compact mechanical heat meter
with M-Bus
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
With M-Bus according EN1434-3 / EN13757
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95165
15 ... 90°C
5 … 55°C
PN 16
DN 15
1.5 m3/h
3.0 m3/h
30 l/h
7 l/h
110 mm
G3/4"
0.200 bar
3.35 m3/h
Return line
AMTRON S2+ 20 2.5_130_G1 B10M
Compact mechanical heat meter
with M-Bus
Return line
Highly accurate single-jet flow sensor
81919489
12.2014
2/18
Text for tenders
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
With M-Bus according EN1434-3 / EN13757
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95166
15 ... 90°C
5 … 55°C
PN 16
DN 20
2.5 m3/h
5.0 m3/h
50 l/h
10 l/h
130 mm
G1"
0.170 bar
6.06 m3/h
Return line
AMTRON S2+ 15 1.5_110_G3/4 B10MEE
Compact mechanical heat meter
with M-Bus and 2 pulse inputs
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
With M-Bus according EN1434-3 / EN13757
2 pulse inputs for the integration of
a cold and a warm water meter
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
81919489
15 ... 90°C
12.2014
3/18
Text for tenders
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95167
5 … 55°C
PN 16
DN 15
1.5 m3/h
3.0 m3/h
30 l/h
7 l/h
110 mm
G3/4"
0.200 bar
3.35 m3/h
Return line
AMTRON S2+ 20 2.5_130_G1 B10MEE
Compact mechanical heat meter
with M-Bus and 2 pulse inputs
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
With M-Bus according EN1434-3 / EN13757
2 pulse inputs for the integration of
a cold and a warm water meter
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95168
15 ... 90°C
5 … 55°C
PN 16
DN 20
2.5 m3/h
5.0 m3/h
50 l/h
10 l/h
130 mm
G1"
0.170 bar
6.06 m3/h
Return line
AMTRON S2+ 15 1.5_110_G3/4 B10R
Compact mechanical heat meter
with Radio
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
81919489
12.2014
4/18
Text for tenders
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
Wireless M-Bus (Radio) 868 MHz according EN13757
OMS compliant
modes S1 / T1 and S2 / T2
short or long telegram
for WALK-BY or AMR read out
transmission interval 2 … 240 min
free choice of transmission times
encryption AES 128
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95169
15 ... 90°C
5 … 55°C
PN 16
DN 15
1.5 m3/h
3.0 m3/h
7 l/h
110 mm
G3/4"
0.200 bar
3.35 m3/h
Return line
AMTRON S2+ 20 2.5_130_G1 B10R
Compact mechanical heat meter
with Radio
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
Wireless M-Bus (Radio) 868 MHz according EN13757
OMS compliant
for modes S1 / T1 and S2 / T2
short or long telegram
for WALK-BY or AMR read out
transmission interval: 2 … 240 min
81919489
12.2014
5/18
Text for tenders
free choice of transmission times
encryption AES 128
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95170
15 ... 90°C
5 … 55°C
PN 16
DN 20
2.5 m3/h
5.0 m3/h
50 l/h
10 l/h
130 mm
G1"
0.170 bar
6.06 m3/h
Return line
AMTRON S2+ 15 1.5_110_G3/4 B10REE
Compact mechanical heat meter
with Radio and 2 pulse inputs
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
Wireless M-Bus (Radio) 868 MHz according EN13757
OMS compliant
for modes S1 / T1 and S2 / T2
short or long telegram
for WALK-BY or AMR read out
transmission interval: 2 … 240 min
free choice of transmission times
encryption AES 128
2 pulse inputs for the integration of
a cold and a warm water meter
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
81919489
15 ... 90°C
5 … 55°C
PN 16
DN 15
1.5 m3/h
3.0 m3/h
30 l/h
7 l/h
110 mm
G3/4"
12.2014
6/18
Text for tenders
Pressure loss at qp:
Value Kvs:
Meter mounted:
95171
0.200 bar
3.35 m3/h
Return line
AMTRON S2+ 20 2.5_130_G1 B10REE
Compact mechanical heat meter
with Radio and 2 pulse inputs
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
Wireless M-Bus (Radio) 868 MHz according EN13757
OMS compliant
for modes S1 / T1 and S2 / T2
short or long telegram
for WALK-BY or AMR read out
transmission interval: 2 … 240 min
free choice of transmission times
encryption AES 128
2 pulse inputs for the integration of
a cold and a warm water meter
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95172
15 ... 90°C
5 … 55°C
PN 16
DN 20
2.5 m3/h
5.0 m3/h
50 l/h
10 l/h
130 mm
G1"
0.170 bar
6.06 m3/h
Return line
AMTRON S2+ 15 1.5_110_G3/4 B5A
Compact mechanical heat meter
with pulse output
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
81919489
12.2014
7/18
Text for tenders
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 5+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
Potential-free pulse output (class A0
according to EN1434) 1kWh / pulse
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
15 ... 90°C
5 … 55°C
PN 16
DN 15
1.5 m3/h
3.0 m3/h
30 l/h
7 l/h
110 mm
G3/4"
0.200 bar
3.35 m3/h
Return line
Heating and Cooling, mounting on return line
95175
AMTRON S2+ 15 1.5_110_G3/4 B10-h&c
Compact mechanical energy meter
for heating and cooling
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
81919489
5 ... 90°C
5 … 55°C
PN 16
DN 15
1.5 m3/h
12.2014
8/18
Text for tenders
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95176
3.0 m3/h
30 l/h
7 l/h
110 mm
G3/4"
0.200 bar
3.35 m3/h
Return line
AMTRON S2+ 20 2.5_130_G1 B10-h&c
Compact mechanical energy meter
for heating and cooling
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95177
5 ... 90°C
5 … 55°C
PN 16
DN 20
2.5 m3/h
5.0 m3/h
50 l/h
10 l/h
130 mm
G1"
0.170 bar
6.06 m3/h
Return line
AMTRON S2+ 15 1.5_110_G3/4 B10M-h&c
Compact mechanical energy meter
for heating and cooling with M-Bus
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
81919489
12.2014
9/18
Text for tenders
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
With M-Bus according EN1434-3 / EN13757
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95178
5 ... 90°C
5 … 55°C
PN 16
DN 15
1.5 m3/h
3.0 m3/h
30 l/h
7 l/h
110 mm
G3/4"
0.200 bar
3.35 m3/h
Return line
AMTRON S2+ 20 2.5_130_G1 B10M-h&c
Compact mechanical energy meter
for heating and cooling with M-Bus
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
With M-Bus according EN1434-3 / EN13757
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
81919489
5 ... 90°C
5 … 55°C
PN 16
DN 20
2.5 m3/h
5.0 m3/h
50 l/h
10 l/h
130 mm
G1"
0.170 bar
6.06 m3/h
Return line
12.2014
10/18
Text for tenders
95179
AMTRON S2+ 15 1.5_110_G3/4 B10MEE-h&c
Compact mechanical energy meter
for heating and cooling with M-Bus and
2 pulse inputs, Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
With M-Bus according EN1434-3 / EN13757
2 pulse inputs for the integration of
a cold and a warm water meter
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95180
5 ... 90°C
5 … 55°C
PN 16
DN 15
1.5 m3/h
3.0 m3/h
30 l/h
7 l/h
110 mm
G3/4"
0.200 bar
3.35 m3/h
Return line
AMTRON S2+ 20 2.5_130_G1 B10MEE-h&c
Compact mechanical energy meter
for heating and cooling with M-Bus and
2 pulse inputs, Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
81919489
12.2014
11/18
Text for tenders
With M-Bus according EN1434-3 / EN13757
2 pulse inputs for the integration of
a cold and a warm water meter
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95181
5 ... 90°C
5 … 55°C
PN 16
DN 20
2.5 m3/h
5.0 m3/h
50 l/h
10 l/h
130 mm
G1"
0.170 bar
6.06 m3/h
Return line
AMTRON S2+ 15 1.5_110_G3/4 B10R-h&c
Compact mechanical heat meter
for heating and cooling with Radio
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
Wireless M-Bus (Radio) 868 MHz according EN13757
OMS compliant
for modes S1 / T1 and S2 / T2
short or long telegram
for WALK-BY or AMR read out
transmission interval: 2 … 240 min
free choice of transmission times
encryption AES 128
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
81919489
5 ... 90°C
5 … 55°C
PN 16
DN 15
1.5 m3/h
3.0 m3/h
7 l/h
110 mm
G3/4"
0.200 bar
3.35 m3/h
12.2014
12/18
Text for tenders
Meter mounted:
95182
Return line
AMTRON S2+ 20 2.5_130_G1 B10R-h&c
Compact mechanical energy meter
for heating and cooling with Radio
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
Wireless M-Bus (Radio) 868 MHz according EN13757
OMS compliant
for modes S1 / T1 and S2 / T2
short or long telegram
for WALK-BY or AMR read out
transmission interval: 2 … 240 min
free choice of transmission times
encryption AES 128
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95183
5 ... 90°C
5 … 55°C
PN 16
DN 20
2.5 m3/h
5.0 m3/h
50 l/h
10 l/h
130 mm
G1"
0.170 bar
6.06 m3/h
Return line
AMTRON S2+ 15 1.5_110_G3/4 B10REE-h&c
Compact mechanical energy meter
for heating and cooling with Radio and
2 pulse inputs, Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
81919489
12.2014
13/18
Text for tenders
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
Wireless M-Bus (Radio) 868 MHz according EN13757
OMS compliant
for modes S1 / T1 and S2 / T2
short or long telegram
for WALK-BY or AMR read out
transmission interval: 2 … 240 min
free choice of transmission times
encryption AES 128
2 pulse inputs for the integration of
a cold and a warm water meter
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95184
5 ... 90°C
5 … 55°C
PN 16
DN 15
1.5 m3/h
3.0 m3/h
30 l/h
7 l/h
110 mm
G3/4"
0.200 bar
3.35 m3/h
Return line
AMTRON S2+ 20 2.5_130_G1 B10REE-h&c
Compact mechanical energy meter
for heating and cooling with Radio and
2 pulse inputs, Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
Wireless M-Bus (Radio) 868 MHz according EN13757
OMS compliant
for modes S1 / T1 and S2 / T2
short or long telegram
for WALK-BY or AMR read out
transmission interval: 2 … 240 min
free choice of transmission times
2 pulse inputs for the integration of
a cold and a warm water meter
81919489
12.2014
14/18
Text for tenders
encryption AES 128
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to 2004/22/EC (MID)
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
5 ... 90°C
5 … 55°C
PN 16
DN 20
2.5 m3/h
5.0 m3/h
50 l/h
10 l/h
130 mm
G1"
0.170 bar
6.06 m3/h
Return line
Cooling, mounting return line
95185
AMTRON S2+ 15 1.5_110_G3/4 B10M-ws/c
Compact mechanical energy meter
for cooling with M-Bus
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
With M-Bus according EN1434-3 / EN13757
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to PTB K 7.2
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95186
81919489
5 ... 50°C
5 … 55 °C
PN 16
DN 15
1.5 m3/h
3.0 m3/h
30 l/h
7 l/h
110 mm
G3/4"
0.230 bar
3.6 m3/h
Return line
AMTRON S2+ 20 2.5_130_G1 B10M-ws/c
12.2014
15/18
Text for tenders
Compact mechanical energy meter
for cooling with M-Bus
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
With M-Bus according EN1434-3 / EN13757
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to PTB K 7.2
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95187
5 ... 50°C
5 … 55 °C
PN 16
DN 20
2.5 m3/h
5.0 m3/h
50 l/h
10 l/h
130 mm
G1"
0.240 bar
6.0 m3/h
Return line
AMTRON S2+ 15 1.5_110_G3/4 B10R-ws/c
Compact mechanical energy meter
for cooling with Radio
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
Wireless M-Bus (Radio) 868 MHz according EN13757
OMS compliant
for modes S1 / T1 and S2 / T2
81919489
12.2014
16/18
Text for tenders
short or long telegram
for WALK-BY or AMR read out
transmission interval: 2 … 240 min
free choice of transmission times
encryption AES 128
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to PTB K 7.2
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
95188
5 ... 50°C
5 … 55 °C
PN 16
DN 15
1.5 m3/h
3.0 m3/h
30 l/h
7 l/h
110 mm
G3/4"
0.230 bar
3.6 m3/h
Return line
AMTRON S2+ 20 2.5_130_G1 B10R-ws/c
Compact mechanical energy meter
for cooling with Radio
Return line
Highly accurate single-jet flow sensor
Calculator rotatable
Calculator removable with 0.3 m cable
2 temperature sensors Pt 500 (Ø 5 mm)
(cable length 1.5 m)
Temperature sensor return line
integrated in flow sensor
Temperature sensor supply line
with screwing CEN M10x1
Comfortable LC-display with 8 digits
Horizontal or vertical mounting
Metrological class 3 according EN 1434
Dynamically controlled measuring cycle from 12.5 ... 60 sec
Battery 10+1 years
Display MWh
15 months memory
Storage of maximum values for flow and power
Optical interface (M-bus protocol)
Wireless M-Bus (Radio) 868 MHz according EN13757
OMS compliant
for modes S1 / T1 and S2 / T2
short or long telegram
for WALK-BY or AMR read out
transmission interval: 2 … 240 min
free choice of transmission times
encryption AES 128
Protection class IP54
Electromagnetic environment C according EN 1434
Approvals according to PTB K 7.2
Temperature range:
Ambient temperature:
Nominal pressure:
Nominal diameter:
Nominal flowrate qp:
Maximum flowrate qs:
Minimum flowrate qi:
Low flow threshold value:
Installation length:
81919489
5 ... 50°C
5 … 55 °C
PN 16
DN 20
2.5 m3/h
5.0 m3/h
50 l/h
10 l/h
130 mm
12.2014
17/18
Text for tenders
Connecting thread:
Pressure loss at qp:
Value Kvs:
Meter mounted:
81919489
G1"
0.240 bar
6.0 m3/h
Return line
12.2014
18/18