SECTION 10 22 39
FOLDING PARTITIONS
PART 1 – GENERAL
**NOTE: THE PK30 ACCORDION FOLDING SYSTEMS ARE FOR FOLDING PARTITIONS
WEIGHING UP TO 176 LBS (80 KG) PER PANEL. REFER TO THE PK30 SYSTEM
WEIGHT CALCULATOR EXCEL SPREADSHEET TO CONFIRM THAT INDIVIDUAL
PANEL WEIGHT IS UNDER THE SYSTEM’S LIMITATIONS. ONE-SIDED
INSTALLATIONS ARE POSSIBLE UP TO 6000 MM (19 FEET-8 INCHES OR 732
INCHES) IN WIDTH OR DOUBLE THIS FIGURE FOR TWO-SIDED (MIRRORED)
INSTALLATIONS. A TOP & BOTTOM CENTER PIVOT HINGE SECURES THE FIRST
PANEL IN THE SET, SUBSEQUENT PANELS ARE HINGED TOGETHER. THE
VARIOFOLD SYSTEM’S SUSPENSION POINT IS AT THE END OF THE PANEL, PANELS
ARE OFFSET TO THE SUSPENSION TRACK WHEN FOLDED/STACKED. VARIOFOLD
MUST BE INSTALLED WITH A CONTINUOUS BOTTOM GUIDE CHANNEL FOR
CONFIGURATIONS WITH MORE THAN TWO PANELS, ALL PANELS MAY BE EQUAL
IN WIDTH.
THE CENTERFOLD SYSTEM’S MID-POINT PANEL SUSPENSION ALLOWS
INSTALLATIONS WITHOUT A CONTINUOUS RECESSED BOTTOM GUIDE CHANNEL,
BOTTOM RAIL LOCKS & DUST-PROOF STRIKES KEEP THE CENTERFOLD WALL
SECURE WHEN CLOSED. THE GEOMETERY OF THE CENTERFOLD SYSTEM
REQUIRES THE FIRST PANEL TO BE ROUGHLY HALF THE WIDTH OF SUBSEQUENT
PANELS.
GENERAL NOTES: A COMMUNICATING PIVOT DOOR MAY BE ADDED TO THE
PANEL STACK, OR TO THE OPPOSING END. ATTACHED TO EVERY OTHER PANEL IS
A FOLDING/PIVOT DOOR CATCH WITH AN INTEGRATED, INDIVIDUALLY
ADJUSTABLE RETAINER TO HOLD THE FOLDING WALL FLUSH WHEN CLOSED.
BOTH VARIANTS HOLD MANY OTHER ACCOMMODATING ADVANTAGES; EASY
PLANNING AND INSTALLATION, EXTREMELY QUIET RUNNING PROPERTIES, LOW
PARKING AREA SPACE REQUIREMENTS AND EXCELLENT QUALITY WITH REGARD
TO MATERIALS AND FINISH.
**NOTE: SPECIAL CONDITIONS CAN BE ACCOMMODATED. PLEASE CONTACT PK30
SYSTEM IF YOUR PROJECT HAS UNUSUAL REQUIREMENTS OR CONDITIONS THAT
HAVE NOT BEEN SPECIFICALLY ADDRESSED. SPECIALIZED SOLUTIONS ARE
AVAILABLE UPON REQUEST.**
1.1 SUMMARY
A.
Section includes folding partitions as shown on the drawings, inferable
therefrom and as specified.
1. Folding partitions includes the following: Provide all elements from a
single manufacturer.
____________________________________________________________________________
Folding Partitions – 10 22 39
Page 1
PROJECT NAME
DATE
____________________________________________________________________________
**NOTE: EDIT “a” BELOW FOR THE TYPES OF PARTITION SYSTEM FOR THE PROJECT.**
a.
Metal framed glass folding partitions including all accessories.
**NOTE: THE SYSTEM MAY INCLUDE SWINGING DOORS. DELETE BELOW IF NO DOORS
AND REVIEW THE ENTIRE SECTION CAREFULLY WHERE OTHER REFERENCES TO
DOORS SHOULD BE DELETED.**
b. Integrated metal framed glass doors including all accessories.
1.2 REFERENCES
B.
Reference Standards: Publications referenced in the text of this Section are
listed by source, designation, where applicable, and title.
1. AAMA 611.98:
Voluntary Specification for Anodized Architectural
Aluminum.
1.3 ADMINISTRATIVE REQUIREMENTS
A.
Coordination:
1. Single Responsibility: Assign undivided responsibility of the folding
partitions to a single firm specializing in this type of work. Do not engage a
firm unacceptable to the manufacturer of the system. The firm shall engage
other specialty firms to perform any part of the work which he is not
equipped or qualified to perform with their own personnel.
**NOTE: CHOOSE ABOVE OR BELOW. ABOVE FOR USE OF JUST THIS SECTION. BELOW
WHERE SOME OR ALL OF THE FOLLOWING SECTIONS ARE PART OF THE
PROJECT.**
1. Single Responsibility: Assign undivided responsibility of the following
scopes of work to a single firm specializing in these types of work. Do not
engage a firm unacceptable to the manufacturer of the system. The firm
shall engage other specialty firms to perform any part of the work which he
is not equipped or qualified to perform with their own personnel.
**NOTE: EDIT BELOW FOR ONLY THOSE SECTIONS USED.**
a.
Section 10 22 19, DEMOUNTABLE PARTITIONS.
b. Section 10 22 43, SLIDING PARTITIONS.
c.
Section 10 22 44, SLIDING-STACKING PARTITIONS.
d. Section 10 22 45, OFFICE ENTRANCES.
**NOTE: USE “2” ONLY WHEN CHOOSING THE SECOND OPTION FOR “1” AND EDITE THE
REFERENCE SECTIONS AS REQUIRED.**
2. Coordinated Submittals:
Coordinate submittals with the following
Sections:
a.
Section 10 22 19, DEMOUNTABLE PARTITIONS.
b. Section 10 22 43, SLIDING PARTITIONS.
c.
Section 10 22 44, SLIDING-STACKING PARTITIONS.
d. Section 10 22 45, OFFICE ENTRANCES.
____________________________________________________________________________
10 22 39 – Folding Partitions
Page 2
PROJECT NAME
DATE
____________________________________________________________________________
B.
Preinstallation Meetings: Prior to the installation of folding partitions, and at the
Contractor's direction, meet at the project site to review the installation
procedures and methods.
1.4 ACTION SUBMITTALS
A.
Product Data: Submit manufacturer's product data and hardware details
including rough in requirements and dimensions, installation instructions, and
parts lists for all folding partitions and accessories required.
1. The broad application range requires that the HAWA-Variotec 150/H
Modular wall hardware system be custom engineered to attain the best
solution for a given project.
**NOTE: BELOW IN SHOP DRAWINGS, THE SUPPORT FOR THE SYSTEM IS NOT
INCLUDED.
SYSTEM REQUIREMENTS FOR THE SUSPENSION TRACK ARE
DEPENDENT UPON THE STRUCTURE/ARCHITECTURE OF THE GIVEN
APPLICATION, THEREFORE THE ARCHITECT/DESIGNER’S ENGINEERING
CONSULTANT
SHOULD
DETERMINE
THE
NECESSARY
STRUCTURAL
REQUIREMENTS FOR SUPPORTING THE SUSPENSION TRACK ACCORDING TO
LOCAL CODES AND CALCULATIONS MADE OF EXISTING CONDITIONS. PK30 WILL
OFFER ALL ASSISTANCE POSSIBLE INCLUDING BUT NOT LIMITED TO PANEL
WEIGHTS, COMBINED PARKING AREA WEIGHTS FOR LOADING CALCULATIONS,
AND EXAMPLES OF POSSIBLE SUPPORT METHODOLOGIES.**
B. Shop Drawings: Prior to ordering materials, submit shop drawings for the
fabrication and installation of folding partitions. As specified under Existing
Conditions, note all field measurements required on the shop drawings. Include
large scale elevations, details, and sections of all component members
anchorage, jointing, and other accessories as follows:
1. Layout and installation details, including relationship to adjacent work.
2. Elevations at minimum 1/4 inch equals 1 foot scale.
3. Detail sections of typical members.
4. Anchors and reinforcement.
5. Hardware mounting locations including dimensions.
6. Glazing details.
C.
Samples:
1. Initial Selection Requirements:
a.
Colors: Provide manufacturer’s standard coupon samples of each
color required.
2. Verification Requirements: Provide only after approval of color selections.
a.
Profiles: Submit the required sets of samples of each component with
each finish on 12 inch long sections. Where color variations are
anticipated include two or more units in each set of samples
indicating the anticipated range.
____________________________________________________________________________
Folding Partitions – 10 22 39
Page 3
PROJECT NAME
DATE
____________________________________________________________________________
b.
c.
Corner Fabrication: 8 inch long legs of full-size corners, including fullsize sections of extrusions with factory-applied color finish.
Glazing: Manufacturer's standard-size unit, but not less than 3 inches
square.
1.5 INFORMATIONAL SUBMITTALS
A.
Sustainable Design Submittals:
1. Recycled Content: Submit certification letter from material suppliers
certifying specified percentage requirements of recycled content indicating
percentages by weight of post-consumer and pre-consumer recycled
content. Include statement indicating costs for each product provided.
1.6 CLOSEOUT SUBMITTALS
A.
Operation and Maintenance Data:
1. Provide manufacturer's care instructions for maintenance of folding
partitions including cleaning instructions, operating instructions and
precautions, and any limitations.
B.
Warranty Documentation: Provide signed warranty as specified.
1.7 QUALITY ASSURANCE
A.
Qualifications: Personnel engaged in the work shall be able to demonstrate
successful experience with work of comparable extent, complexity and quality to
that shown and specified, including quality control and testing procedures. This
includes the following additional requirements:
1. Manufacturers: Capable of providing complete, precision built, engineered,
pre-fitted units with a minimum 10 years’ experience in the sale of foldingsliding door systems for large openings in the North American market.
2. Installers: Experienced in the installation of the manufacturer’s products
or other similar products for large openings. Provide reference list of at
least 3 projects of similar scale and complexity successfully completed in
the last 3 years.
a.
Installers shall be trained and certified by the manufacturer.
**NOTE: BELOW FIRST TIME INSTALLER PROGRAM’S INSTALLATION SUPERVISION AND
ASSISTANCE COSTS $700.00 PER DAY PLUS TRAVEL AND HOTEL EXPENSES. A 2
DAY CERTIFICATION SERVICE IS THE MINIMUM REQUIREMENT FOR
INSTALLATION CERTIFICATION. INSTALLATIONS WITHOUT PK30 CERTIFICATION
ARE NOT WARRANTED. SERVICE CALLS TO ADJUST AND REPAIR THE PK30
PRODUCT ON UNCERTIFIED INSTALLATIONS WILL BE BILLED TO CUSTOMER AT A
RATE OF $700.00 PER DAY PLUS TRAVEL AND LODGING EXPENSES.**
____________________________________________________________________________
10 22 39 – Folding Partitions
Page 4
PROJECT NAME
DATE
____________________________________________________________________________
b.
B.
First Time Installer Program: Where the installer has been trained
and certified by the manufacturer but where this is the installer’s first
time installation of the manufacturer’s product, the manufacturer
shall provide a full time, on site, installation supervisor for a minimum
of 2 days to ensure that the system is correctly installed
Single Source Limitation: Provide all components and accessories for folding
partitions from a single manufacturer.
1.8 DELIVERY, STORAGE, AND HANDLING
A.
Delivery, Storage and Handling Requirements: Deliver materials to job site in
manufacturers original sealed, unopened cartons or crates. Protect units from
damage. Store on pallets in dry, weather protected locations and free from dirt,
dust, construction debris. Comply with the manufacturer’s requirements for
protection including limitations for the contact of any protective materials.
Storage area shall be free from the requirement to move or relocate delivered
materials prior to installation.
1.9 SITE CONDITIONS
A.
Ambient Requirements: Do not deliver or install folding partitions or
components until the installation site is enclosed and all finishing including
ceiling, floor covering and painting are completed.
B.
Existing Conditions:
1. Manufacturer’s shop drawing dimensions, including tolerances shall be
based on the Architect’s drawings.
2. Verify with field measurements prior to fabrication the dimensions of
openings, and stack storage area. Mark field measurements on shop
drawing submittal.
3. Where field dimensions cannot be verified, the General Contractor shall be
responsible for maintaining the tolerances required for installation.
1.10 WARRANTY
A.
Manufacturer’s Warranty: Submit copies of written warranty, signed by the
manufacturer and the installer, agreeing to repair or replace defective
components and work which has failed. Repairs and replacements required
because of failure of materials or workmanship shall be completed without
additional expense to the Owner. The period of the warranty shall be an
extension to 2 years starting on the date of acceptance by the Owner for
substantial completion. Failures include but are not limited to the following:
1. Component structural failure including excessive deflection.
____________________________________________________________________________
Folding Partitions – 10 22 39
Page 5
PROJECT NAME
DATE
____________________________________________________________________________
2.
3.
Faulty operation of components or hardware.
Deterioration of metals, metal finishes including coatings.
PART 2 – PRODUCTS
2.1 SYSTEMS
A.
Manufacturer: Substitutions will not be permitted. Provide precision built, preengineered, pre-fitted sliding partition system from the following:
1. PK30 System LLC
PO BOX 656
3607 Atwood Road
Stone Ridge, NY 12484
(212) 473-8050 (845) 687-9774
website: www.pk30.com
email: [email protected]
**NOTE: EDIT BELOW IF NO SWINGING DOORS.**
B. Product: Sliding partition system for folding metal framed panels and integrated
metal framed glass door including all hardware, accessories, and anchorages.
1. PK30 System.
C. Sustainability Requirements:
**NOTE: BELOW IS BASED ON LEED V3. VERIFY AND MODIFY AS REQUIRED.**
1. Recycled Content:
a.
Products shall have a minimum recycled content of 40 percent preconsumer and 22 percent post consumer.
D.
E.
Performance/Design Criteria: Provide partitions and doors of dimensions and
configurations shown complying with performance requirements specified.
1. Loading:
a.
Withstand gravity loads.
b. Limit lateral deflection to less than L/175 or 3/4 inch, whichever is
less, complying with ASTM E72 tested under a uniformly distributed
load of 5 pounds per square foot.
2. Glass Deflection:
a.
Limit lateral deflections of glass panel edges to less than L/175 of
glass-edge length or 3/4 inch, whichever is less.
Materials:
1. Aluminum: Alloy and temper recommended by the manufacturer for
strength, corrosion resistance, and application of required finish.
a.
Comply with the following:
1) Aluminum Extrusions: ASTM B 221, Alloy 6063, T6,T5/T52.
____________________________________________________________________________
10 22 39 – Folding Partitions
Page 6
PROJECT NAME
DATE
____________________________________________________________________________
2) Aluminum Sheet or Plate: ASTM B 209, Alloy 6061, T6.
3) Aluminum Bars, Rod and Wire: ASTM B 221, Alloy 6063, T6.
b. Provide main extrusions of not less than 0.080-inch wall thickness,
profiles as shown.
c.
Provide extruded glazing stops and other applied trim extrusions with
minimum wall thickness of 0.050-inch.
2. Fasteners; Provide 18/8 stainless steel, or other non-corrosive metal
fasteners compatible with aluminum components, hardware, anchors, and
other items being fastened.
a.
Reinforcement: Where fasteners screw anchor into aluminum
extrusions where there is no screw boss, or that is less than 0.125inch thick, reinforce the interior with aluminum or steel as required to
receive screw threads.
b. Exposed fasteners: Provide all exposed fasteners shall be flat socket
head or Phillips head 18/8 stainless steel machine screws, use only
one type of exposed fastener for all work.
3. Glazing:
a.
Glazing System: Use manufacturer's standard glazing system of setting
blocks, gaskets, and glazing tapes as required to cushion the glass and
prevent metal to glass contact.
b. Glass: Provide manufacturer’s glass of the type as selected by the
Architect. Where custom glass is selected, coordinate with the sliding
partition manufacturer for factory glazing before shipment to the site.
**NOTE: DELETE BELOW OR SPECIFY AS REQUIRED. THE SYSTEM CAN ACCOMMODATE
MANY PANEL TYPES (WOOD, GLASS, PLASTIC, METAL) WITH A THICKNESS
RANGING BETWEEN 1/4 INCH AND 9/16 INCH. WHERE WOOD IS COORDINATE
WITH ARCHITECTURAL WOODWORK, CONSIDER REFERENCING SECTION 06 40 00
AND DESCRIBE THE WOOD PANELS THERE COORDINATING THAT THEY ARE
REQUIRED TO BE PROVIDED TO THE PARTITION INSTALLER FOR INSTALLATION.**
c.
Panels: xxx.
F.
Fabrication:
1. Provide shop assembled panels with hardware and accessories required for
a complete assembly. Provide concealed fastening devices and pressure-fit
components that will not damage ceiling or floor coverings. Fabricate
panels with light and sound seals at floor, ceiling, and other locations where
panels abut fixed construction.
2. Factory prepare interior aluminum frames to receive templated mortised
hardware; include cutouts, reinforcements, mortising, drilling, and tapping,
3. Fabricate frames for glazing with removable stops to allow glazing
replacement without dismantling frame.
4. Fabricate components to allow secure installation without exposed
fasteners.
____________________________________________________________________________
Folding Partitions – 10 22 39
Page 7
PROJECT NAME
DATE
____________________________________________________________________________
G. Design Configuration:
**NOTE: COORDINATE ALL OF THE CONFIGURATIONS DESCRIBED WITH WHAT IS
SHOWN DELETE THOSE NOT REQUIRED.**
1. Sizes and Configurations: As shown for selected number and size of panels,
location of swing panels, and location of tracks and stacking bays.
2. Operation: Adjustable sliding and swinging hardware with the following
track options:
**NOTE: EDIT BELOW TRACK CONFIGURATIONS AS REQUIRED.**
a.
Top and bottom tracks.
b. Top tracks, bottom track will not be permitted.
c.
Top and bottom tracks as shown, some locations a bottom track will
not be permitted.
3. Panel Configurations:
**NOTE: EDIT BELOW PANEL CONFIGURATIONS AS REQUIRED.**
a.
One-sided Installation comprised of ( ) Panels.
b. Two-sided (Bi-Parting Folding Wall) installation comprised of ( )
Panels.
c.
With Pivot Door added to Stack.
d. With Pivot Door added opposite stack.
4. Mounting Types:
**NOTE: EDIT BELOW MOUNTING TYPES AS REQUIRED.**
a.
Surface mounted.
b. Recessed mounted.
H. Finishes:
**NOTE: DELETE OR EDIT THE DIFFERENT FINISH SYSTEMS AS REQUIRED. A PROJECT
MAY HAVE ONLY ONE OR SEVERAL DIFFERENT SYSTEMS, OR SEVERAL COLORS OF
BAKED ENAMEL. COORDINATE WITH DRAWINGS AS REQUIRED TO DESIGNATE
LOCATIONS.**
1. Anodized Coating: Provide the following for all aluminum work shown or
specified to receive anodized finishes, NAAMM nomenclature, as required
to match Architect's sample:
a.
Clear Anodized Finish: AA-M12C22A41, Class I, 0.07 mm or thicker.
1) Color: Manufacturer’s medium matte clear finish.
b. Color Anodized Finish: AA-M12C22A42/A44, Class I, 0.07 mm or
thicker.
1) Color: Manufacturer’s medium matte black finish.
2. Baked Enamel Coating: Thermosetting acrylic enamel coating shall be
factory applied and shall meet the high performance requirements of
AAMA 2603.
a.
Preparation:
Prepare surfaces in accordance with coating
manufacturer’s written recommendations.
This shall include
pretreatment and primer.
____________________________________________________________________________
10 22 39 – Folding Partitions
Page 8
PROJECT NAME
DATE
____________________________________________________________________________
b.
Coating films shall be uniform and free from flow lines, streaks,
blisters, sags or other surface imperfections in dry film state on all
surfaces. Slight variations in appearance of abutting or adjacent
pieces are acceptable. Noticeable variations in the same piece will not
be permitted.
**NOTE: BELOW TYPICAL SHEEN IS 20% GLOSS. VERIFY WITH MANUFACTURER IF A
HIGHER LEVEL OF GLOSS IS REQUIRED.**
c.
Products: Color and sheen as selected by the Architect.
1) Duracron Series, PPG Industries, Inc.
2.4 ACCESSORIES
**NOTE: COORDINATE WITH DRAWINGS FOR LOCATIONS OF WHICH DOORS RECEIVE
WHICH TYPES OF HARDWARE, DEVELOP A HARDWARE SET SCHEDULE FOR EACH
DOOR.**
A. Factory install hardware, except surface mounted hardware. Remove only as
required for final door finishing operation, delivery, and installation at the
project site.
B. Hardware for Sliding/Folding Doors:
**NOTE: COORDINATE WITH THE MANUFACTURER FOR ADDITIONAL HARDWARE
DESIRED.**
1. Operating Hardware: Sliding hardware system for folding partitions with
panel weights of up to 176 pounds.
a.
Product and Manufacturer:
1) Variofold 80/H Sliding Hardware System, Hawa AG.
2) Centerfold 80/H Sliding Hardware System, Hawa AG.
**NOTE: VARIOFOLD HARDWARE SET AS FOLLOWS.**
2. Hardware sets as required in accordance with the application:
a.
Hawa 19532 Basic set for first two starter panels.
b. Hawa 19533 Additional set for every two additional panels added to
stack.
c.
Hawa 15405 Bottom guide channel.
d. Hawa 16852 Top Suspension Track - Aluminum-clear anodized.
**NOTE: CENTERFOLD HARDWARE SET AS FOLLOWS.**
3. Hardware sets as required per application:
a.
Hawa 19535 Basic set for first two starter panels.
b. Hawa 19536 Additional set for every two additional panels added to
stack.
c.
Hawa 16852 Top Suspension Track - Aluminum-clear anodized.
**NOTE: VARIOFOLD/CENTERFOLD COMMON HARDWARE LISTED BELOW. DELETE “4.”
BELOW IF A COMMUNICATING PIVOT DOOR IS NOT ADDED TO STACK. PIVOT
DOORS ADDED TO THE STACK MUST SWING 180° AND FOLD FLAT AGAINST THE
STACK FOR PROPER OPERATION THEREFORE NO PROJECTING HARDWARE SUCH
____________________________________________________________________________
Folding Partitions – 10 22 39
Page 9
PROJECT NAME
DATE
____________________________________________________________________________
AS MORTISE LOCK LEVERS, BAR PULLS AND SURFACE MOUNTED DOOR CLOSERS
MAY BE SPECIFIED**
4. Pivot door added to stack:
a.
Hawa 19620 Pivot Door set to Folded Stack.
**NOTE: DELETE ALL OF “C” BELOW IF NO COMMUNICATING PIVOT DOOR IS ADDED TO
FAR END-OPPOSITE STACK. INDEPENDENT PIVOT DOORS ADDED TO FAR ENDOPPOSITE STACK MAY HAVE TRADITIONAL OPERATING HARDWARE SUCH AS
MORTISE LOCKS, BAR PULLS AND DOOR CLOSERS.**
C. Independent communicating Swing Door Opposite the Stack:
**NOTE:
DELETE BELOW IF NO FLOOR CLOSERS.
BELOW INCLUDES THE
MANUFACTURER’S SPECIAL TOP AND BOTTOM PIVOT REQUIRED FOR THE FLOOR
CLOSER**
1. Center Hung Floor Closers:
a.
Products and Manufacturers:
1) Top Pivot: 16485, Hawa AG.
2) Bottom Pivot for Floor Closer: 13276, Hawa AG.
3) Center Hung, Concealed Floor Closer: BTS80, DORMA Group.
**NOTE: DELETE BELOW IF NO LOCKING PIVOT HINGES. NOTE THAT THIS IS A ‘FREE
SWINGING’ (NO CLOSER) DOOR.**
2. Center Hung Pivot Hinges:
a.
Products and Manufacturers:
1) Top Pivot: 16485, Hawa AG.
**NOTE: BELOW ARE THREE OPTIONS, CHOOSE ONLY ONE AND DELETE THE OTHER.
THE FIRST IS FOR THE VARIOFOLD, THE SECOND FOR THE CENTERFOLD, THE
THIRD IS FOR THE PROPRIETARY PK30 CENTER PIVOT. COORDINATE WITH THE
MANUFACTURER FOR ADVICE ON CHOICE AND COST DIFFERENCES.**
2) Bottom Pivot: 19516, Hawa AG.
2) Bottom Pivot: 19515, Hawa AG.
2) Bottom Pivot: PK06-1010, PK30 System, LLC.
**NOTE: DELETE BELOW OF NO NON-LOCKING PULL HANDLES. BRACKETS INDICATE A
CHOICE OF STAINLESS STEEL OR ALUMINUM, AND THE ROCKWOOD PRODUCT IS
AN EXAMPLE. ANY GLASS MOUNTED BACK TO BACK PULL HANDLE SUGGESTED BY
THE DESIGNER AND APPROVED IN ADVANCE BY PK30 SYSTEM IS ACCEPTABLE,
EDIT THE DESCRIPTION AND PRODUCT AS REQUIRED.
3. Non-Locking Pull Handles:
1-1/4 inch diameter [stainless steel]
[aluminum] tube 36 inches long with flat ends and back to back concealed
mounting.
a.
Products and Manufacturers:
1) MegaTek Series, RM3301, Rockwood Manufacturing Co.
**NOTE: DELETE BELOW IF NO LOCKING PULL HANDLES.**
4. Locking Pull Handles: Locking type pull handle with lock pull handle
manufacturer’s matching dust proof strike.
a.
Products and Manufacturers:
____________________________________________________________________________
10 22 39 – Folding Partitions
Page 10
PROJECT NAME
DATE
____________________________________________________________________________
1) PostMount or GeoMetek Series, Rockwood Manufacturing Co.
**NOTE: DELETE BELOW IF NO MORTISE LOCKS**
5. Mortise Locks: Sliding partition manufacturer’s recommended mortise
locks.
a.
Products and Manufacturers:
**NOTE: THE MANUFACTURER PROVIDES SELECTIONS FROM FSB. REFER TO THE FSB
CATALOG FOR THEIR FULL LINE OF MORTISE LOCKS, LEVER DESIGNS, FUNCTIONS
AND FINISHES. **
1) xxx, FSB USA
**NOTE: DELETE BELOW IF NO BOTTOM RAIL DEADLOCKS**
6. Bottom Rail Deadlocks:
a.
Products and Manufacturers:
1) PK04-3010 Bottom Rail Lock, Key x Thumb-turn Cylinder into
dust-proof floor strike.
2.5 HARDWARE SET SCHEDULE
**NOTE: THERE ARE VARIOUS WAYS TO FORMAT A HARDWARE SET SCHEDULE, THE
FOLLOWING IS JUST AN EXAMPLE AND NEEDS TO HAVE THE SET NUMBER
INCLUDED IN THE DOOR SCHEDULE ON THE DRAWINGS. ALSO, THIS IS AN
EXAMPLE USING ONLY GENERIC NAMES FOR ITEMS, THE SPECIFIER SHOULD
INCLUDE MORE SPECIFIC INFORMATION.**
Set No.
Quantity Item
Finish
**NOTE: IN THE EXAMPLES BELOW, THE ** UNDER THE FINISH COLUMN SHOULD BE
REPLACED BY THE FINISH DESIGNATION.**
**NOTE: FOLDING PARTITION EXAMPLE.**
101
1 set
Folding Partition, operating hardware
**
1
Communicating Door Opposite Stack hardware set
**
**NOTE: SWINGING DOOR EXAMPLE.**
100
1 set
Floor closers, center hung, single acting,
heavy duty, with recessed dress plates,
extended spindles, less exposed alignment
screws, and no holdopen
2
Non-locking pull handles
**
**
PART 3 – EXECUTION
3.1 EXAMINATION
A.
Verification of Conditions:
____________________________________________________________________________
Folding Partitions – 10 22 39
Page 11
PROJECT NAME
DATE
____________________________________________________________________________
1.
Condition of Substrate: Examine the substrates and the conditions under
which the work is to be performed. Notify the Architect and do not proceed
until unsatisfactory conditions have been corrected.
a.
Coordinate with the General Contractor as required to obtain
verification that adequate support has been provided by the installers
of the substrates providing anchorage for the system.
b. Verify that other trades have completed the necessary related work
before installing the sliding hardware track.
c.
Verify that floor and mounting surfaces shall be level, plumb, secure,
true and straight with not less than 1/8 inch in a 10 foot run in any
direction. Substrates shall be of proper dimensions and material.
3.2 PREPARATION
A.
Templates and diagrams: Furnish templates, diagrams, and other data to
fabricators and installers of related work, as necessary, for coordination of the
adjacent finishes.
3.3 INSTALLATION
A.
Install complete system in accordance with manufacturer’s recommendations
and written installation instructions.
B.
Provide appropriate anchorage devices to securely and rigidly fit frames into
place, absolutely level, straight, plumb and square. Install frames in proper
elevation, plane and location, and in proper alignment other work.
1. Installation Tolerance: Install each demountable partition so surfaces vary
not more than 1/8 inch from the plane formed by the faces of adjacent
partitions.
C.
Install frame components in the longest possible lengths, components up to 72
inches shall be single lengths unless otherwise permitted by the Architect.
1. Anchor to the required structural support with anchorage type and spacing
as recommended by the manufacturer.
2. Use concealed installation fasteners to produce tightly fitted and aligned
splices and connections.
**NOTE: BELOW EXPOSED FASTENERS ARE MINIMAL. THE DESIGNER IS ENCOURAGED
TO FAMILIARIZE THEMSELVES WITH THEIR LOCATION BY CONTACTING PK30
SYSTEM.**
3. Do not leave installation screws or other fasteners exposed to view when
installation is complete, except where required by the manufacturer.
D.
Clean track and hardware surfaces prior to hanging sliding door panels.
____________________________________________________________________________
10 22 39 – Folding Partitions
Page 12
PROJECT NAME
DATE
____________________________________________________________________________
E.
Install panels, handles, locks, decorative hardware and trim in accordance with
sliding
partition
manufacturer’s
and
component
manufacturer's
recommendations and installation instructions for each item.
1. Adjust system as required at the ceiling and at the floor to accommodate
out of level conditions.
3.4 SITE QUALITY CONTROL
A.
Non-Conforming Work: Do not install components and accessories damaged
during shipping and storage. Remove damaged materials from the site and
return them to the manufacturer for replacement.
3.5 ADJUSTING
A.
After repeated operation of installed units, adjust all moveable and operating
components as required to provide smooth and continuous long term operation
and safety. Any repairs or replacement of components shall be performed as
required to comply with the sliding partition manufacturer’s requirements for
new installations.
3.6 CLEANING
A.
Remove temporary coverings and protection only when recommended by the
sliding partition manufacturer. Remove construction debris from project site
and legally dispose of debris.
B.
Clean exposed framing and glass surfaces promptly after installation, using
cleaning only methods recommended by sliding partition manufacturer.
3.7 CLOSEOUT ACTIVITIES
A.
Demonstration and Training.: Provide demonstrate and training to the Owner's
personnel to adjust, operate, and maintain the system and accessories partitions.
Demonstration shall be by a representative approved by the manufacturer of the
folding partitions. Refer to Division 01 for additional requirements.
3.8 PROTECTION
A.
Provide protective measures throughout the remainder of the construction
period to ensure that sliding partition system shall be without damage or
deterioration at the time of substantial completion. Remove and replace all
components damaged.
END OF SECTION
____________________________________________________________________________
Folding Partitions – 10 22 39
Page 13