Option - Adder Subtractor, Min/Max Select SI139

Option - Adder Subtractor, Min/Max Select SI139
Input Option 61:
Iout=I 1I 2 OR IOUT =
Adder
I 1I 2
(AVERAGER)
2
Input loads (4-20mA) :
I1 =50 , I 2=50 0.7V
Input Option 62:
Subtractor
IOUT =I1 −I 2
Input loads (4-20mA) :
I1 =50 , I 2=50 0.7V
Input Option 64:
Minimum Selector
The output signal will follow the lower of both input signals.
Input load: 56Ω (4-20mA)
Input Option 65:
Maximum Selector
The output signal will follow the higher of both input signals.
Input load: 56Ω (4-20mA)
Input Option 68: Adder,
I OUT =I 1I 2 (ADDER)
I OUT =
69: Subtractor
I OUT =I 1−I 2
I 1I 2
(AVERAGER)
2
Unlike options 61 and 62 the two inputs can be any current or voltage
signal, however they must be independently sourced or have a
common 0V.
Must specify Calibration for each input when ordering e.g.
In1 Cal:
1-5V
In2 Cal:
0-20mA.
In the interest of development and improvement, APCS reserve the right to amend, without notice, details contained in this publication. APCS will accept no legal liability for any errors,
omissions or amendments.
NESS Corporation
APCS division
Option - Adder Subtractor, Min/Max Select SI139
Drawing: DS13961 Issue: 3 29/10/10
Tel: (02) 8825 9295
Fax: (02) 8825 9290
www.apcs.net.au
Page: 1