HomeRun Combiner Boxes Installation and Operations Manual TABLE OF CONTENTS Notices and Safety Precautions Page 1 Combiner Box Electrical Characteristics Pages 2‐3 Combiner Box Mounting Page 4 Grounding, Fuses and Wiring Pages 5‐6 Maintenance, Service and Operation Page 7 Install Confidence 1010 B Street, Suite 4100 – San Rafael, CA 94901 415-925-9650 – www.sunlink.com 1 SunLink’s HCB Seriies Combiner Boxes B are the professional p so olar installer’s cchoice for comb bining PV Arrayys and complying with the C These bo oxes include: National Electrical Code. Complianc ce with the strin ngent UL1741 safety s listing for continuous ra ated current op peration at 50°C C. Installation friendly TYPE E 3R, 4 or 4X watertight w enclosure for vertica al or horizontal mounting. Spacious wiring w area for ease e of installa ation and mainttenance. Simple, cle ean and solid construction for years of servic ce. SAVE E THESE INST TRUCTIONS - This T manual prrovides importa ant instructionss for the HomerrunTM Series C Combiner Boxess that shall be TM follow wed during insta allation and ma aintenance. The Homerun Series S Combin er Boxes are d designed and te ested to stringe ent internationa al safetyy requirements s. However, as with all electric cal equipment, specific safetyy practices musst be followed. To reduce the risk of injury, carefu ully read this in nstruction book klet in its entiretty before installing, wiring, or using this prod duct in any wayy. 1..1. Disclaimer of Liability Th he installation techniques, t handling and use e of this product are beyond ccompany contro ol. Therefore, S SunLink Corporration does nott asssume respons sibility for loss, damage or exp pense resulting g from imprope er installation, h handling or use e of this producct. 1..2. Listing Infformation Th his product meets or exceeds s the requireme ents set forth by y Underwriters Laboratories ffor componentss used with PV V Modules. This s UL L Standard is UL1741 U for acc cessories used with inverters. 1..3. Limited Warranty W Co ombiner box lim mited warrantie es are for 1 yea ar for materials and workmansship. Impo ortant Safetty Instructio ons There e are NO user-serviceable parts in this enclo osure. Modifying this productt in anyy way will void the manufactures warranty. WARNING G: PV modules pass direct currrent (DC) whe en the module iis under load. D Direct current w will arc across g gaps and may cause injurry or death if im mproper connec ction or disconnection is mad e. Do not conn nect or disconn nect wires to the e combiner box x when curre ent from the mo odules or an ex xternal source is present. WARNING G: Voltage is present in open circuit c condition ns. Photovolta aic modules cre eate voltage an nytime light is p present. CAUTION:: For continued d protection aga ainst risk of fire e, replace fusess with only 600 0VDC / 1000V rated, max. 30 0A fuses. Make conn nections in com mbiner box priorr to connecting g modules. To work on the co ombiner box affter the module es are connected,, cover all modules in the PV array with an opaque o cloth o r material. All US insta allations must be performed in compliance with w the Nation nal Electrical Co ode (NEC), AN NSI/NFPA 70 and any applicable local codes. Installation, maintenance & servicing sh hould be performed only by au uthorized perso onnel. Remove all metallic jewellry prior to insta alling this product to reduce th he chance of a accidental expo osure to live cirrcuits. Use insulatted tools to red duce your risk of o electric shoc ck. Do not insttall or handle th he combiner bo ox if it is wet. Maximum 95% 9 humidity during d use. Contact Su unLink Corpora ation if the combiner box enclo osure is damag ged or its conte ents are comprromised. Storage tem mperature: - 60 0º C - + 85 º C ation Posiitive Ground Configura The H HomerunTM Serries Combiner Boxes may be installed for us se with positive e grounded solar arrays, as re equired for exa ample with M certaiin SunPowerTM solar modules s. If used in a positive p ground configuration substitute the w word “negative e” for every insttance of the word “positive” below w and substitute the word “po ositive” for everry instance of tthe word “nega ative” below. 2 2 HomeRun Combiner Box Installation & Operations Manual Combiner Box Electrical Characteristics DISCONNECTING COMBINER BOX ELECTRICAL CHARACTERISTICS Family ID 100/250S 250 400 30 30 30 1000* 1000* 1000* Voltage Range (VDC) 0‐1000* 0‐1000* 0‐1000* Maximum Continuous DC Current (A) 100/250 250 400 10 10 10 Positive Input Wire Size (AWG) 14‐6 14‐6 14‐6 Positive Input Terminal Torque (in‐lbs) 14.75 14.75 14.75 Negative Input Wire Size (AWG) 14‐4 14‐4 14‐4 40 40 40 14‐4 14‐4 14‐4 Ground Input Terminal Torque (in‐lbs) 40 40 40 Compression Lug Max Positive Output Wire Size (AWG) 250 2 x 300 [2 x 500]** 2 x 750 Compression Lug Max Negative Output Wire Size (AWG) 250 2 x 300 [2 x 500]** 2 x 750 Compression Lug Max Ground Output Wire Size (AWG) 1/0 2 x 250 2 x 250 Mechanical Lug Max Positive Output Wire Size (AWG) 350 350 N/A Mechanical Lug Max Negative Output Wire Size (AWG) 350 350 N/A Mechanical Lug Max Ground Output Wire Size (AWG) 350 350 N/A Compression Lug Output Terminal Torque (in‐lbs) 250 500 500 Mechanical Lug Output Terminal Torque (in‐lbs) 325 325 N/A Input Terminal Temperature Rating 75°C 75°C 75°C Output Terminal Temperature Rating 90°C 90°C 90°C ‐25°C to 50°C ‐25°C to 50°C ‐25°C to 50°C 3R/4/4X 3R/4/4X 3R/4/4X 6 ‐ 48 6 ‐ 48 10 ‐ 48 Maximum Input Fuse Rating (A) Maximum Voltage (VDC) SCCR AT 600VDC (KAIC) Negative Input Terminal Torque (in‐lbs) Ground Input Wire Size (AWG) Operating Temperature NEMA Rating Maximum # of Inputs for this Family 0 = OFF 0 = OFF 0 = OFF 1 = ON 1 = ON 1 = ON *Standard Disconnects are not load break rated at 1000V, specify high voltage disconnect for load break rating above 600V Switch Position **[2 x 500] ‐ Available on some models Rev 1 Page 3 HomeRun Combiner Box Installation & Operations Manual Combiner Box Electrical Characteristics NON‐DISCONNECTING COMBINER BOX ELECTRICAL CHARACTERISTICS Family ID 60 100/250S 250 400 Maximum Input Fuse Rating (A) 20 30 30 30 Maximum Voltage (VDC) 600 1000 1000 1000 0-600 0-1000 0-1000 0-1000 Maximum Continuous DC Current (A) 60 100/250 250 400 SCCR AT 600VDC (KAIC) 10 10 10 10 Positive Input Wire Size (AWG) 14-6 14-6 14-6 Positive Input Terminal Torque (in-lbs) 14.75 14.75 14.75 Negative Input Wire Size (AWG) 14-4 14-4 14-4 40 40 40 14-4 14-4 14-4 Ground Input Terminal Torque (in-lbs) 40 40 40 Max Positive Output Wire Size (AWG) 250 2 x 300 [2 x 500]* 2 x 750 Max Negative Output Wire Size (AWG) 250 2 x 300 [2 x 500]* 2 x 750 Max Ground Output Wire Size (AWG) 1/0 2 x 3/0 2 x 250 Positive, Negative and Ground Output Terminal Torque (in-lbs) 250 500 500 Maximum Input Fuse Rating (A) 30 30 30 Voltage Range (VDC) Negative Input Terminal Torque (in-lbs) Ground Input Wire Size (AWG) Operating Temperature ‐13°F to 122°F ‐25°C to 50°C ‐13°F to 122°F ‐25°C to 50°C ‐13°F to 122°F ‐25°C to 50°C NEMA Rating 3R/4/4X 3R/4/4X 3R/4/4X Maximum # of Inputs for this Family 6 ‐ 48 6 ‐ 48 10 ‐ 48 Switch Position 0 = OFF 1 = ON 0 = OFF 1 = ON 0 = OFF 1 = ON *[2 x 500] - Available on some models COMBINER BOX PART NUMBER DERIVATION TABLE Family ID&Size HCB-XXX HCB-250S # of Strings Disconnecting? Material/NEMA Rating Monitoring Pre-Wired 6-48 (by 2) D or H or N (non-disc) S, SS, or F** – 3R, 4, or 4X M or blank B or Blank 16 H F4X M B The resulting part number for this combiner box example with the listed options: HCB-250S-16-H-F4X-M-B-LTE. *D is disconnect load break rated to 600V, H is disconnect load break rated to 1000V, N is no disconnect **S, SS, and F represent the enclosure materials: Steel, Stainless Steel, and Fiberglass, respectively. Mech. Lugs LTE or blank LTE Rev 1 Page 4 HomeRun Combiner Box Installation & Operations Manual Mounting Mounting Overview A. Install the enclosure using the external enclosure mounting tabs only. Drilling holes in the back plate is not recommended and shall void the product warranty. B. Place in desired location and use the appropriate hardware to mount the combiner box. C. The combiner box may be mounted vertically (door opens out) or horizontally (door opens up). D. Place the box in areas out of continuous water flow and extreme temperature. E. If the box has a disconnect switch, do not mount the box such that the switch handle is blocked or difficult to operate. Please refer to the enclosure installation manual for additional mounting instructions. Step 1 – Choose your Connectors A. The use of UL514B or equivalent conduit fittings is required to maintain the TYPE 4 (or 4X) rating of the enclosure. B. Installation of fittings must comply with UL50 for USA installations to maintain TYPE 4 (or 4x) rating of the enclosure. Step 2 – Install Connectors Metallic Conduit A. Place connector through hole with the o‐ring on the outside of the enclosure. B. Screw on and tighten the locknut. Next screw on the Grounding Bushing, rotate to desired location and tighten set screws. Non‐Metallic Conduit A. Place connector through with the o‐ring on the outside of the enclosure. B. Screw on and tighten the locknut. C. Screw Insulated or plastic bushing onto connector threads to protect conductors from damage. D. Grounding Bushings are not used with non‐metallic conduit. Rev 01 Equivalent connectors from other manufactures may be used as long as they satisfy citations in this section. Page 5 HoomeRun Combiner Box Installatiion & Opperationss Manuaal Grounnding, Fusees and Wirring Groun nding Overview w A A. A ground b bar has been provided for the e convenience of combining several ground ds into one larger ground wirre. B B. Please refe er to NEC Article 690 on grou unding PV arrayys for specific rrequirements. C C. Combiner box models wiith metallic encclosures have ffactory installeed ground wirees or straps to bond the enclo osure body and door. Note: Do not cconnect any grround wires to enclosure boddy bonding locaation or to doo or bonding loca ation. Step 1 – Install Grounding nding With Meetallic Conduit Groun A A. When instaalling metallic conduit grounding bushings m must be used, rrefer to section n 6.3.1 for installation. B B. A continuo ous ground conductor must ggo through th he lay‐in lug on the groundingg bushing wiith the insulation stripped baack on either side e of the lay‐in lu ug set screw. N Note: Bonding of the Groundiing Bushings m must ccomply with the NEC for USA installations. nding With Non‐Metallic Con nduit Groun A A. When instaalling non‐mettallic conduit th he grounding conductor is terminated at tthe ground bar. Step 2 – Select Fuse es A A. Please con nsult the module manufacturer and/or ratin ng label to seleect the appropriate fuse size.. B B. In most cases, the fuse siize is determin ned by multiplyying the short ccircuit current rating by 156% % and roundingg up to the next standard fuse size. C C. Please con nsult NEC Articlle 690 for more e information. D D. A maximum m of a 30 Amp fuse may be u used with this p product. Step 3 – Output Conductor Sizingg A A. The combiner box output design curren nt is determine ed by: (total Iscc x 156%) divid ded by a tempeerature correction factor. B B. Select the appropriate te emperature correction factorr from the NECC. See NEC Articcles 310 and 690 for proper w wire sizing. Step 4 4 ‐ Wiring NOTEE: USE COPPER OR ALUMINUM M CONDUCTO ORS SUITABLE FFOR AT LEAST 775°C. A A. Insert positive input cond ductor from th he source circuit into the Touuch Safe fuse holder and tightten to torque sspecifications n pages 2 and 3 3. as listed on B B. Insert negaative input con nductor from th he source circu uit into the neggative collecto or and tighten tto torque specifications as listed on pages 2 and 3. C C. Crimp a lugg onto the output wires to th he inverter (or other destinattion ), bolt onto the output teerminal busbars and secure to the torq que requirements in as listed on pages 2 an nd 3. If the com mbiner box hass mechanical lu ugs, use a hex driver to tighten the e mechanical lu ug to the torqu ue requirements as in listed iin pages 2 and 3. D D. Make sure all connection ns are tight, seccure and safe ffor many yearss of operation.. EE. DO NOT IN NSTALL FUSES! Rev 0 01 Page 6 HoomeRun Combiner Box Installatiion & Opperationss Manuaal Grouunding, Fusses and Wiring W Step 5 5 – Wire for Mo onitoring* *Onlyy if your combin ner box includess string level currrent monitorin ng. A A. If the comb biner box inclu udes the option n for string leve el current mo onitoring, it will have one or more Obvius A89DC‐08 or A90DC‐12 C Current Monito ors installed inside the combiner box.. B B. You must m maintain a min nimum of ¼” off physical separation n between the wires that connect to the current mo onitors and the e high voltage wires to preve ent contact to the high voltage conductors. Note:: Diagram of th he A89DC‐08 m monitor is for reeference only, please refer to the A A89DC‐08 or A90DC‐12 installlation manuall nd configuratio on of the curren nt monitors. for prroper wiring an Step 5 – Ensure Pro oper Ventilatio on A A. Maintain aa minimum cleaarance of 1” on n all 4 sides of the enclosure . Step 6 – Check Your Work ORE INSTALLING G FUSES, comp plete these simp ple time‐saving g checks. Notee: A multimeterr is needed to vverify the insta allation processs. BEFO Checkk that the multtimeter is capa able or reading the maximum m string voltagee and maximum m string curren nt before proceeeding. A A. Measure V Voltage (Voc) a. Place tthe multimeter in DC voltage e mode. b. Check the open circu uit positive voltage (Voc) from m each individ ual solar arrayy string to the n negative bus bar. e each Voc is the proper polaarity (this mean ns the meter reeads a positivee DC voltage) aand within the intended c. Ensure range.. d. Voc do oes not vary m much with irradiance and tem mperature condditions. B B. Measure C Current (Isc) a. Place tthe multimeter in DC currentt mode. b. Check the short circu uit current (Iscc) of each indivvidual solar arraay string to thee negative bus bar. panel specificaations. c. Compare the measured Isc to the p es vary with irrradiance and temperature so o be careful to consider the cconditions at th he time of meaasurement. d. Isc doe C C. Check Ground Currents D D. Check the DC current fro om each individ dual string (fuse holder) to grround and veriify that no currrent is flowing to ground. pair any ground faults. a. If current is present,, locate and rep Step 7 – Insert Fuse es A A. Insert fuse es into fuse holders and securre it in the clossed position. Step 8 – Conduct Fiinal Inspection n A A. Check the DC voltage fro om the combined output lug tto the negativee bar. B B. Ensure voltage is the pro oper polarity an nd within the d desired voltagee range. C C. Double che eck that all con nduit penetrations are prope erly sealed agaiinst water andd pest intrusion n. D D. Close and ssecure the encclosure door. Rev 1 1 Page 7 HomeRun Combiner Box Installation & Operations Manual Maintenance, Service and Operation Maintenance and Service A. Read the Notices and Safety Precautions on pages 1‐2 for important safety information before performing any maintenance or service. B. Please use protective safety equipment and disconnect all sources of supply before working on this product. C. The only serviceable components in the HomerunTM Solar Array Combiner box are the fuses. a. Before changing a fuse(s) check the system for problems and make repairs as needed. b. Then go through Steps 5‐ 6 on page 7 before installing a new fuse(s). D. WARNING: ‐ For Continued Protection against risk of fire, replace fuses with same type and rating of fuse (600V DC rated, MAX 30A Midget fuses). E. If the combiner box has a disconnect switch it must be switched ten times in a row, once a year, with the system off, to clean contacts. F. Mechanical aspects of the switch handle should be checked for dirt on an annual basis. G. No more than 3x the force of normal operation should be applied to the switch. If switch does not operate within this capacity, check for blockage or obstruction. H. Every 6 months inspect and re‐torque the wire connections. Ongoing Operation A. If the combiner box has a disconnect switch the switch may be used to disconnect the combiner box from current coming from other parts of the array and/or to disconnect the voltage and current of the combiner box from an inverter or other equipment that is downstream of the combiner box. B. To operate the switch simply rotate the handle 90 degrees, the switch contacts will be open if the switch handle is pointing to the off position. C. Always place the switch of every combiner box that is connected to an inverter in the off position before servicing the inverter. D. If the combiner boxes do not have a disconnect switch, turn off the inverter and verify that the current from the combiner boxes to the inverter is zero amps, then open all the fuse holders in the combiner boxes before servicing the inverter. a. Do not open the fuse holders under load. E. The fuse holders are not load break rated, and may cause damage or injury if opened under load. F. There are no other operable parts in the combiner box other than the disconnect switch and fuse holders. Rev 1 Page 8
© Copyright 2025 Paperzz