Three New Product Series
Series
HP6M
HP10M
HP6J
Application
String or Module
Protection
String or Module
Protection
Array or Inverter
Input Protection
Voltage
600VDC
1000VDC
600VDC
Ampere
1-30A
1-30A
70-600A
Size
Midget (10x38mm)
Midget (10x38mm)
Class J
Approvals
UL2579, IEC60269-6
UL2579, IEC60269-6
UL2579
5
HelioProtection Fuse Products
Catalog Number Selection
– Example: HP10M15
HP
10
HelioProtection
Series
6
M
Voltage
Fuse Class
6 = 600VDC
M = Midget
10 = 1000VDC
J = Class J
15
Ampere Rating
Application Overview
7
Application Overview
8
Application Overview
String Combiner Box
9
Application Overview
Array Combiner Box
Inverter Input
10
The importance of
UL 2579 – Fuses for Photovoltaic Systems
11
UL 2579 – Fuses for Photovoltaic Systems
Background Information
UL 248 – Low Voltage Fuses
– Divided into 16 sub-categories
• Class CC, Class RK, Class H, Class J, Plug Fuses, etc…
– Intended Applications
• Power Controls
• Power Low Voltage Distribution
• Power Electronics
12
UL 2579 – Fuses for Photovoltaic Systems
General Performance Characteristics
– Voltage Rating may be up to 1500VDC
– Interrupting Rating is 10kA minimum
– Classification: Non-Renewable, Not Current-Limiting
13
UL 2579 – Fuses for Photovoltaic Systems
Markings
– In addition to the marking requirements in UL 248-1, the fuse must
be marked with the letters “PV” or “gPV” or the text “Photovoltaic
Fuse”.
14
UL 2579 – Fuses for Photovoltaic Systems
Expanded tests specific to PV application
– Verification of Freedom from Unacceptable Levels of Thermally
Induced Drift
• Electrical performance verified after repeated thermal cycling
• Simulates night to day thermal climate cycle
– Verification of Functionality at Temperature Extremes
• Fuse to be conditioned at 50°C and electrically tested to verify
functionality (compared to 25°C for UL 248)
– Current Cycling
• Fuses undergo current and thermal cycling to verify life expectancy and
to prevent pre-mature fuse opening
15
Product Resources
16
Product Resources
Collateral
– Data Sheets
• HP6M, HP10M, HP6J
– Solar Power Brochure
– Performance Curves
•
•
•
•
Time-Current Curves
Temperature De-rating
Watts Loss
Outline Drawings
– PIQ Online Interactive Quiz
17
Applicable Customers and
Why HelioProtection?
18
Applicable Customers
System Integrators and Contractors
– Delivers: No-hassles, certainty
Solar Inverter OEMs
– Delivers: Premium protection, cost savings, reliability
Combiner Box Manufacturers
– Delivers: Premium protection, cost savings, reliability
Utility Power Generation and Distribution
– Delivers: revenue generation – no downtime, safety
19
Why HelioProtection Fuses?
1.
Easy Product Selection
Dedicated solar brand delivers reliable, easy specification and
selection
2.
Meets UL 2579 Standard
Tested for night to day transition
Tested to electrical operate at extreme temperatures
Current cycled for increased liability and longevity
3.
Size Advantages
HP6J frame size is minimum one-third smaller than competitor
offering
20
Questions & Answers