Optimal Allocation of Heat Exchanger Inventory of a Two-Stage Vapor Compression Cycle for Cost Minimization M. J. MORALES S. A. SHERIF Department of Mechanical and Aerospace Engineering University of Florida P.O. Box 116300, 232 MAE Bldg. B Gainesville, Florida 32611-6300 Tel (352) 392-7821/ Fax (352) 392-1071/ Abstract: - This paper reports on an optimization study of a two-stage Carnot refrigerator with the purpose of minimizing the cost of all heat exchangers involved. Several temperature ratios were defined as independent variables and plots were created with respect to those variables to determine which corresponded to a minimum with respect to a dimensionless Heat Exchanger Inventory Cost Equation (HEICE). It was found that only two variables had a significant minimum with respect to the dimensionless HEICE; the ratio between the condenser temperature and average coolant temperature, and the ratio between the evaporator temperature and the condenser temperature. The latter may be referenced to either the low or the high-temperature evaporator. Key Words: - Optimal allocation, heat exchanger inventory, optimization, vapor compression refrigeration, cycle analysis, Carnot cycle W compressor work rate proportion of heat exchanger inventory ~ x value where the maximum COP occurs x Greek Symbols unit cost of conductance for the condenser or the evaporators total heat exchanger inventory cost ratio of condenser temperature to average coolant temperature ratio of evaporator to condenser temperature ratio of average coolant temperature at the condenser to average chilled fluid temperature at the evaporator Subscripts 1 pertaining to low-temperature evaporator 2 pertaining to high-temperature evaporator a pertaining to constant work rate in the HEICE b pertaining to constant cooling capacity of low-temperature evaporator in the HEICE c pertaining to constant cooling capacity of high-temperature evaporator in the HEICE d pertaining to constant heat rejection rate in the HEICE H pertaining to the hot side or condenser Nomenclature x Latin Symbols A area F heat exchanger inventory cost equation G unit cost of conductance of evaporator to unit cost of conductance of condenser h specific enthalpy K ratio of mass flow rate through the lowtemperature evaporator to that through the high-temperature evaporator mass flowrate of refrigerant through the m condenser Q heat transfer rate s specific entropy T01 refrigerant temperature in the low-temperature evaporator T02 refrigerant temperature in the hightemperature evaporator TH average condenser coolant temperature (K) THC refrigerant temperature in the condenser (K) TL1 average chilled fluid temperature through the low-temperature evaporator TL2 average chilled fluid temperature through the high-temperature evaporator U overall heat transfer coefficient 1 1 Introduction Antar and Zubair [1] investigated the minimizing the heat exchanger inventory cost for cases involving constant work rate, constant cooling load, and constant heat rejection rate. That investigation was based on a Carnot refrigerator model developed by Bejan [2]. The same model was applied by Klein and Reindl [3] and will be utilized in this paper, which expands Antar and Zubair’s [1] investigation to a twostage system with two evaporators. Additionally, Sahin and Kodal [4] studied a two-stage combined refrigeration system, which was optimized with respect to the cooling load per total cost. That study, however, only involved one evaporator. The purpose of this study is to examine the parameters that influence the cost of a two-stage Carnot refrigerator with two evaporators. This will be achieved by deriving a dimensionless Heat Exchanger Inventory Cost Equation (HEICE) for the refrigerator. The HEICE is defined as the sum of the costs of the individual heat exchangers in the refrigerator. Minimizing the heat exchanger inventory cost helps reduce the initial cost of a refrigeration system. The system examined in this paper can be thought of as composed of two separate cycles, an outer one and an inner one, each acting as a singlestage cycle. Each cycle circulates the same amount of flow per unit time as the other. Figure 1 represents a schematic of the Carnot two-stage refrigerator model with all its components. The components are Compressor I, Compressor II, condenser, Expander I, Expander II, a low-temperature evaporator and a hightemperature evaporator. Figures 2 shows the T-s diagram associated with the cycle. In principle, the cycle operates as follows: at State Point 1 the refrigerant exits the low-temperature evaporator and enters Compressor I. At State Point 2 the refrigerant exits Compressor I and mixes with the refrigerant exiting the high-temperature evaporator. As seen in Figure 2, State Points 1 and 2 have the same entropy. The mixed flow enters Compressor II and exits at State Point 3 where it enters the condenser. It exits at State Point 4 as saturated liquid, after which it enters Expander II, exiting at State Point 5. As can be seen from Figure 2, the process from State Points 4 to 5 is isentropic (unlike that through expansion valves where the process is isenthalpic). At State Point 5 the refrigerant is split into two channels. One channel feeds the hightemperature evaporator, while the other feeds Expander I. The flow that enters the high-temperature evaporator exits at State Point 2. The one that feeds Expander I exits at State Point 6, later entering the low-temperature evaporator and exiting at State Point 1. Figure 3 shows the outer cycle. This cycle delineates a Carnot refrigeration cycle that exchanges heat with the environment and the refrigerated space. Figure 4, on the other hand, shows the inner cycle. This cycle, which circulates the same amount of mass flow rate as the outer cycle, also exchanges the same amount of heat with the environment as the outer cycle. It also utilizes half of the second compressor power; the other half is utilized by the outer cycle in bringing the refrigerant up to the second stage. The inner cycle can be viewed as a Carnot refrigeration cycle operating at the same high temperature as the outer cycle except that its low temperature is higher than that of the outer cycle. 2 Analysis The objectives of this analysis are to derive a dimensionless HEICE and to examine which parameters within such equation would produce a minimum value of the HEICE. The equation will be derived under one of the following constraints: constant work rate, constant cooling load at the lowtemperature evaporator, constant cooling load at the high-temperature evaporator, and constant heat rejection rate. The equations that govern the heat transfer taking place from and to the two-stage Carnot refrigeration cycle will be developed as part of the analysis. The Heat Exchanger Inventory Cost Equation (HEICE) is defined as = UA)H + 1 (UA)1+ 2 (UA)2 (1) where 1 and 2 are unit costs of conductance for the condenser, low-temperature evaporator, and hightemperature evaporator, respectively, making a 2 parameter with units of dollars. equations apply: The following QH Q2 Q H = (UA)H (THC – TH) (2) Q1 = (UA)1(TL1 – T01) (3) Q 2 = (UA)2(TL2 – T02) (4) H 1 2 Q Q Q + 1 + 2 TL2 T02 THC TH TL1 T01 1 H H H G Q 1 T T T T T H H (5) G2 = 2 H (6) (7) TH H (8) QH THC (m1 m2 )(s3 s 4 ) (9) Q1 T01m1 (s1 s6 ) (10) Q2 T02m2 (s 2 s5 ) (11) s 3 s 4 s1 s 6 s 2 s 5 (12) (1 K)THC T01 (13) Q1 H H H HC L1 01 H H K T 1 K T T T T T 02 2 HC L2 02 H H (15) G 1 = Q θ 1 H 1 1 G Φ 1 K ξ Φ θ 1 1 1 2 K Φ 1 K ξ Φ θ 2 2 2 (16) where the nondimensional temperature ratios are given by The condenser heat rejection rate is the sum of the condenser heat rejection rate of the inner and outer cycles. The parameter K is defined as the ratio of the mass flow rate through the high-temperature evaporator to that of the low-temperature evaporator. Since the cycle is reversible, then QH HC 1 T G 1 K T T T T T 01 1 Multiplying both sides by TH and introducing nondimensional temperature ratios defined below gives Equation (16) Dividing Equation (5) by H gives 1 H 2 Q Q Q = + G1 + G2 TL2 T02 THC TH H TL1 T01 (14) T hand side by H gives TH In order to nondimensionalize Equation (5) the following quantities are introduced: G1 = (K 1)THC KT02 Substituting Equations (13) and (14) into Equation (8), Factoring out Q , and dividing the right Substituting Equations (2) through (4) into Equation (1) yields = THC TH (17) T01 THC (18) T02 THC (19) TL1 TH (20) TL 2 TH (21) 3 Results and Discussion 3.1 Constant Work Rate Dividing Equation (16) by the work rate results in a nondimensional equation. This translates into applying the HEICE to a cycle with constant work rate 3 Fa= Fa = 1 Γ T H γHW G 1 Q θ 1 W H 1 1 G Φ 1 K ξ Φ θ 1 1 1 2 K Φ 1 K ξ Φ θ 2 2 2 1 1 K 2 1 K 2 1 1 K 1 K (22) Applying the First Law of Thermodynamics to the entire system gives Q Q Q W H 1 1 1 1 1 1 1 K 1 K 2 1 K 2 1 1 1 1 K 1 K G1 (23) 2 1 K G1 1 G 2 2 1 1 K 1 K 1 1 1 2 2 Dividing this equation by Q and introducing Equations (13) and (14) results in the following: (27) H T01 KT02 W 1 H Q (1 K)THC (1 K)THC Since TL1 > T01 and TL2 > T02, then ( 1 1 ) and ( 2 2 ) are larger than zero. This means that in order for Fa/1 to be equal to zero, the quantity (24) 1 1 Substituting Equations (18) and (19) into (24) and expressing the reciprocal of both sides of the resulting equation gives H Q W 1 Φ1 KΦ 2 1 (1 K) (1 K) (25) Γ T H γHW 1 1 K 2 1 1 K 1 K 1 K G1 1 G 2 2 1 1 K 1 K 1 1 1 2 2 must be negative or equal to infinity. This is not practical since the right-hand side of Equation (25) must be positive. Therefore there is no practical maximum or minimum with respect to . Furthermore, according to Figure 5, the lower is, the lower Fa will be when the rest of the parameters are held constant, confirming the previous assertion. This same trend holds true even as is changed from 1.03 to 1.05 to 1.06. It is worthy to remark that as 1 increases, Fa approaches an asymptote. The value where the asymptote occurs is also dependent on the value of From Equation (26) we can see that as increases, the value of where the asymptote occurs would be lower. The same behavior is expected when varying the parameter and keeping all other parameters constant. Thus, we may conclude that evaluating the derivative of Fa with respect to should result in no practical minimum or maximum either. The function Fa does appear to have a minimum with respect to the parameter . Setting Fa/ = 0 yields Substituting Equation (25) into (22) gives Fa= 1 K 2 1 K 1 K (26) This is the non-dimensional HEICE for a two . stage Carnot refrigerator with constant work rate W It is clear that there is an inverse relationship between Fa and both 1 and 2 , but no minimum point exists with respect to either one of these parameterst is, therefore, unclear whether there is a minimum with respect to , orTaking the derivative of Fa with respect to and setting it equal to zero gives the following equation: 1 12 1 K 12 G 2 22 1 K 1 K = 1 12 2 22 G1 (28) After assuming values for all other parameters and applying a trial and error procedure, this equation is solved for All assumed values are based on initial, practical temperature values for a two-stage system. Therefore, a value of which produces the minimum 4 Fa can be obtained. Figure 6 shows how Fa varies with respect to at K = 1.00, with the minimum value occurring at 1.04. Figure 7 shows that K has little or no effect on min over a practical range of K = 0.25 to 2.00. The previous analysis was performed assuming a constant work rate. A similar analysis can be undertaken for the cases where Q , Q and Q are constant. The resulting overall HEICEs are, respectively, as follows: 1 Fb= 2 This equation suggests that there should be a minimum with respect to for a constant Q . Figure 8 shows that there is no minimum with respect to over the practical range of values assumed. At K = 2.00, the function Fb was found to have a minimum with respect to . This minimum, though, is of minor relevance since the function stays almost constant throughout the range of . Taking the derivative of Fb with respect to and equating the result to zero gives the following: 1 H 1 K Γ TH γ H Q1 1 1 K 1G1 2 G 2 1 1 K 1 K 1 1 1 2 2 Γ 1 K TH Fc= γHQ2 KΦ 2 1 K 1G1 2 G 2 1 1 K 1 K 1 1 1 2 2 Fb KG 2 ( 2 2 ) K 2 G 2 ( 2 2 ) 2 2 (29) Since both terms in the numerator are higher than zero, this derivative cannot be equal to zero. Therefore, there is no minimum for Fb with respect to Taking the derivative of Fb with respect to and equating the result to zero results in Equation (28), implying that that min is the same for Fa and Fb. By inspection we can see that differentiating Fc and Fd with respect to again results in Equation (28). Therefore, all four F functions share the same min. Differentiating Fc with respect to is analogous to finding Fb/ similarly there are no minima either. The same effect occurs when differentiating Fc with respect to 2. This is analogous to finding Fb/ (30) 1 K 1G1 2 G 2 Γ 1 K 1 K 1 T Fd= H H 1 1 1 2 2 γHQ (31) The above equations will be optimized with respect to the variables they each depend on. 3.3 Constant Heat Rejection Rate This scenario deals with a case of constant heat rejection rate in the condenser. Here we try to determine which of the independent parameters causes the function Fd to have a minimum. Taking the derivative of Fd with respect to and equating the result to zero gives the following: 3.2 Constant Cooling Rates - Both Evaporators This scenario, which deals with constant cooling rates at both evaporators, is herein examined with the purpose of determining whether the functions Fb and Fc have minima with respect to the dimensionless variables previously defined. Taking the derivative of Fb with respect to 1 and equating the result to zero gives the following: 1 1 1 Fd 1 K 1 K 1 12 1 1 (1 ( 2 2 )) 2 1 (34) The numerator portion of this equation cannot be equal to zero because TL1 > T01, meaning that ε1 - Φ1θ > 0 . Consequently there is no Fb (1 K )( 1) G1 2 (1 ( 1)) (1 1) 2 1 K 2 G 2 ( 2 2 ) (33) minimum or maximum with respect to The same result is expected when differentiating with respect to . Also, as mentioned in the previous section, all F functions share the same min. Zubair and Antar [1] (32) 5 also investigated varying G. In this study G1 and G2 are kept constant at 1.00. Therefore it is understood that (UA)tot will also be minimum when the dimensionless HEICE is at a minimum. at the given temperatures and heat transfer parameter values. References: [1] Antar, M. A. and S. M. Zubair, 2002, “Thermoeconomic Considerations in the Optimum Allocation of Heat Transfer Inventory for Refrigeration and Heat Pump Systems,” Journal of Energy Resources Technology, Vol. 124, pp. 28-33. [2] Bejan, A., 1993, “Power and Refrigeration Plants for Minimum Heat Exchanger Inventory,” Journal of Energy Resources Technology, Vol. 115, pp. 148-150. [3] Klein, S. A. and D. T. Reindl, 1998, “The Relationship of Optimum Heat Exchanger Allocation and Minimum Entropy Generation Rate for Refrigeration Cycles,” Journal of Energy Resources Technology, Vol. 120, pp. 172-178. [4] Sahin, B. and A. Kodal, 1995, “Steady-State Thermodynamic Analysis of a Combined Carnot Cycle with Internal Irreversibility,” Energy: The International Journal, Vol. 20, No. 12, pp. 1285-1289. 4 Conclusions The optimization problem described in this paper has three possible parameters with minima of is significance: , and 2. However, when W constant the last two parameters, and 2, provide only a theoretical minimum since that minimum only occurs for negative values of the function Fa, which is impractical. For a constant Q , aside from , only 2 provides a minimum, but only when K is approximately higher than 2. This minimum is of minor significance since Fb is only reduced minimally at this point. The same occurs for the constant Q case, aside from , only 1 provides a minimum, with the same expected results as the constant Q case. The minimum F value, since it is based on a Carnot refrigeration cycle, makes a prediction of what the minimum initial cost of the heat exchangers would be 1 2 1 Figure 1. Schematic of a two-stage Carnot refrigeration cycle Figure 2. T-s diagram of a two-stage Carnot refrigeration cycle 6 Dimensionless HEICE for Constant Work Rate, F a 1400 1200 2 = 0.8181 = 0.960, 2 = 0.880, = 1.00 1000 0.870 800 600 0.890 400 0.850 200 0 1.02 1.03 1.04 1.05 1.06 1.07 THC/TH Figure 6. Dimensionless HEICE for constant work rate vs. = THC/TH: Effect of varying Figure 3. Outer cycle diagram of a two-stage Carnot refrigeration cycle 1200 K = 2.00 Dimensionless HEICE for Fixed Work Rate, Fa 1000 800 K = 0.25 600 400 200 1 = 0.8902 = 0.818, = 0.960, = 0.880 0 Figure 4. Inner cycle diagram of a two-stage Carnot refrigeration cycle 1.010 1.020 1.030 1.040 1.050 1.060 1.070 1.080 THC/TH Figure 7. Dimensionless HEICE for constant work rate vs. = THC/TH: Effect of varying K 115 400 300 0.818, 1 = 0.960, = 0.880, K = 1.00 Dimensionless HEICE for Constant Cooling Capacity, Fb Dimensionless HEICE for Constant Work Rate, Fa 500 1.03 1.06 200 = 1.05 100 0 0.680 0.730 0.780 0.830 0.880 105 1.03 95 85 1.05 75 65 1.06 55 = 0.818, 1 = 0.960, 2 = 0.880, K = 1.00 45 1 = T01/THC 0.810 0.820 0.830 0.840 0.850 0.860 0.870 0.880 1 = T01/THC Figure 5. Dimensionless HEICE for constant work rate vs. 1 = T01/THC: Effect of varying Figure 8. Dimensionless HEICE for constant cooling capacity vs. 1 = T01/THC: Effect of varying for K=1.00 7 0.890
© Copyright 2026 Paperzz