Pressure Distribution: Orifice, Pipe, and Pump Sizing P1 P2 X P3 P3a

Page 1 of 5
Pressure Distribution: Orifice, Pipe, and Pump Sizing
The completed installation is to comply with the Alberta Private Sewage Systems Standard of Practice 2009.
This worksheet is for use in Alberta to: size the orifices in distribution lateral pipes, size effluent delivery piping,
and to calculate the required capacity and pressure head capability of the effluent pump. It can be used for:
calculating delivery of effluent to laterals in disposal fields, mounds, and sand filters.
This worksheet does NOT consider all of the requirements of the 2009 Standard of Practice
Note: Page numbers refer to the Private Sewage Systems Standard of Practice 2009.
Use only one unit of measurement throughout (Imperial measures provided for sample purposes.)
Step 1) Select the pressure to be maintained at the orifices:
Minimum pressure at the orifice:
- 3/16” or less orifice = 5 ft. min.
2.6.2.5 (1) - (p.48) Design Pressure
- larger than 3/16” orifice = 2 ft. min. 2.6.2.5 (1) - (p.48)
at orifice (ft.)
ft
P1
Note: worksheet will not provide an adequate design if laterals are at different elevations. Differing elevations will result in a different pressure head and volume of discharge at the orifices in each lateral. Additional considerations must be made for laterals at differing elevations.
Step 2) Select the size of orifice in the laterals:
- Minimum size:
2.6.1.5 (1e) - (p.46) 1/8 in.
(larger sizes are less likely to plug)
Orifice Diameter
selected (inches)
in
P2
Step 3) Select the spacing of orifices and determine the number of orifices to be installed in
distribution laterals.
Length of Distribution Lateral
Spacing of Orifices
From system design drawings
ft.
ft.
÷
=
orifices
P3a
Select a spacing of orifices to attain even distribution over the treatment area.
Maximum spacings are determined for:
- 5 feet primary treated effluent: 2.6.1.5 (e) - (pp.46-47)
- 3 feet secondary treated effluent: 8.1.1.8 & 2.6.2.2 (c) - (pp. 98 & 47 - 48)
- 3 feet on sandy textured soils: 8.1.1.8 - (p. 98)
(Close spacing provides effective, even distribution)
Total Orifices in each Lateral
X
From P3a this worksheet
Total number of orifices
all laterals
Number of laterals
laterals
=
P3
If laterals are of differing lengths,
calculate each separately and add
the number of orifices together.
Revised: May 5, 2010
Page 2 of 5
Pressure Distribution: Orifice, Pipe, and Pump Sizing
The completed installation is to comply with the Alberta Private Sewage Systems Standard of Practice 2009.
Step 4) Determine the minimum pipe size of the distribution laterals:
Enter the system design information into the 3 boxes below. If distribution laterals are of differing lengths, each
lateral must be considered separately.
Oriifice Diameter
Length of Distribution Lateral
in.
Total Orifices each Lateral
ft.
From P2 this (worksheet )
From P3b (this worksheet)
From system design drawings.
Use Table A.1.A (pp. 140 - 143) with the information above to determine the minimum size of the distribution
lateral pipe.
Size of Distribution Lateral
P4
in.-NPS
From Table A.1.A.
Step 5) Determine the total flow from all orifices:
Gal/min. for each Orifice
@ head pressure selected
Total Number of Orifices
X
From P3 this (worksheet )
Gal./min.
Imp.gal./min.
=
From Table A.1.B. pages 144 &
145
Required from pump.
Step 6) Determine the size of drain back orifice:
Gal/min
Size of drain back hole
P5
Total Gallons per Minute
+
=
Use head pressure
At drain back orifice
Gal/min
P6
Total gpm from pump
From P5
Step 7) Select the type and size of effluent delivery pipe:
Use Tables A.1.C.1 to A.1.C.4 (pp. 146—149)
to aid in decision. A larger pipe will reduce
Pressure loss.
Pipe Type & Size
Selected
in.-NPS
P7
Choose a friction loss from Tables A.1.C.1. to A.1.C.4. in between the bolded lines to ensure a flow velocity
between 2 to 5 feet per second.
Step 8) Calculate the equivalent length of pipe for pressure loss due to fittings:
Equivalent Length of All Fittings
Insert total from Worksheet “A” on last page (p. 5) of
Pressure Distribution Sizing Booklet
P8
(For pressure loss.)
Revised: May 5, 2010
Page 3 of 5
Pressure Distribution: Orifice, Pipe, and Pump Sizing
The completed installation is to comply with the Alberta Private Sewage Systems Standard of Practice 2009.
Step 9) Calculate the equivalent length of pipe from pump to the farthest end of header of distribution
laterals for pressure loss:
Length of Piping (ft.)
ft.
Equivalent Length of Fittings (ft.)
ft.
+
From pump to far header for
the distribution laterals.
Total Equivalent Length (ft.)
ft.
=
P9
For pressure loss
Calculation.
For pressure loss from P8
Step 10) Calculate the pressure head loss in delivery pipe including fittings:
Total Equivalent Length (ft.)
/100 ft
Friction Loss (ft.)
X
Delivery Piping
Pressure Head Loss
ft.
From P9 (this worksheet)
ft.
=
P10
(In delivery piping)
(Per 100 ft. of pipe)
Use Tables A.1.C. on pp
146—150 using volume from
Don’t forget to divide the length
by 100 feet to match the factors
in the tables.
P6 this worksheet.
Step 11) Calculate the total pressure head required at pump:
ft.
Delivery piping pressure loss
Lift distance of effluent from
Effluent level in tank to orifices (ft.)
+
ft.
+
Design pressure at orifices (ft.)
(ft.)
From P10 (this worksheet)
low
Measure from lowest effluent
level in tank to elevation of
orifices.
From P1 (this worksheet)
+
Head loss due to drainback
hole
ft.
***Based on q=16.37Cd²h1/2
See note on page 144 SOP
+
Add 1 ft. to allow for pressure loss
along the distribution lateral
Total pressure head required at
pump (ft.)
1
ft.
ft.
P11
Revised: May 5, 2010
Page 4 of 5
Pressure Distribution: Orifice, Pipe, and Pump Sizing
The completed installation is to comply with the Alberta Private Sewage Systems Standard of Practice 2009.
Step 12) Detail the Pump Specifications Required:
Required Flow Rate (gal./min.)
Required Pressure Head (ft.)
@
From P6 (this worksheet)
ft.
Review pump curve of patented
pumps. Select a pump where
pump capacity exceeds requirements by approximately 20%.
From P11 (this worksheet)
Step 13) Repeat the calculations if it is necessary to change the pump specs:
If the flow rate through the orifices is too high: reduce the orifice diameter in Step 2, increase the orifice spacing in Step 3 or include a distributing valve to sequentially dose small portions of the system.
If the pressure head required is too high: select a lower design pressure in Step 1, reduce the flow rate as above,
or increase the effluent delivery pipe size in Step 6.
Revised: May 5, 2010
Page 5 of 5
Worksheet “A”: Friction Loss Equivalent Length
The completed installation is to comply with the Alberta Private Sewage Systems Standard of Practice 2009.
Calculate the equivalent length of pipe for pressure loss due to fittings:
Friction Loss
As per Table
A.1.C.5 or A.1.C.6 - (p. 150)
Number of Fittings
X
90° Elbows
Total
=
+
X
45° Elbows
=
+
X
Gate and Ball Valves
=
+
Tee-on Branches (TOB)
X
=
+
X
Tee-on Runs (TOR)
=
+
X
Male Iron Pipe Adaptors (MIP)
(M / F Threaded Adaptors)
Total Equivalent Loss
=
=
(Enter this total, Box P8)
*** Head loss due to drain back hole is calculated as follows:
Based on q=16.37Cd2h1/2
Where q = Imperial gallons per minute flow rate
C = coefficient of discharge (0.60)
D = diameter in inches
Revised: May 5, 2010