Supermarket Insulation Specification S1 – General S1.01 Scope All cold and chilled water pipework shall be insulated to prevent condensation and energy losses. All airconditioning and refrigeration pipework shall be insulated to prevent condensation and energy losses. All low and medium temperature heating pipework, domestic hot water pipework and solar hot water pipework shall be insulated to prevent energy losses. All valves, fittings, flanges and associated equipment shall be insulated to the same standards as the linear pipe runs. Where services have the potential to generate or carry nuisance mechanical noise, acoustic insulation, including sound absorption and anti-vibration, shall be applied. S1.02 References The materials, components and completed installations shall conform to applicable Standards current at the time of tendering. Relevant standards may include: BS 353 BS 476 BS 874 BS 5970 EN ISO 8497 EN 12086 EN 12667 EN ISO 846 EN ISO 12241 EN ISO 14304 Glossary of terms relating to thermal insulation. Fire Tests on Building Materials and Structures. Methods of determining thermal properties, with definitions of thermal insulating terms. Thermal insulation of pipework and equipment in the temperature range of -100°C to +870°C Determination of steady-state thermal transmission properties of thermal insulation for circular pipes Thermal insulating products for building applications. Determination of water vapour transmission properties Determination of thermal resistance by means of guarded hot plate and heat flow meter methods. Products of high and medium thermal resistance Evaluation of the action of microorganisms Thermal insulation for building equipment and industrial installations -- Calculation rules Thermal insulation products for building equipment and industrial installations. Factory made flexible elastomeric foam (FEF) products. Specification S1.03 Services to be Insulated Cold water pipework Chilled water pipework Air-conditioning pipework Refrigeration pipework Low temperature heating pipework Medium temperature heating pipework Domestic hot water pipework Solar hot water pipework Air-conditioning ductwork S1.04 Pipe Clearances Shall be sufficient to allow for the full thickness of insulation to be applied around all pipework. The mechanical contractor shall be responsible for ensuring this detail. S1.05 Pipe Clamps Shall only be applied around high density load bearing sections at least matching the thermal performance of the thickness of insulation applied to linear pipe runs. The mechanical contractor shall be responsible for ensuring this detail. S2 Materials S2.01 General All insulation materials shall be: Formaldehyde free. © Kaimann GmbH · Brideoak Street · Oldham · OL4 2HB · +44 (0)161 627 3289 · [email protected] · Status: 30. June 2012 Shown to inhibit the growth of mould. Installed to the manufacturers recommendations. In particular all insulation shall be fully vapour sealed using an approved adhesive or mastic around all pipe supports, clamps, valves and flanges. Class O fire rated under BS 476 Parts 6 & 7 when used indoors. Either inherently UV resistant or otherwise treated with compatible UV resistant paint or coatings when used on pipework outdoors. Provided with a compatible weather & UV resistant finish appropriate to the environment when used on pipework outdoors which is likely to experience damage. Manufactured in accordance with a fully certified EN ISO 9001 quality management system. S3 – Thermal Insulation S3.01 Insulation Specification Materials shall be as described: Kaiflex ST Class O: Flexible Nitrile rubber insulation temperature resistant up to 100°C with a closed cell structure and a built in vapour barrier. The material shall exhibit a Class 1 surface spread of flame rating when tested in accordance with BS 476 Part 7 and a Class 0 fire rating when tested in accordance BS 476 Part 6. The material shall be dust and fibre free and incorporate an anti-microbial additive to prevent mould growth. The thermal conductivity shall be no greater than 0.034 W/(m·K) at 0°C and 0.038 W/(m·K) at 40°C when tested in accordance with EN ISO 8497 or EN 12667. Water vapour transmission shall be no less than 10,000 when tested in accordance with EN 12086. Resistance to bacterial and mould growth shall be no less than Class 1 when tested in accordance with EN ISO 846. Tube material shall be supplied in 2 m lengths or 15 m long coils. Sheets shall be supplied in 1 m continuous rolls. The material shall be black in colour. Kaiflex TC: Flexible Nitrile rubber insulation temperature resistant up to 80°C with a closed cell structure and a built in vapour barrier. The material shall exhibit a Class 1 surface spread of flame rating when tested in accordance with BS 476 Part 7 and a Class 0 fire rating when tested in accordance BS 476 Part 6. The material shall be dust and fibre free and incorporate an anti-microbial additive to prevent mould growth. The thermal conductivity shall be no greater than 0.034 W/(m·K) at 0°C and 0.038 W/(m·K) at 40°C when tested in accordance with EN ISO 8497 or EN 12667. Water vapour transmission shall be no less than 10,000 when tested in accordance with EN 12086. Resistance to bacterial and mould growth shall be no less than Class 1 when tested in accordance with EN ISO 846. The material shall be provided with a black or white PVC film pre-applied. The PVC film shall be UV resistant and waterproof. Tube material shall be supplied in 2 m lengths. Sheets shall be supplied as 2 x 0.5 m flat sheet. The material shall be black in colour with either a black or white finish. Kaiflex RT-ST High density load bearing PIR pipe sections with a Nitrile rubber facing to provide a full water vapour seal between the pipe support and the adjoining insulation. © Kaimann GmbH · Brideoak Street · Oldham · OL4 2HB · +44 (0)161 627 3289 · [email protected] · Status: 30. June 2012 S3.02 Technical Values Material Kaiflex ST Class O Kaiflex TC Temp Range -196ºC to +105ºC -10ºC to +80ºC “λ” Value W/mK at mean temp 0.034 @ 0ºC 0.036 @ 20ºC 0.034 @ 0ºC 0.036 @ 20ºC ODP Rating GWP Rating Fire Class Typical material density kg/m3 0 0 Class O 50-55 0 0 Class O 50-55 S3.03 Material Selection Shall be: Internal External Concealed Exposed Concealed Exposed Domestic Hot Water Pipe Kaiflex ST Class O Kaiflex ST Class O* Kaiflex TC Kaiflex TC Cold Water Pipe Kaiflex ST Class O Kaiflex ST Class O* Kaiflex TC Kaiflex TC Chilled Water Pipe Kaiflex ST Class O Kaiflex ST Class O* Kaiflex TC Kaiflex TC Low Temperature Heating Pipe Kaiflex ST Class O Kaiflex ST Class O* Kaiflex TC Kaiflex TC Medium Temperature Heating Pipe Kaiflex ST Class O Kaiflex ST Class O* Kaiflex TC Kaiflex TC Split Air-Conditioning Pipe Kaiflex ST Class O Kaiflex ST Class O* Kaiflex TC Kaiflex TC Ductwork Kaiflex ST Class O Kaiflex ST Class O* Kaiflex TC Kaiflex TC *See coverings selection for acceptable finishes S3.04 Material Thickness For each service the thickness of insulation applied shall not be less than that defined in the tables below. The following thickness’s shall be taken to represent reasonable provision for the control of energy loss, prevention of pipe freezing and the prevention of surface condensation. S3.04.01 Domestic Hot Water Pipe O.D Kaiflex ST Class O Kaiflex TC mm mm mm 10 13 13 12 19 19 15 19 19 22 25 25 28 25 25 35 25 25 42 25 25 54 25 25 67 25 25 76.1 25 25 88.9 25 25 Insulation Thickness © Kaimann GmbH · Brideoak Street · Oldham · OL4 2HB · +44 (0)161 627 3289 · [email protected] · Status: 30. June 2012 S3.04.02 Cold Water Pipe O.D Kaiflex ST Class O Kaiflex TC Insulation Thickness mm mm mm 10 25* 25* 12 25* 25* 15 25* 25* 22 19 19 28 9 9 35 9 9 42 9 9 54 9 9 67 9 9 76.1 9 9 88.9 9 9 *Thickness not sufficient to provide 12 hours of protection against freezing at -6°C. Insulation should be used in combination with trace heating or other frost protection measures. S3.04.03 Chilled Water 5°C Line Temperature Pipe O.D Kaiflex ST Class O Kaiflex TC Insulation Thickness mm mm mm 21.3 9 9 26.9 13 13 33.7 13 13 42.4 13 13 48.3 13 13 60.3 13 13 76.1 13 13 88.9 13 13 114.3 13 13 273 19 19 Pipe O.D Kaiflex ST Class O Kaiflex TC mm mm mm 21.3 13 13 26.9 13 13 33.7 13 13 42.4 19 19 48.3 19 19 60.3 19 19 76.1 19 19 88.9 19 19 114.3 19 19 0°C Line Temperature Insulation Thickness © Kaimann GmbH · Brideoak Street · Oldham · OL4 2HB · +44 (0)161 627 3289 · [email protected] · Status: 30. June 2012 273 19 19 Kaiflex ST Class O Kaiflex TC S3.04.04 Low Temperature Heating Pipe O.D Insulation Thickness mm mm mm 21.3 19 19 26.9 19 19 33.7 19 19 42.4 19 19 48.3 19 19 60.3 19 19 76.1 19 19 88.9 19 19 114.3 19 19 273 19 19 Kaiflex ST Class O Kaiflex TC S3.04.05 Medium Temperature Heating Pipe O.D Insulation Thickness mm mm mm 21.3 25 25 26.9 25 25 33.7 25 25 42.4 25 25 48.3 25 25 60.3 25 25 76.1 25 25 88.9 25 25 114.3 25 25 273 25 25 Pipe O.D Kaiflex ST Class O Kaiflex TC S3.04.06 Split Air-Conditioning Insulation Thickness mm mm mm 10 13 13 12 13 13 15 13 13 22 13 13 28 13 13 35 13 19 42 19 19 54 19 19 67 19 19 76.1 19 19 © Kaimann GmbH · Brideoak Street · Oldham · OL4 2HB · +44 (0)161 627 3289 · [email protected] · Status: 30. June 2012 88.9 19 19 S3.04.08 Air-Conditioning Ductwork Kaiflex ST Class O Emissivity: 0.05 Emissivity: 0.9 Insulation Thickness mm mm 19 26 S4 - Protective Coverings S4.01 – Covering Specification Materials shall be as described: Kaiflex TC Film: UV resistant PVC film. The colour shall be either white or black. All seams and joints should be covered using a matching 25 or 50 mm wide self-adhesive tape. Application should be at ambient temperatures between 10°C and 30°C and a maximum relative humidity of 75%. The Kaiflex TC surface should be free from all dust, oil, grease and other contaminants before applying Kaiflex TC self-adhesive tape. S4.02 – Covering Selection Shall be: For Kaiflex ST Class O: Internal External Concealed Exposed Concealed Exposed Domestic Hot Water Pipe None required None required or Kaiflex TC Kaiflex TC Kaiflex TC Cold Water Pipe None required None required or Kaiflex TC Kaiflex TC Kaiflex TC Chilled Water Pipe None required None required or Kaiflex TC Kaiflex TC Kaiflex TC Low Temperature Heating Pipe None required None required or Kaiflex TC Kaiflex TC Kaiflex TC Medium Temperature Heating Pipe None required None required or Kaiflex TC Kaiflex TC Kaiflex TC Split Air-Conditioning Pipe None required None required or Kaiflex TC Kaiflex TC Kaiflex TC Ductwork None required None required or Kaiflex TC Kaiflex TC Kaiflex TC S5 – Additional Details S5.01 – Water Vapour Barriers Shall be built into the insulation material itself wherever possible. The water vapour resistance factor of the insulation shall be no less than 10,000 for Kaiflex ST Class O and no less than 4,000 for Kaiflex EPDM. Along all insulation seams and joints Kaiflex Adhesive shall be applied to form a water vapour tight seal between two pieces of Kaiflex. Every 2 m and wherever insulation terminates Kaiflex shall be fixed directly to the pipe using Kaiflex Adhesive to form a water vapour tight seal. S5.02 – Insulation of Pipe Supports Wherever possible the mechanical contractor shall ensure that all pipe clamps are installed around high density load bearing insulation sections at least matching the thermal performance of the insulation on all linear pipe runs. It is the responsibility of the insulation contractor to ensure that the water vapour barrier is continuous around this load bearing section. © Kaimann GmbH · Brideoak Street · Oldham · OL4 2HB · +44 (0)161 627 3289 · [email protected] · Status: 30. June 2012 Where the mechanical contractor has installed pipe clamps directly around the pipe the insulation contractor shall note this and, if appropriate, wrap insulation of at least the same thickness as used on adjoining linear pipe runs around the pipe clamp. It is the responsibility of the insulation contractor to ensure that adhesive has been applied to form a water vapour tight seal at this point. S5.03 – Insulated Valve and Flange Cover Boxes Shall be manufactured directly from Kaiflex sheet of at least the same thickness as used on linear pipe runs following the manufacturers recommendations. The covering shall match that used on the linear pipe runs. Where possible contractors shall apply velcro strips to the valve or flange box seams. S5.04 – Fire Resistant Walls At points where pipework passes through fire resistant walls the fire resistance of the wall shall be maintained. The mechanical contractor shall be responsible for ensuring this detail and obtaining from the manufacturer all relevant test certificates. © Kaimann GmbH · Brideoak Street · Oldham · OL4 2HB · +44 (0)161 627 3289 · [email protected] · Status: 30. June 2012
© Copyright 2026 Paperzz