BID SET

2 LAYERS 6"
FIBERGLASS INSUL.,
INSTALL PERPENDICULAR
TO STRUC. GRID
3/8" GYP. BD. SCREW
FASTEN TO MTL JOISTS
ACOUSTICAL SEALANT
PERIMETER MTL TRIM
JOINT CLOSER.
TYPICAL DATA, TELE., ELEC.
OUTLET BOX W/ CONDUIT
RUN TO TOP OF PARTITION;
SEAL BETWEEN OUTLET BOX
AND GYP. BD.
INTERIOR CORRIDOR & TENENT 1-HR
SEPARATION PARTITION U432
INTERIOR CORRIDOR
SECTION @ CLASSROOM
CLASSROOM
Site Design
Space Planning
Interior Design
1.5-HR RATED HM
DOOR AND FRAME
REVISIONS
PHASE 3
FUTURE
CONSTRUCTION
CORRIDOR
097
CORRIDOR
097
TYPICAL DATA, TELE., ELEC.
OUTLET BOX W/ CONDUIT
RUN TO TOP OF PARTITION;
SEAL BETWEEN OUTLET BOX
AND GYP. BD.
15# FELT MOISTURE
BARRIER BETWEEN MTL
& SLAB
1'-6"
PERIMETER ACOUSTICAL
SEALANT EACH SIDE
5/8" GYP. BD.; FASTENED TO STL
3-5/8" STUDS @ 24 INCHES O.C.;
W/ 3 INCH FIB. GL. ACCOUSTIC
INSULATION, AND 5/8" FIN. GYPSUM
BD; TAPED & SPACKLED.
STL FABRICATED STANDARD
DOUBLE TIER LOCKERS EQUAL
TO THOSE AS M,ANUF. BY
'REPUBLIC' OF CANTON, OH.
4" VINYL BASE TYPICAL
PERIMETER ACOUSTICAL
SEALANT EACH SIDE
CLASSROOM
10'-0"
12'-0"
CORRIDOR
10'-0"
CLASSROOM
1'-6"+
ACOUSTICAL SEALANT
NOTE TO CODE OFFICIAL:
EXISTING PARTITION IS A 1-HR TENANT
SEPARATION PARTITION TO BE FULLY
UPGRADED TO BE A 2-HR SEPARATION
PARTITION IN PHASE-3 CONST.
'J'- BEAD
CONTINUOUS BENT METAL SUPPORTING BASE
TRIM, AS PROVIDED BY OR RECOMMENDED BY
LOCKER MANUFACTURER. FASTEN TO CONC.
AT 32 INCHES O.C. MAX.
CONTINUOUS TREATED 2 X 6
SUPPORT BLOCKING, SCREW
FASTEN TO STUDS
INTERIOR LOCKER
SECTION @ CLASSROOM
2-HR FIRE WALL SECTION
@ 1.5-HR RATED DOOR
COMPLETED EXISTING
2-HR FIRE WALL SECTION
1/4"MIN.
1/4"±
1'-6"
1'-2"
5/8" GYP. BD.;
FASTENED TO STL 3-5/8"
STUDS @ 24 INCHES
O.C.; W/ 3 INCH FIB. GL.
ACCOUSTIC INSULATION,
AND 5/8" FIN. GYPSUM
BD; TAPED & SPACKLED.
18 GA 8 INCH STL STUD
HEADER OVER OPENING
0'-7"
4'-521"
0'-7"
3'-10"
LINE OF PARTITION
ABOVE
7'-8"
15'-1"
CORRIDOR
CLASSROOM
0'-7"
+-4'-521"
0'-7"
05 NOV 2014
Project # :
BID SET
CORRIDOR LOCKER ALCOVE
2-HR FIRE WALL PLAN
@ 1.5-HR RATED DOOR
REVISION 24 NOV14
1'-2"
0'-4"
Issue Date:
1/4"MIN.
REVISION 24 NOV14
TYPICAL CLASS RM /
CORRIDOR SECTION
ACOUSTICAL SEALANT
PLASTIC LAMINATE
SDHEARED TO 3/4" PLY
WD. SHELF
DBL. 8 INCH STL
800S162-97 STUD
HEADER OVER OPENING
CORRIDOR
4" VINYL BASE TYPICAL
1'-6"
ACOUSTICAL SEALANT
10'-0"
10'-0"
CEILING HEIGHT
12'-0"
T.O. STUD
CLASSROOM
TYPICAL DATA, TELE., ELEC.
OUTLET BOX W/ CONDUIT
RUN TO TOP OF PARTITION;
SEAL BETWEEN OUTLET BOX
AND GYP. BD.
FACE LAYER
TYPE 'X' GYP. BD. APPLIED RIGHT ANGLES OR
PARALLEL TO EA. SIDE OF STL. STUD W/ 1- 85"
TYPE 'S' SCREWS @12" O.C.
JOINTS TO BE STAGGERED 24" EA. LAYER & EA.
SIDE. SOUND TESTED W/ 3-21" FRICTION FIT
CAVITY INSULATION.
(STC 55-59)
1
2"
CORRIDOR
NEW
PHASE-3
CORRIDOR
NOTE TO CODE OFFICIAL:
EXISTING PARTITION IS A 1-HR TENANT
SEPARATION PARTITION TO BE FULLY
UPGRADED TO BE A 2-HR SEPARATION
PARTITION IN PHASE-3 CONST.
BASE LAYER
RESILIENT CHANNELS 24" O.C. ATTACHED AT
RIGHT ANGELS TO ONE SIDE W/ 21" TYPE 'S'
SCREW EA. STUD, 21" TYPE 'X' GYP. BD. APPLIED
PARALLEL OR AT RIGHT ANGLES TO EXISTING
STL. STUDS @24" O.C. W/ 1" TYPE 'S' SCREWS
@24" O.C.
3/8" GYP. BD. SCREW
FASTEN TO MTL JOISTS
6" STEEL STUDS @
2'-0: O.C.W/ HORIZ.
BRACING AS NEEDED
W/ 5/8" TYPE X GYP. BD.
SCREWED TO EA. SIDE
OF SSMA
600S-125-33 STUDS
@ 6 INCHES O. C.; W/
3" THK ACCOUSTICAL
FIB. GL. UNFACED
INSUL.
5/8" GYP. BD.; FASTENED
TO STL 5-5/8" STUDS @ 24
INCHES O.C.; W/ 3 INCH
MINERAL WOOL CAVITY
INSULATION, AND 5/8" FIN.
GYPSUM BD; TAPED &
SPACKLED.
U411
UL R1319-141-145
2-HR FIRE RATED SEPARATION PARTITION,
2 LAYERS 6" MINERAL
WOOL INSUL., INSTALL
PERPENDICULAR TO
STRUC. GRID
10'-0"
3/8" GYP. BD. SCREW
FASTEN TO MTL JOISTS
1'-6"
3/8" GYP. BD. SCREW
FASTEN TO MTL JOISTS
FACE LAYER
TYPE 'X' GYP. BD. APPLIED RIGHT ANGLES OR
PARALLEL TO EA. SIDE OF STL. STUD W/ 1- 85"
TYPE 'S' SCREWS @12" O.C.
JOINTS TO BE STAGGERED 24" EA. LAYER & EA.
SIDE. SOUND TESTED W/ 3-21" FRICTION FIT
CAVITY INSULATION.
(STC 55-59)
1
2"
Residential
Office / Commercial
Lt. Industrial
2 LAYERS 6" FIB. GL.
INSUL., INSTALL
PERPENDICULAR TO
STRUC. GRID
SUSPENDEED CEILING
PANEL & GRID SYSTEM
BASE LAYER
RESILIENT CHANNELS 24" O.C. ATTACHED AT
RIGHT ANGELS TO ONE SIDE W/ 21" TYPE 'S'
SCREW EA. STUD, 21" TYPE 'X' GYP. BD. APPLIED
PARALLEL OR AT RIGHT ANGLES TO EXISTING
STL. STUDS @24" O.C. W/ 1" TYPE 'S' SCREWS
@24" O.C.
NEW 85" TYPE 'X' GYP. BD. ADDED TO EXISTING;
SCRW TO EXISTING STL STUDS W/ 1-5/8" TYPE 'S'
SCREWS @12" O.C. JOINTS TO BE STAGGERED 24"
EA. LAYER
6'-6"
2 LAYERS 6" FIB. GL.
INSUL., INSTALL
PERPENDICULAR TO
STRUC. GRID
U411
UL R1319-141-145
2-HR FIRE RATED SEPARATION PARTITION,
NEW 58" TYPE 'X' GYP. BD. ADDED TO EXISTING;
SCRW TO EXISTING STL STUDS W/ 1-5/8" TYPE 'S'
SCREWS @12" O.C. JOINTS TO BE STAGGERED 24"
EA. LAYER
U432: 5/8" LAYER OF
TYPE FRX GYP. BD.
FASTEN TO STEEL
STUDS @ 16" O.C.
3527 Williamson Ave., Borough of Brookhaven, Delaware County, Pa, 19015 Ph.: 610-490-9987 E-mail [email protected]
Registered Architect
U432: 5/8" LAYER OF
TYPE FRX GYP. BD.
FASTEN TO STEEL
STUDS @ 16" O.C.
14 : 007
Wall Sections
Title :
A10
Sheet:
12 of 16