D01502GB0 02-2006 Intellia EPP-20 and EPP

Intellia EPP-20 and EPP-21 Manual Call Points for FX fire detection system
Addressable call points EPP-20 and EPP-21 are used in
addressable ESMI FX fire detection system.
The Intellia series of products are all compatible with the
ALC-board of an FX-panel.
EPP-20 and EPP-21 call points have in built isolation
and EPP products can be installed either flush or surface
mounting.
The address of the EPP-20 and EPP-21 is changed easily
with DIL-switches.
Call points can be tested and resetting with the test key.
EPP-20, EPP-21
Certificates
Technical data
The MCP5 manual call points are tested and certified
according to the Construction Products Directive.
The applied standard is EN54-11:2001/A1.
MANUAL CALL POINT
Mechanical Installation
Flush mount call point is installed directly into the unit
box.
Surface mounted call point is installed into a separate
surface mounting box with one terminal (SR1T-2G) or a
surface mount box (SR2G) and terminal block.
27,5
32
Dimensions
- flush
- surface
Weight
Colour
Operating Temperature
Humidity
Nominal Voltage
Standby Current
Alarm Current
Connectors
Enclosure Class
Tested
93 x 89 x 27,5 mm
93 x 89 x 52 mm
100 g
Red, RAL 3001
-30°C ... +55°C
0 … 95%
24 VDC
300 μA
5 mA
Max 2.5mm2 cable
IP24D
EN54-11
89
93
SURFACE MOUNTING BOX SR1T-2G
Manual call
point
Surface mounting
box SR1T-2G
100 mm free space has to be left below the call point.
Dimensions
- flush
- surface
Weight
Colour
Terminals
Mounting Holes
Inlet in back side
Inlet on lower side
(to be pierced for cable)
Protection Class
ESMI product code
87 x 87 x 32 mm
93 x 89 x 52 mm
90 g
Red, RAL 3001
1 pcs. (for continuation of
the cable shield)
60 mm
1 pc., Ø 20 mm
2 pc., Ø 6 mm
IP 24D
06424310
ESMI product codes
EPP-20
- breakable glass, EN- version,
EPP-21
- flexible element, EN- version,
D01502GB0
06723732
06723735
02-2006
Electrical Installation
SURFACE MOUNTING
FX ALC addressable loop
EPP-20, EPP-21
Address switch
L+ = Loop input +
L+ = Loop output +
L- = Loop input –
L- = Loop output –
Note:
L+ and L- are polarity sensitive.
0
1
1 2 3 45 6 7
L+ L+ L- L-
Surface
mounting box
FLUSH MOUNTING
EPP-20, EPP-21
L+ = Loop input +
L+ = Loop output +
L- = Loop input –
L- = Loop output –
Address switch
0
1
1 23 45 6 7
Note:
L+ and L- are polarity sensitive
L+ L+ L- L-
FX ALC addressable loop
D01502GB0
2
02-2006
Accessories
MANUAL CALL POINT COVER – PS200
REPLACEMENT GLASS ELEMENT – KG1
Transparent hinged cover for call point.
Material
Resetting function
Glass elements in package
ESMI product code
Plastic covered glass
Glass must be replaced
20 pcs
06424900EN
Cover dimensions
Weight
ESMI product code
REPLACEMENT FLEXIBLE ELEMENT – PS210
90 x 104 mm
35 g
06424502
SPARE TEST KEYS – SC017
For testing and resetting EPP-20 and EPP-21 manual call points
Test keys in package
10 pcs
ESMI product code
06424510
Material
Resetting function
Elements in package
ESMI product code
Plastic
Test & Re-set facility
20 pcs
06424920
Esmi reserves the right to modifications.
D01502GB0
3
02-2006
TO TEST
TO REPLACE GLASS/RESETABLE ELEMENT
TO RESET
D01502GB0
4
02-2006