MISO MOD-033-1 Model Validation Process Version 1.0 June 1, 2017 i DOCUMENT REVISION HISTORY Changes (additions, modifications, deletions) made to this document are recorded in the table below. Revision date June 1, 2017 MISO Version, Section & Title Version 1.0 Summary of Changes Initial version Authors Approver Nihal Mohan, Cody Doll David Duebner ii Contents 1 2 a) Purpose ............................................................................ Error! Bookmark not defined. b) Scope of validation ........................................................... Error! Bookmark not defined. R1.1 Power Flow Model Validation ..................................................................................... 3 1.1 Select a scenario ......................................................................................................... 5 1.2 Data Acquisition ........................................................................................................... 5 1.3 Adjust Planning Case to Match S.E. Case ................................................................... 5 1.4 Evaluate model performance per R1.3 guidelines ........................................................ 7 1.5 Resolve differences per R1.4 guidelines ...................................................................... 7 1.6 Document the power flow model validation .................................................................. 7 R1.2 Dynamics Model Validation ........................................................................................ 8 2.1 Selection of Local Dynamic Event ...............................................................................10 2.2 Data Acquisition ..........................................................................................................10 2.3 Prepare a dynamic model and simulate event.............................................................11 2.4 Evaluate dynamic model performance per R1.3 guidelines .........................................11 2.5 Resolve differences per R1.4 guidelines .....................................................................11 2.6 Document the model validation ...................................................................................11 3 R1.3 Guidelines to use to determine unacceptable differences in performance under R1.1 and R1.2 ...................................................................................................................................12 4 R1.4 Guidelines to resolve unacceptable differences .........................................................13 4.1 5 Applicable NERC Standards .......................................................................................14 Data acquisition from RC and TOP per requirement R2 .....................................................16 Appendix A. Case Preparation and Sanity Checks Guidelines .............................................17 Appendix B. Contacts for obtaining information and data .....................................................18 Appendix C. NERC Standard References ............................................................................21 NERC Standard MOD-026-1 .................................................................................................21 NERC Standard MOD-027-1 .................................................................................................21 NERC Standard MOD-032-1 .................................................................................................22 NERC Standard IRO-010-2 ...................................................................................................22 Appendix D. Sample Request for Verification .......................................................................24 Appendix E. Reference Documents ......................................................................................25 MISO i Introduction Pursuant to requirement R1 of MOD-033-1, this document describes MISO’s model data validation process. There are five sections in this document describing in detail the following requirements per MOD-033-1 standard: Section 1: describes MISO’s process for performing R1.1 comparison of the performance of planning power flow model to actual system behavior. Section 2: describes MISO’s process for performing R1.2 comparison of the performance of planning dynamic model to actual system behavior. Section 3: describes the guidelines MISO shall use to determine unacceptable differences in model performance per part R1.3 of the MOD-033-1 standard. Section 4: describes process which MISO shall use to resolve the unacceptable differences to fulfill requirement R1.4. Section 5: describes process which MISO shall follow to obtain data from Reliability Coordinators (RC) and Transmission Operators (TOP) per requirement R2. A high level overview of MOD-033 overall process is described below: Start Select a scenario • Obtain real time data (R2) Prepare models, run simulations • Section 1 and 2 (R1.1,R1.2) Evaluate model performance • Section 3(R1.3) Address differences • Section 4(R1.4) Stop Figure 1-1 High level overview of MOD-033 process The scope of validation is limited to MISO’s Planning Coordinator (PC) functional area. MISO will select dynamic local events for validation based on criterion described in Section 2. A list of quantities which shall be used for validation purposes are described in Section 3. MISO shall notify the equipment owners in MISO of model performance issues; to correct the component model is the responsibility of the model data owner, as described in Section 4. Model performance issues caused by model data outside of MISO’s planning coordinator area will be identified though resolution of those model data issues is outside of scope. MISO may provide model concerns to external parties for their consideration. MISO 2 1 R1.1 Power Flow Model Validation Per part 1.1 of requirement R1, this section documents the process to compare the performance of steady state planning model to actual system behavior. R1.1. Comparison of the performance of the Planning Coordinator’s portion of the existing system in a planning power flow model to actual system behavior, represented by a state estimator case or other Real-time data sources, at least once every 24 calendar months through simulation; A high level overview of the process is shown in Figure 1-1 Power flow model validation. The Planning Coordinator swim lane on top describe the tasks performed by MISO as a planning coordinator and the swim lanes below describes data to be provided by MISO as an RC and the TOPs tasks per requirement R2 of the standard. MISO 3 Figure 1-1 Power flow model validation MISO 4 1.1 Select a scenario For steady state model validation per part R1.1, MISO shall validate a summer peak planning model utilizing State Estimator (S.E.) data for the system peak loading condition or near peak loading condition. 1.2 Data Acquisition 1. Obtain Planning Model: request Outage Coordination group to provide Outage Coordination Daily Base case (OCDB) for summer peak day. There are several advantages of using Outage coordination daily base case planning model. It is developed from Model On Demand (MOD) planning model database with relevant projects applied and known outages for MISO and external entities modeled. The Load and Generation profiles are obtained from NERC SDX system, which more closely match S.E. model. These models are internally vetted through multiple reviews. 2. Obtain State Estimator model: request EMS Network Modeling group to provide the State Estimator model for the system condition being studied. 3. Obtain Equipment Mapping Sources: Obtain S.E. model to planning model mapping. The IDC and MISO commercial node mapping (EP node mapping) to map S.E. case to planning case posted on EMS model section on MISO extranet can be used.1 1.3 Adjust Planning Case to Match S.E. Case 1. Area Names Mapping: MOD planning base case may utilize different area names for some entities compared to S.E. case. The area names are mapped to resolve differences. The planning case has area names changed to match S.E. case. 2. Generation dispatch: Utilizing the mapping sources, generation dispatch in planning model should be modified to match the system conditions from real-time data sources. 3. Load: scale the loads in planning model to match the total system MW and Mvar in S.E.2 case for each Local Balancing Area (LBA). Loads denoted as non-scalable in the models will not be scaled The approach for mapping load and generation is shown in Figure 1-2. For all the buses which exist in both Planning and S.E. models (mapped buses), perform scaling on individual bus levels so that bus level values match. Perform scaling such that following equations 1 https://extranet.misoenergy.org/EMSModels/Pages/EMSModels.aspx . NDA and access privileges required. 2 Pay attention to pseudo-injections of loads at buses for solution convergence by S.E software. If S.E. solution is not realistic, contact EMS Modeling. Data from other real-time sources such as PI historian or SCADA may also be used. MISO 5 hold true on area level. If necessary, individual substation load and generation values may be adjusted:3 Total in Planning Model = B+C MW/ Mvar4 A = C MW/Mvar4 Where: A = Sum total of unmapped quantity in Planning Model B = Sum total of mapped quantity in Planning Model and S.E. model C = Sum total of unmapped quantity in S.E. model Figure 1-2 MISO Load and Gen mapping approach 4. Generator scheduled voltage: The generator scheduled voltage in planning case should be adjusted to match the EMS case. 5. Transformer tap positions (fixed and adjustable): Adjustable LTC transformer taps in the planning case may be adjusted to match the EMS case. Fixed taps cannot be adjusted automatically or remotely and are rarely moved. The position/status of these fixed taps should be compared and any differences found should be noted and resolved. 6. Switched shunts status/position: Switched shunts in planning model should be adjusted to match the EMS case. The position/status of fixed shunts, that cannot switch on or off automatically and are not remotely controlled by an operator, should be compared and any differences noted and resolved. 7. Area interchange: Adjust the interchange data in the planning case to match the S.E. real-time case. 3 4 Python script “MOD33MappingTool.py” developed by System Modeling for initial mapping may be used. For generator mapping, only MW amounts are matched. MISO 6 8. Manual case adjustments: Set the HVDC schedules in planning model for GRE Coal Creek, Square Butte, Manitoba Hydro HVDC links and Mackinaw VSC based on S.E. model. 5 Adjust Minnesota Power’s industrial large motor loads 6 that are modeled as generators in planning case. 9. Model outage facilities consistently: The facility outages in S.E. case need to be applied to be the planning case. If starting planning model is not an Outage Coordination Daily case, then Control Room Operation Window (CROW) outages may be requested from Outage Coordination group. 10. Perform model tuning and sanity checks: The planning model should be solved and reviewed to obtain satisfactory performance. If there are any major issues7 identified, responsible groups should be contacted to resolve the issues. For example, differences in transmission lines and transformer topology should be resolved. Contact Real Time Operations, EMS modeling to compare planning assumptions and operating practices for bus splits, normally open switches, radial lines, etc. Differences in topology will be reviewed. Differences due to Node-Breaker vs. Bus-Branch in planning do not need to be resolved. 1.4 Evaluate model performance per R1.3 guidelines The guidelines for evaluating model performance are described in Section 3.8 It is important to note that engineering judgment must be used in application of the guidelines. 1.5 Resolve differences per R1.4 guidelines If portions of the planning model are found outside the guidelines specified in R1.3, follow the guidelines per Section 4 to resolve the differences. 1.6 Document the power flow model validation Results and communications for R1.4 and R2 will be documented. Differences in model parameters that were identified in the previous steps will be documented, if they are expected to be accurately represented in the planning case. Some items may vary slightly due to differences between node-breaker modeling and bus-branch modeling that do not need to be reconciled as they are electrically equivalent. 5 Step number 5 can be omitted for dynamic event validation, if the event is far from these regions. Note that mapping HVDC and VSC equipment can cause solution convergence issues. 6 Refer MOD-033 mapping workbook “MOD-033_EMS to IDC Equipment Mapping.xlsx” to perform manual adjustments. 7 Attention should be paid to the list of issues are identified in 0, during application of guidelines. 8 Can utilize Python based script “MISOModelValidation_100416.py” for model review to evaluate the quantities. MISO 7 2 R1.2 Dynamics Model Validation Per part 1.2 of requirement R1, this section documents the process to compare performance of dynamic planning model to actual system behavior. R1.2. Comparison of the performance of the Planning Coordinator’s portion of the existing system in a planning dynamic model to actual system response, through simulation of a dynamic local event, at least once every 24 calendar months (use a dynamic local event that occurs within 24 calendar months of the last dynamic local event used in comparison, and complete each comparison within 24 calendar months of the dynamic local event). If no dynamic local event occurs within the 24 calendar months, use the next dynamic local event that occurs; This section describes the process for dynamic model validation in detail. A high level summary of the methodology is as following: select suitable event(s) against which system model response will be validated; determine what real-time measurement information is available such as Phasor Measurement Unit (PMU) or Dynamic Disturbance Recorder data; Obtain real time pre-contingency event conditions and prepare a steady state model by following procedure laid out in Section 1.3. Thereafter perform dynamic model validation. The dynamic model validation process is show in Figure 2-1 below. MISO 8 Figure 2-1 R1.2 Dynamic model validation process MISO 9 2.1 Selection of Local Dynamic Event The following dynamic events shall be considered. 1. Transmission system faults– three-phase, single-phase, multi-phase, normal or delayed clearing, or other low voltage conditions on the transmission elements, including lines or autotransformers 2. Transmission line switching (including opening and closing) without a fault 3. Generating unit(s) tripping or oscillating 4. HVDC tripping or run backs 5. AC or DC controls (mis)operations 6. Planned or unexpected large load tripping, load shedding 7. Large FACTS device switching, failure, or operation 8. System islanding or loss of synchronism 9. Other large system swings exhibiting voltage or frequency fluctuations, particularly with low damping ratio and high amplitude 10. Large system events with significant changes in frequency, voltage or MW values. Event selection will depend on availability of proper disturbance monitoring/recording data. Following event types which are not suitable for MOD-033-1 validation due to limitations in the simulation tools will not be selected: 1. Asymmetric events such as sustained unbalanced flows such as single pole reclosing 2. An event that occurred at the top of the hour when generating units are ramping up or down. In study simulation, during the initialization process, it is assumed that all generating units are static with fixed outputs, but over the course of the simulation timeframe which typically lasts 60 to 120 seconds, some of the units may ramp up or down. 2.2 Data Acquisition Once a dynamic local event is selected, the following data may be acquired: Data that should be acquired: 1. S.E. pre-contingency case from MISO EMS modeling 2. Sequence of event logs from Real Time Operations, Transmission Operators 3. PMU recordings for the event from Real Time Operations or Dynamic Disturbance Recording data 4. MISO dynamic data files from System Modeling group Optional data may be acquired when necessary: 1. PI historian data, SCADA information, Frequency Response Tool data9 2. OCDB planning case for event date from Outage Coordination group Refer Appendix B for details on contact information. 9 PI historian, SCADA data, Frequency Response Tool Data to be acquired if necessary, for example model validation for frequency excursion event. MISO 10 2.3 Prepare a dynamic model and simulate event 1) Set up the power flow case as described above in Section 1. The planning power flow case will be prepared to represent the pre-disturbance system representation. 2) Obtain MISO dynamic data and prepare dynamic model: Post development of the power flow model, obtain latest MTEP model dynamic data and prepare a dynamic model. 3) Creation of Sequence of Events File: Prepare a dynamic disturbance file which adequately describes the sequence of events. 4) Create channels for monitoring the quantities: proper quantities (such as MW and Mvar out of a generating unit, Mvar output of a dynamic reactive device, MW and/or Mvar flows, frequency on a transmission element, voltage magnitudes at major buses) should be monitored when setting up the dynamic simulation. 5) Run the dynamic simulation: run dynamic simulation duration for 10 to 20 seconds. For longer duration dynamic simulations slow acting responses from devices such as AGC, tap-changers, capacitor responses would need to be accounted for. 2.4 Evaluate dynamic model performance per R1.3 guidelines Once the simulation has been run, a comparison of the dynamic simulation results to the actual dynamic system event data will be made. For details on the parameters to compare and what is acceptable performance of this comparison, see Section 3. It is important to note that engineering judgment must be applied in application of the guidelines. Sample buses, branches close to event location should be selected for application of these guidelines. 2.5 Resolve differences per R1.4 guidelines If the planning model performance does not compare to actual system behavior per R1.3 guidelines, follow the guidelines per Section 4 to resolve the differences. 2.6 Document the model validation Charts, results, communications for R1.4 and R2 will be documented. Differences in model simulations that were identified in the previous steps will be documented. Dynamic model validation will focus on system near the dynamic local event. MISO 11 3 R1.3 Guidelines to use to determine unacceptable differences in performance under R1.1 and R1.2 This section describes guidelines which MISO will use to determine unacceptable differences per part 1.1 and 1.2 of requirement R1. R1.3 Guidelines the Planning Coordinator will use to determine unacceptable differences in performance under Part 1.1 or 1.2; and MISO will use engineering judgment to evaluate planning model performance. To facilitate the evaluation, MISO will use review teams comprised of Subject Matter Experts (SME) and management to decide when performance outside the guidelines are acceptable. Table 3-1 lists guidelines which will be used to determine differences in performance for the steady-state model validation (R1.1) that require review. MISO may choose some of the parameters from Table 3-1 in for evaluation of model performance. The items in Table A-1 should be considered for case preparation of the model during the application of the R1.3 guidelines. Table 3-1 provides evaluation criterion, both for percentage differences and absolute differences for the real and reactive power flows to be applied on major transmission facilities as determined by PC. For bus voltages, per unit values will be compared on a percentage basis. For example, 1.02 p.u. in S.E. model, 0.98 pu in planning model is 4% difference. Loadings may be compared on percentage difference or an absolute difference. The reference for difference calculation is real-time data source. For nonzero impedance lines, the branch flow can normalized based on branch normal continuous ratings (Rate A) and % difference should be examined. For example, a line rated for 845 MVA loaded at 211 MVA in S.E. case is at 25% normal continuous ratings and same circuit loaded at 279 MVA in Planning case is at 33% of the normal continuous ratings. The difference in percentage normal loading is equal to 8%. This matrix is capable of accounting the combined impact of real and reactive flows on the line, irrespective of line normal ratings and kV class. Quantity Bus voltage magnitude Acceptable Differences ±2% (>346 kV) ±3% (200>kV>345kV) ±4% (100>kV>199kV) Generating Bus voltage magnitude ±2% MVA Current flow ±10% or ±100 MVA Difference in % normal loading ±10% on branch normal continuous rating Table 3-1 Guidelines to identify acceptable differences between simulated and real time data for steady state validation MISO 12 Dynamic model performance guidelines: In accordance with NERC MOD-033 application guidelines,10 to determine the unacceptable dynamic model performance, MISO will plot the simulation result on the same graph as the actual system response, and the two plots will be given a visual inspection to see if they look similar or not. MISO subject matter experts (SME) will determine if the model performance is acceptable. 4 R1.4 Guidelines to resolve unacceptable differences Per requirement R1.4, each Planning Coordinator must have guidelines to resolve the unacceptable differences in performance between the power flow model to actual system behavior or existing system planning dynamic model to actual system response. MISO shall utilize applicable NERC MOD Standards, IRO-010 standard and MISO tariff provisions to ask equipment and data owners to resolve differences. This section describes process through which MISO shall use to determine unacceptable differences per part 1.3 per requirement R1.4. A high level process for R1.4 is described in Figure 4-. R1.3. Guidelines to resolve the unacceptable differences in performance identified under Part 1.3 “Guidelines for the dynamic event comparison may be less precise. Regardless, the comparison should indicate that the conclusions drawn from the two results should be consistent. For example, the guideline could state that the simulation result will be plotted on the same graph as the actual system response. Then the two plots could be given a visual inspection to see if they look similar or not”, page 9 of 11, MOD-033 application guidelines 10 MISO 13 Per R1.3 evaluations, MISO will send out letter to data owner citing the issue Data owner to review the information, determine corrections • TP to contact GO if issues found in generator model. Cite MOD-026 for exciter, MOD-027 for governor issue, MOD-032 for other issues • GO to review information, perform model correction or validation if required. Interim model can be provided by GO, if GO needs time perform model validation Data owner responds to MISO Figure 4-1 R1.4 process to resolve unacceptable differences 4.1 Applicable NERC Standards Model or equipment Steady state model Applicable NERC Standard, Document MOD-032 IRO-010 Comment NERC MOD-032 enables for the Planning Coordinator to call for reviews of steady state and dynamic data as listed in Attachment 1 of the standard. NERC MOD-032 applies to generators that meet the NERC registration criteria under the Bulk Electric System definition (i.e. greater than 20 MVA for a single unit or greater than 75 MVA aggregate generation connected at 100 kV or above). MISO as Reliability Coordinator shall use applicable provisions of IRO-010 to obtain data required for data validation. MISO 14 Dynamic Model MOD-032 Table 4-1 MISO will requests dynamic model updates made with reference to MOD-032 to concerned TP. TP should contact GO and references to MOD-026 or MOD-027 while requesting model updates.11 Applicable NERC Standards resolving unacceptable differences 11 MISO is not registered as Transmission Planner (TP) for NERC MOD-026 and MOD-027. The TP under MISO PC function should exercise NERC MOD-026 and MOD-027 provisions. NERC MOD-026 requires the Generator Owner to verify generator excitation system or plant volt/var control function models and the parameters used in simulations for the Transmission Planner. When simulations do not match actual real time data then the Transmission Planner, under Requirement R3 can request that the Generator Owner verify the excitation system model and parameters. The Generator Owner must then provide a written response with the technical basis for maintaining the current model, model changes or a plan to provide verification in accordance with the standards R2 requirement. NERC standard MOD-027 is similar to MOD-026 except that it requires verification of the governor and associated functions. Under NERC MOD-026 and MOD-027, Generator Owners may have a long term plan to validate models. In many cases it will be better to use an “interim model” based on a parameter update that can be determined from disturbance data. NERC MOD-026 and MOD-027 Requirement R2 support the use of measured system disturbance data to provide interim parameters for the model. MISO 15 5 Data acquisition from RC and TOP per requirement R2 Requirement R2 of MOD-033 requirement states: R2. Each Reliability Coordinator and Transmission Operator shall provide actual system behavior data (or a written response that it does not have the requested data) to any Planning Coordinator performing validation under Requirement R1 within 30 calendar days of a written request, such as, but not limited to, state estimator case or other Realtime data (including disturbance data recordings) necessary for actual system response validation. MISO is NERC registered Reliability Coordinator, Transmission Operator and Planning Coordinator. Requirement R1 shall be performed by MISO planning coordinator and requirement R2 shall be fulfilled by RC and applicable TOP members. MISO Planning has identified the sources of information required for steady state and dynamic model validation and described them in Sections 1 and 2 and will request data from referenced departments. The contact information for referenced departments is mentioned in Appendix B. Data EMS S.E. case PI Historian Data EMS to Planning Mapping Frequency Response Tool Score Card Synchrophasor Data Dynamic DR/ DFR data13 Sequence of Event Outage Information Outage Coordination Daily Base case Required for Steady State Validation Steady State Validation, Dynamic Validation Mapping the topology, load, generation and other quantities Dynamic Model Validation Dynamic Model Validation Provided by MISO EMS Modeling MISO Real Time Engineering Support Format PSSE .raw format Importable in Microsoft Excel EMS Modeling MISO Text, Microsoft Excel, PDF MISO Shift Operations Microsoft Excel MISO Real Time Engineering Support, TOP in MISO Regions TOP in MISO Regions Per unit, Positive sequence data , Text, CSV or Microsoft Excel12 Per unit, Positive sequence data13 Log files, text, email. Dynamic Model Validation Dynamic Model MISO RC, TOP in MISO Validation, Steady Regions State Validation Steady State Validation , Dynamic Model MISO Outage Validation Coordination group Steady State Validation (CROW) , Dynamic Model Validation Table 5-1 list of data required from RC and TOP Outages Mapped to PSSE models PSSE .raw or .sav format End of procedure. Reference materials provided in Appendices. 12 If positive sequence data is not available, then MISO would require the process and information to convert it in positive sequence 13 If available with TOP and RC MISO 16 Appendix A. Case Preparation and Sanity Checks Guidelines The items in Table A-1 should be considered for case preparation of the model during the application of the R1.3 guidelines. Dynamic model check Generator related dynamic modeling data FACT device dynamic modeling data Bus voltage magnitude Real power flow Reactive power flow Dynamic model preparation Perform sanity checks such as no-disturbance simulation which produce flat lines; ring-down test, namely apply and remove a temporary fault without tripping any element should produce traces that initially oscillate but damp out acceptably If the actual system response is measured at or near a generating facility with more than one unit in service during the dynamic local event, the generator related dynamic modeling data should be closely reviewed. For instance, if the voltage response does not match, the excitation system, including power system stabilizer if equipped, should be reviewed. The Power System Stabilizer status for units nearby could play a key role in this effort. If the actual system response is measured at or near a FACTS device, the dynamic modeling data of the FACTS device should be reviewed. Power flow model preparation Verify that the generation should be modeled as gross instead of net values Verify capacitors and reactors are set correctly Verify that all state estimator loads are accounted for Ensure the state estimator’s extraneous loads are not modeled Verify the polarity of all state estimator loads (e.g. some loads are actually sources due to PV generation) Verify that the network configuration is modeled appropriately based on circuit breaker and switch status (e.g. does a bus need to be modeled as a split bus due to an open circuit?) Verify that the modeled line and transformer impedances are consistent Verify the no-load tap changers are modeled appropriately for all transformers Verify that all planned and forced outages are modeled appropriately Consider whether PI data should be used where state estimator data is questionable Consider whether differences are due to measurement error Verify HVDC systems are appropriately configured Table A-1 Case preparation Guidelines MISO 17 Appendix B. Contacts for obtaining information and data Information Required/ Questions Planning Models Concerned Department Contact Person(s) Contact Information MISO System Modeling David Duebner, Manager; Cody Doll; David Kapostasy; [email protected]; Outage Coordination Daily Basecase MISO Outage Coordination Scott Turner, Manager Abiodun Olayiwola; Michael Catlin; Outage Coordination Inbox [email protected]; [email protected] ; [email protected]; [email protected] ; EMS State Estimator case (S.E.) EMS S.E. to IDC Mapping IDC Models MISO Model Engineering, Modeling & Market Engineering MISO Seams Administration Amanda Schiro, Manager Teneka Jackson [email protected] ; [email protected]; Ron Arness, Manager; Prasad Shinde; Christine Ross; [email protected] [email protected]; [email protected]; [email protected]; Synchrophase rs Data (PMU) MISO Operations Tools & Processes Kristian Ruud, Manager; Kevin Frankeny; Keith Mitchell; Blake Buescher; [email protected] ; [email protected] ; [email protected] ; [email protected]; Dynamic Event MISO Real Time Operations FNET System (Non MISO) MISO Shift Operations, Standards Compliance & Strategy Raja Thappetaobula; [email protected] ; Prof Dr. Yilu Liu [email protected] Steve Swan Terry Bilke, [email protected] CROW Mapping Frequency Response Tool Score Cards [email protected] [email protected]; [email protected] ; Table B-1 MISO Contacts for obtaining information and data For requirement R2, information can be requested from the following parties: MISO 18 MISO Member Transmission Operator Contact Information for MOD-033-1 Transmission Operator Name Name Email ALLETE, Inc. (Minnesota Power, Inc.) Ruth Pallapati [email protected] Ameren Services Company Jason Genovese [email protected] American [email protected] Transmission Curtis Roe Company, LLC Robert Krueger [email protected] Ames Municipal Electric System Lyndon Cook [email protected] Big Rivers Electric Corporation Chris Bradley [email protected] Board of Water, Electric, and Communications Trustees of the City Lewis Ross [email protected] of Muscatine, Iowa Omer Vejzovic [email protected] City of Springfield, Illinois (Office of Public Utilities) Aaron Sullivan [email protected] Cleco Power LLC Chris Thibodeaux [email protected] Columbia, Missouri, City of (Water & Light Dept.) Armin Karabegovic [email protected] Consumers Energy Company Robert Vermurlen [email protected] Cooperative Energy (formerly SMEPA) Jason Goar [email protected] Dairyland Power Cooperative Steve Porter [email protected] Duke Energy Indiana, LLC Phil Briggs [email protected] [email protected] William Hamilton Entergy Melinda Montgomery [email protected] Great River Energy Tim Mickelson [email protected] Hoosier Energy Rural Electric Cooperative, Inc. Todd Taft [email protected] Indianapolis Power & Light Company Russ Mills [email protected] International Transmission Company (d/b/a ITC Ruth Kloecker [email protected] Transmission) Vinit Gupta (alternate) [email protected] (alternate) Ruth Kloecker [email protected] ITC Midwest LLC Vinit Gupta (alternate) [email protected] (alternate) Lafayette Utility Stacee Dunbar System Stewart Dover [email protected] Michigan Electric Transmission Ruth Kloecker [email protected] Company, LLC Vinit Gupta (alternate) [email protected] (alternate) MISO 19 MISO Member Transmission Operator Contact Information for MOD-033-1 Transmission Operator Name Name Email MidAmerican Energy Company Daniel Rathe [email protected] Minnkota Power Will Lovelace [email protected] Cooperative, Inc. Andy Berg [email protected] Montana-Dakota Utilities, Co. Shawn Heilman [email protected] Muscatine Power & Water Ryan Streck [email protected] Northern Indiana Public Service Company Lynn Schmidt [email protected] Otter Tail Power Company Denise Keys [email protected] Rochester Public Utilities Scott Nickels [email protected] Southern Illinois Power Cooperative Jeff Jones [email protected] Southern Indiana Gas & Electric Ryan Abshier [email protected] Company (Vectren) Mike Burk (alternate) [email protected] Southern Minnesota Municipal Power Agency Patrick Egan [email protected] Wolverine Power Supply Cooperative Tyler Bruning [email protected] Xcel Energy Jason Espeseth [email protected] Table B-2 MISO Member Contacts for obtaining information and data MISO 20 Appendix C. NERC Standard References The following NERC standards provide a mechanism to request that equipment owners verify models based on differences between simulations and real-time system performance. Refer to the standards for complete details. NERC Standard MOD-026-1 Under Applicability Section 4.2.4 this standard is applicable to any unit that meets NERC registry criteria when technical justification is achieved by the Transmission Planner demonstrating that the simulated unit or plant response does not match the measured unit or plant response. Requirement R2.1.1 includes the requisite for the Generator Owner to provide documentation demonstrating the applicable unit’s model response matches the recorded response for a voltage excursion from either a staged test or a measured system disturbance. Requirement R3 states that each Generator Owner shall provide a written response to its Transmission Planner within 90 calendar days of receiving one of the following items for an applicable unit: Written notification from its Transmission Planner (in accordance with Requirement R6) that the excitation control system or plant volt/var control function model is not usable, Written comments from its Transmission Planner identifying technical concerns with the verification documentation related to the excitation control system or plant volt/var control function model, or Written comments and supporting evidence from its Transmission Planner indicating that the simulated excitation control system or plant volt/var control function model response did not match the recorded response to a transmission system event. The written response shall contain either the technical basis for maintaining the current model, the model changes, or a plan to perform model verification (in accordance with Requirement R2). NERC Standard MOD-027-1 Per Section 4.2 this standard is applicable to units or multiple units over 100 MVA in Eastern Interconnection. Requirement R2 allows Generator Owners to use a frequency excursion from either a system disturbance or staged testing to verify models and parameters. Requirement R3 states that each Generator Owner shall provide a written response to its Transmission Planner within 90 calendar days of receiving one of the following items for an applicable unit. MISO Written notification, from its Transmission Planner (in accordance with Requirement R5) that the turbine/governor and load control or active power/frequency control model is not “usable,” 21 Written comments from its Transmission Planner identifying technical concerns with the verification documentation related to the turbine/governor and load control or active power/frequency control model, or Written comments and supporting evidence from its Transmission Planner indicating that the simulated turbine/governor and load control or active power/frequency control response did not approximate the recorded response for three or more transmission system events. NERC Standard MOD-032-1 NERC MOD-032 provides a mechanism to go back to equipment owners to verify steady state and dynamic data. Note that the Load Serving Entity (LSE) function was retired with FERC approval. Any requirements listed in the NERC standards that refer to the LSE function are no longer enforced. Dynamics reference item 5 refers to the LSE to provide data regarding dynamic load. It may be necessary for Planning Coordinators to work with Transmission Planners using reference item 10 to develop a requirement for provision of dynamic load data by Transmission Owners or to use local procedures and Tariff references to obtain dynamic load data. R3. Upon receipt of written notification from its Planning Coordinator or Transmission Planner regarding technical concerns with the data submitted under Requirement R2, including the technical basis or reason for the technical concerns, each notified Balancing Authority, Generator Owner, Load Serving Entity, Resource Planner, Transmission Owner, or Transmission Service Provider shall respond to the notifying Planning Coordinator or Transmission Planner as follows] 3.1. Provide either updated data or an explanation with a technical basis for maintaining the current data; 3.2. Provide the response within 90 calendar days of receipt, unless a longer time period is agreed upon by the notifying Planning Coordinator or Transmission Planner. See MOD-032 Attachment 1 for further information. Presently there is a gap in MOD-032 with retirement of the LSE NERC function for the recertification of dynamic load models. NERC Standard IRO-010-2 4. Applicability 4.1. Reliability Coordinator. 4.2. Balancing Authority. 4.3. Generator Owner. 4.4. Generator Operator. 4.5. Load-Serving Entity. 4.6. Transmission Operator. 4.7. Transmission Owner. MISO 22 4.8. Distribution Provider. R1. The Reliability Coordinator shall maintain a documented specification for the data necessary for it to perform its Operational Planning Analyses, Real-time monitoring, and Realtime Assessments. The data specification shall include but not be limited to: 1.1. A list of data and information needed by the Reliability Coordinator to support its Operational Planning Analyses, Real-time monitoring, and Realtime Assessments including non-BES data and external network data, as deemed necessary by the Reliability Coordinator. 1.2. Provisions for notification of current Protection System and Special Protection System status or degradation that impacts System reliability. 1.3. A periodicity for providing data. 1.4. The deadline by which the respondent is to provide the indicated data. R3. Each Reliability Coordinator, Balancing Authority, Generator Owner, Generator Operator, Load-Serving Entity, Transmission Operator, Transmission Owner, and Distribution Provider receiving a data specification in Requirement R2 shall satisfy the obligations of the documented specifications using: … 3.2 A mutually agreeable process for resolving data conflicts MISO 23 Appendix D. Sample Request for Verification Mr. or Ms. Equipment Owner Via e-mail (or address information) Dear Equipment Owner, MISO as the NERC registered Planning Coordinator and Reliability Coordinator entity is requesting that the model parameters for the <insert equipment owner or representative name here and facility name here> for facility be verified under NERC standard <insert applicable NERC standard MOD-026, MOD-027 (as a Transmission Planner), MOD-032 (for steady state) or IRO-010 (as a Reliability Coordinator for Steady State)>.MISO has determined that the model response of the <insert equipment owner or representative name here and facility name here> as shown in Figure 1,<insert additional figure references if required> doesn’t meet the MISO acceptable performance criteria per requirement R1.3 of MOD-033 standard. Model review and tuning must be performed to meet the performance criteria. Please provide a response with a change for the model, plan for changing or a technical basis for continued use of the existing model within 90 calendar days. The response should be emailed to [email protected] Figure D-1 Actual vs. Simulated Model Response If I can provide any additional detail for this request, please contact me via e-mail at <insert email address> here or phone at <insert phone number here>. Sincerely, Engineer /s/ Title,MISO Contact Details MISO 24 Appendix E. MISO Reference Documents “MOD-033 Methodology Reference Document”, NATF, Draft Jan, 2017 “Procedures for Validation of Powerflow and Dynamics Cases “, NERC “Reliability Guideline: PMU Placement and Installation”, NERC Draft 9/22/2016 “System-Wide Model Validation 3002005746”, EPRI, 22-Oct-2015 25
© Copyright 2026 Paperzz