Interface Technology and Switching Devices 2015 / 2016

MCR technology
Highly compact signal conditioners - MINI Analog
Analog IN/Analog OUT
3-way signal conditioner
OUT
1
U,I
US
OUT
IN
Sensor / Field
+ 1
2
– 2
+ 3
– 4
U,I
U,I
OUT U,I
5 +
5
active
4-wire
GND
IN
IN U,I
PLC / DCS
GND 1
+24V
passive
GND 2
6 –
+24V
GND 3
7 +
GND 3
OUT
D W
H
6
8 –
Configurable,
up to 36 signal combinations
+24V
GND 3
POWER

Ex:  
Zone 2
Div. 2
Housing width 6.2 mm
Technical data
Input data
Input signal
– Highly compact signal conditioner for
electrical isolation, conversion,
amplification, and filtering of standard
analog signals
– Up to 36 signal combinations can be
configured using DIP switches
– 3-way isolation
– Low power consumption
– Power supply possible through the foot
element (DIN rail connector)
– Standard configuration:
0 ... 10 V input, 0 ... 20 mA output
U input
0 ... 5 V / 1 ... 5 V
0 ... 10 V / 2 ... 10 V
approx. 100 kΩ
U output
0 ... 5 V / 1 ... 5 V
0 ... 10 V / 2 ... 10 V
approx. 12.5 V
Input resistance
Output data
Output signal
Maximum output signal
No-load voltage
Short-circuit current
Load RB
Ripple
General data
Supply voltage UB
Nominal supply voltage
Current consumption
I input
0 ... 20 mA / 4 ... 20 mA
approx. 50 Ω
I output
0 ... 20 mA / 4 ... 20 mA
28 mA
approx. 12.5 V
approx. 22 mA
≥ 10 kΩ
< 20 mVPP (at 10 kΩ)
U output
19.2 V DC ... 30 V DC
24 V DC
< 9 mA (voltage output,
at 24 V DC incl. load)
< 500 Ω (at 20 mA)
< 20 mVPP (at 500 Ω)
I output
< 19 mA (current output,
at 24 V DC incl. load)
Power consumption
< 200 mW (voltage output)
< 450 mW (current output)
Maximum transmission error
Temperature coefficient
Cut-off frequency (3 dB)
Step response (10-90%)
Electrical isolation
Test voltage, input/output/supply
Degree of protection
Ambient temperature (operation)
Mounting
Housing material
Dimensions W / H / D
Screw connection solid / stranded / AWG
Spring-cage connection solid / stranded / AWG
EMC note
Conformance / approvals
Conformance
ATEX
UL, USA / Canada
≤ 0.1 % (of final value)
< 0.01 %/K, typ. < 0.002 %/K
approx. 100 Hz
approx. 3.2 ms
Basic insulation according to EN 61010
1.5 kV (50 Hz, 1 min.)
IP20
-20 °C ... 65 °C
any
PBT
6.2 / 93.1 / 102.5 mm
0.2 ... 2.5 mm² / 0.2 ... 2.5 mm² / 26 - 12
0.2 ... 2.5 mm² / 0.2 ... 2.5 mm² / 24 - 12
Class A product, see page 625
Notes:
To order a product with an order configuration, enter the required
configuration by referring to the adjacent order key.
Information about power bridging, system cabling, and marking
components can be found from page 116
CE-compliant
 II 3 G Ex nA IIC T4 Gc X
UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5
GL EMC 2 D
GL
Ordering data
Description
MCR 3-way signal conditioner, for electrical isolation of
analog signals
Order configuration
Screw connection
Order configuration
Spring-cage connection
Standard configuration
Screw connection
Standard configuration
Spring-cage connection
92
Type
Order No.
MINI MCR-SL-UI-UI
MINI MCR-SL-UI-UI-SP
MINI MCR-SL-UI-UI-NC
MINI MCR-SL-UI-UI-SP-NC
2864383
2864710
2864150
2864163
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
PHOENIX CONTACT
Pcs. /
Pkt.
1
1
1
1
MCR technology
Highly compact signal conditioners - MINI Analog
Order key MINI MCR-SL-UI-UI(-SP) (standard configuration entered as an example)
Input
Order No.
2864383
Output
/
2864383 =
MINI MCR-SLUI-UI
2864710
MINI MCR-SLUI-UI-SP
IN03
IN01
IN02
IN03
IN04
IN05
IN06
=
=
=
=
=
=
/
0 ... 20 mA
4 ... 20 mA
0 ... 10 V
2 ... 10 V
0 ... 5 V
1 ... 5 V
OUT01
OUT01
OUT02
OUT03
OUT04
OUT05
OUT06
=
=
=
=
=
=
/
0 ... 20 mA
4 ... 20 mA
0 ... 10 V
2 ... 10 V
0 ... 5 V
1 ... 5 V
Factory calibration
certificate (FCC)
NONE
NONE = without FCC
Yes
= with FCC (a fee
is charged)
YESPLUS = FCC with
5 measuring
points (a fee is
charged)
Configuration table for input and output signals
Input
0 - 10 V
Output
0 - 20 mA
4 - 20 mA
0 - 10 V
2 - 10 V
0-5V
1-5V
0 - 20 mA
4 - 20 mA
0 - 10 V
2 - 10 V
0-5V
1-5V
0 - 20 mA
4 - 20 mA
0 - 10 V
2 - 10 V
0-5V
1-5V
0 - 20 mA
4 - 20 mA
0 - 10 V
2 - 10 V
0-5V
1-5V
0 - 20 mA
4 - 20 mA
0 - 10 V
2 - 10 V
0-5V
1-5V
0 - 20 mA
4 - 20 mA
0 - 10 V
2 - 10 V
0-5V
1-5V
2 - 10 V
0-5V
1-5V
0 - 20 mA
4 - 20 mA
DIP 1
OFF
OFF
ON
ON
ON
ON
OFF
OFF
ON
ON
ON
ON
OFF
OFF
ON
ON
ON
ON
OFF
OFF
ON
ON
ON
ON
OFF
OFF
ON
ON
ON
ON
OFF
OFF
ON
ON
ON
ON
DIP switch SW 2
DIP 3
DIP 4
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
DIP 2
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
DIP 5
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
DIP switch SW 1
DIP 1
DIP 2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
DIP 6
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
Application example: level measurement
24V
Level sensor
0...10V
0...20mA
1 IN
OUT 5
2 GND1
GND2 6
Controller
3 UB+
UB+ 7
4 GND3
GND3 8
MINI MCR-SL-UI-UI
24V
Mains voltage
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
For further information and full technical data, visit phoenixcontact.net/products
PHOENIX CONTACT
93