Sequence of Operation Test Form

Sequence of Operation Test Form
Insert logo here
SEQUENCE OF OPERATION TEST FORM
Building Information
Building name:
Building address:
Owner’s name:
Owner’s address:
Owner’s phone/fax/e-mail:
Installing Contractor
Company name:
Address:
Contact person:
Phone/fax/e-mail:
System Input
System Output
1.
A.
Actuate common alarm signal indicator
B.
Actuate audible alarm signal
G.
Display and print change of status and time of
initiating event
H.
Transmit alarm to FD and central station masterbox
J.
Actuate associated exterior fire alarm beacons
K.
Actuate all evacuation signals for the building
L.
Release all magnetically held doors
A.
Actuate common alarm signal indicator
B.
Actuate audible alarm signal
G.
Display and print change of status and time of
initiating event
H.
Transmit alarm to FD and central station masterbox
J.
Actuate associated exterior fire alarm beacons
K.
Actuate all evacuation signals for the building
L.
Release all magnetically held doors
M.
Recall associated elevator in accordance with recall
sequence
P.
Elevator hoistway open
A.
Actuate common alarm signal indicator
B.
Actuate audible alarm signal
G.
Display and print change of status and time of
initiating event
H.
Transmit alarm to FD and central station masterbox
I.
Illuminate associated detector LED indicator
2.
3.
Typical manual pull
station (by device)
floors 1–5
Typical elevator
recall smoke
detector (by device)
by floor (lobby)
Elevator machine
room smoke
detector
For individual use. No other reproduction or transmission in any form permitted.
Test
Results
Date
Initials
1 of 4
Sequence of Operation Test Form
System Input
System Output
3.
J.
Actuate associated exterior fire alarm beacons
K.
Actuate all evacuation signals for the building
L.
Release all magnetically held doors
P.
Elevator hoistway open
A.
Actuate common alarm signal indicator
B.
Actuate audible alarm signal
G.
Display and print change of status and time of
initiating event
H.
Transmit alarm to FD and central station masterbox
J.
Actuate associated exterior fire alarm beacons
K.
Actuate all evacuation signals for the building
L.
Release all magnetically held doors
M.
Recall associated elevator in accordance with recall
sequence
A.
Actuate common alarm signal indicator
B.
Actuate audible alarm signal
F.
Actuate audible trouble signal
G.
Display and print change of status and time of
initiating event
H.
Transmit alarm to FD and central station masterbox
J.
Actuate associated exterior fire alarm beacons
K.
Actuate all evacuation signals for the building
L.
Release all magnetically held doors
Typical wet
sprinkler system
flow control valve
assembly tamper
switch — by floor
C.
Actuate common supervisory signal indicator
D.
Actuate audible supervisory signal
G.
Display and print change of status and time of
initiating event
Typical preaction
sprinkler system
flow control valve
assembly flow
switch — by floor
A.
Actuate common alarm signal indicator
B.
Actuate audible alarm signal
F.
Actuate audible trouble signal
G.
Display and print change of status and time of
initiating event
H.
Transmit alarm to FD and central station masterbox
K.
Actuate all evacuation signals for the building
L.
Release all magnetically held doors
C.
Actuate common supervisory signal indicator
D.
Actuate audible supervisory signal
G.
Display and print change of status and time of
initiating event
4.
5.
6.
7.
8.
Elevator machine
room smoke
detector
(continued)
Typical smoke
detector (by device)
computer room (3rd
floor) preaction
system
Typical wet
sprinkler system
flow control valve
assembly flow
switch — by floor
Typical preaction
sprinkler system
flow control valve
assembly tamper
switch — by floor
For individual use. No other reproduction or transmission in any form permitted.
Test
Results
Date
Initials
2 of 4
Sequence of Operation Test Form
System Input
System Output
9.
A.
Actuate common alarm signal indicator
B.
Actuate audible alarm signal
G.
Display and print change of status and time of
initiating event
H.
Transmit alarm to FD and central station masterbox
L.
Release all magnetically held doors
10.
11.
12.
13.
14.
15.
16.
17.
18.
Kitchen cafeteria
wet chemical
system — 1st floor
P.
Elevator hoistway open
Typical duct smoke
detector (by device)
— by floor
G.
Display and print change of status and time of
initiating event
N.
Shutdown associated mechanical equipment
Fire pump running
C.
Actuate common supervisory signal indicator
D.
Actuate audible supervisory signal
G.
Display and print change of status and time of
initiating event
C.
Actuate common supervisory signal indicator
D.
Actuate audible supervisory signal
G.
Display and print change of status and time of
initiating event
C.
Actuate common supervisory signal indicator
D.
Actuate audible supervisory signal
G.
Display and print change of status and time of
initiating event
C.
Actuate common supervisory signal indicator
D.
Actuate audible supervisory signal
G.
Display and print change of status and time of
initiating event
C.
Actuate common supervisory signal indicator
D.
Actuate audible supervisory signal
G.
Display and print change of status and time of
initiating event
E.
Actuate common trouble signal indicator
F.
Actuate audible trouble signal
G.
Display and print change of status and time of
initiating event
E.
Actuate common trouble signal indicator
F.
Actuate audible trouble signal
G.
Display and print change of status and time of
initiating event
E.
Actuate common trouble signal indicator
F.
Actuate audible trouble signal
G.
Display and print change of status and time of
initiating event
Fire pump power
failure
Fire pump phase
reversal
Fire pump
connected to
emergency power
Fire pump circuit
breaker at
generator output
Fire alarm system
open circuit
Fire alarm system
ground fault
Fire alarm system
battery disconnect
For individual use. No other reproduction or transmission in any form permitted.
Test
Results
Date
Initials
3 of 4
Sequence of Operation Test Form
System Input
System Output
19.
E.
Actuate common trouble signal indicator
F.
Actuate audible trouble signal
G.
Display and print change of status and time of
initiating event
E.
Actuate common trouble signal indicator
F.
Actuate audible trouble signal
G.
Display and print change of status and time of
initiating event
E.
Actuate common trouble signal indicator
F.
Actuate audible trouble signal
G.
Display and print change of status and time of
initiating event
E.
Actuate common trouble signal indicator
F.
Actuate audible trouble signal
20.
21.
22.
Fire alarm system
low battery
Fire alarm system
ac power failure
Fire alarm system
amplifier failure
Generator status
indicator
Test
Results
Date
Initials
Date system left in service:
Test Witnessed by
Owner/authorized agent
Title
Date
Owner/authorized agent
Title
Date
Additional explanations/notes: