FCU EC Fan WT2 Strategy Data Sheet

Data Sheet
FCU EC Fan WT2
Fan Coil Unit - EC Fan - Waterside 2 Pipe and 1 thermic valve.
The IQeco standard strategy controls a fan coil unit’s heat/cool outputs, and electronically commutated fan, in response to a
thermistor temperature sensor with a local setpoint knob and a local switch input (window contact, pushbutton, or Passive Infra Red
movement detector input). The WT2 strategy is for waterside 2 pipe units controlling 1 thermic valve actuator. The strategy is
designed to work with TB/TS Trend Thermistor Room Sensors. The strategy supports the fitting of a WMB Room Display module
without further configuration.
The strategy is designed for use with an IQeco31 and is part of the Plus library.
Order code: IQE31/[y]/BAC/ECFANWT2P/[p] where [y] is unit type F = fixed, P = programmable and [p] is the voltage option.
The strategy will also fit IQeco35 and IQeco38 and can be field downloaded to suitable controllers using SET and the standard
solutions.
Inputs
The following real sensors and digital inputs are connected to the input channels and their values can be monitored by text comms
(including IC Comms):
Real Sensors
IN 1: "Local Discharge Air Temp" (S21), the thermistor temperature sensor for the discharge air.
IN 2: "Local Space Temperature" (S22), the thermistor temperature sensor for the space.
IN 3: "Local Setpoint Adjust" (S23), the local setpoint adjustment potentiometer (scaled in the range -0.5 to +0.5). This generates a
setpoint trim in the range -1°C to +1°C or -1°F to +1°F when the knob ‘Offset Range’ (K3) value is set to 2.
Real Digital Inputs
IN 4: "Window Pushbutton PIR" (I24) this input can be either a window contact which opens, or a pushbutton, or PIR (passive infra
red occupation detector) which closes when the occupation override is required. The type of input is defined by switches ‘Window
Mode 1=Enabled’ (W41) and ‘0=Pushbutton 1=PIR’ (W42).
FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18-Apr-2016
1
FCU EC Fan WT2
Outputs
OUT 1: "Occupation Relay" (D1), this output is used to switch power to the fan controller.
OUT 5,6: "Heat Cool Valve" (D5), this outputs is connected to a thermic actuator.
OUT 9: "EC Fan" (D9), this is connected to the speed input on the EC fan controller.
Default Operation
The behaviour of the strategy before any configuration of knobs as switches is as follows:
The default occupancy state of the strategy is unoccupied.
In most cases when the controller is powered on the fan outputs will not operate as the space temperature used for control will be
within the deadband for the unoccupied state.
There are 3 ways to take the strategy out of the unoccupied state:
1. Set Knob "Remote Occupancy" (K11) to 0.
2. Using a pushbutton connected to IN4. Press the pushbutton once; this should place the unit into bypass. The bypass state is
active until another press of the pushbutton or timeouts after 30 minutes.
3. Use the service button to put the unit into occupied. Details are in "Service Button - Occupancy" section of the strategy
datasheet.
The fan output may not be operating for the following reasons:
a. The fan anti cycling strategy is active. Once switched off the fan will not start for 5 minutes.
b. Changes to the knobs and switches from the defaults are overriding the fan control.
c. The occupancy state is unoccupied.
WallBus Interface Eco
This Standard Strategy can be used with WMB Units which provide Temperature, Humidity, DewPoint and CO2 values to internal
Strategy Sensor Modules.
When adding WMB Units to the system, 963, IQview8 and IQview4 and other User displays will discover these Sensor Modules and
display them in their lists.
WMB units which do not support Humidity or CO2 values will send a value of 0 to the 963 and user displays.
To stop the User Display from showing any one Sensor Module delete the lable string in that module.
For example to prevent the User Display from showing Humidity, delete the label ( $ parameter ) in sensor 32.
You can delete parameters in fixed strategies using one of these methods: parameter viewer in SET system view, live adjust in SET
drawing view or by a text comms message such as S32($="").
You cannot change connections between modules in this fixed strategy.
The Strategy can operate with the new RS-WMB, RD-WMB and RV-WMB sensors which are detailed inTA201348. It can also
operate with the older version of RD-WMB.
The new WMB sensors are available with options for:
Temperature - RD-WMB T, RS-WMB T, RV-WMB T
Temperature and Humidity RD-WMB TH, RS-WMB TH, RV-WMB TH
Temperature, Humidity and CO2 RD-WMB THC and RS-WMB THV.
The Strategy is designed to operate with RD, RS and RV of all the available types.
Sensors which do not support Humidity or CO2 will continue to scroll through all the variables with a display of 0 unless the input in
the interface module is deleted.
For RD-TH, RS-TH, RV-TH sensors
Delete the PVid in t2I10V to prevent the RD displaying CO2 with the value 0
For RD-T, RS-T, RV-T sensors
Delete the PVid in t2I10V to prevent the RD displaying CO2 with the value 0
Delete the PVid in t2I6V to prevent the RD or RV displaying Humidity with the value 0
Delete the PVid in t2I11Vto prevent the RD or RV displaying Outside Air Temperature with the value 0
2
FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18 Apr 2016
FCU EC Fan WT2
The RV sensors have configuration settings such as button graphics and CO2 thresholds. The Strategy does not allow you to link
these settings to strategy. Configuration settings for RV can only be made through the display. See Trend Data sheet TA201354.
For RV and RD meters you can display CO2 from a remote controller by setting up an IC comms to Sensor 34 and deleting the PVid
in t2O4 so that the value in S34 is not overwritten.
This standard solution does not support a CO2 sensor hard wired to the controller.
Knobs Switches <21
The following knobs and switches are grouped by the role they are intended to play within the strategy. They can be monitored and
changed by text comms (including IC Comms). Some can be monitored using display and directory modules (e.g. using IQView):
Modules
1-10
11-20
21-30
31-40
41-50
51-60
Role
Adjustments - Items the users may want to change.
Remote Control - Items that are expected to receive IC Comms e.g. frost protection.
Overrides - Items that enable control to be overridden e.g. heating override.
Settings - Items that should be set up during commissioning.
Options - Items that select an option or behaviour e.g. serial parallel fan.
Energy - Items related to energy.
Adjustments
K1 ‘Pushbutton PIR Timeout’, this knob defines the time in minutes for which the activation of the pushbutton/PIR input overrides
the unit into the occupied state. The default value is 30 minutes.
K2 ‘Setpoint Adjust Timeout’, this knob defines the time in minutes for which any setpoint trim will be applied to the setpoint. The
default value is 60 minutes.
K3 ‘Offset Range’, this knob is used to define the range of ‘Local Setpoint Adjust‘ (S23). The ‘Local Setpoint Adjust‘ (S23) is scaled
to give a range of -0.5 to +0.5; this is multiplied by the ‘Offset Range’ to give the setpoint trim which is applied to the ‘Remote
Setpoint’(K14) to produce the ‘Setpoint’ (S3). The default value is 2°C or 2°F producing a value between -1°C to +1°C or -1°F to
+1°F.
K4 ‘OCC Deadband’, this knob defines the difference between the heating and cooling setpoints during occupation. The default
value is 1°C or 2°F.
K5 ‘NOCC Deadband’, this knob defines the difference between the heating and cooling setpoints during non-occupation. The
default value is 25°C or 45°F.
K6 ‘Standby Deadband’, this knob defines the difference between the heating and cooling setpoints during standby. The default
value is 8°C or 15°F.
K7 ‘Heating Setpoint’, this knob defines the heating setpoint when separate setpoints are selected using switch ‘HeatCool Setpoint
1=Separate’ (W36). The default value is 19.5°C or 67°F.
K8 ‘Cooling Setpoint’, this knob defines the cooling setpoint when separate setpoints are selected using switch ‘HeatCool Setpoint
1=Separate’ (W36). The default value is 20.5°C or 69°F.
W1 ‘Unit Bypass Request 1=Active’, this switch is set to ON if the unit is in bypass and can be used to put the unit into or out of
bypass. The default state is OFF.
Remote Control
K11 ‘Remote Occupancy’, this knob defines unit’s occupancy state: 0(Occupied), 1(Unoccupied), 2(Bypass), 3(Standby). It can be
overridden into bypass (equivalent to Occupied within the unit) from any occupation state by the pushbutton or from standby by the
PIR. The state is overridden to unoccupied by the switch ‘Remote Shutdown 1=Shutdown’ (W11) or the window contact (IN24). The
definition of the occupancy states are detailed below under Occupancy States. The default value is 1(Unoccupied).
K12 ‘Remote Space Temperature‘, this knob is used instead of input ‘Local Space Temperature’ (S22) when the input has an out of
limits or read alarm. It can also be used by setting switch ‘Temperature Select 1=Remote’ (W34) to ON. The default value is 22°C or
71°F.
K13 ‘Remote Setpoint Offset‘, this knob is used instead of input ‘Local Setpoint Adjust’ (S23) to provide the setpoint trim. It is added
to the ‘Remote Setpoint’ (K14) when the input (S23) has an out of limits or read alarm. It can also be used by setting switch ‘SP
Offset Select 1=Remote’ (W35). The default value is 0°C or 0°F.
K14 ‘Remote Setpoint‘, this knob is combined with the setpoint trim to provide the ‘Setpoint’ (S3). The default value is 22°C or 71°F.
K15 ‘Remote Fan Speed‘, this knob is used to set the fan speed in the range of range: 0 (off), 1 (low), 2 (medium), 3 (high), or
4(auto). To ensure that the 'Remote Fan Speed' value is used when sensor ‘Local Fan Speed’ (S27) is fitted the switch 'Fan Speed
Select 1=Remote' (W39) must set to ON. The fan will be switched off during non-occupation unless there is heating demand (fabric
protection) which selects low fan speed. The default value is 4(auto).
K19 ‘Water Flow Temperature’, this knob sets the temperature used to calculate the energy consumption of the unit. The default
value is 50°C or 122°F.
W11 ‘Remote Shutdown 1=Shutdown’, this switch when set to ON forces the unit into the unoccupied state, disables cooling, only
allows sub-zero heating, and disables fabric protection during non-occupation. The default state is OFF.
W12 ‘Frost Condition 1=Frost’, this switch when set to ON forces the unit into a frost condition during non-occupation. During the
frost condition the heating demand is fixed at 98%. The default state is OFF.
W15 ‘Summer Mode 1=Summer’, this switch selects the mode used to drive the output ‘Heat Cool Valve’ (D5). If the switch is set to
ON (summer mode) the valve is driven from the cooling demand else the valve is driven from the heating demand. The default state
is OFF.
Knobs Switches 21 - 40
Overrides
K24 ‘Heat Cool Valve Override Value’, this knob sets the value used to drive the heat cool valve output when switch ‘Valve Override
1=Enabled’ (W24) is enabled. The default value is 50%.
FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18-Apr-2016
3
FCU EC Fan WT2
K28 ‘Fan Speed Override Value EC’, this knob sets the value used to drive the fan speed output when switch ‘Fan Override
1=Enabled’ (W27) is enabled. The analogue value 0 is OFF and 100 is full speed. The default value is 50.
W24 ‘Valve Override 1=Enabled’, this switch when set to ON enables heat cool valve overridde and the heat cool valve output is set
to the value on the knob ‘Heat Cool Valve Override Value’’ (K24). The default state is OFF.
W27 ‘Fan Override 1=Enabled’, this switch when set to ON enables fan to be overriden and the fan outputs are set to the speed
selected on the knob ‘Fan Speed Override Value EC’ (K28). The default value is OFF.
W28 ‘Water Balance 1=Enabled’, this switch when set to ON forces all valve outputs to 100%. The default state is OFF.
Settings
K39 ‘Minimum Fan Speed Setpoint’, this knob defines the minimum speed permitted by the EC fan. The default value is 37%.
K40 ‘Maximum Fan Speed Setpoint’, this knob defines the maximum speed permitted by the EC fan. The default value is 70%.
W31 ‘Service Button Mode 1=Enabled’, this switch when set to ON allows the service button to be used as an input into the
strategy. The default state is ON.
W32 ‘Overrides 0=Disabled 1=Enabled’, this switch when set to ON allows the strategy overrides to be used. The default state is
ON.
W34 ‘Temperature Select 1=Remote’, this switch when set to ON forces the strategy to use the value from knob ‘Remote Space
Temperature‘ (K12) and not sensor ‘Local Space Temperature’ (S22). The default state is OFF.
W35 ‘SP Offset Select 1=Remote’, this switch when set to ON forces the control to use the value from knob ‘Remote Setpoint
Offset‘ (K13) and not sensor ‘Local Setpoint Adjust’ (S23). The default state is OFF.
W36 ‘HeatCool Setpoint 1=Separate’, this switch when set to ON enables the control to use separate setpoints for heating and
cooling use knobs ‘Heating Setpoint’ (K7) and ‘Cooling Setpoint’ (K8). The default state is OFF.
W37 ‘Pushbutton TETS KO 1=Fitted’, this switch when set to ON allows the control to utilise the override pushbutton operation of
the TB/TS/KO range of thermistor room temperature sensors. The default state is OFF.
W39 ‘Fan Speed Select 1=Remote’, this switch when set to ON forces the strategy to use the value from knob ‘Remote Fan Speed‘
(K15) and not sensor ‘Local Fan Speed’ (S27). The default state is OFF.
Knobs Switches >41
Options
W41 ‘Window Mode 1=Enabled’, this switch when set to ON forces the control to treat the digital input ‘Window Pushbutton PIR’
(I24) as a window contact.
W42 ‘0=Pushbutton 1=PIR ‘, this switch is only used when switch ‘Window Mode 1=Enabled’ (W41) is set to OFF. Then the switch
when set to ON treats the digital input ‘Window Pushbutton PIR’ (I24) as a passive infrared detector and when set to OFF treats the
input as a pushbutton. The default state is OFF.
W45 ‘Fan Off at Setpoint 1=Enabled’, this switch when set to ON will disable the fan when the unit is at setpoint and there is no
heating or cooling demand. The default state is OFF.
Energy
K51 ‘ECO Mode Deadband Increase’, this knob defines the value that will be added to the existing deadbands when switch
‘Operating Mode 0=Comfort 1=ECO’ (W51) is set to ON. The default value is 3°C or 7°F.
K52 ‘Power Conversion Factor’, this knob defines the scaling factor that will be multiplied with the heat meter module output to
produce kW. 1kW = 0.948608 Btu/s. The default value is 1 when using kW and 0.948608 when using Btu/s.
W51 ‘Operating Mode 0=Comfort 1=ECO’, this switch when set to ON enables the control to operate in eco mode and increase the
deadband by the value on knob ‘ECO Mode Deadband Increase’ (K51). The default state is ON.
W52 ‘Energy Meter 1=Reset’, this switch when set to ON will reset the energy meter. Once set the control automatically resets the
switch to OFF. The default state is OFF.
Window PushbuttonPIR Operation
The external digital Input ‘Window Pushbutton PIR’ can be used as either a window contact, PIR or Override Pushbutton and its
type configured by Switches ‘0=Pushbutton 1=PIR’ and ‘Window Mode 1=Enabled’’.
In window mode (Switch ‘Window Mode 1=Enabled’ set to ON) the Input ‘Window Pushbutton PIR’ is configured to be a window
contact. When the window contact is open the control will override the unit into Unoccupied.
In pushbutton mode (Switch ‘0=Pushbutton 1=PIR’ set to OFF) the Input ‘Window Pushbutton PIR’ forces the unit into Bypass from
any state for the time set ON Knob ‘Pushbutton PIR Timeout’.
In PIR mode (Switch ‘0=Pushbutton 1=PIR’ set to ON) the Input ‘Window Pushbutton PIR’ will override the unit from Occupied or
Standby into Bypass for at least the time set ON Knob ‘Pushbutton PIR Timeout’.
Within the unit, the Bypass condition is treated the same as Occupied so that although Sensor ‘Occupancy’ shows separate
Occupied and Bypass states, if Bypass is set then Inputs ‘Unit In Bypass’ and ‘Unit Occupied’ will both be set to ON.
The Switch ‘Unit Bypass Request 1=Active’ can be used to stop or start the bypass condition.
When Switch ‘Pushbutton TETS KO 1=Fitted’ is set to ON the external Sensor ‘Local Setpoint Adjust’ out of limits alarm is used to
as the input for PIR or pushbutton override.
Technical Description
A single external digital Input ‘Window Pushbutton PIR’ is used as a window contact, PIR or Override Pushbutton to create a ‘PB
PIR override active’ and ‘Unit interrupt’ digital signals. When used as a PIR or Pushbutton the input is only processed by the
strategy at the rate of the counter module reschedule time. This is to ensure that only one press of the button is reacted to by the
strategy.
The strategy also supports the use of a TE/TS/KO for the override pushbutton using external Sensor ‘Local Setpoint Adjust’ and
Switch ‘Pushbutton TETS KO 1=Fitted’.
Commissioning Details
1. Configure strategy for the type of Input connected to Input ‘Window Pushbutton PIR’ using Switches ‘Window Mode 1=Enabled’
and ‘0=Pushbutton 1=PIR’.
4
FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18 Apr 2016
FCU EC Fan WT2
2. If override is provided by TB/TS/KO set Switch ‘Pushbutton TETS KO 1=Fitted’ to 1.
3. Set the time of Knob ‘Pushbutton PIR Timeout’ for the length of the bypass period required.
Tip.
Input ‘Window Pushbutton PIR’ can be configured as a status monitoring input e.g. filter dirty by changing the E parameter on
function module ‘Input active’ to 100 and setting Switch ‘Window Mode 1=Enabled’ to 0. Remember to change the label on the input
to indicate its function.
Occupancy State
The unit operates in either Occupied, Unoccupied, Bypass, and Standby modes as determined by the ‘Remote Occupancy’ setting.
Occupied:
The unit is on for normal operation and controls to a user defined setpoint. This is Comfort mode as defined in
the European standard EN15500.
Unoccupied:
The unit is off, no fan, heating or cooling. The PIR has no effect although the override pushbutton will override
the unit into bypass. This is Building Protection mode as defined in the European standard EN15500.
Bypass:
The unit has been put into occupation by the override pushbutton or the PIR (occupancy sensor).
Standby:
The unit is activated to reduce its energy consumption. In this mode either the override pushbutton or the PIR
will put the unit back into occupied. This is Economy mode as defined in the European standard EN15500.
Within the unit the Bypass condition is treated the same as Occupied but both inputs ‘Unit In Bypass’ and ‘Unit Occupied’ will be set
to ON.
When Switch ‘Remote Shutdown 1=Shutdown’ is set to ON it will override the unit into unoccupied. The same behaviour occurs if
the unit is in window mode (Switch ‘Window Mode 1=Enabled’ set to ON) and the window contact on Input ‘Window Pushbutton PIR’
is not closed.
Technical Description
A single external digital Input ‘Window Pushbutton PIR’ is used as either a window contact, PIR or Override Pushbutton. The
required occupancy states are decoded to digital signals. 0 = Occupied, 1 = Unoccupied, 2 = Bypass, 3 = Standby. The unit can
also be put in to occupancy using the service pin.
Discharge and Space Temp
Technical Description
With external sensor ‘Local Discharge Air Temp’ fitted the sensor value is gated through to internal sensors ‘Discharge Air
Temperature’. The internal sensor 'Space Temperature' will use the value of either the external sensor 'Room Display Space
Temp', when a Room Display module is fitted, or the value from external sensor ‘Local Space Temperature’, if fitted. If the external
sensor has a ‘Read’ or ‘Out of limit’ alarm the value of input F on the respective gate module will be displayed on the internal
sensor.
Setting switch ‘Temperature Select 1=Remote’ to 1 forces the internal sensor ‘Space Temperature’ to use the value on input F of the
gate module ‘Actual space temperature’.
Heating Cooling Setpoints
The heating and cooling setpoints can be configured to be separately adjusted or calculated. The selected setpoints have half the
current deadband applied as defined by the occupation state. The value of the deadband is increased when not in occupation. The
setpoint can also have an offset (trim) adjustment made locally, that will increase or decrease the required setpoint.
Eco Features
Local offset adjustment is valid for an adjustable time after which it is ignored until a change of the offset value is detected.
The size of the deadband is increased when the unit is in ECO mode.
Technical Description
The setpoint is calculated from Knob ‘Remote Setpoint’ unless Switch ‘HeatCool Setpoint 1=Separate’ is set to 1 when Function
‘Selected heat setpoint’ and Function ‘Selected cool setpoint’ use Knobs ‘Heating Setpoint’ and ‘Cooling Setpoint’ respectively for
they values.
The ‘Heat setpoint’ is calculated by subtracting half the deadband, selected by the mode of occupation, from the value on Function
‘Selected heat setpoint’ and adding any value on Function ‘Setpoint offset’. The ‘Cool setpoint’ is calculated by adding half the
deadband, selected by the mode of occupation, to the value on Function ‘Selected cool setpoint’ and adding any value on Function
‘Setpoint offset’. The ‘Heat setpoint’ and ‘Cool setpoint’ are each halved and combined to provide the ‘Setpoint’.
The normal operation of ‘Setpoint offset’ with the external Sensor ‘Local Setpoint Adjust’ fitted is for the sensor value to be gated
through Function ‘Selected setpoint offset’ and the value of Knob ‘Offset Range’ to be gated through Function ‘Selected offset
range’. If the sensor has a ‘Read’ or ‘Out of limit’ alarm or Switch ‘SP Offset Select 1=Remote’ is set to 1 the strategy gates through
the value of Knob ‘Remote Setpoint Offset’ on Function ‘Selected setpoint offset’ and a value of 1 through Function ‘Selected offset
range’.
If a Room Display module is fitted the strategy will automatically use the value on Knob 'Room Display Setpoint' to calculate any
change in setpoint and feed this through as the offset value.
Any change in the offset value is detected by the strategy and will start Logic timer ‘Adjustment active’. The offset value on Function
‘Selected setpoint offset’ is gated through Function ‘Active setpoint offset’ it is then scaled using the value on Function ‘Selected
FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18-Apr-2016
5
FCU EC Fan WT2
offset range’. Function ‘Setpoint offset’ value is added to the ‘Minimum setpoint’ and ‘Maximum setpoint’ to provide the ‘Heat
setpoint’ and ‘Cool setpoint’ respectively and is set to 0 after the time set on Knob ‘Setpoint Adjust Timeout’ has expired.
Heating Cooling Demands
Heating and cooling demands are calculated by comparing the space temperature with the relevant setpoint. If the space
temperature is below the heating setpoint a heating demand is created and if the space temperature is above the cooling setpoint a
cooling demand is generated, the greater the difference the larger the demand. To prevent hunting of the heating and cooling
demands a deadband is employed to ensure a change equal to half the deadband is detected before a demand is generated or
removed. When the heating or cooling demand reaches 100% the speed of the fan is increased. When a frost condition exists and
the unit state is unoccupied the heating is enabled.
Technical Description
Both heating and cooling sides are controlled by different control loops. The heating loop is enabled whenever ‘Unit interrupt’ is set
to 0 and ‘Summer Mode 1=Summer’ is set to 0. The cooling loop is enabled whenever ‘Unit interrupt’ is set to 0 and ‘Summer Mode
1=Summer’ is set to 1. Both loops are disabled if 'Fan control off selected' is set to 0.
The heating loop compares the ‘Actual space temperature’ with the ‘Heating setpoint’. The proportional + integral (P+I) loop will
modulate the heating output to maintain a constant space temperature. As the temperature decreases below the heating setpoint
the heating output will modulate open. The heating output will be modulated closed as the temperature increases above the heating
setpoint. The loop output is limited to the range 0 to 100%.
The cooling loop compares the ‘Actual space temperature’ with the ‘Cooling setpoint’. The proportional + integral (P+I) loop will
modulate the cooling output to maintain a constant space temperature. As the temperature increases above the cooling setpoint the
cooling output will be modulated open. The cooling output will be modulated closed as the temperature decreases below the cooling
setpoint. The loop output is limited to the range 0 to 100%.
The integral time constant is the time for which the loop output will have added to it an amount equal to product of the error and the
gain (i.e. equal to the proportional part) under conditions of constant error. If the error stays the same for the integral time constant,
the loop output will double and will be 2G(E). The loops have the following default settings: heat loop gain = 6, cool loop gain = -5,
both loop integral time constants = 30 minutes. These settings can be changed by text comms.
The output from the loops (ignoring the integral action) is illustrated by the chart below:
The heating loop will not operate until the ‘Actual space temperature’ drops below the ‘Heating setpoint’ by half the deadband e.g.
Setpoint 22°C (72°F) deadband 4° = 22-2 = 20°C (72-4 = 68°F) during occupation. Similarly for cooling it must rise above the
‘Cooling setpoint’ by half the deadband. The loop gains are set to +6 and -5 by default which gives proportional bands of 16 and 20
°C (°F) and i.e. 100/6 and 100/5. When set to defaults, during occupation, this will give 100% heat at 4°C (39°F), and 100% cool at
44°C (111°F) ignoring the effect of the integral term.
The loop outputs are added together and then split into separate heating and cooling outputs to prevent simultaneous heating and
cooling. The separate demands are rescaled so the demand 0 to 90% drives the relevant valve output between 0 and 100% and the
demand 90 to 100% increases the fan speed. When the heating or cooling demand is greater than 4.5% a respective ‘Heating
6
FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18 Apr 2016
FCU EC Fan WT2
required’ or ‘Cooling required’ signal will be set to 1. The ‘Heating required’ or ‘Cooling required’ signals are reset to 0 when the
respective demand falls below 0.5%.
The heating loop is overridden to 98% if the ‘Frost Condition 1=Frost’ is set to 1 and ‘Unit - unoccupied’ is set to 1. This will bring on
the heating if the unit not in summer mode.
Heat Cool Valve
The cooling demand drives the Heat Cool valve when the switch ‘Summer Mode 1=Summer’ is ON when it is OFF the heating
demand is used. A demand of 100% opens the valve fully and a demand of 0% closes the valve. The valve is fully opened when
Switch ‘Water Balance 1=Enabled’ is ON.
Technical Description
The valve can be overridden, providing Switch 'Overrides 0=Disabled 1=Enabled' is set to 1, by setting Switch ‘Valve Override
1=Enabled’ to 1 and adjusting Knob ‘Heat Cool Valve Override Value’ to the required value between 100 and 0. The overrides are
ignored and the valve is fully opened when Switch ‘Water Balance 1=Enabled’ is 1.
Commissioning Details
1. The Heat Cool valve drive time should be set to match the fitted actuator.
Fan Control - Variable Speed
The fan is ON when the occupation state is occupied; bypass or standby and is OFF when unoccupied. The required speed of the
fan is displayed on the sensor ‘Selected Fan Speed’ where 0 = OFF, 1 = Low, 2 = Medium, 3 = High and 4 = Auto. Low speed is the
value set on knob 'Minimum Fan Speed Setpoint' and High speed is the values set on knob 'Maximum Fan Speed Setpoint'.
Medium speed is the mid value between these two setpoints. If the ‘Selected Fan Speed’ is Auto, the fan will normally run at low
speed, but as the fan demand increases, as a result of an increase in the heating or cooling demand, the fan speed will be
increased to meet the demand, similarly the fan speed will be reduced as demand is met. The actual fan speed is displayed on the
sensor ‘Actual EC Fan Speed’ and is a factor of 10 smaller than the demand i.e. Low = 'Minimum Fan Speed Setpoint' = 37 will
display as 3.7. The fan has an anti cycling timer to protect it from excessive restarts.
Eco Features
The fan can be set to switch OFF whenever the unit is at setpoint i.e. no heating or cooling demand by setting Switch ‘Fan Off at
Setpoint 1=Enabled’ to ON. The fan will restart when a heating or cooling demand exists. This is only applicable when the sensor
‘Selected Fan Speed’ is set to Auto (a value of 4).
Technical Description
The fan is enabled when the occupation state is occupied, bypass or standby and the unit interrupt signal is 0. The driver
'Occupation Relay' is enabled during occupation, time delayed based on the controller address, and is intended to be used to
enable the fan controller.
Automatic control is achieved by rescaling the fan demand set between the ‘Minimum Fan Speed Setpoint’ to the ‘Maximum Fan
Speed Setpoint’. When the required to switch off the ‘Minimum Fan Speed Setpoint’ value is replaced with 0.
The fan control can only be overridden when Logic ‘Unit - unoccupied’ is 0 by either Knob ‘Remote Fan Speed’ or the WMB Room
Display module. The strategy selects the correct control depending on which items are present using the WMB Room Display
module ‘I/O2 Failed status’ bit.
The Knob ‘Remote Fan Speed’ is used when its value is less than 4 or when Switch ‘Fan Speed Select 1=Remote’ is set to 1. When
used the knob has precedence over the external WMB Room Display module.
The WMB Room Display module if fitted uses Knob ‘Room Display Fan Speed’ to display and adjust the speed.
The fan control has an anti cycling timer that delays the time to restart after the fan stops thus preventing unwanted cycling of the
fan. When electric heaters are included in the control the fan will run when Logic ‘Electric heat run on required’ is 1.
The fan control can be overridden, providing Switch 'Overrides 0=Disabled 1=Enabled' is set to 1, by setting Switch ‘Fan Override
1=Enabled’ to 1 and adjusting Knob ‘Fan Speed Override Value EC’ to the required value. The anti cycle timer still operates under
these circumstances.
Commissioning Details
1. Set the ‘Minimum Fan Speed Setpoint’
2. Set the ‘Maximum Fan Speed Setpoint’
3. Confirm that Comparator 'Fan enabled' parameter E value is correctly set to indicate that the fan is enabled.
4. The Timer ‘Anti cycle active’ parameter F requires setting to ensure the minimum off time required for anti cycling the fan. 300
seconds = 5 minutes = 12 starts per hour.
5. The switch 'Fan Speed Select 1=Remote’ requires setting to 1 if the WMB Room Display is to be excluded from the control of the
fan.
FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18-Apr-2016
7
FCU EC Fan WT2
Service Button - Water balance
Pressing the service button in a predefined sequence, when in service button mode, can initiate behaviour in the strategy to start
and stop water balancing where all the valve outputs are set to 100% or 0% i.e. fully open or fully closed. The function is only
available if Switch ‘Service Button Mode 1=Enabled’ is set to ON. For a full description of service pin mode refer to the Trend
publication TE201089 IQeco Configuration Manual Issue 2 or greater. The service button press sequence for the required behaviour
is as follows;
Required Action
Phase 1
Phase 2
Phase 3
Water Balance On for the Lan
No Press
No Press
No Press
Water Balance Off for the Lan
Press
No Press
No Press
Water Balance On for the Unit
No Press
Press
No Press
Water Balance Off for the Unit
Press
Press
No Press
Technical Description
The service button can be used to initiate behaviour designed in the strategy; to achieve this behaviour the controller must be put
into service button mode. Service button mode has 5 stages Entry, Phase 1, Phase 2, Phase 3 and Exit.
Entry - Press and hold the service button for 2 to 5 seconds. When the service button is released a rapidly flashing comms LED
(green) for one second indicates entry into ‘service button mode’. When the flashing stops this indicates the start of Phase 1.
Phase 1 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that a ON condition is
required. If it is pressed then an OFF condition is required. At the end of this stage the comms LED (green) will flash once to
confirm no press and twice to confirm a press. The end of the flashing indicates the start of phase 2.
Phase 2 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that the selection in Phase
1 should be applied to the LAN and if it is pressed then it will be applied to the UNIT. At the end of this stage the comms LED
(green) will flash once to confirm no press and twice to confirm a press. The end of the flashing indicates the start of phase 3.
Phase 3 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that a Water Balance
selection is required and if it is pressed then it will indicate that an Occupancy selection is required. At the end of this stage the
comms LED (green) will flash once to confirm no press and twice to confirm a press. The end of the flashing indicates the start of
the Exit stage.
Exit - This stage lasts for 3 seconds and starts with a rapidly flashing comms LED (green). During this stage if the service button is
not pressed then the service button mode will expire without any further action. The service button must be pressed to confirm the
selections made in phases 1, 2 and 3. Once pressed the LED will go out for the remainder of the stage and the virtual input channel
selected by the choices made during phases 1, 2 and 3 will go ON for one pass of the sequence table. The virtual input channel is
allocated to a Digital Input module to make it available to be used by the strategy. At the end of this stage the service button mode
will be automatically exited and the LED and service button return to their normal operation.
Service Button - Occupancy
Pressing the service button in a predefined sequence, when in service button mode, can initiate behaviour in the strategy to change
the occupancy state to occupied or unoccupied. The function is only available if Switch ‘Service Button Mode 1=Enabled’ is set to
ON. For a full description of service pin mode refer to the Trend publication TE201089 IQeco Configuration Manual Issue 2 or
greater. The service button press sequence for the required behaviour is as follows;
Required Action
Occupied for the Lan
Unoccupied for the Lan
Occupied for the Unit
Unoccupied for the Unit
Phase 1
No Press
Press
No Press
Press
Phase 2
No Press
No Press
Press
Press
Phase 3
Press
Press
Press
Press
Technical Description
The service button can be used to initiate behaviour designed in the strategy; to achieve this behaviour the controller must be put
into service button mode. Service button mode has 5 stages Entry, Phase 1, Phase 2, Phase 3 and Exit.
Entry - Press and hold the service button for 2 to 5 seconds. When the service button is released a rapidly flashing comms LED
(green) for one second indicates entry into ‘service button mode’. When the flashing stops this indicates the start of Phase 1.
Phase 1 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that an ON condition is
required. If it is pressed then an OFF condition is required. At the end of this stage the comms LED (green) will flash once to
confirm no press and twice to confirm a press. The end of the flashing indicates the start of phase 2.
Phase 2 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that the selection in Phase
1 should be applied to the LAN and if it is pressed then it will be applied to the UNIT. At the end of this stage the comms LED
(green) will flash once to confirm no press and twice to confirm a press. The end of the flashing indicates the start of phase 3.
Phase 3 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that a Water Balance
selection is required and if it is pressed then it will indicate that an Occupancy selection is required. At the end of this stage the
comms LED (green) will flash once to confirm no press and twice to confirm a press. The end of the flashing indicates the start of
the Exit stage.
Exit - This stage lasts for 3 seconds and starts with a rapidly flashing comms LED (green). During this stage if the service button is
not pressed then the service button mode will expire without any further action. The service button must be pressed to confirm the
8
FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18 Apr 2016
FCU EC Fan WT2
selections made in phases 1, 2 and 3. Once pressed the LED will go out for the remainder of the stage and the virtual input channel
selected by the choices made during phases 1, 2 and 3 will go ON for one pass of the sequence table. The virtual input channel is
allocated to a Digital Input module to make it available to be used by the strategy. At the end of this stage the service button mode
will be automatically exited and the LED and service button return to their normal operation.
Virtual Energy Meter
An estimation of the unit’s energy consumption is calculated by the controller and can be viewed on Sensor ‘Unit Energy Meter’. The
consumption is measured over a 30 minute period starting from 0 and increasing until the end of the period when the value is stored
in the controller. The controller stores the last 200 values and these can be viewed from suitable displays or supervisory software
e.g. IQView and 963. The calculation totals the estimated energy used by the heat exchangers and the energy consumed by the fan
and by the loads switched by the relay output. The accuracy of the calculation depends on the values configured in the controller
however the default values supplied provide for a like for like comparison between similar units.
Technical Description
The estimated calculations use the heat meter module for the power being provided by the heat exchangers. This power is then
added to the power of the fan and using an integrator module the power consumed is calculated over the period of 15, 30 (default)
or 60 minutes depending on the configuration of the strategy.
Heat exchanger power estimation formula.
Heating Power = (Heating medium temperature - Space temperature) * Coil duty * Valve position / 100
Power kW (D) = (Water Supply Temp DegC (E) - Space Temp DegC (F)) * Coil Duty kW/degK (G) * Valve Position %(0-100)(H) *
0.01 (constant)(I)
Power Btu/s (D) = (Water Supply Temp DegF (F) - Space Temp DegF (E)) * Coil Duty Btu/sDegF (G) * Valve Position %(0-100)(H) *
0.01 (constant)(I)
Cooling Power = (Space temperature - Cooling medium temperature) * Coil duty * Valve position / 100
Power kW (D) = (Space Temp (E) - Water Supply Temp (F)) * Coil Duty kW/degK (G) * Valve Position %(0-100)(H) * 0.01
(constant)(I)
Power Btu/s (D) = (Space Temp DegF (E) - Water Supply Temp DegF (F)) * Coil Duty Btu/sDegF (G) * Valve Position %(0-100)(H) *
0.01 (constant)(I)
To improve the accuracy of the estimation the following parameters should be configured with the correct value for the unit:
Function module
Parameter
Units
‘Heating coil duty max speed’ F
kW/degK (Btu/sDegF)
‘Cooling coil duty max speed’ F
kW/degK (Btu/sDegF)
‘Fan duty max speed’
F
kW
‘Occupation relay duty’
F
kW
The output 'Occupation Relay' is intended to be the relay that switches the power to the EC fan controller and the value of
‘Occupation relay duty’ is the duty when the fan controller is energised. The values calculated are linear and therefore are only an
estimate.
The period the integrator uses for the calculation can be changed by amending the arguments in parameter K on Logic module
‘Meter reset’: F = 15 minutes, G = 30 minutes and H = 60 minutes. If the Logic is changed then the period parameter P on plot
module ‘Unit Energy Meter’ should also be changed to match: 1 = 15 minutes, 7 = 30 minutes and 0 = 60 minutes.
Useful conversions:
1 kW = 0.948608 Btu/s
1 hp = 0.7074163 Btu/s
1 Btu/h/3600 = 1 Btu/s
Commissioning Details
1. Set the values of the duty for the coils.
2. Set the values of the duty for the fan.
3. Set the value of the duty for the occupation relay.
4. Confirm the water flow temperatures are received from the main plant.
IC Comms and Alarm Group
Technical Description
The IC Comms are configured for master slave operation directed to standard knobs and switches one or all of the following: Space
Temperature, Setpoint, Occupancy and Fan Speed. The IC Comms modules use attribute 3 and to prohibit unwanted
communications are, by default, disabled.
One alarm group route and destination modules are configured to send Trend text alarms to address 1 on the local lan, this would
normally be the IQ3/BINC VCNC port 10001. To prohibit unwanted alarms the route, by default, is disabled.
Analogue node 99 is provided so a value can be placed in it to indicate the state of the unit during commissioning and witnessing.
The meaning of the value is user defined. It is suggested a bit state approach be used where values 1, 2, 4, 8 ,16 etc each
indicating a separate operation. Summing the values provide a state of the unit.
Suggested values:
1=
Addressed,
2=
Attributes Set,
4=
Pre-commissioned,
8=
Commissioned,
16 =
Witnessed,
FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18-Apr-2016
9
FCU EC Fan WT2
32 =
64 =
128 =
Backed up,
(TBC) ,
Has a Problem.
An exampled of its use.
e.g 11 = 1+2+8 = Addressed, Attributes Set and Commissioned.
Digital Input 'Strategy Override 1=Active' when 1 indicates that one of the outputs is being overridden by the strategy and not in
normal control.
Commissioning Details
1. For master slave configuration configure attribute 3 and enabled IC Comms if master unit.
2. If alarms are required configure alarm destination address and enable alarm route.
10
FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18 Apr 2016
FCU EC Fan WT2
Please send any comments about this or any other Trend technical publication to [email protected]
© 2011 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Z.A. La Pièce, 16,
1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.
Trend Control Systems Limited
Albery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.
Trend Control Systems
Albery House,
Springfield Road,
Horsham.
RH12 2PQ
Telephone:
+44 (0)1403 211888
Fax:
+44 (0)1403 240271
Email:
[email protected]
Address Module
Identifier
Issue
Revision
0
1
1
0
2
0
3
0
Project Change Note / Comments
Alarm Lan
0
Alarm Address
0
Controller Version
Date Approved
Approved By
Page 2, 7, 9, 10, 12 Added new interface
to WMB sensors.
Page 12 F77 F=1 on state is 1 not 255
Attribute F
Attribute G
Pages Affected
Serial Number
Strategy Name
FCU EC Fan WT2
Page 2, 7, 9, 10, 12 Added new interface
to WMB sensors.
Product Order Code
Notes
Site
GUID:
{31009522-BE09-4A36-BEC3-9EA8ABCDD52D}
Project:
IQeco_Standard_Strategies_v3.2.1
The IQeco standard strategy controls a fan coil unit’s heat/cool outputs, and electronically commutated fan.
Client:
The control responses to a thermistor temperature sensor with a local setpoint knob and a local window contact input and a pushbutton, or Passive Infra Red movement detector input.
Details:
Fan Coil Unit with EC Fan
Waterside 2 Pipes with 1 thermic Valve.
The WT2 strategy is for waterside 2 pipe units controlling 1 thermic valve actuator.
The strategy supports the fitting of a WMB Room display module without further configuration.
Drawn By:
Engineer
Engineer:
M Spencer
Controller Type:
IQeco 31
Project Number:
1
Outstation:
014
Lan:
019
Date:
4/15/2016
Page:
01 of 18
FCU EC Fan WT2
Strategy pages
Title Page
WallBus Interface Eco
Real Inputs
Knobs Switches <21
Knobs Switches 21 - 40
Knobs Switches >41
Window PushbuttonPIR Operation
Occupancy State
Discharge and Space Temp
Heating Cooling Setpoints
Heating Cooling Demands
Heat Cool Valve
Fan Control - Variable Speed
Fan Control - Variable page 2
Service Button - Water balance
Service Button - Occupancy
Virtual Energy Meter
IC Comms and Alarm Group
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
180
Interface module for WMB Displays
170
185
184
Room Display Space Temp
Occupancy Code
160
1
G18D
Unit - occupied
From Page 8
150
E
0
F
G18D
B
t2
D
Wallbus
GATE
2
S31V
4
F100D
K47D
K48D
S32V
1
1
1
S34V
S39V
1
F77D
W1D
F42D
140
Setpoint Highlimit
K47
24
D
KNOB
DegC
0
0
0
Disabled
120
Units
Pin Level
Top of Range
Bottom of Range
Clip To Limits
Setpoint Lowlimit
110
K48
18
D
KNOB
DegC
0
0
0
Disabled
100
Address
I1 - Temperature Display
I2 - Fan Configuration
I3 - Occupancy Display
I4 - Setpoint High limit
I5 - Setpoint low limit
I6 - Humidity Display
I7 - Setpoint Enable
I8 - Fan Enable
I9 - Override Enable
I10 - CO2 Display
I11 - OutsideAirTemperature
I12 - TempConfig
I13 - Fan State Display
I14 - Override State Display
I15 - Setpoint
O1 - Local Temperature
O2 - Local Humidity
O3 - Local Dewpoint
O4 - Local CO2
O5 - Setpoint
O6 - Override State
O7 - Fan State
DegC
50
-5
600
600
Disabled
Disabled
RD-WMB-THC
To Page(s) 9,10,13,
A1
D
Analogue
S39
Read Alarm
Out. Limits Alarm
Low Alarm
High Alarm
70
S32
60
Temperature Display
V
S32V
S
INTERNAL
%RH
0
0
0
0
Disabled
Disabled
Humidity
To Page(s)
Units
High Alarm Limit
Low Alarm Limit
High Alarm Delay
Low Alarm Delay
Low Alarm
High Alarm
186
t2I6V
Humidity Display
Dewpoint
S40
V
t2O3V
S
INTERNAL
DegC
0
0
0
0
Disabled
Disabled
V
A1D
S
INTERNAL
DegC
0
0
0
0
Disabled
Disabled
t2I1V
t2O2V
Outside Air Temp
V
Units
High Alarm Limit
Low Alarm Limit
High Alarm Delay
Low Alarm Delay
Low Alarm
High Alarm
181
182
0
Room Display Space Temp
To Page(s) 9,
Humidity
Units
Pin Level
Top of Range
Bottom of Range
Clip To Limits
Outside Air Temp
S31V
S
INTERNAL
t2*e
90
80
V
t2O1V
Failed
D = F when B = 1
130
S31
RD-WMB-THC
F100
Units
High Alarm Limit
Low Alarm Limit
High Alarm Delay
Low Alarm Delay
Low Alarm
High Alarm
Units
High Alarm Limit
Low Alarm Limit
High Alarm Delay
Low Alarm Delay
Low Alarm
High Alarm
188
CO2
S34
V
t2O4V
S
INTERNAL
ppm
0
0
0
0
Disabled
Disabled
50
40
t2I10V
CO2 Display
Units
High Alarm Limit
Low Alarm Limit
High Alarm Delay
Low Alarm Delay
Low Alarm
High Alarm
30
20
10
For RS-WMB, RD-WMB refer to Data Sheet TA201348. For RV-WMB refer to Data Sheet TA201354 for more information
Drawing Reference
SET-019-014-02
Page Details
WallBus Interface Eco
SET Strategy
Designed By:
Trend Control Systems
D60D 3201 DA65 8FD9 921A 697A 87
Issue
3
Revision
-
00
Checked By
Project Number:
1
Date:
Outstation:
014
Page:
4/15/2016
02 of 18
10
180
20
30
40
50
60
70
80
0
1
S21
i
c
150
140
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
Window Pushbutton PIR
V
EXTERNAL
160
100
1
Local Discharge Air Temp
170
90
DegC
101
0
50
-5
600
600
0
0
Disabled
Disabled
Disabled
Disabled
Units
Type
Offset
High Alarm Limit
Low Alarm Limit
High Alarm Delay
Low Alarm Delay
Out.Limits Delay
Read Alarm Delay
Read Alarm
Out. Limits Alarm
Low Alarm
High Alarm
I24
S21V
4
Local Discharge Air Temp
To Page(s) 9,
Local Discharge Air Temp
S21V
S
15 Min
96
Period
Records
c
EXTERNAL
0
Alarm Delay
0
Required State
Disabled State Alarm
Hours Run
Starts
S
I24S
Window Pushbutton PIR
To Page(s) 7,8,
P7
SYNC
130
120
2
Local Space Temperature
110
0
2
S22
i
c
Default Operation
V
EXTERNAL
100
90
80
DegC
101
0
50
-5
600
600
0
0
Disabled
Disabled
Disabled
Disabled
Units
Type
Offset
High Alarm Limit
Low Alarm Limit
High Alarm Delay
Low Alarm Delay
Out.Limits Delay
Read Alarm Delay
Read Alarm
Out. Limits Alarm
Low Alarm
High Alarm
S22V
The behaviour of the strategy before any configuration of knobs and switches is as follows:
Local Space Temperature
To Page(s) 9,
The default occupancy state of the strategy is unoccupied.
In most cases when the controller is powered on the fan outputs will not operate as the
space temperature used for control will be within the deadband for the unoccupied state.
There are 3 ways to take the strategy out of the unoccupied state:
1. Set Knob “Remote Occupancy” (K11) to 0.
2. Using a pushbutton connected to IN4.
Press the pushbutton once; this should place the unit into bypass.
The bypass state is active until another press of the pushbutton or timeouts after 30 minutes.
3. Use the service button to put the unit into occupied.
Details are in “Service Button - Occupancy” section of the strategy datasheet.
70
60
3
Local Setpoint Adjust
50
0
3
i
c
S23
V
EXTERNAL
40
30
20
DegC
102
0
0.6
-0.6
600
600
0
0
Disabled
Disabled
Disabled
Disabled
Units
Type
Offset
High Alarm Limit
Low Alarm Limit
High Alarm Delay
Low Alarm Delay
Out.Limits Delay
Read Alarm Delay
Read Alarm
Out. Limits Alarm
Low Alarm
High Alarm
The fan output may not be operating for the following reasons:
a. The fan anti cycling strategy is active. Once switched off the fan will not start for 5 minutes.
b. Changes to the knobs and switches from the defaults are overriding the fan control.
c. The occupancy state is unoccupied.
S23V
Local Setpoint Adjust
To Page(s) 10,
5
One shot switch reset
F1
500
E
0
F
F1D
D
10
One shot switch reset
To Page(s) 17,
COMPARATOR
D = 1 when F > E
Drawing Reference
SET-019-014-03
Page Details
Real Inputs
SET Strategy
Designed By:
Trend Control Systems
D60D 3201 DA65 8FD9 921A 697A 87
Issue
3
Revision
-
00
Checked By
Project Number:
1
Date:
Outstation:
014
Page:
4/7/2016
03 of 18
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
180
Pushbutton PIR Timeout
170
160
Cooling Setpoint
K1
30
D
KNOB
min
79
1440
0
K1D
Pushbutton PIR Timeout
To Page(s) 7,
Units
Pin Level
Top of Range
Bottom of Range
K11D = 1
K8
20.5
KNOB
DegC
79
34
18
Remote Occupancy
From Page 8
K8D
D
Units
Pin Level
Top of Range
Bottom of Range
Remote Occupancy
To Page(s) 4,8,16,
Setpoint Adjust Timeout
150
Remote Space Temperature
K2
60
D
KNOB
140
min
79
1440
0
130
K2D
DegC
79
30
0
K12D
Remote Space Temperature
To Page(s) 9,
Units
Pin Level
Top of Range
Bottom of Range
2
D
KNOB
K3D
D
KNOB
Offset Range
To Page(s) 10,
Units
Pin Level
Top of Range
Bottom of Range
DegC
79
10
-10
DegC
79
0
0
K13D
Remote Setpoint Offset
To Page(s) 10,
Units
Pin Level
Top of Range
Bottom of Range
W11
0
D
KNOB
90
DegC
60
2
0.5
Frost Condition 1=Frost
W12
25
D
KNOB
DegC
60
25
8
KNOB
W1D = 0
K5
K5D
Unit Bypass Request 1=Active
From Page 7
4
D
60
Units
Pin Level
Top of Range
Bottom of Range
Pin Level
K14D
K15D
K15
KNOB
enum
79
4
0
Remote Fan Speed
To Page(s) 13,
0 = Off
1 = Low
2 = Medium
3 = High
4 = Auto
(1001-7)
Summer Mode 1=Summer
40
79
D
KNOB
DegC
60
8
1
W15D
D
SWITCH
K6
8
W15
0
Standby Deadband
50
Frost Condition 1=Frost
To Page(s) 11,
Remote Setpoint
To Page(s) 10,
Units
Pin Level
Top of Range
Bottom of Range
Remote Fan Speed
W1D
Unit Bypass Request 1=Active
To Page(s) 4,
NOCC Deadband
To Page(s) 10,
Units
Pin Level
Top of Range
Bottom of Range
79
D
DegC
79
24
18
W12D
D
SWITCH
K14
22
OCC Deadband
To Page(s) 10,
Units
Pin Level
Top of Range
Bottom of Range
NOCC Deadband
80
70
K4D
Remote Shutdown 1=Shutdown
To Page(s) 8,
Pin Level
Remote Setpoint
K4
1
W11D
D
SWITCH
79
0
100
Water Flow Temperature
To Page(s) 17,
Units
Pin Level
Top of Range
Bottom of Range
110
OCC Deadband
K19D
D
KNOB
Remote Shutdown 1=Shutdown
K13
0
K19
50
Remote Setpoint Offset
K3
DegC
79
10
1
D
KNOB
Setpoint Adjust Timeout
To Page(s) 10,
Units
Pin Level
Top of Range
Bottom of Range
Water Flow Temperature
K12
22
Offset Range
120
K11D
Cooling Setpoint
To Page(s) 10,
Summer Mode 1=Summer
To Page(s) 11,12,
Pin Level
K6D
Standby Deadband
To Page(s) 10,
Units
Pin Level
Top of Range
Bottom of Range
Heating Setpoint
30
K7
19.5
D
KNOB
20
DegC
79
24
8
Units
Pin Level
Top of Range
Bottom of Range
K7D
Heating Setpoint
To Page(s) 10,
10
Drawing Reference
SET-019-014-04
Page Details
Knobs Switches <21
SET Strategy
Designed By:
Trend Control Systems
D60D 3201 DA65 8FD9 921A 697A 87
Issue
3
Revision
-
00
Checked By
Project Number:
1
Date:
Outstation:
014
Page:
3/24/2016
04 of 18
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
180
170
Service Button Mode 1=Enabled
W31
1
79
Minimum Fan Speed Setpoint
150
D
KNOB
%
79
50
0
140
K39D
W32
1
Minimum Fan Speed Setpoint
To Page(s) 14,
Units
Pin Level
Top of Range
Bottom of Range
79
%
79
100
50
Pin Level
W34
79
Pin Level
SP Offset Select 1=Remote
Maximum Fan Speed Setpoint
To Page(s) 14,
W35
0
0
D
KNOB
%
60
100
0
Valve Override 1=Enabled
K24D
Heat Cool Valve Override Value
To Page(s) 12,
Units
Pin Level
Top of Range
Bottom of Range
D
SWITCH
60
Pin Level
W24D
79
Pushbutton TETS KO 1=Fitted
W37
D
%
60
100
0
Units
Pin Level
Top of Range
Bottom of Range
W37D
D
SWITCH
79
K28
KNOB
70
HeatCool Setpoint 1=Separate
To Page(s) 10,
Pin Level
Fan Speed Override Value EC
50
W36D
D
SWITCH
Valve Override 1=Enabled
To Page(s) 12,
Pin Level
W36
0
0
80
SP Offset Select 1=Remote
To Page(s) 10,
HeatCool Setpoint 1=Separate
W24
0
W35D
D
SWITCH
79
K24
Temperature Select 1=Remote
To Page(s) 9,
K40D
110
Heat Cool Valve Override Value
W34D
D
SWITCH
D
Units
Pin Level
Top of Range
Bottom of Range
Overrides 0=Disabled 1=Enabled
To Page(s) 12,14,
Temperature Select 1=Remote
K40
KNOB
120
W32D
D
SWITCH
Maximum Fan Speed Setpoint
70
90
Pin Level
0
130
Service Button Mode 1=Enabled
To Page(s) 15,16,
Overrides 0=Disabled 1=Enabled
K39
37
100
W31D
D
SWITCH
160
Pushbutton TETS KO 1=Fitted
To Page(s) 7,
Pin Level
K28D
Fan Speed Override Value EC
To Page(s) 14,
60
Fan Override 1=Enabled
Fan Speed Select 1=Remote
W27
0
D
50
SWITCH
60
Pin Level
W27D
W39
0
Fan Override 1=Enabled
To Page(s) 14,
W39D
D
SWITCH
79
Fan Speed Select 1=Remote
To Page(s) 13,
Pin Level
40
W28D = 0
Water Balance 1=Enabled
From Page 15
30
W28D
Water Balance 1=Enabled
To Page(s) 5,
20
10
Drawing Reference
SET-019-014-05
Page Details
Knobs Switches 21 - 40
SET Strategy
Designed By:
Trend Control Systems
D60D 3201 DA65 8FD9 921A 697A 87
Issue
3
Revision
-
00
Checked By
Project Number:
1
Date:
Outstation:
014
Page:
3/24/2016
05 of 18
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
180
Window Mode 1=Enabled
170
ECO Mode Deadband Increase
W41
0
D
SWITCH
79
W41D
Window Mode 1=Enabled
To Page(s) 7,8,
Pin Level
0=Pushbutton 1=PIR
160
W42
0
SWITCH
150
D
KNOB
DegC
79
6
2
Operating Mode 0=Comfort 1=ECO
K51D
ECO Mode Deadband Increase
To Page(s) 10,
Units
Pin Level
Top of Range
Bottom of Range
W51
1
W51D
D
SWITCH
60
Operating Mode 0=Comfort 1=ECO
To Page(s) 10,
Pin Level
W52D = 0
D
79
K51
3
W42D
Power Conversion Factor
0=Pushbutton 1=PIR
To Page(s) 7,
Pin Level
1
K52
D
KNOB
140
Energy Meter 1=Reset
From Page 17
79
0
0
Units
Pin Level
Top of Range
Bottom of Range
W52D
Energy Meter 1=Reset
To Page(s) 6,
K52D
Power Conversion Factor
To Page(s) 17,
130
120
Fan Off at Setpoint 1=Enabled
110
W45
0
D
SWITCH
79
100
Pin Level
W45D
Fan Off at Setpoint 1=Enabled
To Page(s) 14,
90
80
70
60
50
40
30
20
10
Drawing Reference
SET-019-014-06
Page Details
Knobs Switches >41
SET Strategy
Designed By:
Trend Control Systems
D60D 3201 DA65 8FD9 921A 697A 87
Issue
3
Revision
-
00
Checked By
Project Number:
1
Date:
Outstation:
014
Page:
3/24/2016
06 of 18
10
20
30
40
50
60
70
80
90
100
110
120
180
130
140
150
160
170
180
190
200
210
220
230
240
17
20
Minutes to seconds
K1D = 30
170
Pushbutton PIR Timeout
From Page 4
60
E
K1D
G
1
F
160
F3
PIR override active
G8
D
G4D
MULTIPLY
S
G8D
D
D=G*E*F
PIR override active
To Page(s) 8,
TIMER
150
0
0
F3D
G20D
Unit - unoccupied
From Page 8
140
W42D = 0
0=Pushbutton 1=PIR
From Page 6
W41D = 0
130
Window Mode 1=Enabled
From Page 6
12
G1
I24S
Window Pushbutton PIR
From Page 3
I24S
S
F2D
A
0.5
E
G1M
F
M
F
W41D
G
F2D
H
G4
t2O6V
E
J or
K or
L or
M
G8D
F
G4D
G
D
COMB
Override State t2O6V
J Comb.
K Comb.
L Comb.
M Comb.
1
1
Window Mode 1=Enabled
From Page 6
W42D = 0
0=Pushbutton 1=PIR
From Page 6
80
13
KO Override Request
S23o1S
Out - Local Setpoint Adjust
From Page 3
S23o1S E
0
W37D = 0
Pushbutton TETS KO 1=Fitted
From Page 5
14
Pulse generator reset
I24S
Window Pushbutton PIR
From Page 3
W41D = 0
Window Mode 1=Enabled
From Page 6
40
S23o1S E
G3
J or
K or
L or
M
I24S
F
0
G
W41D
H
E
FH
J Comb.
K Comb.
L Comb.
M Comb.
J or
K or
L or
M
Unit Bypass Request 1=Active
G6D
H
J Comb.
K Comb.
L Comb.
M Comb.
D
SWITCH
60
H
FG
EF
W1
G9D
D
Pin Level
COMB
t2I14V
Override State Display
18
16
Reschedule Time
Scale Factor
Sts - Window Pushbutton PIR
From Page 3
60
22
G9
D = 1 when F > E
W41D = 0
50
21
COMPARATOR
999
I24N
70
W42D
PB PIR override active
To Page(s) 8,
PB PIR override active
COUNTER
100
90
E
D
R
G9D
PIR request
G20D
eFgH
F2
Window Pushbutton PIR count
On Delay
Minimum On
Off Delay
15
Input active
11
120
110
250
F
J or
K or
L or
M
W37D
G
G3D
H
EGh
J Comb.
K Comb.
L Comb.
M Comb.
D
COMB
COMB
F2D
E
W41D
F
W42D
G
G2D
H
Efg
H
G2
Pushbutton override active
Pushbutton request
G6
G5
t2O6V
E
J or
K or
L or
M
G8D
F
G5D
G
G7D
H
Efgh
eG
J Comb.
K Comb.
L Comb.
M Comb.
COMB
J Comb.
K Comb.
L Comb.
M Comb.
D
19
J or
K or
L or
M
COMB
Pushbutton override reset
G7
G6D
S
F3D
0
0
On Delay
Minimum On
Off Delay
D
D
D
TIMER
Window Mode:
Switch "Window Mode 1=Enabled" set to 1
Input "Window Pushbutton PIR" when open circuit
will force control to change to unoccupied.
(1001-13)
30
PIR mode:
Switch "0=Pushbutton 1=PIR" set to 1
Control will change from standby to
bypass upon movement being
detected by the PIR for the amount
of time determined by knob
"Pushbutton PIR Timeout".
(1001-11)
Pushbutton Mode:
Switch "0=Pushbutton 1=PIR" set to 0
Control will change from
unoccupied to bypass for
the amount of time determined
by knob "Pushbutton PIR Timeout"
when the pushbutton is pressed.
If the button is pressed whilst in bypass
the unit will be returned to unoccupied.
(1001-12)
20
10
Drawing Reference
SET-019-014-07
Page Details
Window PushbuttonPIR Operation
SET Strategy
Designed By:
Trend Control Systems
D60D 3201 DA65 8FD9 921A 697A 87
Issue
3
Revision
-
00
Checked By
Project Number:
1
Date:
Outstation:
014
Page:
3/24/2016
07 of 18
10
20
180
30
40
50
W41D = 0
I24S
Window Pushbutton PIR
From Page 3
160
150
80
90
W41D
I24S
F
W11D
G
120
130
140
150
160
J or
K or
L or
M
H
J Comb.
K Comb.
L Comb.
M Comb.
34
a
b
F8
D
G
D
COMB
A TO D
Unit interrupt:
When in window mode and input
"Window Pushbutton PIR" is 0 or the
unit has been sent a shutdown command
control is forced to unoccupied.
(1001-14)
g
h
0 = Occupied
1 = Unoccupied
2 = Bypass
3 = Standby
(1001-1)
Bypass select
K11D = 1
Remote Occupancy
From Page 8
K11D
E
2
F
G17D
B
100
33
F6
GATE
F6D
E
1
F
G16D
B
S10
D
Bypass request
G8D
PIR override active
From Page 7
70
E
F
50
G
G20D
H
Fg
FGh
J Comb.
K Comb.
L Comb.
M Comb.
26
K11D
1
E
0
F
F9D
B
Remote Occupancy
Occupancy value select
F10
K11D
E
F10D
F
G75D
B
F11
D
D = 1 when F > E
D = F when B = 1
D
D
F
GATE
G
G19D
H
ef
H
J Comb.
K Comb.
L Comb.
M Comb.
F8a
E
F8b
F
0
G
GATE
D = F when B = 1
KNOB
enum
79
3
0
Units
Pin Level
Top of Range
Bottom of Range
D
Unit Occupied is enabled
when the zone is occupied.
(1001-2)
Unit In Bypass
I3
G19D
G19
J or
K or
L or
M
0
H
J Comb.
K Comb.
L Comb.
M Comb.
D
Page Details
Occupancy State
SET Strategy
Designed By:
0
Alarm Delay
0
Required State
Disabled State Alarm
Hours Run
Starts
G19D
Unit - bypass
To Page(s)
COMB
Unit Bypass mode is the occupied
state used when the Pushbutton
or PIR are activated.
Bypass uses the same deadband
as occupied.
(1001-4)
V
Units
High Alarm Limit
Low Alarm Limit
High Alarm Delay
Low Alarm Delay
Low Alarm
High Alarm
G20D
37
E
F8b
F
Unit Unoccupied
I2
Unit - unoccupied
To Page(s) 7,11,14,
Unit - unoccupied
F8a
K11D
Remote Occupancy
To Page(s) 4,8,16,
Trend Control Systems
D60D 3201 DA65 8FD9 921A 697A 87
S
INTERNAL
G20D
G20
J or
K or
L or
M
0
G
0
H
Ef
J Comb.
K Comb.
L Comb.
M Comb.
S
INTERNAL
0
Alarm Delay
0
Required State
Disabled State Alarm
Hours Run
Starts
D
COMB
Unit Unoccupied mode is activated
when the zone is unoccupied
for longer periods of time.
In this mode PIR has no effect
although the Pushbutton will
override the unit into bypass.
(1001-3)
Unit In Standby
I4
38
G21D
F8a
E
F8b
F
0
G
G21
J or
K or
L or
M
0
H
EF
J Comb.
K Comb.
L Comb.
M Comb.
D
COMB
Issue
3
Revision
-
S
INTERNAL
Service button occ active
From Page 16
Drawing Reference
SET-019-014-08
0
Alarm Delay
0
Required State
Disabled State Alarm
Hours Run
Starts
G18D
Unit - occupied
To Page(s) 2,10,
COMB
eF
G75D
10
J or
K or
L or
M
Unit - standby
K11
F11D
E
COMPARATOR
0
0 = Occupied
1 = Unoccupied
2 = Bypass
3 = Standby
(1001-1)
29
28
Occ nocc select
D
F
S
INTERNAL
S
INTERNAL
COMB
27
F9
0.5
250
I1
F8b
D
Unit not in occ mode
To Page(s) 16,
Unit not in occ mode
20
J or
K or
L or
M
F9D
40
30
G17
G8D
60
240
G18D
F7D
enum
4
-1
0
0
Disabled
Disabled
GATE
31
G9D
230
G18
E
Occupancy
F7
D = F when B = 1
0
220
Unit Occupied
F8a
39
Unoccupied select
D
D = F when B = 1
G9D
210
35
32
PB PIR override active
From Page 7
200
Unit - bypass
Unoccupied select
To Page(s)
120
c
d
e
f
F7D
80
190
Unit - occupied
Occupancy decoder
130
90
180
36
F7D
0
Ef
G
110
170
G16D
G16
E
110
Unit interrupt
To Page(s) 11,14,
Window Mode:
Switch "Window Mode 1=Enabled" set to 1
Input "Window Pushbutton PIR" when open circuit
will force control to change to unoccupied.
(1001-13)
140
100
Unit interrupt
W11D = 0
Remote Shutdown 1=Shutdown
From Page 4
70
30
Window Mode 1=Enabled
From Page 6
170
60
00
0
Alarm Delay
0
Required State
Disabled State Alarm
Hours Run
Starts
G21D
Unit - standby
To Page(s) 10,
Unit Standby is activated
to reduce the energy consumption
of the zone. In this mode either
the PIR if selected or the Pushbutton
will put the zone back into occupied.
(1001-5)
Checked By
Project Number:
1
Date:
Outstation:
014
Page:
3/24/2016
08 of 18
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
180
S21V
Local Discharge Air Temp
From Page 3
170
42
S31V
Actual discharge temp
S21V
160
150
S21r1S
Rd - Local Discharge Air Temp
From Page 3
S21o1S
140
41
Out - Local Discharge Air Temp
From Page 3
130
0
F
G26D
B
G26
E
J or
K or
L or
M
S21o1S F
0
G
0
H
E
F
J Comb.
K Comb.
L Comb.
M Comb.
F16
D
GATE
45
Selected space temperature
F16D
S22V
Actual discharge temp
To Page(s)
D = F when B = 1
Discharge temp 0=Fitted
S21r1S
E
Room Display Space Temp
From Page 2
Local Space Temperature
From Page 3
43
S31V
E
S22V
F
t2e
B
Discharge Air Temperature
S1
F17
D
GATE
D = F when B = 1
V
F16D
D
S
INTERNAL
DegC
40
10
0
0
Disabled
Disabled
COMB
46
Units
High Alarm Limit
Low Alarm Limit
High Alarm Delay
Low Alarm Delay
Low Alarm
High Alarm
Space temperature select
K12D = 22
Remote Space Temperature
From Page 4
120
44
RD-WMB-THC
From Page 2
S22r1S
Rd - Local Space Temperature
From Page 3
100
S22o1S
t2e
E
0
F
S22r1S
F
G27D
B
J or
K or
L or
M
S22o1S H
F19D
D
Actual space temperature
To Page(s) 11,
GATE
D = F when B = 1
48
Space Temperature
S2
S
INTERNAL
DegC
40
10
0
0
Disabled
Disabled
COMB
47
Actual space temperature
K12D = 22
Remote Space Temperature
From Page 4
80
V
F19D
D
J Comb.
K Comb.
L Comb.
M Comb.
EG
EH
F18
G27
G
Out - Local Space Temperature
From Page 3
90
E
K12D
Select temperature 1=Remote
t2e
110
F17D
F18D
E
K12D
F
W34D
B
W34D = 0
Temperature Select 1=Remote
From Page 5
F19
Units
High Alarm Limit
Low Alarm Limit
High Alarm Delay
Low Alarm Delay
Low Alarm
High Alarm
D
GATE
D = F when B = 1
70
Space Temperature
60
P1
S2V
S
15 Min
100
Period
Records
SYNC
50
40
30
20
10
Drawing Reference
SET-019-014-09
Page Details
Discharge and Space Temp
SET Strategy
Designed By:
Trend Control Systems
D60D 3201 DA65 8FD9 921A 697A 87
Issue
3
Revision
-
00
Checked By
Project Number:
1
Date:
Outstation:
014
Page:
4/4/2016
09 of 18
10
20
30
40
50
180
S23o1S
170
Out - Local Setpoint Adjust
From Page 3
W35D = 0
160
SP Offset Select 1=Remote
From Page 5
t2e
150
RD-WMB-THC
From Page 2
70
80
90
Offset Range
From Page 4
G31
E
J or
K or
L or
M
S23o1S F
W35D
G
t2e
H
EH
FH
G
J Comb.
K Comb.
L Comb.
M Comb.
D
130
Remote Setpoint Offset
From Page 4
F21D
E
K13D
F
G31D
Room display offset value
From Page 10
S23V
110
Local Setpoint Adjust
From Page 3
t2e
100
F
t2e
B
F
G31D
B
K6D = 8
Standby Deadband
From Page 4
G21D
70
F
G21D
B
Unit - standby
From Page 8
OCC Deadband
From Page 4
F21
F24D
E
F22D
G
0.05
F
W36D = 0
HeatCool Setpoint 1=Separate
From Page 5
0
F
W36D
PROXIMITY
G31D
F23D
E
t2e
F
D
Eco mode selected deadband
From Page 10
GATE
30
K14D
E
K7D
F
W36D
B
20
K8D = 20.5
Cooling Setpoint
From Page 4
10
J or
K or
L or
M
G
H
e
fgh
J Comb.
K Comb.
L Comb.
M Comb.
D
E
F30D
F
G18D
GATE
B
G18D
Unit - occupied
From Page 8
F32
F
W36D
B
E
1
F
E
F46D
G
1
F
MULTIPLY
W51D = 1
Page Details
Heating Cooling Setpoints
E
K51D
F
W51D
B
F43
D
GATE
D = F when B = 1
55
Eco mode selected deadband
To Page(s) 10,
Room display offset value
F47
D
DIVIDE
F47D
E
F48D
F
F44D
B
F48
F48D
D
Room display offset value
To Page(s) 10,
GATE
D = F when B = 1
53
1
G
H
1
E
-1
F
H
Minutes to seconds
1
E
K2D
G
60
F
MULTIPLY
E
0.5
F
F35D
F
B
G
E
1
F
0.5
G
F35
H
D
PROXIMITY
81
S3
S
INTERNAL
DegC
30
-30
0
0
Disabled
Disabled
K47D = 24
Setpoint Highlimit
From Page 2
78
F38
V
F42D
ADD/SCLR
Units
High Alarm Limit
Low Alarm Limit
High Alarm Delay
Low Alarm Delay
Low Alarm
High Alarm
Heat setpoint
D
GATE
F38D
E
1
F
F40
D
D = F when B = 1 F28D
Setpoint offset
From Page 10
75
1
H
E
F35D
F
79
COMPARATOR
D = 1 when F > E
ADD/SCLR
D = (E * G) + (F * H)
GATE
F36D
E
F35D
F
F37D
D60D 3201 DA65 8FD9 921A 697A 87
E
1
F
1
G
F39D
F39
F41
0.5
E
0.5
F
F40D
G
F42
D
F41D
H
ADD/SCLR
D = (E * G) + (F * H)
H
ADD/SCLR
D = (E * G) + (F * H)
F42D
D
B
GATE
Issue
3
F28D
D
77
Maximum setpoint
D = F when B = 1
Trend Control Systems
Actual setpoint
Cool setpoint
D
F36
80
ADD/SCLR
D = (E * G) + (F * H)
F37
F36D
Heat setpoint
To Page(s) 11,
G
F28D
Heat cool setpoint overlap
ADD/SCLR
D
F33D
F
F40D
D
H
G
0.05
F44
E +/- F
Setpoint Lowlimit
From Page 2
Minimum setpoint
Heat setpoint - deaband
F32D
H
F37D
K44D
K48D = 18
76
ADD/SCLR
E
Setpoint
D = (E * G) + (F * H)
F36D
-0.5
Units
Pin Level
Top of Range
Bottom of Range
F42D
F45
G
73
F
D
KNOB
DegC
79
K47D
K48D
D
D=G*E*F
F34
0.5
K44
t2O5V
ADD/SCLR
Setpoint no offset
D
Room display not changed
Room Display Setpoint
83
F25
52
51
D = (E * G) + (F * H)
E
E
Setpoint t2O5V
G
F35D
1
F46
D
D = (E * G) + (F * H)
F34D
Room display not changed
To Page(s) 10,
Room display changed value
On Delay
Minimum On
Off Delay
F45D
Cool setpoint + deadband
SET Strategy
Designed By:
0
Operating Mode 0=Comfort 1=ECO
From Page 6
D = F when B = 1
Drawing Reference
SET-019-014-10
K51D = 3
ECO Mode Deadband Increase
From Page 6
D
F36D
F34D
D
82
Setpoint offset
To Page(s) 10,
D
Room display calculated change
F26D
61
74
F33
250
F43D
K44D
D = (E * G) + (F * H)
Selected cool setpoint
K8D
F43D
GATE
E
S
Calculated deadband
D
71
K14D
F
GATE
COMB
D
D = F when B = 1
240
Eco mode selected deadband
54
D
K2D = 60
F31
GATE
230
D
63
0
0
F25D
Setpoint Adjust Timeout
From Page 4
F31D
Deadband 1=OCC
F29D
D = F when B = 1
K14D = 22
Remote Setpoint
From Page 4
F27D
D
69
F30
220
F28D
D=G*E*F
G33
72
70
Heating Setpoint
From Page 4
G
TIMER
F44D
F29
Selected heat setpoint
K7D = 19.5
E
F26D
F27
Adjustment active
G32
G31D
Room display not changed
From Page 10
D = F when B = 1
40
B
Value changed
D
GATE
B
210
F44D
RD-WMB-THC
From Page 2
OCC deadband select 1=0
E
200
F28
62
F23
E +/- F
D
68
K4D
F
G33D
G32D
D = F when B = 1
K4D = 1
60
F22D
GATE
Value has not changed
F43D
K6D
190
1
D = F when B = 1
59
GATE
E
E
D
B
Deadband 0=NOCC 1=Standby
K5D
180
D=F(G/E)
F44D
80
0
D = F when B = 1
67
K5D = 25
170
Active setpoint offset
F24
F
D
D = F when B = 1
NOCC Deadband
From Page 4
65
GATE
t2e
RD-WMB-THC
From Page 2
90
D
E
F23D
Select setpoint 1=Remote
From Page 10
50
E
1
F24D
F22
E
S23V
K3D
F22D
Selected setpoint adjustment
F48D
160
Setpoint offset
Last change value
56
F48D
150
F26
60
D = F when B = 1
120
140
66
Select setpoint 1=Remote
To Page(s) 10,
COMB
B
130
D = F when B = 1
Selected setpoint offset
K13D = 0
120
Selected offset range
G31D
58
140
110
K3D = 2
Select setpoint 1=Remote
S23r1S
100
64
57
S23r1S
Rd - Local Setpoint Adjust
From Page 3
60
Revision
-
00
Actual setpoint
To Page(s)
F41D
Cool setpoint
To Page(s) 11,
Checked By
t2I15V
Project Number:
1
Date:
Outstation:
014
Page:
Setpoint
3/24/2016
10 of 18
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
180
170
Frost Condition 1=Frost
From Page 4
G20D
Unit - unoccupied
From Page 8
150
Heat setpoint
From Page 10
Loop override required
W12D = 0
160
F40D
86
W12D
G20D
F
0
G
0
H
EF
140
J or
K or
L or
M
Actual space temperature
From Page 9
87
W15D = 0
110
F40D
Heating loop enable
G16D
E
W15D
F
F78D
G
0
H
100
efg
Heat setpoint
From Page 10
G37
J or
K or
L or
M
D
COMB
G36D
A
F19D
P
F40D
O
nul
U
98
L
L1
3
E
F52D
G
4
F
LOOP
S
5
6
30
Reschedule Time
Gain
Integral Time
Deadband
0
E
F51D
G
90
91
1
E
-1
F
L1D
G
L2D
H
F51
90
E
F51D
G
100
F
0
A
F19D
P
F41D
O
G38
nul
U
J or
K or
L or
M
0
L
60
F41D
89
Cool setpoint
From Page 10
Cooling loop enable
F78D
Fan control off selected
From Page 13
30
F78D
G
0
H
eFg
G36D
G
G39
J or
K or
L or
M
F54D
H
EG
gH
J Comb.
K Comb.
L Comb.
M Comb.
G39D
D
Heating required
To Page(s) 14,
COMB
Heating Demand
D
HYST BAND
D
COMB
J Comb.
K Comb.
L Comb.
M Comb.
P2
S11V
S
15 Min
100
Period
Records
SYNC
F52D
96
Heat demand
To Page(s) 12,
F52
Heating Demand
S11
S
INTERNAL
%
101
-1
0
0
Disabled
Disabled
RSCL TO
L2
F57
RSCL TO
F51D
G
-100
F
Fan demand
F57D
E
1
F
1
G
F59
F59D
D
101
E
F58D
F58
H
Fan demand
To Page(s) 14,
ADD/SCLR
D = (E * G) + (F * H)
D
Cooling Demand
RSCL TO
D=100(G-E)/(F-E)
D
G38D
S
5
-5
30
Reschedule Time
Gain
Integral Time
Deadband
0
E
F51D
G
-90
Period
Records
S12
S
INTERNAL
%
101
-1
0
0
Disabled
Disabled
RSCL TO
F53D
Cool demand
To Page(s) 12,
Cooling required
3
E
F53D
G
4
F
F55
D
HYST BAND
V
F53D
D
95
20
SYNC
97
D=100(G-E)/(F-E)
10
S
15 Min
100
Cooling Demand
F53
F
P3
S12V
94
Cool demand
LOOP
Units
High Alarm Limit
Low Alarm Limit
High Alarm Delay
Low Alarm Delay
Low Alarm
High Alarm
102
D
Fan cool demand
-90
V
F52D
D
D=100(G-E)/(F-E)
ADD/SCLR
D = (E * G) + (F * H)
Cool loop
F
F
100
90
W15D
E
F56D
F54
F
D
E
F56D
Fan heat demand
70
250
Heating required
D=100(G-E)/(F-E)
Heat cool demand
G16D
HYST BAND
Heat demand
D
80
40
F
92
90
50
240
E=Level F=Band
G37D
J Comb.
K Comb.
L Comb.
M Comb.
230
99
D
Heating requested
F19D
Summer Mode 1=Summer
From Page 4
F56
93
130
G16D
G
COMB
Heat loop
Unit interrupt
From Page 8
E
F40D
D
88
120
F19D
E=Level F=Band
J Comb.
K Comb.
L Comb.
M Comb.
220
Heating below setpoint
1
G36
E
210
98
F19D
Actual space temperature
From Page 9
200
Units
High Alarm Limit
Low Alarm Limit
High Alarm Delay
Low Alarm Delay
Low Alarm
High Alarm
F55D
Cooling required
To Page(s) 14,
E=Level F=Band
Drawing Reference
SET-019-014-11
Page Details
Heating Cooling Demands
SET Strategy
Designed By:
Trend Control Systems
D60D 3201 DA65 8FD9 921A 697A 87
Issue
3
Revision
-
00
Checked By
Project Number:
1
Date:
Outstation:
014
Page:
3/24/2016
11 of 18
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
180
106
F52D
Heat demand
From Page 11
170
F53D
Cool demand
From Page 11
160
Heat cool value select
F52D
E
F53D
F
W15D
B
W15D = 0
Summer Mode 1=Summer
From Page 4
110
109
F61
Heat Cool Valve
Heat cool valve demand
D
107
GATE
Override or balance select
K24D = 0
D = F when B = 1
Heat Cool Valve Override Value
From Page 5
G65D
150
Water balance required
From Page 15
K24D
E
100
F
G65D
B
F62
E
F62D
F
G41D
B
D5
F63
F63D
D
GATE
360
0
0
F63D
GATE
l
5
S
TIME PROP.
D = F when B = 1
D
D = F when B = 1
Period
Override Enable
Override Value
Heat cool valve demand
To Page(s) 17,
108
140
F61D
Valve override required
130
W24D = 0
Valve Override 1=Enabled
From Page 5
W32D = 1
120
Overrides 0=Disabled 1=Enabled
From Page 5
G65D
E
0
F
W24D
G
G41
J or
K or
L or
M
W32D
H
E
GH
J Comb.
K Comb.
L Comb.
M Comb.
110
D
COMB
G41D
Valve override required
To Page(s) 18,
100
90
80
70
60
50
40
30
20
10
Drawing Reference
SET-019-014-12
Page Details
Heat Cool Valve
SET Strategy
Designed By:
Trend Control Systems
D60D 3201 DA65 8FD9 921A 697A 87
Issue
3
Revision
-
00
Checked By
Project Number:
1
Date:
Outstation:
014
Page:
3/24/2016
12 of 18
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
180
121
122
Room Display Fan Speed
Selected fan speed adjustment
170
t2e
160
RD-WMB-THC
From Page 2
K45D
E
4
F
t2e
B
F72
D
Fan State t2O7V
t2O7V
123
enum
79
255
0
D = F when B = 1
F72D
150
E
K15D
F
G46D
B
F73
126
GATE
Remote Fan Speed
From Page 4
W39D = 0
Fan Speed Select 1=Remote
From Page 5
F73D
E
K15D
F
W39D
B
129
Fan control auto selected
4
E
F77D
G
0.01
F
D
4
E
F74D
F
F75D
B
F76D
D
Fan control auto selected
To Page(s) 14,
PROXIMITY
130
Fan speed selected
F74
F76
E +/- F
128
Remote fan speed selected
K15D = 4
130
Units
Pin Level
Top of Range
Bottom of Range
D
D = F when B = 1
140
D
KNOB
Remote fans speed adjustment
GATE
K45
Room Display Fan Speed
0 = Off
1 = Low
2 = Medium
3 = High
4 = Auto
255 = On
(1001-23)
Fan control off selected
F77
F78
D
F77D
E
0.9
F
F78D
D
GATE
D = F when B = 1
GATE
D = F when B = 1
Fan control off selected
To Page(s) 11,14,
COMPARATOR
D = 1 when F > E
125
Select fan speed 1=Remote
120
110
t2e
RD-WMB-THC
From Page 2
124
100
Local fan speed select
Remote Fan Speed
From Page 4
0
E
0
F
K15D
E
3.9
F
J or
K or
L or
M
G
t2e
H
H
G
J Comb.
K Comb.
L Comb.
M Comb.
COMB
F77D
Fan speed in range
G46
F71D
F71
K15D = 4
90
127
D
2
E
F74D
G
2
F
Fan speed selected
To Page(s) 14,
F75
131
D
Selected Fan Speed
S7
PROXIMITY
0 = Off
1 = Low
2 = Medium
3 = High
4 = Auto
(1001-7)
V
F77D
S
INTERNAL
E +/- F
t2I13V
Fan State Display
D
enum
4.5
-0.5
0
0
Disabled
Disabled
Units
High Alarm Limit
Low Alarm Limit
High Alarm Delay
Low Alarm Delay
Low Alarm
High Alarm
COMPARATOR
D = 1 when F > E
80
70
60
50
40
30
20
10
Drawing Reference
SET-019-014-13
Page Details
Fan Control - Variable Speed
SET Strategy
Designed By:
Trend Control Systems
D60D 3201 DA65 8FD9 921A 697A 87
Issue
3
Revision
-
00
Checked By
Project Number:
1
Date:
Outstation:
014
Page:
3/24/2016
13 of 18
10
20
30
40
50
60
70
80
90
180
100
110
120
130
140
150
Heating required
From Page 11
G20D
Unit - unoccupied
From Page 8
G16D
160
132
Unit interrupt
From Page 8
Fan demanded
G39D
150
Heating required
From Page 11
F55D
Cooling required
From Page 11
140
W45D = 0
Fan Off at Setpoint 1=Enabled
From Page 6
G20D
E
G47
J or
K or
L or
M
G39D
F
F55D
G
W45D
H
eFH
eGH
eh
J Comb.
K Comb.
L Comb.
M Comb.
130
G39D
E
G20D
F
G16D
G
J or
K or
L or
M
G47D
H
EFg
gH
J Comb.
K Comb.
L Comb.
M Comb.
210
220
230
240
250
134
D
COMB
135
G20D
Unit - unoccupied
From Page 8
COMB
F76D
Fan control auto selected
From Page 13
G47D
E
0
F
G20D
G
F76D
H
h
G
egH
G50
J or
K or
L or
M
Fan speed selected
From Page 13
G49D
Fan enabled to run
From Page 14
0
E
1
F
G49D
B
E
F79
F79D
F
G51D
B
142
Fan control off selected
From Page 13
D
GATE
F
Unit - unoccupied
From Page 8
G20D
G
F76D
F76D
H
H
G
J Comb.
K Comb.
L Comb.
M Comb.
Fan control auto selected
From Page 13
F80D
E
0.5
F
Unit interrupt
From Page 8
40
W27D = 0
139
J or
K or
L or
M
Fan demand
From Page 11
Fan manual demand
D
1
E
F80D
G
3
COMB
F
F81
F59D
E
F81D
F
G50D
B
W27D
F
Unit - unoccupied
From Page 8
G20D
G
G49D
G49D
H
G20D
30
Fan enabled to run
From Page 14
eg
eGH
F
E
F84D
F
G50D
B
156
G56D
S
INTERNAL
D
V
10.1
-0.5
0
0
Disabled
Disabled
GATE
Units
High Alarm Limit
Low Alarm Limit
High Alarm Delay
Low Alarm Delay
Low Alarm
High Alarm
Calculated fan speed
F90D
E
F83D
G
K40D
F
F91
D
K28D = 50
Fan Speed Override Value EC
From Page 5
F91D
E
K28D
F
G53D
152
151
EC Fan
Fan anti cycle seleted
RSCL FR
F86D
E
0
F
G55D
B
F86
D9
F88
F88D
D
GATE
9
S
ANALOGUE
D = F when B = 1
0
0
D
B
l
Override Enable
Override Value
GATE
W27D
E
W32D
F
0
G
F85D
H
EF
l
154
146
149
Fan speed override required
Fan on required
G53
J or
K or
L or
M
0.5
S
D = 1 when F > E
148
Anti cycling active
G54
0
0
E
J or
K or
L or
M
D9l
F
F87D
F
G54D
G
F89D
H
fG
EGh
Gh
J Comb.
K Comb.
L Comb.
M Comb.
D
D
COMPARATOR
D = 1 when F > E
COMB
Fan Running
I5
F89D
F89D
S
S
D
0
Alarm Delay
0
Required State
Disabled State Alarm
Hours Run
Starts
145
Override Enable
Override Value
Override speed off
TIMER
F85
K28D = 50
Fan Speed Override Value EC
From Page 5
TIMER
0.5
E
F
COMPARATOR
S
DIGITAL
D
On Delay
Minimum On
Off Delay
D
COMB
F89
G55
G55D
E
D
F86D
Fan enabled
Fan anti cycle active
F87
J Comb.
K Comb.
L Comb.
M Comb.
1
150
INTERNAL
G56
SET Strategy
Designed By:
V
D9l
144
GATE
Delayed fan start
R1L
0
0
SYNC
S17
F90
Effective fan speed
GATE
D1
R1L
Period
Records
153
D
D
P5
S
15 Min
100
Minimum fan speed select
K39D
F83
Occupation Relay
G52D
Actual EC Fan Speed
S17V
Actual EC Fan Speed
147
157
J Comb.
K Comb.
L Comb.
M Comb.
COMB
D=(G/100)(F-E)+E
Fan Override 1=Enabled
From Page 5
COMB
Page Details
Fan Control - Variable page 2
B
K40D = 70
W32D = 1
D
G49D
Fan enabled to run
To Page(s) 14,
D = F when B = 1
Maximum Fan Speed Setpoint
From Page 5
Overrides 0=Disabled 1=Enabled
From Page 5
Local Address
Drawing Reference
SET-019-014-14
F
F82D
W27D = 0
RSCL TO
D=100(G-E)/(F-E)
J or
K or
L or
M
D
D = F when B = 1
G52
10
J Comb.
K Comb.
L Comb.
M Comb.
F84
D = F when B = 1
D
Fan power required
E
E
Fan required speed
155
G16D
Fan Override 1=Enabled
From Page 5
H
D = F when B = 1
50
G16D
0
COMPARATOR
F59D
G51
J or
K or
L or
M
0
141
Fan control required
0
E
D = 1 when F > E
137
E
K39D
F82
GATE
F78D
G20D
140
F80
D = F when B = 1
F78D
G
G49
Off fan speed select
Fan speed = off
D = F when B = 1
D
0
K39D = 37
Minimum Fan Speed Setpoint
From Page 5
COMB
D
Fan on value select
100
F77D
F
143
Minimum Fan Speed Setpoint
From Page 5
Fan manual value select
136
E
0
D
J Comb.
K Comb.
L Comb.
M Comb.
138
110
G48D
Manual fan speed enabled
D
F77D
20
200
Fan enabled to run
120
60
190
G48
K39D = 37
70
180
133
170
80
170
Fan required
G39D
90
160
K28D
E
20
F
D
0
0
300
On Delay
Minimum On
Off Delay
F89D
Fan enabled
To Page(s)
COMPARATOR
D = 1 when F > E
Trend Control Systems
D60D 3201 DA65 8FD9 921A 697A 87
Issue
3
Revision
-
00
Checked By
Project Number:
1
Date:
Outstation:
014
Page:
3/24/2016
14 of 18
10
20
30
40
50
60
70
80
90
180
SB - Water Balance ON Lan
I101
Service Button Mode 1=Enabled
From Page 5
S
W31D
E
I101S
F
101 c
EXTERNAL
0
Alarm Delay
0
Required State
Disabled State Alarm
Hours Run
Starts
SB - Water Balance OFF Lan
I102
G
0
H
EF
EG
J Comb.
K Comb.
L Comb.
M Comb.
0
Alarm Delay
0
Required State
Disabled State Alarm
Hours Run
Starts
I103
W31D
E
I101S
F
I103S
G
0
H
EF
EG
S
103 c
EXTERNAL
110
0
Alarm Delay
0
Required State
Disabled State Alarm
Hours Run
Starts
D
170
180
190
159
164
Water balance iccoms disable
G61D
S
COMB
On Delay
Minimum On
Off Delay
200
210
220
230
240
250
G66
G62D
E
0
F
0
G
0
H
e
J Comb.
K Comb.
L Comb.
M Comb.
J or
K or
L or
M
D
TIMER
0
0
300
D
COMB
G63
J or
K or
L or
M
D
G65D
COMB
W31D
I104
I102S
S
EXTERNAL
0
Alarm Delay
0
Required State
Disabled State Alarm
Hours Run
Starts
E
F
Water balance required
G63D
E
J or
K or
L or
M
F
G64
0
G
J or
K or
L or
M
W28D
H
E
fH
J Comb.
K Comb.
L Comb.
M Comb.
G
0
H
EF
EG
J Comb.
K Comb.
L Comb.
M Comb.
D
COMB
163
G65
G64D
I104S
Water balance required
To Page(s) 12,
162
J Comb.
K Comb.
L Comb.
M Comb.
Water balance disable
104 c
90
160
G62
161
SB - Water Balance OFF Unit
100
150
Water balance enable
SB - Water Balance ON Unit
120
140
160
S
EXTERNAL
140
J or
K or
L or
M
130
Water balance iccoms required
G61
I102S
102 c
130
120
158
170
150
110
Service button WB enable
W31D = 1
160
100
Water balance iccoms
Water Balance 1=Enabled
D
N6
W28
G65D
W28D
D
L
W28S
R
SWITCH
60
Pin Level
Trend
COMB
3
0
1
GLOBAL TO
Remote Attributes
Remote Lan
Message Interval
Failed Bit
80
70
Required Action
Water Balance On for the Lan
Water Balance Off for the Lan
Water Balance On for the Unit
Water Balance Off for the Unit
60
50
40
Phase 1
No Press
Press
No Press
Press
Phase 2
No Press
No Press
Press
Press
Phase 3
No Press
No Press
No Press
No Press
30
20
10
Drawing Reference
SET-019-014-15
Page Details
Service Button - Water balance
SET Strategy
Designed By:
Trend Control Systems
D60D 3201 DA65 8FD9 921A 697A 87
Issue
3
Revision
-
00
Checked By
Project Number:
1
Date:
Outstation:
014
Page:
3/24/2016
15 of 18
10
20
30
40
50
60
70
80
90
180
SB - Occupancy ON Lan
Service Button Mode 1=Enabled
From Page 5
I105
S
W31D
E
I105S
F
105 c
EXTERNAL
0
Alarm Delay
0
Required State
Disabled State Alarm
Hours Run
Starts
SB - Occupancy OFF Lan
I106
G
0
H
EF
EG
J Comb.
K Comb.
L Comb.
M Comb.
0
Alarm Delay
0
Required State
Disabled State Alarm
Hours Run
Starts
I107
W31D
E
I105S
F
I107S
G
0
H
EF
EG
S
107 c
EXTERNAL
110
0
Alarm Delay
0
Required State
Disabled State Alarm
Hours Run
Starts
I108
S
108 c
EXTERNAL
90
160
170
180
190
166
D
G71D
S
COMB
210
220
230
240
250
170
G76
G72D
E
0
F
0
G
0
H
e
J Comb.
K Comb.
L Comb.
M Comb.
J or
K or
L or
M
D
TIMER
0
0
300
200
Occupancy iccoms disable
G72
On Delay
Minimum On
Off Delay
D
COMB
G73
J or
K or
L or
M
D
G75D
COMB
G73D
E
168
G74D
F
0
G
F9D
H
EH
Fh
J Comb.
K Comb.
L Comb.
M Comb.
0
Alarm Delay
0
Required State
Disabled State Alarm
Hours Run
Starts
W31D
E
I106S
F
Service button occ active
G74
J or
K or
L or
M
I108S
G
0
H
EF
EG
J Comb.
K Comb.
L Comb.
M Comb.
Service button occ active
To Page(s) 8,
169
J Comb.
K Comb.
L Comb.
M Comb.
Occupancy disable
SB - Occupancy OFF Unit
100
150
Occupancy enable
SB - Occupancy ON Unit
120
140
167
S
EXTERNAL
140
J or
K or
L or
M
130
Occupancy iccoms required
G71
I106S
106 c
130
120
165
170
150
110
Service button Occ enable
W31D = 1
160
100
D
COMB
G75
J or
K or
L or
M
Occupancy Iccoms
N7
K11D = 1
Remote Occupancy
From Page 8
D
K11D
Trend
COMB
3
0
1
0
L
K11V
R
GLOBAL TO
Remote Attributes
Remote Lan
Message Interval
Significant Change
Failed Bit
F9D
80
Unit not in occ mode
From Page 8
70
Required Action
Occupied for the Lan
Unoccupied for the Lan
Occupied for the Unit
Unoccupied for the Unit
60
50
40
Phase 1
No Press
Press
No Press
Press
Phase 2
No Press
No Press
Press
Press
Phase 3
Press
Press
Press
Press
30
20
10
Drawing Reference
SET-019-014-16
Page Details
Service Button - Occupancy
SET Strategy
Designed By:
Trend Control Systems
D60D 3201 DA65 8FD9 921A 697A 87
Issue
3
Revision
-
00
Checked By
Project Number:
1
Date:
Outstation:
014
Page:
3/24/2016
16 of 18
10
20
30
40
50
60
70
80
90
100
180
120
130
140
150
160
170
180
190
200
230
240
250
Power kW (D) = (Water Supply Temp DegC (E) – Space Temp DegC (F)) * Coil Duty kW/degK (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I)
Power Btu/s (D) = (Water Supply Temp DegF (F) – Space Temp DegF (E)) * Coil Duty Btu/sDegF (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I)
Cooling Power = (Space temperature – Cooling medium temperature) * Coil duty * Valve position / 100
172
Power kW (D) = (Space Temp (E) – Water Supply Temp (F)) * Coil Duty kW/degK (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I)
Power Btu/s (D) = (Space Temp DegF (E) – Water Supply Temp DegF (F)) * Coil Duty Btu/sDegF (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I)
(1001-25)
Heating coil duty max speed
0
Heating Coil Duty Fan Off >>>
Heating Coil Duty Max Speed >>>
E
F107
0.327778 F
I5S
Fan Running
From Page 14
I5S
140
B
D
D = F when B = 1
Actual EC Fan Speed
From Page 14
130
1 kW = 0.948608 Btu/s
1 hp = 0.7074163 Btu/s
1 Btu/h/3600 = 1 Btu/s
173
Calculated heating duty
GATE
S17V
F107D
E
0.1
G
S17V
F
F108
189
K19D = 50
Water Flow Temperature
From Page 4
D
S2V
MULTIPLY
Space Temperature
From Page 9
D=G*E*F
120
F63D
Heat cool valve demand
From Page 12
Heating coil energy level
K19D
E
S2V
F
F108D
G
F118
110
Heat and cool energy level
D
F63D
H
0.01
I HEAT METER
K19D = 50
100
Water Flow Temperature
From Page 4
175
90
F63D
Cooling coil duty max speed
Cooling Coil Duty Fan Off >>>
0
Cooling Coil Duty Max Speed >>>
I5S
Fan Running
From Page 14
E
0.333333 F
I5S
B
Heat cool valve demand
From Page 12
F110
70
S17V
Actual EC Fan Speed
From Page 14
F110D
E
0.1
G
S17V
F
178
60
Fan Duty Maximum Speed kW >>> 0.16
I5S
Fan Running
From Page 14
I5S
E
B
F
F111D
G
H
F63D
H
0.01
I HEAT METER
Actual EC Fan Speed
From Page 14
E
0.1
G
S17V
F
30
I5S
Fan Running
From Page 14
F111
E
F120D
F
I5S
B
D
Occupation Relay Duty kW>>
D1l
Occupation Relay
From Page 14
0.5
F
D1l
B
kWh
500
-1
0
0
Disabled
Disabled
F122
D
GATE
F122D
E
1
F
K52D
G
F123
197
Unit energy consumption
D
F121D
H
ADD/SCLR
D = (E * G) + (F * H)
F114
SET Strategy
Designed By:
G
3600
F
G81D
H
F124
∫dt
D
INTEGRATOR
D=D+(G*seconds/F)
Energy Meter 1=Reset
D
F1D
MULTIPLY
One shot switch reset
From Page 3
F1D
192
60
D
F114D
E
1
F
1
G
F116D
Meter reset
15 minute pulse
F121
30 minute pulse
T1r
Trend Control Systems
D60D 3201 DA65 8FD9 921A 697A 87
ADD/SCLR
Issue
3
E
T1o
F
T1q
G
T1r
H
E
G
J Comb.
K Comb.
L Comb.
M Comb.
60 minute pulse
H
Revision
-
00
Checked By
G81
W52D
T1q
D
GATE
196
D
Pin Level
T1o
Fan and electric heater energy
F116
W52
SWITCH
D = (E * G) + (F * H)
Page Details
Virtual Energy Meter
F123D
195
D = F when B = 1
Drawing Reference
SET-019-014-17
Units
High Alarm Limit
Low Alarm Limit
High Alarm Delay
Low Alarm Delay
Low Alarm
High Alarm
194
183
E
V
Unit total energy level
MULTIPLY
Occupation relay duty
0.01
SYNC
D = F when B = 1
D=G*E*F
20
Period
Records
S
INTERNAL
Heating coolng load
0
Calculated fan duty
F113D
30 Min
200
F124D
193
179
GATE
ADD/SCLR
S51
K52D = 1
S17V
10
F119D
P6
S
D
Power Conversion Factor
From Page 6
D = F when B = 1
40
G
Unit Energy Meter
D=G*E*F
D
1
198
K19D
F113
F
Unit Energy Meter
S51V
F119
E
Fan duty max speed
0
F120
D = (E * G) + (F * H)
S2V
Calculated cooling duty
GATE
F
Coiling coil energy level
176
D = F when B = 1
E
1
D
D=0 if F>E Else D=(E-F)*G*H*I
D
F118D
190
S2V
Space Temperature
From Page 9
(1001-26)
191
D=0 if F>E Else D=(E-F)*G*H*I
50
220
Heating Power = (Heating medium temperature – Space temperature) * Coil duty * Valve position / 100
160
80
210
Heat exchanger power estimation.
170
150
110
J or
K or
L or
M
D
COMB
Project Number:
1
Date:
Outstation:
014
Page:
3/24/2016
17 of 18
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
180
170
160
150
140
130
120
Slave Remote Space Temp
N1
S2V
110
Space Temperature
From Page 9
S2V
Trend
3
0
0
0.1
100
L
K12V
R
GLOBAL TO
Remote Attributes
Remote Lan
Message Interval
Significant Change
Slave Remote Setpoint
90
N2
S3V
Setpoint
From Page 10
S3V
Trend
80
3
0
0
0.01
70
L
K14V
R
GLOBAL TO
Remote Attributes
Remote Lan
Message Interval
Significant Change
G41D
Valve override required
From Page 12
9
Slave Remote Occupancy
N3
S10V
Occupancy
From Page 8
S10V
60
Trend
3
0
0
0.5
50
Override active
L
K11V
R
G53D
Fan speed override required
From Page 14
GLOBAL TO
Remote Attributes
Remote Lan
Message Interval
Significant Change
A99 State Holder
Slave Remote Fan Speed
N4
S7V
40
Selected Fan Speed
From Page 13
S7V
Trend
3
0
0
0.5
30
L
GLOBAL TO
Remote Attributes
Remote Lan
Message Interval
Significant Change
20
K15V
R
A99 State Holder can hold a value to indicate the state of the unit.
The meaning of the value is user defined.
It is suggested a bit state approach be used where values 1, 2, 4, 8 ,16 etc
each indicating a separate operation.
Summing the values provide a state of the unit.
Suggested values:
1=
Addressed,
2=
Attributes Set,
4=
Pre-commissioned,
State Holder
8=
Commissioned,
A99 D
0
V
16 =
Witnessed,
Analogue
32 =
Backed up,
Read Alarm
64 =
(TBC) ,
Out. Limits Alarm
Low Alarm
128 = Has a Problem.
E
G53D
F
0
G
0
H
E
F
J Comb.
K Comb.
L Comb.
M Comb.
Alarm Group 1
0
Stratgey Override 1=Active
I11
G111D
D
0
Alarm Delay
0
Required State
Disabled State Alarm
Hours Run
Starts
COMB
Alarm Destination
e1
G
0
An exampled of its use.
Drawing Reference
SET-019-014-18
Page Details
IC Comms and Alarm Group
SET Strategy
Designed By:
D60D 3201 DA65 8FD9 921A 697A 87
0
H
ALARM ROUTE
Priority
ALARM DEST
1
0
Disabled
1
0
e.g 11 = 1+2+8 = Addressed, Attributes Set and Commissioned.
Trend Control Systems
S
F
E
High Alarm
10
o1D
D
N
ALARM GROUP
Issue
3
Revision
-
00
Checked By
S
INTERNAL
o1
g1O
O
L
J or
K or
L or
M
Alarm Route 1
g1
R
H
G111
G41D
Message Format
Retry Pause Int.
Inhibit Cleared
Alarm Address
Remote Lan
Project Number:
1
Date:
Outstation:
014
Page:
3/24/2016
18 of 18
Address Module
BACnet Application Module
Identifier
Device Instance
0
Attribute F
Manual Device Instance
0
Attribute G
Send I-Am at Startup
Disabled
Alarm Lan
0
Alarm Address
0
MSTP
Controller Version
Strategy Name
FCU EC Fan WT2
Revision
3
Project:
IQeco_Standard_Strategies_v3.2.1
Max Info Frames
10
Address / Network / IO
Project Number: 1
Date: 3/24/2016
Outstation:
Page: T01 of T05
014
Sensor
Number
Type Label
Units
1
2
Discharge Air Temperature
DegC
F16D
2
2
Space Temperature
DegC
F19D
3
2
Setpoint
DegC
F42D
7
2
Selected Fan Speed
enum
F77D
10
2
Occupancy
enum
F7D
11
2
Heating Demand
%
F52D
12
2
Cooling Demand
%
F53D
17
2
Actual EC Fan Speed
V
21
1
Local Discharge Air Temp
DegC
101 - 10k Therm DegC TBTS
0
1
22
1
Local Space Temperature
DegC
101 - 10k Therm DegC TBTS
0
2
23
1
Local Setpoint Adjust
DegC
102 - Knob TB 0.5deg trim0
31
2
Room Display Space Temp
DegC
t2O1V
32
2
Humidity
%RH
t2O2V
34
2
CO2
ppm
t2O4V
39
2
Outside Air Temp
DegC
A1D
40
2
Dewpoint
DegC
t2O3V
51
2
Unit Energy Meter
kWh
F124D
Project:
IQeco_Standard_Strategies_v3.2.1
S.E.T.
Part Number
Offset
Source
I/O
Channel
D9l
Sensor List
3
Project Number: 1
Date: 3/24/2016
Outstation:
Page: T02 of T05
014
Dig In
Number
Label
I/O
Channel Source
1
Unit Occupied
0
G18D
2
Unit Unoccupied
0
G20D
3
Unit In Bypass
0
G19D
4
Unit In Standby
0
G21D
5
Fan Running
0
F89D
11
Stratgey Override 1=Active
0
G111D
24
Window Pushbutton PIR
4
101
SB - Water Balance ON Lan
101
102
SB - Water Balance OFF Lan
102
103
SB - Water Balance ON Unit
103
104
SB - Water Balance OFF Unit
104
105
SB - Occupancy ON Lan
105
106
SB - Occupancy OFF Lan
106
107
SB - Occupancy ON Unit
107
108
SB - Occupancy OFF Unit
108
Project:
IQeco_Standard_Strategies_v3.2.1
Digital Inputs List
Project Number: 1
Date: 3/24/2016
Outstation:
Page: T03 of T05
014
Knob
Number
Label
Units
Value
Max. Level
Min. Level
Pin Level
1
Pushbutton PIR Timeout
min
30
1440
0
79
2
Setpoint Adjust Timeout
min
60
1440
0
79
3
Offset Range
DegC
2
10
1
79
4
OCC Deadband
DegC
1
2
0.5
60
5
NOCC Deadband
DegC
25
25
8
60
6
Standby Deadband
DegC
8
8
1
60
7
Heating Setpoint
DegC
19.5
24
8
79
8
Cooling Setpoint
DegC
20.5
34
18
79
11
Remote Occupancy
enum
F11D
3
0
79
12
Remote Space Temperature
DegC
22
30
0
79
13
Remote Setpoint Offset
DegC
0
10
-10
79
14
Remote Setpoint
DegC
22
24
18
79
15
Remote Fan Speed
enum
4
4
0
79
19
Water Flow Temperature
DegC
50
0
0
79
24
Heat Cool Valve Override Value
%
0
100
0
60
28
Fan Speed Override Value EC
%
50
100
0
60
39
Minimum Fan Speed Setpoint
%
37
50
0
79
40
Maximum Fan Speed Setpoint
%
70
100
50
79
44
Room Display Setpoint
DegC
t2O5V
K47D
K48D
79
45
Room Display Fan Speed
enum
t2O7V
255
0
79
47
Setpoint Highlimit
DegC
24
0
0
0
48
Setpoint Lowlimit
DegC
18
0
0
0
51
ECO Mode Deadband Increase
DegC
3
6
2
79
52
Power Conversion Factor
1
0
0
79
Project:
IQeco_Standard_Strategies_v3.2.1
Knobs List
Project Number: 1
Date: 3/24/2016
Outstation:
Page: T04 of T05
014
Switch
Number
Label
Status
Pin Level
State
1
Unit Bypass Request 1=Active
G9D
60
11
Remote Shutdown 1=Shutdown
0
79
12
Frost Condition 1=Frost
0
79
15
Summer Mode 1=Summer
0
79
24
Valve Override 1=Enabled
0
60
27
Fan Override 1=Enabled
0
60
28
Water Balance 1=Enabled
G65D
60
31
Service Button Mode 1=Enabled
1
79
32
Overrides 0=Disabled 1=Enabled
1
79
34
Temperature Select 1=Remote
0
79
35
SP Offset Select 1=Remote
0
79
36
HeatCool Setpoint 1=Separate
0
79
37
Pushbutton TETS KO 1=Fitted
0
79
39
Fan Speed Select 1=Remote
0
79
41
Window Mode 1=Enabled
0
79
42
0=Pushbutton 1=PIR
0
79
45
Fan Off at Setpoint 1=Enabled
0
79
51
Operating Mode 0=Comfort 1=ECO
1
60
52
Energy Meter 1=Reset
F1D
60
Project:
IQeco_Standard_Strategies_v3.2.1
Switch List
Project Number: 1
Date: 3/24/2016
Outstation:
Page: T05 of T05
014