Data Sheet FCU EC Fan WT2 Fan Coil Unit - EC Fan - Waterside 2 Pipe and 1 thermic valve. The IQeco standard strategy controls a fan coil unit’s heat/cool outputs, and electronically commutated fan, in response to a thermistor temperature sensor with a local setpoint knob and a local switch input (window contact, pushbutton, or Passive Infra Red movement detector input). The WT2 strategy is for waterside 2 pipe units controlling 1 thermic valve actuator. The strategy is designed to work with TB/TS Trend Thermistor Room Sensors. The strategy supports the fitting of a WMB Room Display module without further configuration. The strategy is designed for use with an IQeco31 and is part of the Plus library. Order code: IQE31/[y]/BAC/ECFANWT2P/[p] where [y] is unit type F = fixed, P = programmable and [p] is the voltage option. The strategy will also fit IQeco35 and IQeco38 and can be field downloaded to suitable controllers using SET and the standard solutions. Inputs The following real sensors and digital inputs are connected to the input channels and their values can be monitored by text comms (including IC Comms): Real Sensors IN 1: "Local Discharge Air Temp" (S21), the thermistor temperature sensor for the discharge air. IN 2: "Local Space Temperature" (S22), the thermistor temperature sensor for the space. IN 3: "Local Setpoint Adjust" (S23), the local setpoint adjustment potentiometer (scaled in the range -0.5 to +0.5). This generates a setpoint trim in the range -1°C to +1°C or -1°F to +1°F when the knob ‘Offset Range’ (K3) value is set to 2. Real Digital Inputs IN 4: "Window Pushbutton PIR" (I24) this input can be either a window contact which opens, or a pushbutton, or PIR (passive infra red occupation detector) which closes when the occupation override is required. The type of input is defined by switches ‘Window Mode 1=Enabled’ (W41) and ‘0=Pushbutton 1=PIR’ (W42). FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18-Apr-2016 1 FCU EC Fan WT2 Outputs OUT 1: "Occupation Relay" (D1), this output is used to switch power to the fan controller. OUT 5,6: "Heat Cool Valve" (D5), this outputs is connected to a thermic actuator. OUT 9: "EC Fan" (D9), this is connected to the speed input on the EC fan controller. Default Operation The behaviour of the strategy before any configuration of knobs as switches is as follows: The default occupancy state of the strategy is unoccupied. In most cases when the controller is powered on the fan outputs will not operate as the space temperature used for control will be within the deadband for the unoccupied state. There are 3 ways to take the strategy out of the unoccupied state: 1. Set Knob "Remote Occupancy" (K11) to 0. 2. Using a pushbutton connected to IN4. Press the pushbutton once; this should place the unit into bypass. The bypass state is active until another press of the pushbutton or timeouts after 30 minutes. 3. Use the service button to put the unit into occupied. Details are in "Service Button - Occupancy" section of the strategy datasheet. The fan output may not be operating for the following reasons: a. The fan anti cycling strategy is active. Once switched off the fan will not start for 5 minutes. b. Changes to the knobs and switches from the defaults are overriding the fan control. c. The occupancy state is unoccupied. WallBus Interface Eco This Standard Strategy can be used with WMB Units which provide Temperature, Humidity, DewPoint and CO2 values to internal Strategy Sensor Modules. When adding WMB Units to the system, 963, IQview8 and IQview4 and other User displays will discover these Sensor Modules and display them in their lists. WMB units which do not support Humidity or CO2 values will send a value of 0 to the 963 and user displays. To stop the User Display from showing any one Sensor Module delete the lable string in that module. For example to prevent the User Display from showing Humidity, delete the label ( $ parameter ) in sensor 32. You can delete parameters in fixed strategies using one of these methods: parameter viewer in SET system view, live adjust in SET drawing view or by a text comms message such as S32($=""). You cannot change connections between modules in this fixed strategy. The Strategy can operate with the new RS-WMB, RD-WMB and RV-WMB sensors which are detailed inTA201348. It can also operate with the older version of RD-WMB. The new WMB sensors are available with options for: Temperature - RD-WMB T, RS-WMB T, RV-WMB T Temperature and Humidity RD-WMB TH, RS-WMB TH, RV-WMB TH Temperature, Humidity and CO2 RD-WMB THC and RS-WMB THV. The Strategy is designed to operate with RD, RS and RV of all the available types. Sensors which do not support Humidity or CO2 will continue to scroll through all the variables with a display of 0 unless the input in the interface module is deleted. For RD-TH, RS-TH, RV-TH sensors Delete the PVid in t2I10V to prevent the RD displaying CO2 with the value 0 For RD-T, RS-T, RV-T sensors Delete the PVid in t2I10V to prevent the RD displaying CO2 with the value 0 Delete the PVid in t2I6V to prevent the RD or RV displaying Humidity with the value 0 Delete the PVid in t2I11Vto prevent the RD or RV displaying Outside Air Temperature with the value 0 2 FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18 Apr 2016 FCU EC Fan WT2 The RV sensors have configuration settings such as button graphics and CO2 thresholds. The Strategy does not allow you to link these settings to strategy. Configuration settings for RV can only be made through the display. See Trend Data sheet TA201354. For RV and RD meters you can display CO2 from a remote controller by setting up an IC comms to Sensor 34 and deleting the PVid in t2O4 so that the value in S34 is not overwritten. This standard solution does not support a CO2 sensor hard wired to the controller. Knobs Switches <21 The following knobs and switches are grouped by the role they are intended to play within the strategy. They can be monitored and changed by text comms (including IC Comms). Some can be monitored using display and directory modules (e.g. using IQView): Modules 1-10 11-20 21-30 31-40 41-50 51-60 Role Adjustments - Items the users may want to change. Remote Control - Items that are expected to receive IC Comms e.g. frost protection. Overrides - Items that enable control to be overridden e.g. heating override. Settings - Items that should be set up during commissioning. Options - Items that select an option or behaviour e.g. serial parallel fan. Energy - Items related to energy. Adjustments K1 ‘Pushbutton PIR Timeout’, this knob defines the time in minutes for which the activation of the pushbutton/PIR input overrides the unit into the occupied state. The default value is 30 minutes. K2 ‘Setpoint Adjust Timeout’, this knob defines the time in minutes for which any setpoint trim will be applied to the setpoint. The default value is 60 minutes. K3 ‘Offset Range’, this knob is used to define the range of ‘Local Setpoint Adjust‘ (S23). The ‘Local Setpoint Adjust‘ (S23) is scaled to give a range of -0.5 to +0.5; this is multiplied by the ‘Offset Range’ to give the setpoint trim which is applied to the ‘Remote Setpoint’(K14) to produce the ‘Setpoint’ (S3). The default value is 2°C or 2°F producing a value between -1°C to +1°C or -1°F to +1°F. K4 ‘OCC Deadband’, this knob defines the difference between the heating and cooling setpoints during occupation. The default value is 1°C or 2°F. K5 ‘NOCC Deadband’, this knob defines the difference between the heating and cooling setpoints during non-occupation. The default value is 25°C or 45°F. K6 ‘Standby Deadband’, this knob defines the difference between the heating and cooling setpoints during standby. The default value is 8°C or 15°F. K7 ‘Heating Setpoint’, this knob defines the heating setpoint when separate setpoints are selected using switch ‘HeatCool Setpoint 1=Separate’ (W36). The default value is 19.5°C or 67°F. K8 ‘Cooling Setpoint’, this knob defines the cooling setpoint when separate setpoints are selected using switch ‘HeatCool Setpoint 1=Separate’ (W36). The default value is 20.5°C or 69°F. W1 ‘Unit Bypass Request 1=Active’, this switch is set to ON if the unit is in bypass and can be used to put the unit into or out of bypass. The default state is OFF. Remote Control K11 ‘Remote Occupancy’, this knob defines unit’s occupancy state: 0(Occupied), 1(Unoccupied), 2(Bypass), 3(Standby). It can be overridden into bypass (equivalent to Occupied within the unit) from any occupation state by the pushbutton or from standby by the PIR. The state is overridden to unoccupied by the switch ‘Remote Shutdown 1=Shutdown’ (W11) or the window contact (IN24). The definition of the occupancy states are detailed below under Occupancy States. The default value is 1(Unoccupied). K12 ‘Remote Space Temperature‘, this knob is used instead of input ‘Local Space Temperature’ (S22) when the input has an out of limits or read alarm. It can also be used by setting switch ‘Temperature Select 1=Remote’ (W34) to ON. The default value is 22°C or 71°F. K13 ‘Remote Setpoint Offset‘, this knob is used instead of input ‘Local Setpoint Adjust’ (S23) to provide the setpoint trim. It is added to the ‘Remote Setpoint’ (K14) when the input (S23) has an out of limits or read alarm. It can also be used by setting switch ‘SP Offset Select 1=Remote’ (W35). The default value is 0°C or 0°F. K14 ‘Remote Setpoint‘, this knob is combined with the setpoint trim to provide the ‘Setpoint’ (S3). The default value is 22°C or 71°F. K15 ‘Remote Fan Speed‘, this knob is used to set the fan speed in the range of range: 0 (off), 1 (low), 2 (medium), 3 (high), or 4(auto). To ensure that the 'Remote Fan Speed' value is used when sensor ‘Local Fan Speed’ (S27) is fitted the switch 'Fan Speed Select 1=Remote' (W39) must set to ON. The fan will be switched off during non-occupation unless there is heating demand (fabric protection) which selects low fan speed. The default value is 4(auto). K19 ‘Water Flow Temperature’, this knob sets the temperature used to calculate the energy consumption of the unit. The default value is 50°C or 122°F. W11 ‘Remote Shutdown 1=Shutdown’, this switch when set to ON forces the unit into the unoccupied state, disables cooling, only allows sub-zero heating, and disables fabric protection during non-occupation. The default state is OFF. W12 ‘Frost Condition 1=Frost’, this switch when set to ON forces the unit into a frost condition during non-occupation. During the frost condition the heating demand is fixed at 98%. The default state is OFF. W15 ‘Summer Mode 1=Summer’, this switch selects the mode used to drive the output ‘Heat Cool Valve’ (D5). If the switch is set to ON (summer mode) the valve is driven from the cooling demand else the valve is driven from the heating demand. The default state is OFF. Knobs Switches 21 - 40 Overrides K24 ‘Heat Cool Valve Override Value’, this knob sets the value used to drive the heat cool valve output when switch ‘Valve Override 1=Enabled’ (W24) is enabled. The default value is 50%. FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18-Apr-2016 3 FCU EC Fan WT2 K28 ‘Fan Speed Override Value EC’, this knob sets the value used to drive the fan speed output when switch ‘Fan Override 1=Enabled’ (W27) is enabled. The analogue value 0 is OFF and 100 is full speed. The default value is 50. W24 ‘Valve Override 1=Enabled’, this switch when set to ON enables heat cool valve overridde and the heat cool valve output is set to the value on the knob ‘Heat Cool Valve Override Value’’ (K24). The default state is OFF. W27 ‘Fan Override 1=Enabled’, this switch when set to ON enables fan to be overriden and the fan outputs are set to the speed selected on the knob ‘Fan Speed Override Value EC’ (K28). The default value is OFF. W28 ‘Water Balance 1=Enabled’, this switch when set to ON forces all valve outputs to 100%. The default state is OFF. Settings K39 ‘Minimum Fan Speed Setpoint’, this knob defines the minimum speed permitted by the EC fan. The default value is 37%. K40 ‘Maximum Fan Speed Setpoint’, this knob defines the maximum speed permitted by the EC fan. The default value is 70%. W31 ‘Service Button Mode 1=Enabled’, this switch when set to ON allows the service button to be used as an input into the strategy. The default state is ON. W32 ‘Overrides 0=Disabled 1=Enabled’, this switch when set to ON allows the strategy overrides to be used. The default state is ON. W34 ‘Temperature Select 1=Remote’, this switch when set to ON forces the strategy to use the value from knob ‘Remote Space Temperature‘ (K12) and not sensor ‘Local Space Temperature’ (S22). The default state is OFF. W35 ‘SP Offset Select 1=Remote’, this switch when set to ON forces the control to use the value from knob ‘Remote Setpoint Offset‘ (K13) and not sensor ‘Local Setpoint Adjust’ (S23). The default state is OFF. W36 ‘HeatCool Setpoint 1=Separate’, this switch when set to ON enables the control to use separate setpoints for heating and cooling use knobs ‘Heating Setpoint’ (K7) and ‘Cooling Setpoint’ (K8). The default state is OFF. W37 ‘Pushbutton TETS KO 1=Fitted’, this switch when set to ON allows the control to utilise the override pushbutton operation of the TB/TS/KO range of thermistor room temperature sensors. The default state is OFF. W39 ‘Fan Speed Select 1=Remote’, this switch when set to ON forces the strategy to use the value from knob ‘Remote Fan Speed‘ (K15) and not sensor ‘Local Fan Speed’ (S27). The default state is OFF. Knobs Switches >41 Options W41 ‘Window Mode 1=Enabled’, this switch when set to ON forces the control to treat the digital input ‘Window Pushbutton PIR’ (I24) as a window contact. W42 ‘0=Pushbutton 1=PIR ‘, this switch is only used when switch ‘Window Mode 1=Enabled’ (W41) is set to OFF. Then the switch when set to ON treats the digital input ‘Window Pushbutton PIR’ (I24) as a passive infrared detector and when set to OFF treats the input as a pushbutton. The default state is OFF. W45 ‘Fan Off at Setpoint 1=Enabled’, this switch when set to ON will disable the fan when the unit is at setpoint and there is no heating or cooling demand. The default state is OFF. Energy K51 ‘ECO Mode Deadband Increase’, this knob defines the value that will be added to the existing deadbands when switch ‘Operating Mode 0=Comfort 1=ECO’ (W51) is set to ON. The default value is 3°C or 7°F. K52 ‘Power Conversion Factor’, this knob defines the scaling factor that will be multiplied with the heat meter module output to produce kW. 1kW = 0.948608 Btu/s. The default value is 1 when using kW and 0.948608 when using Btu/s. W51 ‘Operating Mode 0=Comfort 1=ECO’, this switch when set to ON enables the control to operate in eco mode and increase the deadband by the value on knob ‘ECO Mode Deadband Increase’ (K51). The default state is ON. W52 ‘Energy Meter 1=Reset’, this switch when set to ON will reset the energy meter. Once set the control automatically resets the switch to OFF. The default state is OFF. Window PushbuttonPIR Operation The external digital Input ‘Window Pushbutton PIR’ can be used as either a window contact, PIR or Override Pushbutton and its type configured by Switches ‘0=Pushbutton 1=PIR’ and ‘Window Mode 1=Enabled’’. In window mode (Switch ‘Window Mode 1=Enabled’ set to ON) the Input ‘Window Pushbutton PIR’ is configured to be a window contact. When the window contact is open the control will override the unit into Unoccupied. In pushbutton mode (Switch ‘0=Pushbutton 1=PIR’ set to OFF) the Input ‘Window Pushbutton PIR’ forces the unit into Bypass from any state for the time set ON Knob ‘Pushbutton PIR Timeout’. In PIR mode (Switch ‘0=Pushbutton 1=PIR’ set to ON) the Input ‘Window Pushbutton PIR’ will override the unit from Occupied or Standby into Bypass for at least the time set ON Knob ‘Pushbutton PIR Timeout’. Within the unit, the Bypass condition is treated the same as Occupied so that although Sensor ‘Occupancy’ shows separate Occupied and Bypass states, if Bypass is set then Inputs ‘Unit In Bypass’ and ‘Unit Occupied’ will both be set to ON. The Switch ‘Unit Bypass Request 1=Active’ can be used to stop or start the bypass condition. When Switch ‘Pushbutton TETS KO 1=Fitted’ is set to ON the external Sensor ‘Local Setpoint Adjust’ out of limits alarm is used to as the input for PIR or pushbutton override. Technical Description A single external digital Input ‘Window Pushbutton PIR’ is used as a window contact, PIR or Override Pushbutton to create a ‘PB PIR override active’ and ‘Unit interrupt’ digital signals. When used as a PIR or Pushbutton the input is only processed by the strategy at the rate of the counter module reschedule time. This is to ensure that only one press of the button is reacted to by the strategy. The strategy also supports the use of a TE/TS/KO for the override pushbutton using external Sensor ‘Local Setpoint Adjust’ and Switch ‘Pushbutton TETS KO 1=Fitted’. Commissioning Details 1. Configure strategy for the type of Input connected to Input ‘Window Pushbutton PIR’ using Switches ‘Window Mode 1=Enabled’ and ‘0=Pushbutton 1=PIR’. 4 FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18 Apr 2016 FCU EC Fan WT2 2. If override is provided by TB/TS/KO set Switch ‘Pushbutton TETS KO 1=Fitted’ to 1. 3. Set the time of Knob ‘Pushbutton PIR Timeout’ for the length of the bypass period required. Tip. Input ‘Window Pushbutton PIR’ can be configured as a status monitoring input e.g. filter dirty by changing the E parameter on function module ‘Input active’ to 100 and setting Switch ‘Window Mode 1=Enabled’ to 0. Remember to change the label on the input to indicate its function. Occupancy State The unit operates in either Occupied, Unoccupied, Bypass, and Standby modes as determined by the ‘Remote Occupancy’ setting. Occupied: The unit is on for normal operation and controls to a user defined setpoint. This is Comfort mode as defined in the European standard EN15500. Unoccupied: The unit is off, no fan, heating or cooling. The PIR has no effect although the override pushbutton will override the unit into bypass. This is Building Protection mode as defined in the European standard EN15500. Bypass: The unit has been put into occupation by the override pushbutton or the PIR (occupancy sensor). Standby: The unit is activated to reduce its energy consumption. In this mode either the override pushbutton or the PIR will put the unit back into occupied. This is Economy mode as defined in the European standard EN15500. Within the unit the Bypass condition is treated the same as Occupied but both inputs ‘Unit In Bypass’ and ‘Unit Occupied’ will be set to ON. When Switch ‘Remote Shutdown 1=Shutdown’ is set to ON it will override the unit into unoccupied. The same behaviour occurs if the unit is in window mode (Switch ‘Window Mode 1=Enabled’ set to ON) and the window contact on Input ‘Window Pushbutton PIR’ is not closed. Technical Description A single external digital Input ‘Window Pushbutton PIR’ is used as either a window contact, PIR or Override Pushbutton. The required occupancy states are decoded to digital signals. 0 = Occupied, 1 = Unoccupied, 2 = Bypass, 3 = Standby. The unit can also be put in to occupancy using the service pin. Discharge and Space Temp Technical Description With external sensor ‘Local Discharge Air Temp’ fitted the sensor value is gated through to internal sensors ‘Discharge Air Temperature’. The internal sensor 'Space Temperature' will use the value of either the external sensor 'Room Display Space Temp', when a Room Display module is fitted, or the value from external sensor ‘Local Space Temperature’, if fitted. If the external sensor has a ‘Read’ or ‘Out of limit’ alarm the value of input F on the respective gate module will be displayed on the internal sensor. Setting switch ‘Temperature Select 1=Remote’ to 1 forces the internal sensor ‘Space Temperature’ to use the value on input F of the gate module ‘Actual space temperature’. Heating Cooling Setpoints The heating and cooling setpoints can be configured to be separately adjusted or calculated. The selected setpoints have half the current deadband applied as defined by the occupation state. The value of the deadband is increased when not in occupation. The setpoint can also have an offset (trim) adjustment made locally, that will increase or decrease the required setpoint. Eco Features Local offset adjustment is valid for an adjustable time after which it is ignored until a change of the offset value is detected. The size of the deadband is increased when the unit is in ECO mode. Technical Description The setpoint is calculated from Knob ‘Remote Setpoint’ unless Switch ‘HeatCool Setpoint 1=Separate’ is set to 1 when Function ‘Selected heat setpoint’ and Function ‘Selected cool setpoint’ use Knobs ‘Heating Setpoint’ and ‘Cooling Setpoint’ respectively for they values. The ‘Heat setpoint’ is calculated by subtracting half the deadband, selected by the mode of occupation, from the value on Function ‘Selected heat setpoint’ and adding any value on Function ‘Setpoint offset’. The ‘Cool setpoint’ is calculated by adding half the deadband, selected by the mode of occupation, to the value on Function ‘Selected cool setpoint’ and adding any value on Function ‘Setpoint offset’. The ‘Heat setpoint’ and ‘Cool setpoint’ are each halved and combined to provide the ‘Setpoint’. The normal operation of ‘Setpoint offset’ with the external Sensor ‘Local Setpoint Adjust’ fitted is for the sensor value to be gated through Function ‘Selected setpoint offset’ and the value of Knob ‘Offset Range’ to be gated through Function ‘Selected offset range’. If the sensor has a ‘Read’ or ‘Out of limit’ alarm or Switch ‘SP Offset Select 1=Remote’ is set to 1 the strategy gates through the value of Knob ‘Remote Setpoint Offset’ on Function ‘Selected setpoint offset’ and a value of 1 through Function ‘Selected offset range’. If a Room Display module is fitted the strategy will automatically use the value on Knob 'Room Display Setpoint' to calculate any change in setpoint and feed this through as the offset value. Any change in the offset value is detected by the strategy and will start Logic timer ‘Adjustment active’. The offset value on Function ‘Selected setpoint offset’ is gated through Function ‘Active setpoint offset’ it is then scaled using the value on Function ‘Selected FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18-Apr-2016 5 FCU EC Fan WT2 offset range’. Function ‘Setpoint offset’ value is added to the ‘Minimum setpoint’ and ‘Maximum setpoint’ to provide the ‘Heat setpoint’ and ‘Cool setpoint’ respectively and is set to 0 after the time set on Knob ‘Setpoint Adjust Timeout’ has expired. Heating Cooling Demands Heating and cooling demands are calculated by comparing the space temperature with the relevant setpoint. If the space temperature is below the heating setpoint a heating demand is created and if the space temperature is above the cooling setpoint a cooling demand is generated, the greater the difference the larger the demand. To prevent hunting of the heating and cooling demands a deadband is employed to ensure a change equal to half the deadband is detected before a demand is generated or removed. When the heating or cooling demand reaches 100% the speed of the fan is increased. When a frost condition exists and the unit state is unoccupied the heating is enabled. Technical Description Both heating and cooling sides are controlled by different control loops. The heating loop is enabled whenever ‘Unit interrupt’ is set to 0 and ‘Summer Mode 1=Summer’ is set to 0. The cooling loop is enabled whenever ‘Unit interrupt’ is set to 0 and ‘Summer Mode 1=Summer’ is set to 1. Both loops are disabled if 'Fan control off selected' is set to 0. The heating loop compares the ‘Actual space temperature’ with the ‘Heating setpoint’. The proportional + integral (P+I) loop will modulate the heating output to maintain a constant space temperature. As the temperature decreases below the heating setpoint the heating output will modulate open. The heating output will be modulated closed as the temperature increases above the heating setpoint. The loop output is limited to the range 0 to 100%. The cooling loop compares the ‘Actual space temperature’ with the ‘Cooling setpoint’. The proportional + integral (P+I) loop will modulate the cooling output to maintain a constant space temperature. As the temperature increases above the cooling setpoint the cooling output will be modulated open. The cooling output will be modulated closed as the temperature decreases below the cooling setpoint. The loop output is limited to the range 0 to 100%. The integral time constant is the time for which the loop output will have added to it an amount equal to product of the error and the gain (i.e. equal to the proportional part) under conditions of constant error. If the error stays the same for the integral time constant, the loop output will double and will be 2G(E). The loops have the following default settings: heat loop gain = 6, cool loop gain = -5, both loop integral time constants = 30 minutes. These settings can be changed by text comms. The output from the loops (ignoring the integral action) is illustrated by the chart below: The heating loop will not operate until the ‘Actual space temperature’ drops below the ‘Heating setpoint’ by half the deadband e.g. Setpoint 22°C (72°F) deadband 4° = 22-2 = 20°C (72-4 = 68°F) during occupation. Similarly for cooling it must rise above the ‘Cooling setpoint’ by half the deadband. The loop gains are set to +6 and -5 by default which gives proportional bands of 16 and 20 °C (°F) and i.e. 100/6 and 100/5. When set to defaults, during occupation, this will give 100% heat at 4°C (39°F), and 100% cool at 44°C (111°F) ignoring the effect of the integral term. The loop outputs are added together and then split into separate heating and cooling outputs to prevent simultaneous heating and cooling. The separate demands are rescaled so the demand 0 to 90% drives the relevant valve output between 0 and 100% and the demand 90 to 100% increases the fan speed. When the heating or cooling demand is greater than 4.5% a respective ‘Heating 6 FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18 Apr 2016 FCU EC Fan WT2 required’ or ‘Cooling required’ signal will be set to 1. The ‘Heating required’ or ‘Cooling required’ signals are reset to 0 when the respective demand falls below 0.5%. The heating loop is overridden to 98% if the ‘Frost Condition 1=Frost’ is set to 1 and ‘Unit - unoccupied’ is set to 1. This will bring on the heating if the unit not in summer mode. Heat Cool Valve The cooling demand drives the Heat Cool valve when the switch ‘Summer Mode 1=Summer’ is ON when it is OFF the heating demand is used. A demand of 100% opens the valve fully and a demand of 0% closes the valve. The valve is fully opened when Switch ‘Water Balance 1=Enabled’ is ON. Technical Description The valve can be overridden, providing Switch 'Overrides 0=Disabled 1=Enabled' is set to 1, by setting Switch ‘Valve Override 1=Enabled’ to 1 and adjusting Knob ‘Heat Cool Valve Override Value’ to the required value between 100 and 0. The overrides are ignored and the valve is fully opened when Switch ‘Water Balance 1=Enabled’ is 1. Commissioning Details 1. The Heat Cool valve drive time should be set to match the fitted actuator. Fan Control - Variable Speed The fan is ON when the occupation state is occupied; bypass or standby and is OFF when unoccupied. The required speed of the fan is displayed on the sensor ‘Selected Fan Speed’ where 0 = OFF, 1 = Low, 2 = Medium, 3 = High and 4 = Auto. Low speed is the value set on knob 'Minimum Fan Speed Setpoint' and High speed is the values set on knob 'Maximum Fan Speed Setpoint'. Medium speed is the mid value between these two setpoints. If the ‘Selected Fan Speed’ is Auto, the fan will normally run at low speed, but as the fan demand increases, as a result of an increase in the heating or cooling demand, the fan speed will be increased to meet the demand, similarly the fan speed will be reduced as demand is met. The actual fan speed is displayed on the sensor ‘Actual EC Fan Speed’ and is a factor of 10 smaller than the demand i.e. Low = 'Minimum Fan Speed Setpoint' = 37 will display as 3.7. The fan has an anti cycling timer to protect it from excessive restarts. Eco Features The fan can be set to switch OFF whenever the unit is at setpoint i.e. no heating or cooling demand by setting Switch ‘Fan Off at Setpoint 1=Enabled’ to ON. The fan will restart when a heating or cooling demand exists. This is only applicable when the sensor ‘Selected Fan Speed’ is set to Auto (a value of 4). Technical Description The fan is enabled when the occupation state is occupied, bypass or standby and the unit interrupt signal is 0. The driver 'Occupation Relay' is enabled during occupation, time delayed based on the controller address, and is intended to be used to enable the fan controller. Automatic control is achieved by rescaling the fan demand set between the ‘Minimum Fan Speed Setpoint’ to the ‘Maximum Fan Speed Setpoint’. When the required to switch off the ‘Minimum Fan Speed Setpoint’ value is replaced with 0. The fan control can only be overridden when Logic ‘Unit - unoccupied’ is 0 by either Knob ‘Remote Fan Speed’ or the WMB Room Display module. The strategy selects the correct control depending on which items are present using the WMB Room Display module ‘I/O2 Failed status’ bit. The Knob ‘Remote Fan Speed’ is used when its value is less than 4 or when Switch ‘Fan Speed Select 1=Remote’ is set to 1. When used the knob has precedence over the external WMB Room Display module. The WMB Room Display module if fitted uses Knob ‘Room Display Fan Speed’ to display and adjust the speed. The fan control has an anti cycling timer that delays the time to restart after the fan stops thus preventing unwanted cycling of the fan. When electric heaters are included in the control the fan will run when Logic ‘Electric heat run on required’ is 1. The fan control can be overridden, providing Switch 'Overrides 0=Disabled 1=Enabled' is set to 1, by setting Switch ‘Fan Override 1=Enabled’ to 1 and adjusting Knob ‘Fan Speed Override Value EC’ to the required value. The anti cycle timer still operates under these circumstances. Commissioning Details 1. Set the ‘Minimum Fan Speed Setpoint’ 2. Set the ‘Maximum Fan Speed Setpoint’ 3. Confirm that Comparator 'Fan enabled' parameter E value is correctly set to indicate that the fan is enabled. 4. The Timer ‘Anti cycle active’ parameter F requires setting to ensure the minimum off time required for anti cycling the fan. 300 seconds = 5 minutes = 12 starts per hour. 5. The switch 'Fan Speed Select 1=Remote’ requires setting to 1 if the WMB Room Display is to be excluded from the control of the fan. FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18-Apr-2016 7 FCU EC Fan WT2 Service Button - Water balance Pressing the service button in a predefined sequence, when in service button mode, can initiate behaviour in the strategy to start and stop water balancing where all the valve outputs are set to 100% or 0% i.e. fully open or fully closed. The function is only available if Switch ‘Service Button Mode 1=Enabled’ is set to ON. For a full description of service pin mode refer to the Trend publication TE201089 IQeco Configuration Manual Issue 2 or greater. The service button press sequence for the required behaviour is as follows; Required Action Phase 1 Phase 2 Phase 3 Water Balance On for the Lan No Press No Press No Press Water Balance Off for the Lan Press No Press No Press Water Balance On for the Unit No Press Press No Press Water Balance Off for the Unit Press Press No Press Technical Description The service button can be used to initiate behaviour designed in the strategy; to achieve this behaviour the controller must be put into service button mode. Service button mode has 5 stages Entry, Phase 1, Phase 2, Phase 3 and Exit. Entry - Press and hold the service button for 2 to 5 seconds. When the service button is released a rapidly flashing comms LED (green) for one second indicates entry into ‘service button mode’. When the flashing stops this indicates the start of Phase 1. Phase 1 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that a ON condition is required. If it is pressed then an OFF condition is required. At the end of this stage the comms LED (green) will flash once to confirm no press and twice to confirm a press. The end of the flashing indicates the start of phase 2. Phase 2 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that the selection in Phase 1 should be applied to the LAN and if it is pressed then it will be applied to the UNIT. At the end of this stage the comms LED (green) will flash once to confirm no press and twice to confirm a press. The end of the flashing indicates the start of phase 3. Phase 3 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that a Water Balance selection is required and if it is pressed then it will indicate that an Occupancy selection is required. At the end of this stage the comms LED (green) will flash once to confirm no press and twice to confirm a press. The end of the flashing indicates the start of the Exit stage. Exit - This stage lasts for 3 seconds and starts with a rapidly flashing comms LED (green). During this stage if the service button is not pressed then the service button mode will expire without any further action. The service button must be pressed to confirm the selections made in phases 1, 2 and 3. Once pressed the LED will go out for the remainder of the stage and the virtual input channel selected by the choices made during phases 1, 2 and 3 will go ON for one pass of the sequence table. The virtual input channel is allocated to a Digital Input module to make it available to be used by the strategy. At the end of this stage the service button mode will be automatically exited and the LED and service button return to their normal operation. Service Button - Occupancy Pressing the service button in a predefined sequence, when in service button mode, can initiate behaviour in the strategy to change the occupancy state to occupied or unoccupied. The function is only available if Switch ‘Service Button Mode 1=Enabled’ is set to ON. For a full description of service pin mode refer to the Trend publication TE201089 IQeco Configuration Manual Issue 2 or greater. The service button press sequence for the required behaviour is as follows; Required Action Occupied for the Lan Unoccupied for the Lan Occupied for the Unit Unoccupied for the Unit Phase 1 No Press Press No Press Press Phase 2 No Press No Press Press Press Phase 3 Press Press Press Press Technical Description The service button can be used to initiate behaviour designed in the strategy; to achieve this behaviour the controller must be put into service button mode. Service button mode has 5 stages Entry, Phase 1, Phase 2, Phase 3 and Exit. Entry - Press and hold the service button for 2 to 5 seconds. When the service button is released a rapidly flashing comms LED (green) for one second indicates entry into ‘service button mode’. When the flashing stops this indicates the start of Phase 1. Phase 1 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that an ON condition is required. If it is pressed then an OFF condition is required. At the end of this stage the comms LED (green) will flash once to confirm no press and twice to confirm a press. The end of the flashing indicates the start of phase 2. Phase 2 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that the selection in Phase 1 should be applied to the LAN and if it is pressed then it will be applied to the UNIT. At the end of this stage the comms LED (green) will flash once to confirm no press and twice to confirm a press. The end of the flashing indicates the start of phase 3. Phase 3 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that a Water Balance selection is required and if it is pressed then it will indicate that an Occupancy selection is required. At the end of this stage the comms LED (green) will flash once to confirm no press and twice to confirm a press. The end of the flashing indicates the start of the Exit stage. Exit - This stage lasts for 3 seconds and starts with a rapidly flashing comms LED (green). During this stage if the service button is not pressed then the service button mode will expire without any further action. The service button must be pressed to confirm the 8 FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18 Apr 2016 FCU EC Fan WT2 selections made in phases 1, 2 and 3. Once pressed the LED will go out for the remainder of the stage and the virtual input channel selected by the choices made during phases 1, 2 and 3 will go ON for one pass of the sequence table. The virtual input channel is allocated to a Digital Input module to make it available to be used by the strategy. At the end of this stage the service button mode will be automatically exited and the LED and service button return to their normal operation. Virtual Energy Meter An estimation of the unit’s energy consumption is calculated by the controller and can be viewed on Sensor ‘Unit Energy Meter’. The consumption is measured over a 30 minute period starting from 0 and increasing until the end of the period when the value is stored in the controller. The controller stores the last 200 values and these can be viewed from suitable displays or supervisory software e.g. IQView and 963. The calculation totals the estimated energy used by the heat exchangers and the energy consumed by the fan and by the loads switched by the relay output. The accuracy of the calculation depends on the values configured in the controller however the default values supplied provide for a like for like comparison between similar units. Technical Description The estimated calculations use the heat meter module for the power being provided by the heat exchangers. This power is then added to the power of the fan and using an integrator module the power consumed is calculated over the period of 15, 30 (default) or 60 minutes depending on the configuration of the strategy. Heat exchanger power estimation formula. Heating Power = (Heating medium temperature - Space temperature) * Coil duty * Valve position / 100 Power kW (D) = (Water Supply Temp DegC (E) - Space Temp DegC (F)) * Coil Duty kW/degK (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I) Power Btu/s (D) = (Water Supply Temp DegF (F) - Space Temp DegF (E)) * Coil Duty Btu/sDegF (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I) Cooling Power = (Space temperature - Cooling medium temperature) * Coil duty * Valve position / 100 Power kW (D) = (Space Temp (E) - Water Supply Temp (F)) * Coil Duty kW/degK (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I) Power Btu/s (D) = (Space Temp DegF (E) - Water Supply Temp DegF (F)) * Coil Duty Btu/sDegF (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I) To improve the accuracy of the estimation the following parameters should be configured with the correct value for the unit: Function module Parameter Units ‘Heating coil duty max speed’ F kW/degK (Btu/sDegF) ‘Cooling coil duty max speed’ F kW/degK (Btu/sDegF) ‘Fan duty max speed’ F kW ‘Occupation relay duty’ F kW The output 'Occupation Relay' is intended to be the relay that switches the power to the EC fan controller and the value of ‘Occupation relay duty’ is the duty when the fan controller is energised. The values calculated are linear and therefore are only an estimate. The period the integrator uses for the calculation can be changed by amending the arguments in parameter K on Logic module ‘Meter reset’: F = 15 minutes, G = 30 minutes and H = 60 minutes. If the Logic is changed then the period parameter P on plot module ‘Unit Energy Meter’ should also be changed to match: 1 = 15 minutes, 7 = 30 minutes and 0 = 60 minutes. Useful conversions: 1 kW = 0.948608 Btu/s 1 hp = 0.7074163 Btu/s 1 Btu/h/3600 = 1 Btu/s Commissioning Details 1. Set the values of the duty for the coils. 2. Set the values of the duty for the fan. 3. Set the value of the duty for the occupation relay. 4. Confirm the water flow temperatures are received from the main plant. IC Comms and Alarm Group Technical Description The IC Comms are configured for master slave operation directed to standard knobs and switches one or all of the following: Space Temperature, Setpoint, Occupancy and Fan Speed. The IC Comms modules use attribute 3 and to prohibit unwanted communications are, by default, disabled. One alarm group route and destination modules are configured to send Trend text alarms to address 1 on the local lan, this would normally be the IQ3/BINC VCNC port 10001. To prohibit unwanted alarms the route, by default, is disabled. Analogue node 99 is provided so a value can be placed in it to indicate the state of the unit during commissioning and witnessing. The meaning of the value is user defined. It is suggested a bit state approach be used where values 1, 2, 4, 8 ,16 etc each indicating a separate operation. Summing the values provide a state of the unit. Suggested values: 1= Addressed, 2= Attributes Set, 4= Pre-commissioned, 8= Commissioned, 16 = Witnessed, FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18-Apr-2016 9 FCU EC Fan WT2 32 = 64 = 128 = Backed up, (TBC) , Has a Problem. An exampled of its use. e.g 11 = 1+2+8 = Addressed, Attributes Set and Commissioned. Digital Input 'Strategy Override 1=Active' when 1 indicates that one of the outputs is being overridden by the strategy and not in normal control. Commissioning Details 1. For master slave configuration configure attribute 3 and enabled IC Comms if master unit. 2. If alarms are required configure alarm destination address and enable alarm route. 10 FCU EC Fan WT2 Strategy Data Sheet TA201211 Issue 3, 18 Apr 2016 FCU EC Fan WT2 Please send any comments about this or any other Trend technical publication to [email protected] © 2011 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited. Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes. Trend Control Systems Limited Albery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols. Trend Control Systems Albery House, Springfield Road, Horsham. RH12 2PQ Telephone: +44 (0)1403 211888 Fax: +44 (0)1403 240271 Email: [email protected] Address Module Identifier Issue Revision 0 1 1 0 2 0 3 0 Project Change Note / Comments Alarm Lan 0 Alarm Address 0 Controller Version Date Approved Approved By Page 2, 7, 9, 10, 12 Added new interface to WMB sensors. Page 12 F77 F=1 on state is 1 not 255 Attribute F Attribute G Pages Affected Serial Number Strategy Name FCU EC Fan WT2 Page 2, 7, 9, 10, 12 Added new interface to WMB sensors. Product Order Code Notes Site GUID: {31009522-BE09-4A36-BEC3-9EA8ABCDD52D} Project: IQeco_Standard_Strategies_v3.2.1 The IQeco standard strategy controls a fan coil unit’s heat/cool outputs, and electronically commutated fan. Client: The control responses to a thermistor temperature sensor with a local setpoint knob and a local window contact input and a pushbutton, or Passive Infra Red movement detector input. Details: Fan Coil Unit with EC Fan Waterside 2 Pipes with 1 thermic Valve. The WT2 strategy is for waterside 2 pipe units controlling 1 thermic valve actuator. The strategy supports the fitting of a WMB Room display module without further configuration. Drawn By: Engineer Engineer: M Spencer Controller Type: IQeco 31 Project Number: 1 Outstation: 014 Lan: 019 Date: 4/15/2016 Page: 01 of 18 FCU EC Fan WT2 Strategy pages Title Page WallBus Interface Eco Real Inputs Knobs Switches <21 Knobs Switches 21 - 40 Knobs Switches >41 Window PushbuttonPIR Operation Occupancy State Discharge and Space Temp Heating Cooling Setpoints Heating Cooling Demands Heat Cool Valve Fan Control - Variable Speed Fan Control - Variable page 2 Service Button - Water balance Service Button - Occupancy Virtual Energy Meter IC Comms and Alarm Group 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 180 Interface module for WMB Displays 170 185 184 Room Display Space Temp Occupancy Code 160 1 G18D Unit - occupied From Page 8 150 E 0 F G18D B t2 D Wallbus GATE 2 S31V 4 F100D K47D K48D S32V 1 1 1 S34V S39V 1 F77D W1D F42D 140 Setpoint Highlimit K47 24 D KNOB DegC 0 0 0 Disabled 120 Units Pin Level Top of Range Bottom of Range Clip To Limits Setpoint Lowlimit 110 K48 18 D KNOB DegC 0 0 0 Disabled 100 Address I1 - Temperature Display I2 - Fan Configuration I3 - Occupancy Display I4 - Setpoint High limit I5 - Setpoint low limit I6 - Humidity Display I7 - Setpoint Enable I8 - Fan Enable I9 - Override Enable I10 - CO2 Display I11 - OutsideAirTemperature I12 - TempConfig I13 - Fan State Display I14 - Override State Display I15 - Setpoint O1 - Local Temperature O2 - Local Humidity O3 - Local Dewpoint O4 - Local CO2 O5 - Setpoint O6 - Override State O7 - Fan State DegC 50 -5 600 600 Disabled Disabled RD-WMB-THC To Page(s) 9,10,13, A1 D Analogue S39 Read Alarm Out. Limits Alarm Low Alarm High Alarm 70 S32 60 Temperature Display V S32V S INTERNAL %RH 0 0 0 0 Disabled Disabled Humidity To Page(s) Units High Alarm Limit Low Alarm Limit High Alarm Delay Low Alarm Delay Low Alarm High Alarm 186 t2I6V Humidity Display Dewpoint S40 V t2O3V S INTERNAL DegC 0 0 0 0 Disabled Disabled V A1D S INTERNAL DegC 0 0 0 0 Disabled Disabled t2I1V t2O2V Outside Air Temp V Units High Alarm Limit Low Alarm Limit High Alarm Delay Low Alarm Delay Low Alarm High Alarm 181 182 0 Room Display Space Temp To Page(s) 9, Humidity Units Pin Level Top of Range Bottom of Range Clip To Limits Outside Air Temp S31V S INTERNAL t2*e 90 80 V t2O1V Failed D = F when B = 1 130 S31 RD-WMB-THC F100 Units High Alarm Limit Low Alarm Limit High Alarm Delay Low Alarm Delay Low Alarm High Alarm Units High Alarm Limit Low Alarm Limit High Alarm Delay Low Alarm Delay Low Alarm High Alarm 188 CO2 S34 V t2O4V S INTERNAL ppm 0 0 0 0 Disabled Disabled 50 40 t2I10V CO2 Display Units High Alarm Limit Low Alarm Limit High Alarm Delay Low Alarm Delay Low Alarm High Alarm 30 20 10 For RS-WMB, RD-WMB refer to Data Sheet TA201348. For RV-WMB refer to Data Sheet TA201354 for more information Drawing Reference SET-019-014-02 Page Details WallBus Interface Eco SET Strategy Designed By: Trend Control Systems D60D 3201 DA65 8FD9 921A 697A 87 Issue 3 Revision - 00 Checked By Project Number: 1 Date: Outstation: 014 Page: 4/15/2016 02 of 18 10 180 20 30 40 50 60 70 80 0 1 S21 i c 150 140 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 Window Pushbutton PIR V EXTERNAL 160 100 1 Local Discharge Air Temp 170 90 DegC 101 0 50 -5 600 600 0 0 Disabled Disabled Disabled Disabled Units Type Offset High Alarm Limit Low Alarm Limit High Alarm Delay Low Alarm Delay Out.Limits Delay Read Alarm Delay Read Alarm Out. Limits Alarm Low Alarm High Alarm I24 S21V 4 Local Discharge Air Temp To Page(s) 9, Local Discharge Air Temp S21V S 15 Min 96 Period Records c EXTERNAL 0 Alarm Delay 0 Required State Disabled State Alarm Hours Run Starts S I24S Window Pushbutton PIR To Page(s) 7,8, P7 SYNC 130 120 2 Local Space Temperature 110 0 2 S22 i c Default Operation V EXTERNAL 100 90 80 DegC 101 0 50 -5 600 600 0 0 Disabled Disabled Disabled Disabled Units Type Offset High Alarm Limit Low Alarm Limit High Alarm Delay Low Alarm Delay Out.Limits Delay Read Alarm Delay Read Alarm Out. Limits Alarm Low Alarm High Alarm S22V The behaviour of the strategy before any configuration of knobs and switches is as follows: Local Space Temperature To Page(s) 9, The default occupancy state of the strategy is unoccupied. In most cases when the controller is powered on the fan outputs will not operate as the space temperature used for control will be within the deadband for the unoccupied state. There are 3 ways to take the strategy out of the unoccupied state: 1. Set Knob “Remote Occupancy” (K11) to 0. 2. Using a pushbutton connected to IN4. Press the pushbutton once; this should place the unit into bypass. The bypass state is active until another press of the pushbutton or timeouts after 30 minutes. 3. Use the service button to put the unit into occupied. Details are in “Service Button - Occupancy” section of the strategy datasheet. 70 60 3 Local Setpoint Adjust 50 0 3 i c S23 V EXTERNAL 40 30 20 DegC 102 0 0.6 -0.6 600 600 0 0 Disabled Disabled Disabled Disabled Units Type Offset High Alarm Limit Low Alarm Limit High Alarm Delay Low Alarm Delay Out.Limits Delay Read Alarm Delay Read Alarm Out. Limits Alarm Low Alarm High Alarm The fan output may not be operating for the following reasons: a. The fan anti cycling strategy is active. Once switched off the fan will not start for 5 minutes. b. Changes to the knobs and switches from the defaults are overriding the fan control. c. The occupancy state is unoccupied. S23V Local Setpoint Adjust To Page(s) 10, 5 One shot switch reset F1 500 E 0 F F1D D 10 One shot switch reset To Page(s) 17, COMPARATOR D = 1 when F > E Drawing Reference SET-019-014-03 Page Details Real Inputs SET Strategy Designed By: Trend Control Systems D60D 3201 DA65 8FD9 921A 697A 87 Issue 3 Revision - 00 Checked By Project Number: 1 Date: Outstation: 014 Page: 4/7/2016 03 of 18 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 180 Pushbutton PIR Timeout 170 160 Cooling Setpoint K1 30 D KNOB min 79 1440 0 K1D Pushbutton PIR Timeout To Page(s) 7, Units Pin Level Top of Range Bottom of Range K11D = 1 K8 20.5 KNOB DegC 79 34 18 Remote Occupancy From Page 8 K8D D Units Pin Level Top of Range Bottom of Range Remote Occupancy To Page(s) 4,8,16, Setpoint Adjust Timeout 150 Remote Space Temperature K2 60 D KNOB 140 min 79 1440 0 130 K2D DegC 79 30 0 K12D Remote Space Temperature To Page(s) 9, Units Pin Level Top of Range Bottom of Range 2 D KNOB K3D D KNOB Offset Range To Page(s) 10, Units Pin Level Top of Range Bottom of Range DegC 79 10 -10 DegC 79 0 0 K13D Remote Setpoint Offset To Page(s) 10, Units Pin Level Top of Range Bottom of Range W11 0 D KNOB 90 DegC 60 2 0.5 Frost Condition 1=Frost W12 25 D KNOB DegC 60 25 8 KNOB W1D = 0 K5 K5D Unit Bypass Request 1=Active From Page 7 4 D 60 Units Pin Level Top of Range Bottom of Range Pin Level K14D K15D K15 KNOB enum 79 4 0 Remote Fan Speed To Page(s) 13, 0 = Off 1 = Low 2 = Medium 3 = High 4 = Auto (1001-7) Summer Mode 1=Summer 40 79 D KNOB DegC 60 8 1 W15D D SWITCH K6 8 W15 0 Standby Deadband 50 Frost Condition 1=Frost To Page(s) 11, Remote Setpoint To Page(s) 10, Units Pin Level Top of Range Bottom of Range Remote Fan Speed W1D Unit Bypass Request 1=Active To Page(s) 4, NOCC Deadband To Page(s) 10, Units Pin Level Top of Range Bottom of Range 79 D DegC 79 24 18 W12D D SWITCH K14 22 OCC Deadband To Page(s) 10, Units Pin Level Top of Range Bottom of Range NOCC Deadband 80 70 K4D Remote Shutdown 1=Shutdown To Page(s) 8, Pin Level Remote Setpoint K4 1 W11D D SWITCH 79 0 100 Water Flow Temperature To Page(s) 17, Units Pin Level Top of Range Bottom of Range 110 OCC Deadband K19D D KNOB Remote Shutdown 1=Shutdown K13 0 K19 50 Remote Setpoint Offset K3 DegC 79 10 1 D KNOB Setpoint Adjust Timeout To Page(s) 10, Units Pin Level Top of Range Bottom of Range Water Flow Temperature K12 22 Offset Range 120 K11D Cooling Setpoint To Page(s) 10, Summer Mode 1=Summer To Page(s) 11,12, Pin Level K6D Standby Deadband To Page(s) 10, Units Pin Level Top of Range Bottom of Range Heating Setpoint 30 K7 19.5 D KNOB 20 DegC 79 24 8 Units Pin Level Top of Range Bottom of Range K7D Heating Setpoint To Page(s) 10, 10 Drawing Reference SET-019-014-04 Page Details Knobs Switches <21 SET Strategy Designed By: Trend Control Systems D60D 3201 DA65 8FD9 921A 697A 87 Issue 3 Revision - 00 Checked By Project Number: 1 Date: Outstation: 014 Page: 3/24/2016 04 of 18 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 180 170 Service Button Mode 1=Enabled W31 1 79 Minimum Fan Speed Setpoint 150 D KNOB % 79 50 0 140 K39D W32 1 Minimum Fan Speed Setpoint To Page(s) 14, Units Pin Level Top of Range Bottom of Range 79 % 79 100 50 Pin Level W34 79 Pin Level SP Offset Select 1=Remote Maximum Fan Speed Setpoint To Page(s) 14, W35 0 0 D KNOB % 60 100 0 Valve Override 1=Enabled K24D Heat Cool Valve Override Value To Page(s) 12, Units Pin Level Top of Range Bottom of Range D SWITCH 60 Pin Level W24D 79 Pushbutton TETS KO 1=Fitted W37 D % 60 100 0 Units Pin Level Top of Range Bottom of Range W37D D SWITCH 79 K28 KNOB 70 HeatCool Setpoint 1=Separate To Page(s) 10, Pin Level Fan Speed Override Value EC 50 W36D D SWITCH Valve Override 1=Enabled To Page(s) 12, Pin Level W36 0 0 80 SP Offset Select 1=Remote To Page(s) 10, HeatCool Setpoint 1=Separate W24 0 W35D D SWITCH 79 K24 Temperature Select 1=Remote To Page(s) 9, K40D 110 Heat Cool Valve Override Value W34D D SWITCH D Units Pin Level Top of Range Bottom of Range Overrides 0=Disabled 1=Enabled To Page(s) 12,14, Temperature Select 1=Remote K40 KNOB 120 W32D D SWITCH Maximum Fan Speed Setpoint 70 90 Pin Level 0 130 Service Button Mode 1=Enabled To Page(s) 15,16, Overrides 0=Disabled 1=Enabled K39 37 100 W31D D SWITCH 160 Pushbutton TETS KO 1=Fitted To Page(s) 7, Pin Level K28D Fan Speed Override Value EC To Page(s) 14, 60 Fan Override 1=Enabled Fan Speed Select 1=Remote W27 0 D 50 SWITCH 60 Pin Level W27D W39 0 Fan Override 1=Enabled To Page(s) 14, W39D D SWITCH 79 Fan Speed Select 1=Remote To Page(s) 13, Pin Level 40 W28D = 0 Water Balance 1=Enabled From Page 15 30 W28D Water Balance 1=Enabled To Page(s) 5, 20 10 Drawing Reference SET-019-014-05 Page Details Knobs Switches 21 - 40 SET Strategy Designed By: Trend Control Systems D60D 3201 DA65 8FD9 921A 697A 87 Issue 3 Revision - 00 Checked By Project Number: 1 Date: Outstation: 014 Page: 3/24/2016 05 of 18 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 180 Window Mode 1=Enabled 170 ECO Mode Deadband Increase W41 0 D SWITCH 79 W41D Window Mode 1=Enabled To Page(s) 7,8, Pin Level 0=Pushbutton 1=PIR 160 W42 0 SWITCH 150 D KNOB DegC 79 6 2 Operating Mode 0=Comfort 1=ECO K51D ECO Mode Deadband Increase To Page(s) 10, Units Pin Level Top of Range Bottom of Range W51 1 W51D D SWITCH 60 Operating Mode 0=Comfort 1=ECO To Page(s) 10, Pin Level W52D = 0 D 79 K51 3 W42D Power Conversion Factor 0=Pushbutton 1=PIR To Page(s) 7, Pin Level 1 K52 D KNOB 140 Energy Meter 1=Reset From Page 17 79 0 0 Units Pin Level Top of Range Bottom of Range W52D Energy Meter 1=Reset To Page(s) 6, K52D Power Conversion Factor To Page(s) 17, 130 120 Fan Off at Setpoint 1=Enabled 110 W45 0 D SWITCH 79 100 Pin Level W45D Fan Off at Setpoint 1=Enabled To Page(s) 14, 90 80 70 60 50 40 30 20 10 Drawing Reference SET-019-014-06 Page Details Knobs Switches >41 SET Strategy Designed By: Trend Control Systems D60D 3201 DA65 8FD9 921A 697A 87 Issue 3 Revision - 00 Checked By Project Number: 1 Date: Outstation: 014 Page: 3/24/2016 06 of 18 10 20 30 40 50 60 70 80 90 100 110 120 180 130 140 150 160 170 180 190 200 210 220 230 240 17 20 Minutes to seconds K1D = 30 170 Pushbutton PIR Timeout From Page 4 60 E K1D G 1 F 160 F3 PIR override active G8 D G4D MULTIPLY S G8D D D=G*E*F PIR override active To Page(s) 8, TIMER 150 0 0 F3D G20D Unit - unoccupied From Page 8 140 W42D = 0 0=Pushbutton 1=PIR From Page 6 W41D = 0 130 Window Mode 1=Enabled From Page 6 12 G1 I24S Window Pushbutton PIR From Page 3 I24S S F2D A 0.5 E G1M F M F W41D G F2D H G4 t2O6V E J or K or L or M G8D F G4D G D COMB Override State t2O6V J Comb. K Comb. L Comb. M Comb. 1 1 Window Mode 1=Enabled From Page 6 W42D = 0 0=Pushbutton 1=PIR From Page 6 80 13 KO Override Request S23o1S Out - Local Setpoint Adjust From Page 3 S23o1S E 0 W37D = 0 Pushbutton TETS KO 1=Fitted From Page 5 14 Pulse generator reset I24S Window Pushbutton PIR From Page 3 W41D = 0 Window Mode 1=Enabled From Page 6 40 S23o1S E G3 J or K or L or M I24S F 0 G W41D H E FH J Comb. K Comb. L Comb. M Comb. J or K or L or M Unit Bypass Request 1=Active G6D H J Comb. K Comb. L Comb. M Comb. D SWITCH 60 H FG EF W1 G9D D Pin Level COMB t2I14V Override State Display 18 16 Reschedule Time Scale Factor Sts - Window Pushbutton PIR From Page 3 60 22 G9 D = 1 when F > E W41D = 0 50 21 COMPARATOR 999 I24N 70 W42D PB PIR override active To Page(s) 8, PB PIR override active COUNTER 100 90 E D R G9D PIR request G20D eFgH F2 Window Pushbutton PIR count On Delay Minimum On Off Delay 15 Input active 11 120 110 250 F J or K or L or M W37D G G3D H EGh J Comb. K Comb. L Comb. M Comb. D COMB COMB F2D E W41D F W42D G G2D H Efg H G2 Pushbutton override active Pushbutton request G6 G5 t2O6V E J or K or L or M G8D F G5D G G7D H Efgh eG J Comb. K Comb. L Comb. M Comb. COMB J Comb. K Comb. L Comb. M Comb. D 19 J or K or L or M COMB Pushbutton override reset G7 G6D S F3D 0 0 On Delay Minimum On Off Delay D D D TIMER Window Mode: Switch "Window Mode 1=Enabled" set to 1 Input "Window Pushbutton PIR" when open circuit will force control to change to unoccupied. (1001-13) 30 PIR mode: Switch "0=Pushbutton 1=PIR" set to 1 Control will change from standby to bypass upon movement being detected by the PIR for the amount of time determined by knob "Pushbutton PIR Timeout". (1001-11) Pushbutton Mode: Switch "0=Pushbutton 1=PIR" set to 0 Control will change from unoccupied to bypass for the amount of time determined by knob "Pushbutton PIR Timeout" when the pushbutton is pressed. If the button is pressed whilst in bypass the unit will be returned to unoccupied. (1001-12) 20 10 Drawing Reference SET-019-014-07 Page Details Window PushbuttonPIR Operation SET Strategy Designed By: Trend Control Systems D60D 3201 DA65 8FD9 921A 697A 87 Issue 3 Revision - 00 Checked By Project Number: 1 Date: Outstation: 014 Page: 3/24/2016 07 of 18 10 20 180 30 40 50 W41D = 0 I24S Window Pushbutton PIR From Page 3 160 150 80 90 W41D I24S F W11D G 120 130 140 150 160 J or K or L or M H J Comb. K Comb. L Comb. M Comb. 34 a b F8 D G D COMB A TO D Unit interrupt: When in window mode and input "Window Pushbutton PIR" is 0 or the unit has been sent a shutdown command control is forced to unoccupied. (1001-14) g h 0 = Occupied 1 = Unoccupied 2 = Bypass 3 = Standby (1001-1) Bypass select K11D = 1 Remote Occupancy From Page 8 K11D E 2 F G17D B 100 33 F6 GATE F6D E 1 F G16D B S10 D Bypass request G8D PIR override active From Page 7 70 E F 50 G G20D H Fg FGh J Comb. K Comb. L Comb. M Comb. 26 K11D 1 E 0 F F9D B Remote Occupancy Occupancy value select F10 K11D E F10D F G75D B F11 D D = 1 when F > E D = F when B = 1 D D F GATE G G19D H ef H J Comb. K Comb. L Comb. M Comb. F8a E F8b F 0 G GATE D = F when B = 1 KNOB enum 79 3 0 Units Pin Level Top of Range Bottom of Range D Unit Occupied is enabled when the zone is occupied. (1001-2) Unit In Bypass I3 G19D G19 J or K or L or M 0 H J Comb. K Comb. L Comb. M Comb. D Page Details Occupancy State SET Strategy Designed By: 0 Alarm Delay 0 Required State Disabled State Alarm Hours Run Starts G19D Unit - bypass To Page(s) COMB Unit Bypass mode is the occupied state used when the Pushbutton or PIR are activated. Bypass uses the same deadband as occupied. (1001-4) V Units High Alarm Limit Low Alarm Limit High Alarm Delay Low Alarm Delay Low Alarm High Alarm G20D 37 E F8b F Unit Unoccupied I2 Unit - unoccupied To Page(s) 7,11,14, Unit - unoccupied F8a K11D Remote Occupancy To Page(s) 4,8,16, Trend Control Systems D60D 3201 DA65 8FD9 921A 697A 87 S INTERNAL G20D G20 J or K or L or M 0 G 0 H Ef J Comb. K Comb. L Comb. M Comb. S INTERNAL 0 Alarm Delay 0 Required State Disabled State Alarm Hours Run Starts D COMB Unit Unoccupied mode is activated when the zone is unoccupied for longer periods of time. In this mode PIR has no effect although the Pushbutton will override the unit into bypass. (1001-3) Unit In Standby I4 38 G21D F8a E F8b F 0 G G21 J or K or L or M 0 H EF J Comb. K Comb. L Comb. M Comb. D COMB Issue 3 Revision - S INTERNAL Service button occ active From Page 16 Drawing Reference SET-019-014-08 0 Alarm Delay 0 Required State Disabled State Alarm Hours Run Starts G18D Unit - occupied To Page(s) 2,10, COMB eF G75D 10 J or K or L or M Unit - standby K11 F11D E COMPARATOR 0 0 = Occupied 1 = Unoccupied 2 = Bypass 3 = Standby (1001-1) 29 28 Occ nocc select D F S INTERNAL S INTERNAL COMB 27 F9 0.5 250 I1 F8b D Unit not in occ mode To Page(s) 16, Unit not in occ mode 20 J or K or L or M F9D 40 30 G17 G8D 60 240 G18D F7D enum 4 -1 0 0 Disabled Disabled GATE 31 G9D 230 G18 E Occupancy F7 D = F when B = 1 0 220 Unit Occupied F8a 39 Unoccupied select D D = F when B = 1 G9D 210 35 32 PB PIR override active From Page 7 200 Unit - bypass Unoccupied select To Page(s) 120 c d e f F7D 80 190 Unit - occupied Occupancy decoder 130 90 180 36 F7D 0 Ef G 110 170 G16D G16 E 110 Unit interrupt To Page(s) 11,14, Window Mode: Switch "Window Mode 1=Enabled" set to 1 Input "Window Pushbutton PIR" when open circuit will force control to change to unoccupied. (1001-13) 140 100 Unit interrupt W11D = 0 Remote Shutdown 1=Shutdown From Page 4 70 30 Window Mode 1=Enabled From Page 6 170 60 00 0 Alarm Delay 0 Required State Disabled State Alarm Hours Run Starts G21D Unit - standby To Page(s) 10, Unit Standby is activated to reduce the energy consumption of the zone. In this mode either the PIR if selected or the Pushbutton will put the zone back into occupied. (1001-5) Checked By Project Number: 1 Date: Outstation: 014 Page: 3/24/2016 08 of 18 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 180 S21V Local Discharge Air Temp From Page 3 170 42 S31V Actual discharge temp S21V 160 150 S21r1S Rd - Local Discharge Air Temp From Page 3 S21o1S 140 41 Out - Local Discharge Air Temp From Page 3 130 0 F G26D B G26 E J or K or L or M S21o1S F 0 G 0 H E F J Comb. K Comb. L Comb. M Comb. F16 D GATE 45 Selected space temperature F16D S22V Actual discharge temp To Page(s) D = F when B = 1 Discharge temp 0=Fitted S21r1S E Room Display Space Temp From Page 2 Local Space Temperature From Page 3 43 S31V E S22V F t2e B Discharge Air Temperature S1 F17 D GATE D = F when B = 1 V F16D D S INTERNAL DegC 40 10 0 0 Disabled Disabled COMB 46 Units High Alarm Limit Low Alarm Limit High Alarm Delay Low Alarm Delay Low Alarm High Alarm Space temperature select K12D = 22 Remote Space Temperature From Page 4 120 44 RD-WMB-THC From Page 2 S22r1S Rd - Local Space Temperature From Page 3 100 S22o1S t2e E 0 F S22r1S F G27D B J or K or L or M S22o1S H F19D D Actual space temperature To Page(s) 11, GATE D = F when B = 1 48 Space Temperature S2 S INTERNAL DegC 40 10 0 0 Disabled Disabled COMB 47 Actual space temperature K12D = 22 Remote Space Temperature From Page 4 80 V F19D D J Comb. K Comb. L Comb. M Comb. EG EH F18 G27 G Out - Local Space Temperature From Page 3 90 E K12D Select temperature 1=Remote t2e 110 F17D F18D E K12D F W34D B W34D = 0 Temperature Select 1=Remote From Page 5 F19 Units High Alarm Limit Low Alarm Limit High Alarm Delay Low Alarm Delay Low Alarm High Alarm D GATE D = F when B = 1 70 Space Temperature 60 P1 S2V S 15 Min 100 Period Records SYNC 50 40 30 20 10 Drawing Reference SET-019-014-09 Page Details Discharge and Space Temp SET Strategy Designed By: Trend Control Systems D60D 3201 DA65 8FD9 921A 697A 87 Issue 3 Revision - 00 Checked By Project Number: 1 Date: Outstation: 014 Page: 4/4/2016 09 of 18 10 20 30 40 50 180 S23o1S 170 Out - Local Setpoint Adjust From Page 3 W35D = 0 160 SP Offset Select 1=Remote From Page 5 t2e 150 RD-WMB-THC From Page 2 70 80 90 Offset Range From Page 4 G31 E J or K or L or M S23o1S F W35D G t2e H EH FH G J Comb. K Comb. L Comb. M Comb. D 130 Remote Setpoint Offset From Page 4 F21D E K13D F G31D Room display offset value From Page 10 S23V 110 Local Setpoint Adjust From Page 3 t2e 100 F t2e B F G31D B K6D = 8 Standby Deadband From Page 4 G21D 70 F G21D B Unit - standby From Page 8 OCC Deadband From Page 4 F21 F24D E F22D G 0.05 F W36D = 0 HeatCool Setpoint 1=Separate From Page 5 0 F W36D PROXIMITY G31D F23D E t2e F D Eco mode selected deadband From Page 10 GATE 30 K14D E K7D F W36D B 20 K8D = 20.5 Cooling Setpoint From Page 4 10 J or K or L or M G H e fgh J Comb. K Comb. L Comb. M Comb. D E F30D F G18D GATE B G18D Unit - occupied From Page 8 F32 F W36D B E 1 F E F46D G 1 F MULTIPLY W51D = 1 Page Details Heating Cooling Setpoints E K51D F W51D B F43 D GATE D = F when B = 1 55 Eco mode selected deadband To Page(s) 10, Room display offset value F47 D DIVIDE F47D E F48D F F44D B F48 F48D D Room display offset value To Page(s) 10, GATE D = F when B = 1 53 1 G H 1 E -1 F H Minutes to seconds 1 E K2D G 60 F MULTIPLY E 0.5 F F35D F B G E 1 F 0.5 G F35 H D PROXIMITY 81 S3 S INTERNAL DegC 30 -30 0 0 Disabled Disabled K47D = 24 Setpoint Highlimit From Page 2 78 F38 V F42D ADD/SCLR Units High Alarm Limit Low Alarm Limit High Alarm Delay Low Alarm Delay Low Alarm High Alarm Heat setpoint D GATE F38D E 1 F F40 D D = F when B = 1 F28D Setpoint offset From Page 10 75 1 H E F35D F 79 COMPARATOR D = 1 when F > E ADD/SCLR D = (E * G) + (F * H) GATE F36D E F35D F F37D D60D 3201 DA65 8FD9 921A 697A 87 E 1 F 1 G F39D F39 F41 0.5 E 0.5 F F40D G F42 D F41D H ADD/SCLR D = (E * G) + (F * H) H ADD/SCLR D = (E * G) + (F * H) F42D D B GATE Issue 3 F28D D 77 Maximum setpoint D = F when B = 1 Trend Control Systems Actual setpoint Cool setpoint D F36 80 ADD/SCLR D = (E * G) + (F * H) F37 F36D Heat setpoint To Page(s) 11, G F28D Heat cool setpoint overlap ADD/SCLR D F33D F F40D D H G 0.05 F44 E +/- F Setpoint Lowlimit From Page 2 Minimum setpoint Heat setpoint - deaband F32D H F37D K44D K48D = 18 76 ADD/SCLR E Setpoint D = (E * G) + (F * H) F36D -0.5 Units Pin Level Top of Range Bottom of Range F42D F45 G 73 F D KNOB DegC 79 K47D K48D D D=G*E*F F34 0.5 K44 t2O5V ADD/SCLR Setpoint no offset D Room display not changed Room Display Setpoint 83 F25 52 51 D = (E * G) + (F * H) E E Setpoint t2O5V G F35D 1 F46 D D = (E * G) + (F * H) F34D Room display not changed To Page(s) 10, Room display changed value On Delay Minimum On Off Delay F45D Cool setpoint + deadband SET Strategy Designed By: 0 Operating Mode 0=Comfort 1=ECO From Page 6 D = F when B = 1 Drawing Reference SET-019-014-10 K51D = 3 ECO Mode Deadband Increase From Page 6 D F36D F34D D 82 Setpoint offset To Page(s) 10, D Room display calculated change F26D 61 74 F33 250 F43D K44D D = (E * G) + (F * H) Selected cool setpoint K8D F43D GATE E S Calculated deadband D 71 K14D F GATE COMB D D = F when B = 1 240 Eco mode selected deadband 54 D K2D = 60 F31 GATE 230 D 63 0 0 F25D Setpoint Adjust Timeout From Page 4 F31D Deadband 1=OCC F29D D = F when B = 1 K14D = 22 Remote Setpoint From Page 4 F27D D 69 F30 220 F28D D=G*E*F G33 72 70 Heating Setpoint From Page 4 G TIMER F44D F29 Selected heat setpoint K7D = 19.5 E F26D F27 Adjustment active G32 G31D Room display not changed From Page 10 D = F when B = 1 40 B Value changed D GATE B 210 F44D RD-WMB-THC From Page 2 OCC deadband select 1=0 E 200 F28 62 F23 E +/- F D 68 K4D F G33D G32D D = F when B = 1 K4D = 1 60 F22D GATE Value has not changed F43D K6D 190 1 D = F when B = 1 59 GATE E E D B Deadband 0=NOCC 1=Standby K5D 180 D=F(G/E) F44D 80 0 D = F when B = 1 67 K5D = 25 170 Active setpoint offset F24 F D D = F when B = 1 NOCC Deadband From Page 4 65 GATE t2e RD-WMB-THC From Page 2 90 D E F23D Select setpoint 1=Remote From Page 10 50 E 1 F24D F22 E S23V K3D F22D Selected setpoint adjustment F48D 160 Setpoint offset Last change value 56 F48D 150 F26 60 D = F when B = 1 120 140 66 Select setpoint 1=Remote To Page(s) 10, COMB B 130 D = F when B = 1 Selected setpoint offset K13D = 0 120 Selected offset range G31D 58 140 110 K3D = 2 Select setpoint 1=Remote S23r1S 100 64 57 S23r1S Rd - Local Setpoint Adjust From Page 3 60 Revision - 00 Actual setpoint To Page(s) F41D Cool setpoint To Page(s) 11, Checked By t2I15V Project Number: 1 Date: Outstation: 014 Page: Setpoint 3/24/2016 10 of 18 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 180 170 Frost Condition 1=Frost From Page 4 G20D Unit - unoccupied From Page 8 150 Heat setpoint From Page 10 Loop override required W12D = 0 160 F40D 86 W12D G20D F 0 G 0 H EF 140 J or K or L or M Actual space temperature From Page 9 87 W15D = 0 110 F40D Heating loop enable G16D E W15D F F78D G 0 H 100 efg Heat setpoint From Page 10 G37 J or K or L or M D COMB G36D A F19D P F40D O nul U 98 L L1 3 E F52D G 4 F LOOP S 5 6 30 Reschedule Time Gain Integral Time Deadband 0 E F51D G 90 91 1 E -1 F L1D G L2D H F51 90 E F51D G 100 F 0 A F19D P F41D O G38 nul U J or K or L or M 0 L 60 F41D 89 Cool setpoint From Page 10 Cooling loop enable F78D Fan control off selected From Page 13 30 F78D G 0 H eFg G36D G G39 J or K or L or M F54D H EG gH J Comb. K Comb. L Comb. M Comb. G39D D Heating required To Page(s) 14, COMB Heating Demand D HYST BAND D COMB J Comb. K Comb. L Comb. M Comb. P2 S11V S 15 Min 100 Period Records SYNC F52D 96 Heat demand To Page(s) 12, F52 Heating Demand S11 S INTERNAL % 101 -1 0 0 Disabled Disabled RSCL TO L2 F57 RSCL TO F51D G -100 F Fan demand F57D E 1 F 1 G F59 F59D D 101 E F58D F58 H Fan demand To Page(s) 14, ADD/SCLR D = (E * G) + (F * H) D Cooling Demand RSCL TO D=100(G-E)/(F-E) D G38D S 5 -5 30 Reschedule Time Gain Integral Time Deadband 0 E F51D G -90 Period Records S12 S INTERNAL % 101 -1 0 0 Disabled Disabled RSCL TO F53D Cool demand To Page(s) 12, Cooling required 3 E F53D G 4 F F55 D HYST BAND V F53D D 95 20 SYNC 97 D=100(G-E)/(F-E) 10 S 15 Min 100 Cooling Demand F53 F P3 S12V 94 Cool demand LOOP Units High Alarm Limit Low Alarm Limit High Alarm Delay Low Alarm Delay Low Alarm High Alarm 102 D Fan cool demand -90 V F52D D D=100(G-E)/(F-E) ADD/SCLR D = (E * G) + (F * H) Cool loop F F 100 90 W15D E F56D F54 F D E F56D Fan heat demand 70 250 Heating required D=100(G-E)/(F-E) Heat cool demand G16D HYST BAND Heat demand D 80 40 F 92 90 50 240 E=Level F=Band G37D J Comb. K Comb. L Comb. M Comb. 230 99 D Heating requested F19D Summer Mode 1=Summer From Page 4 F56 93 130 G16D G COMB Heat loop Unit interrupt From Page 8 E F40D D 88 120 F19D E=Level F=Band J Comb. K Comb. L Comb. M Comb. 220 Heating below setpoint 1 G36 E 210 98 F19D Actual space temperature From Page 9 200 Units High Alarm Limit Low Alarm Limit High Alarm Delay Low Alarm Delay Low Alarm High Alarm F55D Cooling required To Page(s) 14, E=Level F=Band Drawing Reference SET-019-014-11 Page Details Heating Cooling Demands SET Strategy Designed By: Trend Control Systems D60D 3201 DA65 8FD9 921A 697A 87 Issue 3 Revision - 00 Checked By Project Number: 1 Date: Outstation: 014 Page: 3/24/2016 11 of 18 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 180 106 F52D Heat demand From Page 11 170 F53D Cool demand From Page 11 160 Heat cool value select F52D E F53D F W15D B W15D = 0 Summer Mode 1=Summer From Page 4 110 109 F61 Heat Cool Valve Heat cool valve demand D 107 GATE Override or balance select K24D = 0 D = F when B = 1 Heat Cool Valve Override Value From Page 5 G65D 150 Water balance required From Page 15 K24D E 100 F G65D B F62 E F62D F G41D B D5 F63 F63D D GATE 360 0 0 F63D GATE l 5 S TIME PROP. D = F when B = 1 D D = F when B = 1 Period Override Enable Override Value Heat cool valve demand To Page(s) 17, 108 140 F61D Valve override required 130 W24D = 0 Valve Override 1=Enabled From Page 5 W32D = 1 120 Overrides 0=Disabled 1=Enabled From Page 5 G65D E 0 F W24D G G41 J or K or L or M W32D H E GH J Comb. K Comb. L Comb. M Comb. 110 D COMB G41D Valve override required To Page(s) 18, 100 90 80 70 60 50 40 30 20 10 Drawing Reference SET-019-014-12 Page Details Heat Cool Valve SET Strategy Designed By: Trend Control Systems D60D 3201 DA65 8FD9 921A 697A 87 Issue 3 Revision - 00 Checked By Project Number: 1 Date: Outstation: 014 Page: 3/24/2016 12 of 18 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 180 121 122 Room Display Fan Speed Selected fan speed adjustment 170 t2e 160 RD-WMB-THC From Page 2 K45D E 4 F t2e B F72 D Fan State t2O7V t2O7V 123 enum 79 255 0 D = F when B = 1 F72D 150 E K15D F G46D B F73 126 GATE Remote Fan Speed From Page 4 W39D = 0 Fan Speed Select 1=Remote From Page 5 F73D E K15D F W39D B 129 Fan control auto selected 4 E F77D G 0.01 F D 4 E F74D F F75D B F76D D Fan control auto selected To Page(s) 14, PROXIMITY 130 Fan speed selected F74 F76 E +/- F 128 Remote fan speed selected K15D = 4 130 Units Pin Level Top of Range Bottom of Range D D = F when B = 1 140 D KNOB Remote fans speed adjustment GATE K45 Room Display Fan Speed 0 = Off 1 = Low 2 = Medium 3 = High 4 = Auto 255 = On (1001-23) Fan control off selected F77 F78 D F77D E 0.9 F F78D D GATE D = F when B = 1 GATE D = F when B = 1 Fan control off selected To Page(s) 11,14, COMPARATOR D = 1 when F > E 125 Select fan speed 1=Remote 120 110 t2e RD-WMB-THC From Page 2 124 100 Local fan speed select Remote Fan Speed From Page 4 0 E 0 F K15D E 3.9 F J or K or L or M G t2e H H G J Comb. K Comb. L Comb. M Comb. COMB F77D Fan speed in range G46 F71D F71 K15D = 4 90 127 D 2 E F74D G 2 F Fan speed selected To Page(s) 14, F75 131 D Selected Fan Speed S7 PROXIMITY 0 = Off 1 = Low 2 = Medium 3 = High 4 = Auto (1001-7) V F77D S INTERNAL E +/- F t2I13V Fan State Display D enum 4.5 -0.5 0 0 Disabled Disabled Units High Alarm Limit Low Alarm Limit High Alarm Delay Low Alarm Delay Low Alarm High Alarm COMPARATOR D = 1 when F > E 80 70 60 50 40 30 20 10 Drawing Reference SET-019-014-13 Page Details Fan Control - Variable Speed SET Strategy Designed By: Trend Control Systems D60D 3201 DA65 8FD9 921A 697A 87 Issue 3 Revision - 00 Checked By Project Number: 1 Date: Outstation: 014 Page: 3/24/2016 13 of 18 10 20 30 40 50 60 70 80 90 180 100 110 120 130 140 150 Heating required From Page 11 G20D Unit - unoccupied From Page 8 G16D 160 132 Unit interrupt From Page 8 Fan demanded G39D 150 Heating required From Page 11 F55D Cooling required From Page 11 140 W45D = 0 Fan Off at Setpoint 1=Enabled From Page 6 G20D E G47 J or K or L or M G39D F F55D G W45D H eFH eGH eh J Comb. K Comb. L Comb. M Comb. 130 G39D E G20D F G16D G J or K or L or M G47D H EFg gH J Comb. K Comb. L Comb. M Comb. 210 220 230 240 250 134 D COMB 135 G20D Unit - unoccupied From Page 8 COMB F76D Fan control auto selected From Page 13 G47D E 0 F G20D G F76D H h G egH G50 J or K or L or M Fan speed selected From Page 13 G49D Fan enabled to run From Page 14 0 E 1 F G49D B E F79 F79D F G51D B 142 Fan control off selected From Page 13 D GATE F Unit - unoccupied From Page 8 G20D G F76D F76D H H G J Comb. K Comb. L Comb. M Comb. Fan control auto selected From Page 13 F80D E 0.5 F Unit interrupt From Page 8 40 W27D = 0 139 J or K or L or M Fan demand From Page 11 Fan manual demand D 1 E F80D G 3 COMB F F81 F59D E F81D F G50D B W27D F Unit - unoccupied From Page 8 G20D G G49D G49D H G20D 30 Fan enabled to run From Page 14 eg eGH F E F84D F G50D B 156 G56D S INTERNAL D V 10.1 -0.5 0 0 Disabled Disabled GATE Units High Alarm Limit Low Alarm Limit High Alarm Delay Low Alarm Delay Low Alarm High Alarm Calculated fan speed F90D E F83D G K40D F F91 D K28D = 50 Fan Speed Override Value EC From Page 5 F91D E K28D F G53D 152 151 EC Fan Fan anti cycle seleted RSCL FR F86D E 0 F G55D B F86 D9 F88 F88D D GATE 9 S ANALOGUE D = F when B = 1 0 0 D B l Override Enable Override Value GATE W27D E W32D F 0 G F85D H EF l 154 146 149 Fan speed override required Fan on required G53 J or K or L or M 0.5 S D = 1 when F > E 148 Anti cycling active G54 0 0 E J or K or L or M D9l F F87D F G54D G F89D H fG EGh Gh J Comb. K Comb. L Comb. M Comb. D D COMPARATOR D = 1 when F > E COMB Fan Running I5 F89D F89D S S D 0 Alarm Delay 0 Required State Disabled State Alarm Hours Run Starts 145 Override Enable Override Value Override speed off TIMER F85 K28D = 50 Fan Speed Override Value EC From Page 5 TIMER 0.5 E F COMPARATOR S DIGITAL D On Delay Minimum On Off Delay D COMB F89 G55 G55D E D F86D Fan enabled Fan anti cycle active F87 J Comb. K Comb. L Comb. M Comb. 1 150 INTERNAL G56 SET Strategy Designed By: V D9l 144 GATE Delayed fan start R1L 0 0 SYNC S17 F90 Effective fan speed GATE D1 R1L Period Records 153 D D P5 S 15 Min 100 Minimum fan speed select K39D F83 Occupation Relay G52D Actual EC Fan Speed S17V Actual EC Fan Speed 147 157 J Comb. K Comb. L Comb. M Comb. COMB D=(G/100)(F-E)+E Fan Override 1=Enabled From Page 5 COMB Page Details Fan Control - Variable page 2 B K40D = 70 W32D = 1 D G49D Fan enabled to run To Page(s) 14, D = F when B = 1 Maximum Fan Speed Setpoint From Page 5 Overrides 0=Disabled 1=Enabled From Page 5 Local Address Drawing Reference SET-019-014-14 F F82D W27D = 0 RSCL TO D=100(G-E)/(F-E) J or K or L or M D D = F when B = 1 G52 10 J Comb. K Comb. L Comb. M Comb. F84 D = F when B = 1 D Fan power required E E Fan required speed 155 G16D Fan Override 1=Enabled From Page 5 H D = F when B = 1 50 G16D 0 COMPARATOR F59D G51 J or K or L or M 0 141 Fan control required 0 E D = 1 when F > E 137 E K39D F82 GATE F78D G20D 140 F80 D = F when B = 1 F78D G G49 Off fan speed select Fan speed = off D = F when B = 1 D 0 K39D = 37 Minimum Fan Speed Setpoint From Page 5 COMB D Fan on value select 100 F77D F 143 Minimum Fan Speed Setpoint From Page 5 Fan manual value select 136 E 0 D J Comb. K Comb. L Comb. M Comb. 138 110 G48D Manual fan speed enabled D F77D 20 200 Fan enabled to run 120 60 190 G48 K39D = 37 70 180 133 170 80 170 Fan required G39D 90 160 K28D E 20 F D 0 0 300 On Delay Minimum On Off Delay F89D Fan enabled To Page(s) COMPARATOR D = 1 when F > E Trend Control Systems D60D 3201 DA65 8FD9 921A 697A 87 Issue 3 Revision - 00 Checked By Project Number: 1 Date: Outstation: 014 Page: 3/24/2016 14 of 18 10 20 30 40 50 60 70 80 90 180 SB - Water Balance ON Lan I101 Service Button Mode 1=Enabled From Page 5 S W31D E I101S F 101 c EXTERNAL 0 Alarm Delay 0 Required State Disabled State Alarm Hours Run Starts SB - Water Balance OFF Lan I102 G 0 H EF EG J Comb. K Comb. L Comb. M Comb. 0 Alarm Delay 0 Required State Disabled State Alarm Hours Run Starts I103 W31D E I101S F I103S G 0 H EF EG S 103 c EXTERNAL 110 0 Alarm Delay 0 Required State Disabled State Alarm Hours Run Starts D 170 180 190 159 164 Water balance iccoms disable G61D S COMB On Delay Minimum On Off Delay 200 210 220 230 240 250 G66 G62D E 0 F 0 G 0 H e J Comb. K Comb. L Comb. M Comb. J or K or L or M D TIMER 0 0 300 D COMB G63 J or K or L or M D G65D COMB W31D I104 I102S S EXTERNAL 0 Alarm Delay 0 Required State Disabled State Alarm Hours Run Starts E F Water balance required G63D E J or K or L or M F G64 0 G J or K or L or M W28D H E fH J Comb. K Comb. L Comb. M Comb. G 0 H EF EG J Comb. K Comb. L Comb. M Comb. D COMB 163 G65 G64D I104S Water balance required To Page(s) 12, 162 J Comb. K Comb. L Comb. M Comb. Water balance disable 104 c 90 160 G62 161 SB - Water Balance OFF Unit 100 150 Water balance enable SB - Water Balance ON Unit 120 140 160 S EXTERNAL 140 J or K or L or M 130 Water balance iccoms required G61 I102S 102 c 130 120 158 170 150 110 Service button WB enable W31D = 1 160 100 Water balance iccoms Water Balance 1=Enabled D N6 W28 G65D W28D D L W28S R SWITCH 60 Pin Level Trend COMB 3 0 1 GLOBAL TO Remote Attributes Remote Lan Message Interval Failed Bit 80 70 Required Action Water Balance On for the Lan Water Balance Off for the Lan Water Balance On for the Unit Water Balance Off for the Unit 60 50 40 Phase 1 No Press Press No Press Press Phase 2 No Press No Press Press Press Phase 3 No Press No Press No Press No Press 30 20 10 Drawing Reference SET-019-014-15 Page Details Service Button - Water balance SET Strategy Designed By: Trend Control Systems D60D 3201 DA65 8FD9 921A 697A 87 Issue 3 Revision - 00 Checked By Project Number: 1 Date: Outstation: 014 Page: 3/24/2016 15 of 18 10 20 30 40 50 60 70 80 90 180 SB - Occupancy ON Lan Service Button Mode 1=Enabled From Page 5 I105 S W31D E I105S F 105 c EXTERNAL 0 Alarm Delay 0 Required State Disabled State Alarm Hours Run Starts SB - Occupancy OFF Lan I106 G 0 H EF EG J Comb. K Comb. L Comb. M Comb. 0 Alarm Delay 0 Required State Disabled State Alarm Hours Run Starts I107 W31D E I105S F I107S G 0 H EF EG S 107 c EXTERNAL 110 0 Alarm Delay 0 Required State Disabled State Alarm Hours Run Starts I108 S 108 c EXTERNAL 90 160 170 180 190 166 D G71D S COMB 210 220 230 240 250 170 G76 G72D E 0 F 0 G 0 H e J Comb. K Comb. L Comb. M Comb. J or K or L or M D TIMER 0 0 300 200 Occupancy iccoms disable G72 On Delay Minimum On Off Delay D COMB G73 J or K or L or M D G75D COMB G73D E 168 G74D F 0 G F9D H EH Fh J Comb. K Comb. L Comb. M Comb. 0 Alarm Delay 0 Required State Disabled State Alarm Hours Run Starts W31D E I106S F Service button occ active G74 J or K or L or M I108S G 0 H EF EG J Comb. K Comb. L Comb. M Comb. Service button occ active To Page(s) 8, 169 J Comb. K Comb. L Comb. M Comb. Occupancy disable SB - Occupancy OFF Unit 100 150 Occupancy enable SB - Occupancy ON Unit 120 140 167 S EXTERNAL 140 J or K or L or M 130 Occupancy iccoms required G71 I106S 106 c 130 120 165 170 150 110 Service button Occ enable W31D = 1 160 100 D COMB G75 J or K or L or M Occupancy Iccoms N7 K11D = 1 Remote Occupancy From Page 8 D K11D Trend COMB 3 0 1 0 L K11V R GLOBAL TO Remote Attributes Remote Lan Message Interval Significant Change Failed Bit F9D 80 Unit not in occ mode From Page 8 70 Required Action Occupied for the Lan Unoccupied for the Lan Occupied for the Unit Unoccupied for the Unit 60 50 40 Phase 1 No Press Press No Press Press Phase 2 No Press No Press Press Press Phase 3 Press Press Press Press 30 20 10 Drawing Reference SET-019-014-16 Page Details Service Button - Occupancy SET Strategy Designed By: Trend Control Systems D60D 3201 DA65 8FD9 921A 697A 87 Issue 3 Revision - 00 Checked By Project Number: 1 Date: Outstation: 014 Page: 3/24/2016 16 of 18 10 20 30 40 50 60 70 80 90 100 180 120 130 140 150 160 170 180 190 200 230 240 250 Power kW (D) = (Water Supply Temp DegC (E) – Space Temp DegC (F)) * Coil Duty kW/degK (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I) Power Btu/s (D) = (Water Supply Temp DegF (F) – Space Temp DegF (E)) * Coil Duty Btu/sDegF (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I) Cooling Power = (Space temperature – Cooling medium temperature) * Coil duty * Valve position / 100 172 Power kW (D) = (Space Temp (E) – Water Supply Temp (F)) * Coil Duty kW/degK (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I) Power Btu/s (D) = (Space Temp DegF (E) – Water Supply Temp DegF (F)) * Coil Duty Btu/sDegF (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I) (1001-25) Heating coil duty max speed 0 Heating Coil Duty Fan Off >>> Heating Coil Duty Max Speed >>> E F107 0.327778 F I5S Fan Running From Page 14 I5S 140 B D D = F when B = 1 Actual EC Fan Speed From Page 14 130 1 kW = 0.948608 Btu/s 1 hp = 0.7074163 Btu/s 1 Btu/h/3600 = 1 Btu/s 173 Calculated heating duty GATE S17V F107D E 0.1 G S17V F F108 189 K19D = 50 Water Flow Temperature From Page 4 D S2V MULTIPLY Space Temperature From Page 9 D=G*E*F 120 F63D Heat cool valve demand From Page 12 Heating coil energy level K19D E S2V F F108D G F118 110 Heat and cool energy level D F63D H 0.01 I HEAT METER K19D = 50 100 Water Flow Temperature From Page 4 175 90 F63D Cooling coil duty max speed Cooling Coil Duty Fan Off >>> 0 Cooling Coil Duty Max Speed >>> I5S Fan Running From Page 14 E 0.333333 F I5S B Heat cool valve demand From Page 12 F110 70 S17V Actual EC Fan Speed From Page 14 F110D E 0.1 G S17V F 178 60 Fan Duty Maximum Speed kW >>> 0.16 I5S Fan Running From Page 14 I5S E B F F111D G H F63D H 0.01 I HEAT METER Actual EC Fan Speed From Page 14 E 0.1 G S17V F 30 I5S Fan Running From Page 14 F111 E F120D F I5S B D Occupation Relay Duty kW>> D1l Occupation Relay From Page 14 0.5 F D1l B kWh 500 -1 0 0 Disabled Disabled F122 D GATE F122D E 1 F K52D G F123 197 Unit energy consumption D F121D H ADD/SCLR D = (E * G) + (F * H) F114 SET Strategy Designed By: G 3600 F G81D H F124 ∫dt D INTEGRATOR D=D+(G*seconds/F) Energy Meter 1=Reset D F1D MULTIPLY One shot switch reset From Page 3 F1D 192 60 D F114D E 1 F 1 G F116D Meter reset 15 minute pulse F121 30 minute pulse T1r Trend Control Systems D60D 3201 DA65 8FD9 921A 697A 87 ADD/SCLR Issue 3 E T1o F T1q G T1r H E G J Comb. K Comb. L Comb. M Comb. 60 minute pulse H Revision - 00 Checked By G81 W52D T1q D GATE 196 D Pin Level T1o Fan and electric heater energy F116 W52 SWITCH D = (E * G) + (F * H) Page Details Virtual Energy Meter F123D 195 D = F when B = 1 Drawing Reference SET-019-014-17 Units High Alarm Limit Low Alarm Limit High Alarm Delay Low Alarm Delay Low Alarm High Alarm 194 183 E V Unit total energy level MULTIPLY Occupation relay duty 0.01 SYNC D = F when B = 1 D=G*E*F 20 Period Records S INTERNAL Heating coolng load 0 Calculated fan duty F113D 30 Min 200 F124D 193 179 GATE ADD/SCLR S51 K52D = 1 S17V 10 F119D P6 S D Power Conversion Factor From Page 6 D = F when B = 1 40 G Unit Energy Meter D=G*E*F D 1 198 K19D F113 F Unit Energy Meter S51V F119 E Fan duty max speed 0 F120 D = (E * G) + (F * H) S2V Calculated cooling duty GATE F Coiling coil energy level 176 D = F when B = 1 E 1 D D=0 if F>E Else D=(E-F)*G*H*I D F118D 190 S2V Space Temperature From Page 9 (1001-26) 191 D=0 if F>E Else D=(E-F)*G*H*I 50 220 Heating Power = (Heating medium temperature – Space temperature) * Coil duty * Valve position / 100 160 80 210 Heat exchanger power estimation. 170 150 110 J or K or L or M D COMB Project Number: 1 Date: Outstation: 014 Page: 3/24/2016 17 of 18 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 180 170 160 150 140 130 120 Slave Remote Space Temp N1 S2V 110 Space Temperature From Page 9 S2V Trend 3 0 0 0.1 100 L K12V R GLOBAL TO Remote Attributes Remote Lan Message Interval Significant Change Slave Remote Setpoint 90 N2 S3V Setpoint From Page 10 S3V Trend 80 3 0 0 0.01 70 L K14V R GLOBAL TO Remote Attributes Remote Lan Message Interval Significant Change G41D Valve override required From Page 12 9 Slave Remote Occupancy N3 S10V Occupancy From Page 8 S10V 60 Trend 3 0 0 0.5 50 Override active L K11V R G53D Fan speed override required From Page 14 GLOBAL TO Remote Attributes Remote Lan Message Interval Significant Change A99 State Holder Slave Remote Fan Speed N4 S7V 40 Selected Fan Speed From Page 13 S7V Trend 3 0 0 0.5 30 L GLOBAL TO Remote Attributes Remote Lan Message Interval Significant Change 20 K15V R A99 State Holder can hold a value to indicate the state of the unit. The meaning of the value is user defined. It is suggested a bit state approach be used where values 1, 2, 4, 8 ,16 etc each indicating a separate operation. Summing the values provide a state of the unit. Suggested values: 1= Addressed, 2= Attributes Set, 4= Pre-commissioned, State Holder 8= Commissioned, A99 D 0 V 16 = Witnessed, Analogue 32 = Backed up, Read Alarm 64 = (TBC) , Out. Limits Alarm Low Alarm 128 = Has a Problem. E G53D F 0 G 0 H E F J Comb. K Comb. L Comb. M Comb. Alarm Group 1 0 Stratgey Override 1=Active I11 G111D D 0 Alarm Delay 0 Required State Disabled State Alarm Hours Run Starts COMB Alarm Destination e1 G 0 An exampled of its use. Drawing Reference SET-019-014-18 Page Details IC Comms and Alarm Group SET Strategy Designed By: D60D 3201 DA65 8FD9 921A 697A 87 0 H ALARM ROUTE Priority ALARM DEST 1 0 Disabled 1 0 e.g 11 = 1+2+8 = Addressed, Attributes Set and Commissioned. Trend Control Systems S F E High Alarm 10 o1D D N ALARM GROUP Issue 3 Revision - 00 Checked By S INTERNAL o1 g1O O L J or K or L or M Alarm Route 1 g1 R H G111 G41D Message Format Retry Pause Int. Inhibit Cleared Alarm Address Remote Lan Project Number: 1 Date: Outstation: 014 Page: 3/24/2016 18 of 18 Address Module BACnet Application Module Identifier Device Instance 0 Attribute F Manual Device Instance 0 Attribute G Send I-Am at Startup Disabled Alarm Lan 0 Alarm Address 0 MSTP Controller Version Strategy Name FCU EC Fan WT2 Revision 3 Project: IQeco_Standard_Strategies_v3.2.1 Max Info Frames 10 Address / Network / IO Project Number: 1 Date: 3/24/2016 Outstation: Page: T01 of T05 014 Sensor Number Type Label Units 1 2 Discharge Air Temperature DegC F16D 2 2 Space Temperature DegC F19D 3 2 Setpoint DegC F42D 7 2 Selected Fan Speed enum F77D 10 2 Occupancy enum F7D 11 2 Heating Demand % F52D 12 2 Cooling Demand % F53D 17 2 Actual EC Fan Speed V 21 1 Local Discharge Air Temp DegC 101 - 10k Therm DegC TBTS 0 1 22 1 Local Space Temperature DegC 101 - 10k Therm DegC TBTS 0 2 23 1 Local Setpoint Adjust DegC 102 - Knob TB 0.5deg trim0 31 2 Room Display Space Temp DegC t2O1V 32 2 Humidity %RH t2O2V 34 2 CO2 ppm t2O4V 39 2 Outside Air Temp DegC A1D 40 2 Dewpoint DegC t2O3V 51 2 Unit Energy Meter kWh F124D Project: IQeco_Standard_Strategies_v3.2.1 S.E.T. Part Number Offset Source I/O Channel D9l Sensor List 3 Project Number: 1 Date: 3/24/2016 Outstation: Page: T02 of T05 014 Dig In Number Label I/O Channel Source 1 Unit Occupied 0 G18D 2 Unit Unoccupied 0 G20D 3 Unit In Bypass 0 G19D 4 Unit In Standby 0 G21D 5 Fan Running 0 F89D 11 Stratgey Override 1=Active 0 G111D 24 Window Pushbutton PIR 4 101 SB - Water Balance ON Lan 101 102 SB - Water Balance OFF Lan 102 103 SB - Water Balance ON Unit 103 104 SB - Water Balance OFF Unit 104 105 SB - Occupancy ON Lan 105 106 SB - Occupancy OFF Lan 106 107 SB - Occupancy ON Unit 107 108 SB - Occupancy OFF Unit 108 Project: IQeco_Standard_Strategies_v3.2.1 Digital Inputs List Project Number: 1 Date: 3/24/2016 Outstation: Page: T03 of T05 014 Knob Number Label Units Value Max. Level Min. Level Pin Level 1 Pushbutton PIR Timeout min 30 1440 0 79 2 Setpoint Adjust Timeout min 60 1440 0 79 3 Offset Range DegC 2 10 1 79 4 OCC Deadband DegC 1 2 0.5 60 5 NOCC Deadband DegC 25 25 8 60 6 Standby Deadband DegC 8 8 1 60 7 Heating Setpoint DegC 19.5 24 8 79 8 Cooling Setpoint DegC 20.5 34 18 79 11 Remote Occupancy enum F11D 3 0 79 12 Remote Space Temperature DegC 22 30 0 79 13 Remote Setpoint Offset DegC 0 10 -10 79 14 Remote Setpoint DegC 22 24 18 79 15 Remote Fan Speed enum 4 4 0 79 19 Water Flow Temperature DegC 50 0 0 79 24 Heat Cool Valve Override Value % 0 100 0 60 28 Fan Speed Override Value EC % 50 100 0 60 39 Minimum Fan Speed Setpoint % 37 50 0 79 40 Maximum Fan Speed Setpoint % 70 100 50 79 44 Room Display Setpoint DegC t2O5V K47D K48D 79 45 Room Display Fan Speed enum t2O7V 255 0 79 47 Setpoint Highlimit DegC 24 0 0 0 48 Setpoint Lowlimit DegC 18 0 0 0 51 ECO Mode Deadband Increase DegC 3 6 2 79 52 Power Conversion Factor 1 0 0 79 Project: IQeco_Standard_Strategies_v3.2.1 Knobs List Project Number: 1 Date: 3/24/2016 Outstation: Page: T04 of T05 014 Switch Number Label Status Pin Level State 1 Unit Bypass Request 1=Active G9D 60 11 Remote Shutdown 1=Shutdown 0 79 12 Frost Condition 1=Frost 0 79 15 Summer Mode 1=Summer 0 79 24 Valve Override 1=Enabled 0 60 27 Fan Override 1=Enabled 0 60 28 Water Balance 1=Enabled G65D 60 31 Service Button Mode 1=Enabled 1 79 32 Overrides 0=Disabled 1=Enabled 1 79 34 Temperature Select 1=Remote 0 79 35 SP Offset Select 1=Remote 0 79 36 HeatCool Setpoint 1=Separate 0 79 37 Pushbutton TETS KO 1=Fitted 0 79 39 Fan Speed Select 1=Remote 0 79 41 Window Mode 1=Enabled 0 79 42 0=Pushbutton 1=PIR 0 79 45 Fan Off at Setpoint 1=Enabled 0 79 51 Operating Mode 0=Comfort 1=ECO 1 60 52 Energy Meter 1=Reset F1D 60 Project: IQeco_Standard_Strategies_v3.2.1 Switch List Project Number: 1 Date: 3/24/2016 Outstation: Page: T05 of T05 014
© Copyright 2026 Paperzz