Appendix-P
Communication Notice between PLCs and PWS
Communication between PLCs and PWS
P
IMPORTANT NOTES: "The Register and Range of Relay Numbers" listed in this appendix is
the range that allows for setting. In real operation, please be sure not to exceed the maximum
range of the numbers that the PLC-CPU defined.
NOTE: Set the PLC's communications parameters according to the following table; set the
Workstation's baud rate and data format to match the PLC's transmission speed and format;
Set the Workstation‘s Default Controller Station Number to match the PLC’s address:
The Driver File
For P.L.C. Brand Name
Page
P513.TSK
Allen-Bradley MICROLOGIX 1000
P-03
P553.TSK
Allen-Bradley PLC-5
-
P503.TSK
Allen-Bradley SLC 5/03 & 5/04
-
P003.TSK
Computer (as master)
-
P013.TSK
Computer (as slave)
-
PH03.TSK
Facon FB Series
P-05
PA13.TSK
Fuji NB Series
P-06
PA03.TSK
Fuji Micrex-F Series
-
P413.TSK
GE Series 90 CCM
-
P403.TSK
GE Series 90 SNP
P-07
PB13.TSK
Hitachi EC Series
-
PB03.TSK
Hitachi H Series
P-09
PE63.TSK
IDEC FA-2J
-
PE53.TSK
IDEC Micro-3
P-10
PK53.TSK
Jetter NANO-B
-
PK03.TSK
Klockner Moeller PS4-201
P-11
PK13.TSK
Klockner Moeller PS316
P-11
P913.TSK
KOYO Direct DL Series
-
PL03.TSK
LG K10/60H/200H
P-12
PL23.TSK
LG K500H/1000H
-
P703.TSK
Mitsubishi FX Series
P-13
P713.TSK
Mitsubishi FX-10GM/20GM Series
-
P723.TSK
Mitsubishi FX2N Series
P-13
PWS Workstation
Release 10/98
P-1
Communication Notice between PLCs and PWS
The Driver File
For P.L.C
For P.L.C. Brand Name
Page
P803.TSK
Mitsubishi A Series
P-14
P813.TSK
Mitsubishi A1S/A2S CPU Port
P-14
P823.TSK
Mitsubishi A2A/A2AS CPU Port
P-14
P833.TSK
Mitsubishi A1N CPU Series
P-14
P843.TSK
Mitsubishi A3N CPU Series
P-14
P853.TSK
Mitsubishi A0J2 CPU Series
P-14
P303.TSK
Modicon PC984(RTU mode)
P-16
P313.TSK
Modicon TSX QUANTUM Series
P-16
P603.TSK
Matsushita FP Series
P-17
P103.TSK
Omron C Series
P-19
P113.TSK
Omron CV Series
-
PY53.TSK
Sharp JW Series
P-21
P203.TSK
Simatic S5 Series (90U, 95U, 100U, 102U, 103U, 115U, 135U)
P-22
via PG port
P-2
P213.TSK
Simatic S5 3964R
-
P253.TSK
Simatic S7-200 Series (mono-link PPI port)
P-24
P257.TSK
Simatic S7-200 Series (multi-link PPI port)
P-24
P263.TSK
Simatic S7 3964R-CP340
-
P273.TSK
Simatic S7-300 Series (via MPI cable)
P-26
P277.TSK
Simatic S7-300 Series (via HMI cable)
-
PD03.TSK
Square D Model 400-700
P-27
PY03.TSK
Taian TP Series
-
PW03.TSK
Telemecanique TSX Micro
P-28
P903.TSK
TI 500/505
-
P913.TSK
TI 435
P-29
P923.TSK
TI 325/330
-
PT03.TSK
Toshiba M20/M40
-
PT13.TSK
Toshiba T1/T2
P-30
P013.TSK
Unidriver UD70
--
PC03.TSK
KOYO SA Series
P-31
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, p513.tsk, Allen-Bradley Micrologic 1000
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range With the Register
Data Size
Output file
O0:n
n=0
Word
Input file
I1:n
n=0-1
Word
Status file
S2:nn
nn=0-32
Word
Bit file
B3:nn
nn=0-31
Word
Timer flag
T4:nn.0
nn=0-39
Word
Timer Preset Value
T4:nn.1
nn=0-39
Word
Timer Accumulator Value
T4:nn.2
nn=0-39
Word
Counter flag
C5:nn.0
nn=0-31
Word
Counter Preset Value
C5:nn.1
nn=0-31
Word
Counter Accumulator Value
C5:nn.2
nn=0-31
Word
Control file
R6:nn.0
nn=0-15
Word
Control Size of Bit Array
R6:nn.1
nn=0-15
Word
Control Reserved file
R6:nn.2
nn=0-15
Word
Integer file
N7:nnn
nnn=0-104
Word
Note 1: The Workstation can read up to 30 words in one read command.
Note 2: The Workstation doesnot support block read for registers in Timer, Counter, and
Control files.
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block register, the bit address should be zero.
Relay Type
Format
Range With the Relay
Output
O0:n/bb
n=0 ; bb=0-15
Input
I1:n/bb
n=0-1; bb=0-15
Status
S2:nn/bb
nn=0-32; bb=0-15
Bit
B3:nn/bb
nn=0-31; bb=0-15
Timer
T4:nn.0/bb
nn=0-39; bb=0-15
Timer Preset Value
T4:nn.1/bb
nn=0-39; bb=0-15
Timer Accumulator Value
T4:nn.2/bb
nn=0-39; bb=0-15
Counter flag
C5:nn.0/bb
nn=0-31; bb=0-15
Counter Preset Value
C5:nn.1/bb
nn=0-31; bb=0-15
Counter Accumulator Value
C5:nn.2/bb
nn=0-31; bb=0-15
Control
R6:nn.0/bb
nn=0-15; bb=0-15
Control Size of Bit Array
R6:nn.1/bb
nn=0-15; bb=0-15
Control Reserved
R6:nn.2/bb
nn=0-15; bb=0-15
Integer
N7:nnn/bb
nnn=0-104; bb=0-15
Note 3: The Workstation can read up to 480 bits in one read command.
Note 4: The Workstation doesnot support block read for bits in Timer, Counter, and Control
files.
PWS Workstation
Release 10/98
P-3
Communication Notice between PLCs and PWS
3. Exam ple for the connections between PW S & RS232C of 1761 -CBL-PM02:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS-Setting
a. Communication format
:RS232C
b. Node Address
:N
c. Transmission Speed
:19200 bps
Set the Workstation's operating
d. Transmission Format
:8-bits,none, 1-bit
parameters to match the PLC.
(data bits,parity,stop bits)
e. Com Port
:FULL DUPLEX ; DF1
f. CRC ERROR Check
:YES
Note:You should open those files in the PLC that the Workstation will access.
P-4
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, ph03.tsk, FACON FB SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Input Relay
Output Relay
Internal Relay
Step Relay
Format
WXnnnn
WYnnnn
WMnnnn
WSnnnn
Range With the Register
nnnn=0-9984; (Must be 0 or multiple of 8)
nnnn=0-9984; (Must be 0 or multiple of 8)
nnnnn=0-9984; (Must be 0 or multiple of 8)
nnnn=0-9984; (Must be 0 or multiple of 8)
Timer Present Value
RTnnnn
nnnn=0-9999
Counter Present Value
RCnnnn
nnnn=0-9999
Data Register
Rnnnnn
nnnn=0-65534
Data Register
Dnnnnn
nnnn=0-65534
Note 1: The Workstation can read up to 64 words in one read command.
Data Size
Word
Word
Word
Word
Word
Word
Word
Word
2. The table below shows the format of every on/off location the Workstation can access. An
On/off block must start at an address that is a mutiple of 8. You cannot specify On/off blocks
to read Timer Flags and Counter Flags.
Relay Type
Format
Range With the Relay
Assign Format with Relay
Input Relay
Xnnnn
nnn=0-9999
Ex. X32 (Must be 0 or multiple of 8)
Output Relay
Ynnnn
nnn=0-9999
Ex. Y8 (Must be 0 or multiple of 8)
Internal Relay
Mnnnn
nnnn=0-9999
Ex. M0 (Must be 0 or multiple of 8)
Step Relay
Snnnn
nnn=0-9999
Ex. S16 (Must be 0 or multiple of 8)
Timer Flag
Tnnnn
nnn=0-9999
None
Counter Flag
Cnnnn
nnn=0-9999
None
3. Exam ple of the connections between PW S & RS232C of FB -MC type:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS232C
COM2 ==> RS232
b.Node Address
:1
c.Transmission Speed
:9600/19200 bps
Set the Workstation's operating
d.Transmission Format
:7-bit, even,1-bit
parameters to match the PLC.
PWS Workstation
Release 10/98
P-5
Communication Notice between PLCs and PWS
PLC Connections, Pa13.tsk, FUJI NB SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Data Register
Special Register
Timer Current Value
Counter Current Value
Input Relay
Output Relay
Internal Relay
Latch Relay
Special Relay
Step Relay
Format
Dnnn
Dnnnn
TNnnn
CNnn
WXnn
WYnn
WMnn
WLnn
WMnnn
WSnnn
Range With the Register
nnn=hex number 0-3ff
nnnn=hex number 8000-80ff
nnn=hex number 0-1ff
nn=hex number 0-ff
nn=hex number 0-1f
nn=hex number 0-1f
nn=hex number 0-3f
nn=hex number 0-3f
nnn=hex nuumber 800-81f
nnn=hex number 0-3f
Data Size
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block register, the bit number must be zero.
Relay Type
Timer output
Counter output
Input Relay
Output Relay
Internal Relay
Latch Relay
Special Relay
Step Relay
Format
Tnnn
Cnn
Xnnn
Ynnn
Mnnn
Lnnn
Mnnnn
Snnn
Range With the Relay
nnn=hex number 0-1ff
nn=hex number 0-ff
nnn=hex number 0-1ff
nnn=hex number 0-1ff
nnn=hex number 0-3ff
nnn=hex number 0-3ff
nnnn=hex number 8000-81ff
nnn=hex number 0-3ff
On/off Block
The last digit is 0
The last digit is 0
The last digit is 0
The last digit is 0
The last digit is 0
The last digit is 0
The last digit is 0
The last digit is 0
3. Exam ple of the connections between PW S & RS422 of NB/NS/NJ -CPU port:
4. P.L.C. & PWS setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS422
COM2=RS232/422/485
b.Node Address
:None
c.Transmission Speed
:19200 bps
Set the Workstation's operating
d.Transmission Format
:8-bit,ODD,1-bit
parameters to match the PLC.
e. P.L.C. password
:none or 0000-9999
0000 or ****
P-6
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, p403.tsk, GE-FANUC 90-SNP
1. The table below shows the form ats of every register the PW S can access.
Register
Type
Discrete Inputs
Format
%Innnnn
Range With the Register
nnnnn=1-12288; Must be 1or ( Multiple of
Data Size
Word
16)+1
Discrete Outputs
%Qnnnnn
nnnnn=1-12288; Must be 1or ( Multiple of
Word
Discrete
%Tnnn
nnn=1-256; Must be 1or ( Multiple of 16)+1
Word
Discrete Internals
%Mnnnnn
nnnnn=1-12288; Must be 1or ( Multiple of
Word
%SA Discretes
%SAnnn
nnn=1-128; Must be 1or ( Multiple of 16)+1
Word
%SB Discretes
%SBnnn
nnn=1-128; Must be 1or ( Multiple of 16)+1
Word
%SC Discretes
%SCnnn
nnn=1-128; Must be 1or ( Multiple of 16)+1
Word
%S Discretes
%Snnn
nnn=1-128; Must be 1or ( Multiple of 16)+1
Word
Genius Global Data
%Gnnnn
nnnn=1-7680; Must be 1or ( Multiple of 16)+1
Word
Registers
%Rnnnnn
nnnnn=1-16384
Word
Analog Inputs
%AInnnn
nnnn=1-8192
Word
Analog Outputs
%AQnnnn
nnnn=1-8192
Word
16)+1
Temporaries
16)+1
Note 1: The PWS can read up to 50 Words in one read command.
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block register, use an address that is a multiple of 16
plus 1.
Relay Type
Format
Range
On/off Block
Discrete Inputs
%Innnnn
nnnnn=1-12288
Must be 1or ( Multiple of 16)+1
Discrete Outputs
%Qnnnnn
nnnnn=1-12288
Must be 1or ( Multiple of 16)+1
Discrete Temporaries
%Tnnn
nnn=1-256
Must be 1or ( Multiple of 16)+1
Discrete Internals
%Mnnnnn
nnnnn=1-12288
Must be 1or ( Multiple of 16)+1
%SA Discretes
%SAnnn
nnn=1-128
Must be 1or ( Multiple of 16)+1
%SB Discretes
%SBnnn
nnn=1-128
Must be 1or ( Multiple of 16)+1
%SC Discretes
%SCnnn
nnn=1-128
Must be 1or ( Multiple of 16)+1
%S Discretes
%Snnn
nnn=1-128
Must be 1or ( Multiple of 16)+1
Genius Global Data
%Gnnnn
nnnn=1-7680
Must be 1or ( Multiple of 16)+1
** The PWS can read up to 800 Bits in one read command。
PWS Workstation
Release 10/98
P-7
Communication Notice between PLCs and PWS
3. Exam ple of the connections between PW S & RS232 of PLC m iniconverter k it:
3.1 Example of the connections between PWS & RS422 of
PLC 9030 CPU port:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS422 CPU PORT
:RS232C
b.Node Address
:None
c.Transmission Speed
:19200/9600 bps
d.Transmission Format
:8-bit, none,1
e.P.L.C. ID
:blank
f. P.L.C. password
:none or ********
00000000 or ********
P-8
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, pb03.tsk, HITACHI H SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range With the Register
Data Size
External input
WXnnnm
nnn=hex number 0-4ff;m=0-9
Word
External output
WYnnnm
nnn=hex number 0-4ff; m=0-9
Word
Internal output
WRnnnn
nnnn=hex number 0-c3ff
Word
Internal output
WRnnnn
nnnn=hex number f000-f1ff
Word
Internal output
WMnnn
nnn=hex number 0-3ff
Word
1st CPU link area
WLnnn
nnn=hex number 0-3ff
Word
2nd CPU link area
WLnnnn
nnnn=hex 1000-13ff
Word
Timer/Counter Current Value
TCnnn
nnn=0-511
Word
Note 1: The Workstation can read up to 120 words in one read command.
Note 2: Block access for WX and WY areas are not allowed.
2. The table below shows the format of every on/off location the Workstation can access.
Relay Type
Format
Range
On/off Block
External input
Xnnnmm
nnn=hex. 0-4ff; mm=00-95
Not provide
External output
Ynnnmm
nnn=hex. 0-4ff; mm=00-95
Not provide
Internal output
Rnnn
nnn=hex number 0-7ff
Unlimited
Internal output
Mnnnn
nnnn=hex number 0-3fff
Unlimited
1st CPU link area
Lnnnn
nnnn=hex number 0-3fff
Unlimited
2nd CPU link area
Lnnnnn
nnnnn=hex number 10000-13fff Unlimited
On-delay timer bit
TDnnn
nnn=0-255
Unlimited
Single-shot timer bit
SSnnn
nnn=0-255
Unlimited
Up counter bit
CUnnn
nnn=0-511
Unlimited
Up/down counter up coil
CTUnnn
nnn=0-511
Unlimited
Up/down counter down coil
CTDnnn
nnn=0-511
Unlimited
Up/down counter contact
CTnnn
nnn=0-511
Unlimited
Timer/counter value clear bit CLnnn
nnn=0-511
Unlimited
Rising edge detection bit
DIFnnn
nnn=0-511
Unlimited
Falling edge detection bit
DFNnnn
nnn=0-511
Unlimited
Note 3: The Workstation can read up to 240 bits in one read command.
3. Exam ple of the connection s between PW S & RS232 of PLC H200 -CPU port:
4. P.L.C. & PWS setting:
A. P.L.C. Setting
a.Communication Format :RS232C
b.Transmission Speed
:19200/9600 bps
c.Transmission Format :7-bit, EVEN, 1-bit
d.CTS Handshanking
:Enabled
PWS Workstation
Release 10/98
B.
PWS- Setting
P-9
Communication Notice between PLCs and PWS
PLC Connections, pe53.tsk, IDEC MICRO-3 SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range With the Register
Data Size
Input Relay
Xn
n=0-3
Byte
Output Relay
Yn
n=0-3
Byte
Internal Relay
Mnn
nn=0-31
Byte
Shift Register
Rnn
nn=0-48;Must be 0 or multiple of 8
Bit
Timer Preset
TPnn
nn=0-31(read only)
Word
Timer Current
Tnn
nn=0-31
Word
Counter Preset
CPnn
nn=0-31(read only)
Word
Counter Current
Cnn
nn=0-31
Word
Data Register
Dnn
nn=0-99
Word
Calender/Clock
Wn
n=0-6
Word
Note 1: The Workstation can read up to 50 words in one read command.
Note 2: Timer Preset and Counter Preset are read only. If the value of a TP or CP is in a
data register, then the value read is the address of that data register.
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block register in X, Y, or M area, use an address
that its bit address("b") is 0("0").
Relay Type
Format
Range
On/off Block
Input Relay
Xnb
n=0-3; b=0-7
b=0 Ex. X10
Output Relay
Ynb
n=0-3; b=0-7
b=0 Ex. Y00
Internal Relay
Mnnb
nn=0-31; b=0-7
b=0 Ex. M10
Shift Register
Rnn
nn=0-63
Must be 0 or multiple of 8
Timer Status
Tnn
nn=0-31
Must be 0 or multiple of 8
Counter Status
Cnn
nn=0-31
Must be 0 or multiple of 8
Note 1: The Workstation can read up to 800 bits in one read command.
Note 2: Timer Status and Counter Status are read only.
3. Exam ple of the connections between PW S & RS485 of PLC Micro3 -CPU port:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS485
PWS back DIP-Switch SW10=ON
b.Node Address
:0-31;255
If your application has only one PLC, then
set the parameter to 255; otherwise, set it
c.Transmission Speed
:9600bps
d.Transmission Format
:7-bit;EVEN, 1-bit
to the PLC's "PLC Address for Network
e.CTS Handshaking
:Disabled
Communication" that you set with the
program loader
P-10
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, pk03.tsk, KLOCKNER MOELLER PS SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range With the Register
Word Marker
MWnnnnn
nnnnn=0-32766
Note 1: The Workstation can read up to 32 words in one read command.
Data Size
Word
2. The table below shows the address format of the on/off location the Workstation can access.
When you specify the address of an On/off Block register, the bit address("b") should be 0.
Relay Type
Format
Range
On/off Block
Bit Marker
Mnnnnn.b
nnnnn=0-32766;b=0-7
Note 2: The Workstation can read up to 512 bits in one read command.
b=0 Ex. M10.0
3. Exam ple of the connections between PW S & PLC -CPU ZB4-303-KB1:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS232
b.Node Address
:0=PS4-201
PLC node 0 (Refer to what PLC was set)
:1=PS316
PLC node 1
c.Transmission Speed
:9600bps
d.Transmission Format
:8-bit; None;1bit
PWS Workstation
Release 10/98
P-11
Communication Notice between PLCs and PWS
PLC Connections, pl03.tsk, LG K10/60H/200H SERIES
1. The table below shows the form ats of every register the PW S can access.
Register
Type
Format
Range With the
Register
Auxiliary Relay
Mnn
nn=0-63
Input/Output Relay
Pnn
nn=0-15
Keep Relay
Knn
nn=0-31
Link Relay
Lnn
nn=0-31
Special Relay
Fnn
nn=0-15
Timer Current Value
Tnnn
nnn=0-255
Counter Current Value
Cnnn
nnn=0-255
Timer Set Value
TSnnn
nnn=0-255
Counter Set Value
CSnnn
nnn=0-255
Data Register
Dnnnn
nnnn=0-1023
Note 1: The Workstation can read up to 32 words in one read command.
Data Size
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block register, use an address that is a multiple of
16.
Relay Type
Format
Range
On/off Block
Auxiliary Relay
Mnnb
nn=0-63; b=hex number0-f
The last digit “b” is 0
Input/Output Relay
Pnnb
nn=0-15; b=hex number0-f
The last digit “b” is 0
Keep Relay
Knnb
nn=0-31; b=hex number0-f
The last digit “b” is 0
Link Relay
Lnnb
nn=0-31; b=hex number0-f
The last digit “b” is 0
Special Relay
Fnnb
nn=0-15; b=hex number0-f
The last digit “b” is 0
Timer Relay
Tnnn
nnn=0-255
Must be 0 or multiple of 16
Counter Relay
Cnnn
nnn=0-255
Must be 0 or multiple of 16
Note 2: The Workstation can read up to 256 bits in one read command.
3. Exam ple of the connections between PW S & RS232 of PLC -K200H CPU:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP-Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS232C
b.Node Address
: 00
c.Transmission Speed
:9600 bps
d.Transmission Format
:8-bit,NONE,1-bit
P-12
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, p703.tsk, MITSUBISHI FX2/FX2N SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range With the Register
Auxiliary Relay
Mnnnn
nnnn=0-3071;Must be 0 or a multiple of 8
Special Auxiliary Relay Mnnnn
nnnn=8000-8255;Must be 0 or a multiple of8
Status Relay
Snnn
nnn=0-999; Must be 0 or a multiple of 8
Input Relay
Xnnn
nnn=octal number 0-377; The last digit is 0
Output Relay
Ynnn
nnn=octal number 0-377; The last digit is 0
Timer PV
Tnnn
nnn=0-255
16-bit Counter PV
Cnnn
nnn=0-199
32-bit Counter PV
Cnnn
nnn=200-255
Data Register
Dnnn
nnn=0-1023(7999) D1000=FILE REGISTER
Special Data Register
Dnnnn
nnnn=8000-8255
Note 1: The Workstation can read up to 32 words in one read command.
Data Size
Word
Word
Word
Word
Word
Word
Word
D-Word
Word
Word
Relay Type
Format
Range
On/off Block
Auxiliary Relay
Mnnnn
0-3071
Must be 0 or multiple of 8
Special Auxiliary Relay
Mnnnn
8000-8255
Must be 0 or multiple of 8
Status Relay
Snnn
0-999
Must be 0 or multiple of 8
Input Relay
Xnnn
Octal number 0-377
The last digit is 0
Output Relay
Ynnn
Octal number 0-377
The last digit is 0
Timer Flag
Tnnn
0-255
Must be 0 or multiple of 8
Counter Flag
Cnnn
0-255
Must be 0 or multiple of 8
Note 2: The Workstation can read up to 512 bits in one read command.
2. Exam ple of the connections between PW S & RS422 of PLC -FX2 CPU:
2.1 Exam ple of the connections between PW S & RS422 of FX2N/FX0N CPU:
3. P.L.C. & PW S setting: a.Com m unication Form at:RS422 ; b.Transm ission
Speed:9600 bps ; c. Transm ission Form at:7 -bit,EVEN,1-bit.
PWS Workstation
Release 10/98
P-13
Communication Notice between PLCs and PWS
PLC Connections, p8x3.tsk, MITSUBISHI A SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range With the Register
Input Relay
Xnnn
nnn=hex number 0-7ff; The last digit is 0
Output Relay
Ynnn
nnn=hex number 0-7ff; The last digit is 0
Link Relay
Bnnn
nnn=hex number 0-fff; The last digit is 0
Internal Relay
Mnnnn
nnnn=0-8191;Must be 0 or multiple of 16
Special Relay
Mnnnn
nnnn=9000-9255; Must be multiple of 16
Latch Relay
Lnnnn
nnnn=0-2047; Must be 0 or multiple of 16
Annunciator
Fnnnn
nnnn=0-2047; Must be 0 or multiple of 16
Timer PV
TNnnn
nnn=0-999
Counter PV
CNnnn
nnn=0-999
Data Register
Dnnnn
nnnn=0-6143
Special Register
Dnnnn
nnnn=9000-9255
File Register
Rnnnn
nnnn=0-8191
Link Register
Wnnn
nnn=hex number 0-fff
Note 1: The Workstation can read up to 64 words in one read command.
Data Size
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block register, use an address that is a multiple of
16.
Relay Type
Format
Range
On/off Block
Input Relay
Xnnn
hex number 0-7ff
The last digit must be 0
Output Relay
Ynnn
hex number 0-7ff
The last digit must be 0
Link Relay
Bnnn
hex number 0-fff
The last digit must be 0
Internal Relay
Mnnnn
0-8191
Must be 0 or multiple of 16
Special Relay
Mnnnn
9000-9255
The last 3 digits must be multiple of 16
Latch Relay
Lnnnn
0-2047
Must be 0 or multiple of 16
Annunciator
Fnnnn
0-2047
Must be 0 or multiple of 16
Timer Contact
TSnnn
0-999
Must be 0 or multiple of 16
Timer Coil
TCnnn
0-999
Must be 0 or multiple of 16
Counter Contact CSnnn
0-999
Must be 0 or multiple of 16
Counter Coil
CCnnn
0-999
Must be 0 or multiple of 16
Note 2: The Workstation can read up to 512 bits in one read command.
3. Exam ple of the connections between PW S & RS232 of PLC AJ71UC24-R2/S8:
P-14
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
3.1 Exam ple of the connections between PW S & RS422 of AnA and A1S CPU:
3.2 Exam ple of the connections between PW S & RS422 of PLC AJ71UC24:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS422 or RS232C
AJ71UC24
sw1=ON :RS422
1.PWS back DIP-Switch SW10=OFF
sw1=Off
:RS232
2.PWS back DIP-Switch SW10=ON
b.NODE ADDRESS.
:00(CPU PORT)
Refer to what PLC was set
:00(AISJ71C24-S3)
**PWS node address is 255
:00-31(AJ71UC24)
**PWS node address is 255
c.Transmission Speed
:9600/19200 bps
:CPU PORT=9600bps
d.Transmission Format
:8-bit,ODD,1-bit
e.Comm. Protocol
:Format 1;5;A
f.Check Sum
:YES
g.Write during Run
:Allowed
Set the Workstation's baud rate and data format to match the PLC's transmission speed and
format.
Set the address of the Workstation as 255 and the address of the PLC as 0 when an
A1SJ71C24 or AJ71C24 is used for the communications.
To connect the Workstation to the PLC CPU port, set the Workstation communication
parameters according to the following; set the DIP switch No.10 to off when COM2 is used.
Baud Rate = 9600; Data Format = (8 data bits, odd parity, 1 stop bit)
PWS Workstation
Release 10/98
P-15
Communication Notice between PLCs and PWS
PLC Connections, p303.tsk, MODICON PC984 SERIES
PLC Connections, p313.tsk, MODICON TSX QUANTUM
1. The table below shows the form ats of every register the PW S can access.
Register
Type
Format
Range
Data Size
Input Registers
nnnnn
nnnnn=30001-40000
Word
Output Registers
nnnnn
nnnnn=40001-50000
Word
Input Registers (TSX Quantum)
nnnnnn
nnnnn=300001-365535
Word
Output Registers (TSX Quantum)
nnnnnn
nnnnn=400001-565535
Note 1: The Workstation can read up to 125 words in one read command.
Word
2. The table below shows the format of every on/off location the Workstation can access.
Relay Type
Format
Range
Discrete Outputs
nnnnn
nnnnn=1-10000
Discrete Inputs
nnnnn
nnnnn=10001-20000
Discrete Outputs (TSX Quantum)
nnnnn
nnnnn=000001-065535
Discrete Inputs (TSX Quantum)
nnnnn
nnnnn=100001-165535
Note 2: The Workstation can read up to 2000 bits in one read command.
3. Exam ple of the connections between PW S & RS232 of PLC CPU port:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS232C
PLC node address is 01
b.Node Address
:1
(Refer to what PLC was set)
: 01—247 (mem setup)
c.Transmission Speed
:19200/9600 bps
d.Transmission Format
:8, EVEN ,1
:(7,O,1);(7,E,1);(7,E,2)
RTU MODE
:(8,E,1);(8,O,1);(8,N,1)
P-16
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, p603.tsk, MATSUSHITA FP SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range
Data Size
Internal Relay
WRnn
nn=0-97(875)
Word
Max.27
Special Internal Relay
WRnnn
nnn=900-910
Word
Max.27
Link Relay
WLnnn
nnn=0-127(639)
Word
Max.27
External Input Relay
WXnnn
nnn=0-127(255)
Word
Max.27
External Output Relay
WYnnn
nnn=0-127(255)
Word
Max.27
Timer/Counter P.V.
EVnnn
nnn=0-255(2047)
Word
Max.24
Timer/Counter S.V.
SVnnn
nnn=0-255 (2047)
Word
Max.24
Data Register
DTnnnn
nnnn=0-2047 (10239)
Word
Max.27
Special Data Register
DTnnnn
nnnn=9000-9255
Word
Max.27
Link Data Register
LDnnn
nnn=0-127(8447)
Word
Max.27
File Register
FLnnnnn
nnnn=0-8191 (32764)**
Word
Max.27
Note 1: The maximal number of words that the Workstaion can read in one command is 27 for
every type of registers except Timer/Counter registers.
The maximum for Timer/Counter registers is 24.
Note 2: The Register setting range of FP10SH is nnnn=0- 32764.
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block in WR, WL, WX or WY area, use an
address that its bit address("b") is 0("0"). When you specify the address of an On/off Block in T
or C area, use an address that is a multiple of 16.
Range
On/off Block
Relay Type
Format
Internal Relay
Rnnnb
nn=0-97(875);b= 0-f
b=0 Ex. R1230
Special Internal Relay
Rnnnb
nnn=900-910;b= 0-f
b=0 Ex. R9100
Link Relay
Lnnnb
nnn=0-127(639);b=0-f
b=0 Ex. L110
External Input Relay
Xnnnb
nnn=0-127(255);b=0-f
b=0 Ex. X00
External Output Relay
Ynnnb
nnn=0-127(255);b=0-f
b=0 Ex. Y00
Timer Flag Contact
Tnnn
nnn=0-255(2047)
Must be 0 or multiple of 16
Counter Flag Contact
Cnnn
nnn=0-255(2047) **
Must be 0 or multiple of 16
Note 3: The Workstation can read up to 432 bits in one read command.
Note 4: The Relay setting range of FP10SH is nnnn=0-2047.
3. Exam ple of the connections between PW S & RS232 of FP3 CCU or FP1 LINK:
PWS Workstation
Release 10/98
P-17
Communication Notice between PLCs and PWS
3.1 Example of the connections between PWS & RS422 of PLC FP3 CPU port:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS422/RS232C
b.Node Address
:01-32;FP1=computer link
:FP CPU PORT =238
CPU PORT's node address of is 238
c.Transmission Speed
:19200/9600 bps
FP10SH -CPU 115.2K bps
d.Transmission Format
:1.Data length 8-bit
:2.Parity
Yes;odd
:3.Stop bits
1-bit
P-18
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, p103.tsk, OMRON C SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type Format
Range
Data Size
IR area
IRnnn
nnn=0-255
Word(16bit)
HR area
HRnn
nn=0-99
Word(16bit)
AR area
ARnn
nn=0-27
Word(16bit)
LR area
LRnn
nn=0-63
Word(16bit)
TC area
TCnnn
nnn=0-511
Word(16bit)
DM area
DMnnnn
nnnn=0-6655
Word(16bit)
Note 1: The Workstation can read up to 28 words with one read command.
Block Size
Max. 28
Max. 28
Max. 28
Max. 28
Max. 28
Max. 28
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block is in IR,HR,AR or LR area, use an address
that its bit address("bb") is 0("00"). When you specify the address of an On/off Block in TC
area, use an address that is a multiple of 16.
Relay Type
Format
Range
On/off Block
IR area
IRnnnbb
nnn=0-255; bb=00-15
bb=00 Ex. IR12300
HR area
HRnnbb
nn=0-99 ; bb=00-15
bb=00 Ex. HR2300
AR area
ARnnbb
nn=0-27 ; bb=00-15
bb=00 Ex. AR100
LR area
LRnnbb
nn=0-63 ; bb=00-15
bb=00 Ex. LR2300
TC area
TCnnn
nnn=0-511
multiple of 16 Ex.TC16
Note 2: The maximal number of bits the Workstation can read with one command is 112.
3. Exam ple of the connections between PW S & RS232 of PLC link port:
3.1 Exam ple of the connections between PW S & RS422 of PLC LK202 :
PWS Workstation
Release 10/98
P-19
Communication Notice between PLCs and PWS
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A.
a.Communication
Format
b.Node Address
P.L.C. Setting
:RS232C
:RS422
:RS485
:00(00-31 to setting)
1.Mini-H type
2.CQM1-CPU21
3.C200H-LK201
c.Transmission Speed
1.CQM1-CPU21
2.C200H-LK201
d.Transmission Format
e.Operation Mode
f. CTS handshaking
g.Communication Protocol
h.5V-POWER SUPPLY
P-20
:DM0923=0000
:DM6648=0000
:Main brand sw1=0 , sw2=0
:19200/9600 bps
:DIP-sw5=OFF (Attention)
:sw3=5 sw4=2 (9600bps)
:1.initial value
7-bit,ENEN,2
:2.adjustable
:Monitor Mode
:Either position
:Multiple-Link
:OFF
B. PWS- Setting
COM2=RS232/422/485
PWS back DIP-Switch SW10=ON
Refer to what PLC was set
Set the Workstation's baud rate,
data format, default controller
station number to match the PLC's
transmission speed, transmission
format, and unit number.
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, py53.tsk, SHARP JW SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range With the Register
Data Size
Register
09ooo
ooo=octal number 0-776
Byte
Register
19ooo
ooo=octal number 0-776
Byte
Register
29ooo
ooo=octal number 0-776
Byte
Register
39ooo
ooo=octal number 0-776
Byte
Timer Value
Tooo
ooo=octal number 0-377
Word
Counter Value
Cooo
ooo=octal number 0-377
Word
Relay
oooo
oooo=octal number 0-1576
Note 1: The PWS can read up to 60 Words in one read command。
Byte
2. The table below shows the format of every on/off location the Workstation can access.
Relay Type
Format
Range
On/off Block
Relay
ooooo
ooooo=octal number 0-15776
The last digit must be 0
Timer Contact
Tooo
ooo=octal number 0-377
The last digit must be 0
Counter Contact
Cooo
ooo=octal number 0-377
The last digit must be 0
Note 2: The Workstation can only read one bit with one read command, so it is meaningless
to use on/off blocks.
3. Exam ple of the connections between PW S & RS232/422 of PLC JW -CPU
port:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS232/RS422/RS485
COM2=RS232/422/485
b.Node Address
c.Transmission Speed
SYS#236= Hex 31
d.Transmission Format
:01; SYS#237=Hex01
:19200/9600bps
: (9600,7,even,2)
:Setting of SYS#236
e.CTS handshaking
:enable
PWS Workstation
Release 10/98
node address is 01
Refer to what PLC was set
P-21
Communication Notice between PLCs and PWS
P.22 PLC Connections, p203.tsk, SIEMENS S5 SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Input Image
Output Image
Extended I/O
Flag Bits
Peripheral I/O
System Data Area
System Data Area
System Data Area
System Data Area
Timer Current
Counter Current
Data Block
Format
IBnnn
QBnnn
OBnnn
FBnnn
PBnnn
RSnnn
RInnn
RJnnn
RTnnn
Tnnn
Cnnn
DBmmm/nnn
DBnnn
Range With the Register
Data Size
Block Size
nnn=0-127
Byte
Max. 30
nnn=0-127
Byte
Max. 30
nnn=0-255
Byte
Max. 30
nnn=0-255
Byte
Max. 30
nnn=0-255
Byte
Max. 30
nnn=0-255
Word
Max. 30
nnn=0-255
Word
Max. 30
nnn=0-255
Word
Max. 30
nnn=0-255
Word
Max. 30
nnn=0-255
Word
Max. 30
nnn=0-255
Word
Max. 30
mmm=0-255; mmm is Block number
Max. 30
nnn=0-255;
nnn is the numbers which defines block
If the mmm not set the numbers, the numbers
of mmm is 3= DB3/nnn
Data Block
DWmmm/nnn
mmm=0-127; mmm is Block number
Max. 30
DWnnn
nnn=0-255;
nnn is the numbers which defines block
If the mmm not set the numbers, the numbers
of mmm is 3= DW3/nnn
Note 1: See the paragraph of Workstation Setting to know the maximal number (30 Words) of
words the Workstation can read with one read command.
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block register, use an address that its bit address("b")
is 0.
Range
On/off Block
Relay Type
Format
b=0 Ex. IB30.0
Input Image
IBnnn.b
nnn=0-127; b=0-7
b=0 Ex. QB2.0
Output Image
QBnnn.b
nnn=0-127; b=0-7
b=0 Ex. OB0.0
Extended I/O
OBnnn.b
nnn=0-255; b=0-7
b=0 Ex. FB23.0
Flag Bits
FBnnn.b
nnn=0-255; b=0-7
b=0 Ex. PB23.0
Peripheral I/O
PBnnn.b
nnn=0-255; b=0-7
Note 2: The Workstation can read up to 256 bits with one read command.
When the Workstation changes an on/off location, it reads a byte from the PLC that contains 8
on/off locations, changes the desired bit, and writes the byte to the PLC. These steps require
more than one PLC scan to complete, so your PLC ladder program must not control other bits
within the same byte. If it does, there is a risk that the Workstation will reverse a change that
the PLC makes.
For example, if the Workstation changes FB100.3, it reads FB100.0 through FB100.7 as a
single byte, changes FB100.3 within that byte, and writes that entire byte back to the PLC. If
your PLC ladder changes some other relay within that byte in the meantime, then the
Workstation's subsequent write will cancel that change.
P-22
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
3. Exam ple of the connections between PW S & S5 RS232/Current -loop
converter:
You must use a RS-232/Current-loop converter cable directly.
You have to use an RS-232/Current-loop converter between the Workstation RS-232 port and
the PLC PG port. The PWS-12xx, PWS-17xx, PWS-31xx, PWS-700T/X, PWS-21xx, and
PWS-37XX do not support current-loop signals.
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the
A. P.L.C. Setting
a.Communication Format :20mA CURRENT LOOP
:RS-232/Current-loop
converter
b.Node Address
:None
c.Transmission Speed
:9600 bps
d.Transmission Format
:8-bit, EVEN ,1-bit
e.PLC Mode Code
:In PLC Program Data Block
n=3~255 Need OPEN
f. Command
Delay
PWS Workstation
Release 10/98
DIP -Switch as below:
B. PWS- Setting
Refer to what PLC was set
PLC. MODE CODE Setting
0: 90U
1: 95U
2:100U
3:102U 4:103U
5:115U
6:135U/921
7:135U/922 8:135U/928
This parameter is borrowed for determining the maximal number of words
the Workstation can read with one read command. The more words the
Workstation can read with one command the better performance you will
get for the block read operations. Note that not all applications can have
64-word or 32-word, because the Workstation's response time of
communication may not fast enough with your application. You have to test
it carefully.
0, 3-255: 16 words 1: 32 words 2: 64 words
P-23
Communication Notice between PLCs and PWS
PLC Connections, p253.tsk, SIEMENS S7-200 SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range With the Register
Data Size
Input Image
IWn
n=0-6
Word
Input Image
IDn
n=0-4
Double Word
Output Image
QWn
n=0-6
Word
Output Image
QDn
n=0-4
Double Word
Internal Bits
MWnn
nn=0-30
Word
Internal Bits
MDnn
nn=0-28
Double Word
Timer
Tnnn
nnn=0-255
Word
Counter
Cnnn
nnn=0-255
Word
Special S
SWnn
nn=0-30
Word
Special S
SDnn
nn=0-28
Double Word
Special Bits
SMWnnn
nnn=0-27
Word* read only
Special Bits
SMWnnn
nnn=28-192
Word
Special Bits
SMDnnn
nnn=0-190
Double Word
Analog input word
AIWnn
nn=0-30
Word* read only
Analogoutputword
AQWnn
nn=0-30
Word* read only
Data Area
VWnnnn
nnnn=0-5118
Word
Data Area
VDnnnn
nnnn=0-5116
Double Word
Note 1: The Workstation can read up to 32 words with one read command.
Note 2: In application,please be sure not to exceed the max. relay setting range of PLC-CPU
defined.AQW; SW;SD can’t used in CPU212,214,otherwise it will communication error.
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block, use an address that its bit address("b") is 0.
Range
On/off Block
Relay Type
Format
Input Image
In.b
n=0-7; b=0-7
b=0 Ex. I3.0
Output Image
Qn.b
n=0-7; b=0-7
b=0 Ex. Q2.0
Internal Bit
Mnn.b
nn=0-31;b=0-7
b=0 Ex. M0.0
Timer Bit
Tnnn
nnn=0-255
b=0 Ex.T0 *read only
Counter Bit
Cnnn
nnn=0-255
b=0 Ex.C0 *read only
Special Bit
SMnnn.b
nnn=0-193 ;b=0-7
b=0 Ex. SM23.0
Data Area Bit
Vnnnn.b
nnnn=0-5119 ;b=0-7
b=0 Ex. V2323.0
Special M
Snn.b
nn=0-31; b=0-7
b=0 Ex. S25.0
Note 3: The Workstation can read up to 512 bits with one read command.
P-24
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
3. Exam ple of the connections between PW S & RS485 of PLC PPI -port:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
a.Communication Format
:RS485
b.Node Address
:02 (01-32)
c.Transmission Speed
d.Transmission Format
e Command Delay
:9600 /19200/38400bps
:8-bit, EVEN, 1-bit
:
B. PWS- Setting
PWS back DIP-Switch SW10 set to
ON
Match the PLC address
( the default is 02)
Most applications can work without
this delay, i.e. Command Delay is 0.
However, if the communications
between the Workstation and your
PLC fails occasionally, setting this
parameter to a non-zero value may
solve the problem.
** The com m unication refresh data in PPI m ono -link faster than m ulti -link .
PWS Workstation
Release 10/98
P-25
Communication Notice between PLCs and PWS
PLC Connections, p273.tsk, SIEMENS S7-300 SERIES MPI
1. The table below shows the form ats of every register the PW S can access.
Register Type
Input Image
Input Image
Output Image
Output Image
Bits
Bits
Data Area (DB10)
Format
IWnnnnn
IDnnnnn
QWnnnnn
QDnnnnn
MWnnn
MDnnn
DBWnnnnn
Data Area (DB10)
DBDnnnnn
Range With the Register
nnnnn=0-65534
nnnnn=0-65532
nnnnn=0-65534
nnnnn=0-65532
nnnnn=0-254
nnnnn=0-252
nnnnn=0-655,34; DBWnnnnn is a
word address, the Byte nnnnn &
nnnnn+1 make DBWnnnnn
nnnnn=0-655,32; DBDnnnnn is a
double word address, the DBWnnnn
& DBWnnnn+1 make DBDnnnn
Data Size
Word
Double Word
Word
Double Word
Word
Double Word
Word
Double Word
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block, use an address that its bit address("b") is 0.
Relay Type
Input Image
Output Image
Bit
Data Area Bit
(=DB10)
Data Area Bit
(=DB10)
Format
Innnnn.b
Qnnnnn.b
Mnnn.b
DBXnnnn.b
Range
nnnnn=0-65535; b=0-7
nnnnn=0-65535; b=0-7
nnn=0-255; b=0-7
nnnn=0-8190 ;b=0-7
Vnnnnn.b
nnnnn=0-65535; b=0-7
DB10.DBXnnnnn.b is a bit address, It is in #b
bit of #nnnnn word with DB10
On/off Block
b=0 Ex. I3.0
b=0 Ex. Q2.0
b=0 Ex. M0.0
b=0 Ex. DBX23.0
DBX23.0=DB10.DBX23.0
b=0 Ex. V23.0
V23.0=DB10.DBX23.0
3. Exam ple of the connect ions between PW S & MPI 6ES7-972-0CA21-0XA0:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :MPI CABLE RS232
COM2=RS232
b.Node Address.
:02
c.Transmission Speed
:19200/38400 bps
d.Transmission Format
:8-bit, ODD, 1-bit
PWS Command Delay Setting
e. OPEN DATA BLOCK
:DB10 block for S7-300-CPU
P-26
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, pd03.tsk, SQUARE-D 400-700 SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range With the Register
I/O and Data Registers
Snnnn
nnnn=1-8000
Control Registers
Snnnn
nnnn=8001-8192
Note 1: The Workstation can read up to 128 words in one read command.
Data Size
Word
Word
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block, the bit address("bb") should be 1("01").
Range
On/off Block
Relay Type
Format
The last digit bb=01
I/O and Data Registers
Snnnn/bb
nnnn=1-8000; bb=1-16
The last digit bb=01
Control Registers
Snnnn/bb
nnnn=8001-8192;bb=1-16
Note 2: The Workstation can read up to 2048 bits in one read command.
3. Exam ple of The connections between PW S & RS422 of PLC:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS422
b.Transmission Speed
:9600 /19200bps
c.Transmission Format
:8-bit,EVEN,1
d.Routing codes
StationNumbers
If your Workstation is connected directly to the processor module, it doesn't matter what
station numbers you enter for the PLC and Workstation.
For application where one or more Workstations are connected to one or more PLCs, Square
D provides Network Interface Modules(NIMs) that provide ports for the Workstation, the PLC,
and the SY/NET network. You must set the PLC and Workstation numbers to their respective
NIM addresses. For example, if you set the rotary switches on the NIM to 24, and if the
Workstation is connected to port 0 and the PLC to port 1, then the Workstation's station
number is 024 and the PLC's station number is 214.
You must set the DIP switches on NIM for SY/MAX operation. On DIP switches S4 and S5, be
sure that switches 2 and 3 are in the down position. Also make sure that switch 1 has the
factory setting of up, which disables the receive broadcast mode.
Square D refers to station numbers as "routing numbers," where the Workstation is the
"source" and PLC is the "destination." The Workstation supports only a single level of routing
numbers, which means that it can access any PLC on the NIM's network, but cannot access a
PLC on any other networks.
PWS Workstation
Release 10/98
P-27
Communication Notice between PLCs and PWS
PLC Connections, pw03.tsk, TELEMECANIQUE TSX SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Internal Word %MWnnnn
Format
Wnnnn
Range
nnnn=0-9999
Data Size
Word
Note 1: The Workstation can read up to 60 words with one read command.
2. The table below shows the format of on/off location the Workstation can access. The bit
address ("bb") of an on/off block must be 0.
Relay Type
Format
Range
On/off Block
bb=00 Ex. W0:0
Bit of Internal Word
Wnnnn:bb
nnnn=0-9999; bb=0-15
Note 2: The Workstation can read up to 960 bits with one read command.
When the Workstation changes a bit, it reads a word from the PLC that contains 16 bits, changes
the desired bit, and writes the word to the PLC. These steps require more than one PLC scan to
complete, so your PLC ladder program must not control other bits within the same word. If it does,
there is a risk that the Workstation will reverse a change that the PLC makes.
For example, if the Workstation changes W1234:7, it readsW1234:0 through W1234:15 as a
single word, changes bit 7 within that word, and writes that entire word back to the PLC. If your
PLC ladder changes some other relay within that word in the meantime, then the Workstation's
subsequent write will cancel that change.
3. Exam ple of the connections between PW S & RS232 of PLC TSXPCU1030:
3.1 Exam ple of the connections between PW S & RS485 of Micro -CPU TER-port:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS232
COM2=RS232/422/485
RS485
RS485; DIP-Switch SW10 set ON
b.NODE ADDRESS.
:0--8
Communication set by PWS software
MASTER
PWS node address is 1—8 SLAVE
c.Transmission Speed
:9600bps/19200bps
d.Transmission Format
:8-bit,ODD,1-bit
P-28
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, p913.tsk, TI435 SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Timer Accumulated
Counter Accumulated
V Memory
Link Relays
Input Status
Output Status
Control Relays
Stage
Timer Status
Counter Status
Spec. Relay 1
Spec. Relay 2
Format
Vnnn
Vnnnn
Vnnnn
Vnnnnn
Vnnnnn
Vnnnnn
Vnnnnn
Vnnnnn
Vnnnnn
Vnnnnn
Vnnnnn
Vnnnnn
Range With the Register
nnn=octal number 0-177
nnnn=octal number 1000-1177
nnnn=octal number 1400-7777
nnnnn=octal number40000-40037
nnnnn=octal number40400-40423
nnnnn=octal number40500-40523
nnnnn=octal number40600-40635
nnnnn=octal number41000-41027
nnnnn=octal number41100-41107
nnnnn=octal number41140-41147
nnnnn=octal number41200-41205
nnnnn=octal number41216-41230
Data Size
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block, use an address the last digit must be 0.
Relay Type
Format
Range
On/off Block
Input Status
Xnnn
nnn=octal number 0-477
The last digit must be 0
Outpuut Status
Ynnn
nnn=octal number 0-477
The last digit must be 0
Control Relays
Cnnn
nnn=octal number 0-737
The last digit must be 0
Stage
Snnn
nnn=octal number 0-577
The last digit must be 0
Timer Status
Tnnn
nnn=octal number 0-177
The last digit must be 0
Counter Status
CTnnn
nnn=octal number 0-177
The last digit must be 0
Spec. Relay 1
SPnnn
nnn=octal number 0-137
The last digit must be 0
Spec. Relay 2
SPnnn
nnn=octal number 320-617
The last digit must be 0
3. Exam ple of the connections between PW S & RS232 of PLC TI435:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format
:RS232C
b.Node Address
:None
c.Transmission Speed
:9600/19200 bps
# TI435 & KOYO SU6 / DL Series
d.Transmission Format
:8-bit; ODD ; 1-bit
P.L.C are the same.
e. Protocol Mode
:HEX. (TISOFT AUX26)
If this port is setup in the "ASCII" mode, then the Workstation will not communicate with the PLC.
PWS Workstation
Release 10/98
P-29
Communication Notice between PLCs and PWS
PLC Connections, pt13.tsk, TOSHIBA T1/T2 SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range
External input register
XWnn
nn=0-63
Output Relay Register
YWnn
nn=0-63
Auxiliary relay register
RWnnn
nnn=0-127
Special register
SWnnn
nnn=0-255
Timer register
Tnnn
nnn=0-255
Counter register
Cnnn
nnn=0-255
Data register
Dnnnn
nnnn=0-4095
Link register
Wnnnn
nnnn=0-1023
Link relay register
LWnnn
nnn=0-255
File register
Fnnnn
nnnn=0-1023
Note 1: The Workstation can read up to 32 words in one read command.
Data Size
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block, use an address that its bit address("b") is 0.
Relay Type
Format
Range
On/off Block
External input device
Xnnb
nn=0-63; b= hex number 0-f
b=0 Ex. X10
External output device
Ynnb
nn=0-63; b= 0-f
b=0 Ex. Y00
Auxiliary relay device
Rnnnb
nnn=0-127; b= 0-f
b=0 Ex. R100
Special device
Snnnb
nnn=0-255; b= 0-f
b=0 Ex. S230
Link device
Znnnb
nnn=0-511; b= 0-f
b=0 Ex. Z30
Link relay
Lnnnb
nnn=0-255; b= 0-f
b=0 Ex. L2550
3. Exam ple of the connections between PW S & RS232 of PLC T1 CPU -port:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS232
b.Node Address
:0=T1
c.Transmission Speed
:9600bps
d.Transmission Format
:8-bit,ODD,1-bit
P-30
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, pc03.tsk, KOYO SA SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
TMR/CTR Accumulater
Register Values
Format
nnn
mmm
Range
Data Size
nnn=octal number 600-677
Word
mmm=octal number 400-576;
Even Bytes
mmm must be a multiple of 2
Note1: Although the registers are 8 bits wide, the Workstation handles each pair of registers as
if it were a single 16-bit register, where the even-numbered register contains the low byte and
the odd-numbered register contains the high byte. For example, if you specify register 406, then
406 is the low byte and 407 is the high byte. ADP3 doesn't accept odd-numbered register
addresses.
2. The table below shows the format of every on/off location the Workstation can access. When
you specify the address of an On/off Block register, use an address that last digit must be 0.
Relay Type
Format
Range
On/off Block
Input/Output Bits
Bnnn
nnn=octal number 0-157
The last digit must be 0
Input/Output Bits
Bnnn
nnn=octal number 700-767
The last digit must be 0
Internal Relay Bits
Bnnn
nnn=octal number 160-377
The last digit must be 0
Shift Register Bits
Bnnn
nnn=octal number 400-577
The last digit must be 0
TMR/CTR Bits
Bnnn
nnn=octal number 600-677
The last digit must be 0
When the Workstation changes a relay, it reads a byte from the PLC that contains 8 relays,
changes the desired bit, and writes the byte to the PLC. These steps require more than one PLC
scan to complete, so your PLC ladder program must not control other bits within the same byte.
If it does, there is a risk that the Workstation will reverse a change that the PLC makes.
For example, if the Workstation changes B3, it reads B0 through B7 as a single byte, changes
B3 within that byte, and writes that entire byte back to the PLC. If your PLC ladder changes
some other relay within that byte in the meantime, then the Workstation's subsequent write will
cancel that change.
3. Exam ple of the connections between PW S & RS232C of PLC SA21 E03 -DM:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS422 or RS232C
b.Node Address
:None
c.Transmission Speed
:9600/19200 bps
d.Transmission Format
:8-bit, odd, 1 stop bit
e.Operation Mode
:RUN Mode
e.Comm. Mode
:ASCII mode. SW2-8=ON
PWS Workstation
Release 10/98
P-31
Communication Notice between PLCs and PWS
PLC Connections, p553.tsk, Allen-Bradley PLC-5
1. The table below shows the form a ts of every register the PW S can access.
Register Type
Output file
Input file
Status file
Bit file
Format
O:ooo
I:ooo
S:nnn
Bfff:nnn
B:nnn
Timer file
Tfff:nnn
T:nnn
Tfff:nnn.PRE
T:nnn.PRE
Tfff:nnn.ACC
T:nnn.ACC
Cfff:nnn
C:nnn
Cfff:nnn.PRE
C:nnn.PRE
Cfff:nnn.ACC
C:nnn.ACC
Rfff:nnn
R:nnn
Rfff:nnn.LEN
R:nnn.LEN
Rfff:nnn.POS
R:nnn.POS
Nfff:nnn
N:nnn
Counter file
Control file
Integer file
Note 1:
Note 2:
Range
ooo=octal number 0-277
ooo=octal number 0-277
nnn=0-127
fff=3-999;
default file is 3 if fff omitted;
nnn=0-999
fff=3-999;
default file is 4 if fff omitted;
nnn=0-999
Data Size
Word
Word
Word
Word
fff=3-999;
default file is 5 if fff omitted;
nnn=0-999
Word
fff=3-999;
default file is 6 if fff omitted;
nnn=0-999
Word
fff=3-999;
default file is 7 if fff omitted;
nnn=0-999
Word
Word
The Workstation can read up to 60 words in one read command.
The Workstation doesnot support block read for registers in Timer, Counter, and
Control files.
3. Exam ple for the connections between PW S and RS232C of PLC-5:
P-32
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block register, the bit address should be zero.
Relay Type
Output file
O:xxx/yy
Input file
I:xxx/yy
Status file
Bit file
S:nnn/bb
Bfff:nnn/bb
Timer file
Tfff:nnn/bb
Tfff:nnn.PRE/bb
Tfff:nnn.EN
Cfff:nnn/bb
Cfff:nnn.PRE/bb
Cfff:nnn.CU
Cfff:nnn.DN
Cfff:nnn.UN
Rfff:nnn/bb
Rfff:nnn.LEN/bb
Rfff:nnn.EN
Rfff:nnn.DN
Rfff:nnn.ER
Rfff:nnn.IN
Nfff:nnn/bb
Counter file
Control file
Integer file
Note 3:
Note 4:
Format
Tfff:nnn.DN
Tfff:nnn.ACC/bb
Tfff:nnn.TT
Cfff:nnn.ACC/bb
Cfff:nnn.CD
Cfff:nnn.OV
Rfff:nnn.POS/bb
Rfff:nnn.EU
Rfff:nnn.EM
Rfff:nnn.UL
Rfff:nnn.FD
Range With the Relay
xxx=octal number 0-277;
yy=octal number 0-7;10-17
xxx=octal number 0-277;
yy=octal number 0-7;10-17
nnn=0-127; bb=0-15
fff=3-999;
default file is 3 if fff omitted;
nnn=0-999; bb=0-15
fff=3-999;
default file is 4 if fff omitted;
nnn=0-999; bb=0-15;
fff=3-999;
default file is 5 if fff omitted;
nnn=0-999; bb=0-15
fff=3-999;
default file is 6 if fff omitted;
nnn=0-999; bb=0-15
fff=3-999;
default file is 7 if fff omitted;
nnn=0-999; bb=0-15
The Workstation can read up to 960 bits in one read command.
The Workstation doesnot support block read for bits in Timer, Counter, and
Control files.
4. P.L.C. and W ork station settings:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS-Setting
a. Communication format
:RS232C
b. Node Address
:N
PLC Node Address N
c. Transmission Speed
:9600/19200 bps
Refer to what PLC was set.
d. Transmission Format
:8-bits,none, 1-bit
(data bits,parity,stop bits)
e. PLC-5
:FULL DUPLEX
f. BCC ERROR Check
:YES
Note:You should open those files in the PLC that the Workstation will access.
PWS Workstation
Release 10/98
P-33
Communication Notice between PLCs and PWS
PLC Connections, p503.tsk, Allen-Bradley SLC-503/504
1. The table below shows the form ats of every register the PW S can access.
Register Type
Output file
Input file
Status file
Bit file
Timer file
Counter file
Control file
Integer file
Note 1:
Note 2:
Format
Range With the Register
nn= 0-30
nn= 0-30
nn=0-31
fff= 3 or 10-255;
default file is 3 if fff omitted;
nnn=0-255
fff= 4 or 10-255;
default file is 4 if fff omitted;
nnn=0-255
Data Size
Word
Word
Word
Word
C:nnn
fff=5 or 10-255;
default file is 5 if fff omitted;
nnn=0-255
Word
R:nnn
fff=6 or 10-255;
default file is 6 if fff omitted;
nnn=0-255
Word
fff=7 or 10-255;
default file is 7 if fff omitted;
nnn=0-255
Word
O:nn
I:nn
S:nn
Bfff:nnn
B:nnn
Tfff:nnn
Tfff:nnn.PRE
T:nnn.PRE
Tfff:nnn.ACC
T:nnn.ACC
Cfff:nnn
Cfff:nnn.PRE
C:nnn.PRE
Cfff:nnn.ACC
C:nnn.ACC
Rfff:nnn
Rfff:nnn.LEN
R:nnn.LEN
Rfff:nnn.POS
R:nnn.POS
Nfff:nnn
N:nnn
T:nnn
Word
The Workstation can read up to 30 words in one read command.
The Workstation doesnot support block read for registers in Timer, Counter, and
Control files.
3. Exam ple for the connections between PW S & RS232C of PLC SLC -503/504:
P-34
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block register, the bit address should be zero.
Relay Type
Output file
Input file
Status file
Bit file
Timer file
Counter file
Control file
Integer file
Note 3:
Note 4:
Format
O:nn/bb
I:nn/bb
S:nn/bb
Bfff:nnn/bb
Tfff:nnn/bb
Tfff:nnn.PRE/bb
Tfff:nnn.ACC/bb Tfff:nnn.EN
Tfff:nnn.TT
Tfff:nnn.DN
Cfff:nnn/bb
Cfff:nnn.PRE/bb
Cfff:nnn.ACC/bb Cfff:nnn.CU
Cfff:nnn.CD
Cfff:nnn.DN
Cfff:nnn.OV
Cfff:nnn.UN
Rfff:nnn/bb
Rfff:nnn.LEN/bb
Rfff:nnn.POS/bb Rfff:nnn.EN
Rfff:nnn.EU
Rfff:nnn.DN
Rfff:nnn.EM
Rfff:nnn.ER
Rfff:nnn.UL
Rfff:nnn.IN
Rfff:nnn.FD
Nfff:nnn/bb
Range With the Relay
nn= 0-30; bb= 0-15
nn= 0-30; bb= 0-15
nn= 0-31; bb= 0-15
fff= 3 or 10-255;
default file is 3 if fff omitted;
nnn=0-255; bb=0-15
fff= 4 or 10-255;
default file is 4 if fff omitted;
nnn=0-255; bb=0-15
fff=5 or 10-255;
default file is 5 if fff omitted;
nnn=0-255; bb=0-15
fff=6 or 10-255;
default file is 6 if fff omitted;
nnn=0-255; bb=0-15
fff=7 or 10-255;
default file is 7 if fff omitted;
nnn=0-255; bb=0-15
The Workstation can read up to 480 bits in one read command.
The Workstation doesnot support block read for bits in Timer, Counter, and Control
files.
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS-Setting
a. Communication format
:RS232C =SLC-503/504
b. Node Address
:N
c. Transmission Speed
:9600/19200 bps
Set the Workstation's operating
d. Transmission Format
:8-bits,none, 1-bit
parameters to match the PLC.
(data bits,parity,stop bits)
e. SLC-503/504
:FULL DUPLEX ; DF1
f. BCC ERROR Check
:YES
Note:You should open those files in the PLC that the Workstation will access.
PWS Workstation
Release 10/98
P-35
Communication Notice between PLCs and PWS
PLC Connections, pa03.tsk, FUJI F SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range With the Register
Input/Output Relays
WBnnnn
nnnn=0-9999
Auxiliary Relays
WMnnnn
nnnn=0-9999
Data Memory
BDnnnn
nnnn=0-9999
Note 1: The Workstation can read up to 52 words in one read command.
Data Size
Word
Word
Double word
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block register, the bit number must be zero.
Relay Type
Input/output Relays
Discrete Outputs
Format
Bnnnnb
Mnnnnb
Range With the Relay
nnnn=0-9999;b=0-f
nnnn=0-9999;b=0-f
On/off Block
The last digit “b” is 0
The last digit “b” is 0
3. Exam ple of the connections between PW S & RS232 of T -LINK FFK120A:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS232C
Set the Workstation's operating
b.Node Address
:None
parameters to match the PLC.
c.Transmission Speed
:19200 bps/9600bps
d.Transmission Format
:7-bit,EVEN,1
To set the operating parameters of the General Interface Module FFU120B:
1) Use the Character Formation Switch on the back side to select transmission speed and
transmission format. The switch #8 should be set to on.
P-36
2)
Set Mode Switch to 1 for RS-232C communications or 3 for the RS-422/RS-485
communications.
3)
Use RS-485 Channel Set Dials to select the channel number.
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, p413.tsk, GE-FANUC 90-CCM
1. The table below shows the form ats of every register the PW S can access.
Register Type
Input Table
Format
%Innnnn
Output Table
%Qnnnnn
Register Table
%Rnnnnn
Range With the Register
nnnnn=1-12288;Must be 1or ( Multiple of
16)+1
nnnnn=1-12288; Must be 1or ( Multiple of
16)+1
nnnnn=1-16384
Data Size
Word
Word
Word
Note 1: The PWS can read up to 50 Words in one read command.
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block register, use an address that is a multiple of 16
plus 1.
Relay Type
Format
Range
On/off Block
%Innnnn
nnnnn=1-12288
Must be 1or ( Multiple of 16)+1
Input Table
%Qnnnnn
nnnnn=1-12288
Must be 1or ( Multiple of 16)+1
Output Table
Note 2: The Workstation can read up to 800 bits in one read command.
3. Exam ple of the connections between PW S & RS232 of PLC PCM 331:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS422 /RS485
:RS232C
b.Node Address
:None
c.Transmission Speed
:19200/9600 bps
d.Transmission Format
: 8bit,odd ,1
e.P.L.C. ID
:blanks
f. P.L.C. password
:none or ********
00000000 or ********
PWS Workstation
Release 10/98
P-37
Communication Notice between PLCs and PWS
PLC Connections, pb13.tsk, HITACHI EC SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range With the Register
Internal Register
WMnnn
nnn=400, 402, 404, …, 654
Internal Register
WMnnn
nnn=700, 702, 704, …, 954
Internal Register
WMnnn
nnn=960, 962, 964, …, 990
Timer/Counter Register
TCnnn
nnn=100-195
Timer/Counter Register
TCnnn
nnn=200-295
Note 1: The Workstation can read up to 60 words in one read command.
Data Size
Word
Word
Word
Word
Word
2. The table below shows the format of every on/off location the Workstation can access.
Relay Type
Format
Range
On/off Block
Input Relay
Xnnn
nnn=0-15, 20-35, 40-55, 60-75, ,180-195
X0,X20,X40…
Output Relay
Ynnn
nnn=200-215, 220-235, 240-255, ,
Y200,Y220…
380-395
Auxiliary Relay
Mnnn
nnn=400-655, 700-955, 960-991
M400,M420…
Timer/Counter Relay
TCnn
nn=0-95
TC0,TC1TC80
3. Exam ple of the connections between PW S & RS232 of PLC CPU port:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS232C
COM2 ==> RS232
If use COM2 as communication port please choose
exclusive protocol.
b.Node Address
:None
c.Transmission Speed
:9600 bps
d.Transmission Format
:7-bit ,EVEN, 1- bit
e.CTS Handshanking
:Enabled
P-38
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, pe63.tsk, IDEC FA-2J SERIES
1. T he table below shows the form ats of every register the PW S can access.
Register Type
Format
Range With the Register
Input Relay
Inn
nn=0-15
Output Relay
Qnn
nn=0-15
Internal Relay
Mnn
nn=0-29
nnn=0-127;Must be 0 or multiple of 8
Shift Register
Rnnn
Timer Preset
TPnn
nn=0-79
Timer
Tnn
nn=0-79
Counter Preset
CPnn
nn=0-46
Counter
Cnn
nn=0-46
Data Register
Dnnn
nnn=0-399
Note 1: The Workstation can read up to 50 Words in one read command.
Note 2: Besides TP, CP and D area, all other locations are read only.
Data Size
Byte
Byte
Byte
Byte
Word
Word
Word
Word
Word
2. The table below shows the format of every on/off location the Workstation can access. The
bit address ("b") of an on/off block register in I, Q, or M area must be 0.
The address of an on/off block register in R area must be divisible by 8.
Relay Type
Format
Range
On/off Block
Input Relay
Innb
n=0-15; b=0-7
b=0 Ex. I10
Output Relay
Qnnb
n=0-15; b=0-7
b=0 Ex. Q00
Internal Relay
Mnnb
nn=0-29; b=0-7
b=0 Ex. M10
Must be 0 or multiple of 8
Shift Register
Rnnn
nn=0-127
The Workstation can read up to 8 bits with one read command.
Note 1:
3. Exam ple of the connections between PW S & RS232 of Adapter PF2 -CLA:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS232
b.Node Address
:0
c.Transmission Speed
:9600bps
d.Transmission Format
:8-bit,EVEN,1-bit
PWS Workstation
Release 10/98
P-39
Communication Notice between PLCs and PWS
PLC Connections, pl23.tsk, LG K500H/1000H SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range With the Register
Data Size
Auxiliary Relay
Mnnn
nnn=0-191
Word
Input/Output Relay
Pnn
nn=0-63
Word
Keep Relay
Knn
nn=0-31
Word
Link Relay
Lnn
nn=0-63
Word
Special Relay
Fnn
nn=0-31
Word
Timer Current Value
Tnnn
nnn=0-255
Word
Counter Current Value
Cnnn
nnn=0-255
Word
Data Register
Dnnnn
nnnn=0-9999
Word
Note 1: The Workstation can read up to 32 words in one read command.
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block register, the bit address("b") should be 0.
Relay Type
Format
Range
On/off Block
Auxiliary Relay
Mnnnb
nnn=0-191;b=hex number 0-f
The last digit “b” is 0
Input/Output Relay
Pnnb
nn=0-63; b=hex number 0-f
The last digit “b” is 0
Keep Relay
Knnb
nn=0-31; b=hex number 0-f
The last digit “b” is 0
Link Relay
Lnnb
nn=0-63; b=hex number 0-f
The last digit “b” is 0
Special Relay
Fnnb
nn=0-31; b=hex number 0-f
The last digit “b” is 0
Note 2: The Workstation can read up to 256 bits in one read command.
3. Exam ple of the connections between PW S & RS232 of PLC -K1000H CPU:
3.1 Exam ple of the connections between PW S & RS485 of PLC -K1000H CPU:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS422 or RS232C
COM2=RS232/422/485
sw1=Off
:RS422/485
sw1=on
:RS232
b.Node Address
:00(CPU PORT)
PLC node address is 00
:00--15(RS422)
Refer to what PLC was set
c.Transmission Speed
:9600/19200 bps
d.Transmission Format
:8-bit,NONE,1-bit
P-40
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, p113.tsk, OMRON CV SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range With the Register
Data Size
CIO area
CIOnnnn
nnnn=0-2555
Word(16bit)
AR area
ARnnn
nnn=0-511
Word(16bit)
TC area
TCnnnn
nnnn=0-1023 /2048-3071
Word(16bit)
DM area
DMnnnn
nnnn=0-9999
Word(16bit)
Note 1: The Workstation can read up to 28 words with one read command.
Block Size
Max. 28 words
Max. 28 words
Max. 28 words
Max. 28 words
2. The table below shows the format of every on/off location the Workstation can access. The
bit address ("bb") of an on/off block in CIO area must be 0. The address of an on/off block in
TC area must be divisible by 16.
Relay Type
Format
Range
On/off Block
CIO area
CIOnnnnbb
nnnn=0-2555; bb=00-15
bb=00 Ex.CIO2300
TC area
TCnnnn
nnnn=0-1023 /2048-3071
mulitple of 16 Ex.TC16
Note 2: The maximal number of bits the Workstation can read with one command is 112.
3. Exam ple of the connections between PW S & RS232 of PLC CV -CPU port:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A.
a.Communication
Format
P.L.C. Setting
:RS232C
b.Node Address
c.Transmission Speed
d.Transmission
Format
PWS Workstation
Release 10/98
:RS422
:RS485
:00(00-31to set)
:19200/9600 bps
:initial value 7-bit,ENEN,2
B. PWS- Setting
COM2=RS232/422/485
PWS back DIP-Switch SW10=ON
Refer to what PLC was set
Set the Workstation's baud rate, data
format, default controller station
number to match the PLC's
transmission speed, transmission
format, and unit number.
P-41
Communication Notice between PLCs and PWS
PLC Connections, p263.tsk, SIEMENS S7-300 CP340 3964R
1. The table below shows the form ats of every register the PW S can access.
Register Type
DBmmm.DBWnnnn
Format
mmm=1-255
nnnn=0-8190
DBmmm.DBDnnnn
mmm=1-255
nnnn=0-8188
Range
nnnn=0-8190; DBWnnnn is a word
address, the Byte nnnn & nnnn+1
make DBWnnnn
nnnnn=0-8188;DBDnnnn is a double
word address, the DBWnnnn &
DBWnnnn+1 make DBDnnnn
Data Size
Word
Double
Word
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block, use an address that its bit address("b") is 0.
Relay Type
Format
Range
DBmmm.DBXnnnn.b
mmm=1-255
DBmmm.DBXnnnn.b is bit address. It
nnnn=0-8190 ; b=0-7
is in #b bit of #nnnnn word with
DBmmm
Note 1: The Workstation can read up to 256 bits in one read command.
3. Exam ple of the connections between PW S & RS232 of CP340:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format
:CP340
b.FUNCTION BLOCK
:FB40,FB2,FB3,DB2,DB3,FC40 for CP
P-42
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, p277.tsk, SIEMENS S7-300 SERIES HMI
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Input Image
IWnnnnn
Input Image
IDnnnnn
Output Image
QWnnnnn
Output Image
QDnnnnn
Bits
MWnnn
Bits
MDnnn
Timer Image
Tnnnnn.10ms
Timer Image
Tnnnnn.100ms
Timer Image
Tnnnnn.1s
Timer Image
Tnnnnn.10s
Counter Image
Cnnnnn
DBmmm.DBWnnnnn mmm=1-255
nnnn=0-65534
DBmmm.DBDnnnn
n
mmm=1-255
nnnn=0-65532
Data Area (DB10)
DBWnnnnn
Data Area (DB10)
DBDnnnnn
Data Area (DB10)
VWnnnnn
Data Area (DB10)
VDnnnnnn
Range With the Register
nnnnn=0-65534 length=1-1023
nnnnn=0-65532 length=1-1023
nnnnn=0-65534 length=1-1023
nnnnn=0-65532 length=1-1023
nnnnn=0-65534 length=1-128
nnnnn=0-65532 length=1-128
nnnnn=0-65534 length=1-1023
nnnnn=0-65534 length=1-1023
nnnnn=0-65534 length=1-1023
nnnnn=0-65534 length=1-1023
nnnnn=0-65534 length=1-1023
nnnn=0-65534; DBWnnnn is a word
address, the Byte nnnn & nnnn+1
make DBWnnnn
nnnnn=0-655328;DBDnnnn is a
double word address, the DBWnnnn
& DBWnnnn+1 make DBDnnnn
nnnnn=0-655,34; DBWnnnnn is a
word address, the Byte nnnnn &
nnnnn+1 make DBWnnnnn
nnnnn=0-655,32; DBDnnnnn is a
double word address, the DBWnnnn
& DBWnnnn+1 make DBDnnnn
nnnnn=0-655,34; VWnnnnn is a
word address, the Byte nnnnn &
nnnnn+1 make DBWnnnnn
nnnnn=0-655,32; VDnnnnn is a
double word address, the DBWnnnn
& DBWnnnn+1 make DBDnnnn
Data Size
Word
Double Word
Word
Double Word
Word
Double Word
Word
Word
Word
Word
Word
Word
Double Word
Word
Double Word
Word
Double Word
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block, use an address that its bit address("b") is 0.
Relay Type
Format
Range
On/off Block
b=0 Ex. I3.0
Input Image
Innnnn.b
nnnnn=0-65535; b=0-7
b=0 Ex. Q2.0
Output Image
Qnnnnn.b
nnnnn=0-65535; b=0-7
b=0 Ex. M0.0
Bit
Mnnnnn.b
nnnnn=0-65535; b=0-7
b=0 Ex. DB22.DBX20.0
Data Area Bit
DBmm.DBXnnnnn.b mmm=1-31
nnnnn=0-65535 ;b=0-7
b=0 Ex. DBX23.0
Data Area Bit
DBXnnnnn.b
nnnnn=0-65535 ;b=0-7
(DB10.DBX23.0)
(=DB10)
b=0 Ex. V23.0
Data Area Bit
Vnnnnn.b
nnnnn=0-65535; b=0-7
(=DB10)
DB10.DBXnnnnn.b is a bit address, It is in #b bit V23.0=DB10.DBX23.0
of #nnnnn word with DB10
3. Exam ple of the connections between PW S & HMI 6ES7-972-0CA10-0XA0:
PWS Workstation
Release 10/98
P-43
Communication Notice between PLCs and PWS
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :HMI CABLE RS232
COM2=RS232
b.Node Address
:02
c.Transmission Speed
:9600/19200/38400 bps
d.Transmission Format
:8-bit, ODD, 1-bit
PWS Command Delay Setting
e. OPEN DATA BLOCK
:DB block for S7-300-CPU
P-44
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, py03.tsk, TAIAN TP SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range With the Register
Input Register
WXnn
nn=1-24
Output Register
WYnn
nn=1-27
Special Register
WSnn
nn=1-40
Constant Register
WCnnn
nnn=1-512
Data Register
Vnnnn
nnnn=1-1024
Note 1: The Workstation can read up to 60 words with one read command.
Data Size
Word
Word
Word
Word
Word
2. The table below shows the format of every on/off location the Workstation can access. The
address of an on/off block must be a multiple of 16 plus 1.
Relay Type
Format
Range
On/off Block
Input Relay
Xnnn
nnnn=1-384
Must be 1 or ( multiple of 16) +1
Output Relay
Ynnn
nnnn=1-384
Must be 1 or ( multiple of 16) +1
Auxiliary Relay
Cnnnn
nnnn=1-1024
Must be 1 or ( multiple of 16) +1
Note 2: The Workstation can read up to 960 bits with one read command.
3. Exam ple of Com m unication connections:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS Setting
a.Communication Format :RS232
b.Node Address
:0
c.Transmission Speed
:9600bps
d.Transmission Format
:8-bit,odd,1-bit
PWS Workstation
Release 10/98
P-45
Communication Notice between PLCs and PWS
PLC Connections, p903.tsk, TI500/505/545 SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range With the Register
Data Size
V Memory
Vnnnnn
nnnnn=1-65535
Word
Input Registers
WXnnnn
nnnn=1-4095
Word
Output Registers
WYnnnn
nnnn=1-4095
Word
Timer/Counter Presets
TCPnnnnn
nnnnn=1-10240
Word
Timer/Counter Current
TCCnnnnn
nnnnn=1-10240
Word
Drum Counter Presets
DCPddd/ss
ddd=drum 1-255 ; ss=step 1-16
Word
Drum Counter Current
DCCddd
ddd=drum 1-255
Word
Drum Step Presets
DSPddd
ddd=drum 1-255
Word
Drum Step Current
DSCddd
ddd=drum 1-255
Word
Drum Time Base
DTBddd
ddd=drum 1-255
Word
2. The table below shows the format of every on/off location the Workstation can access.
Relay Type
Format
Range
On/off Block
Must be 1 or ( multiple of 16) +1
Discrete Inputs
Xnnnn
nnnn=1-4095
Must be 1 or ( multiple of 16) +1
Discrete Outputs
Ynnnn
nnnn=1-4095
Must be 1 or ( multiple of 16) +1
Control Relays
Cnnnn
nnnn=1-4095
3. Exam ple of the connections between PW S & RS232 of PLC link port:
3.1 Exam ple of the connections between PW S & RS422 of PLC link port:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS- Setting
a.Communication Format :RS422or RS232C
COM2=RS232/422/485
b.Node Address
:None
c.Transmission Speed
:9600 bps
d.Transmission Format
:7-bit,odd,1-stop bit
P-46
PWS Workstation
Release 10/98
Appendix-P
Communication Notice between PLCs and PWS
PLC Connections, p923.tsk, TI325/330 SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range
Data Size
TMR/CTR Accumulater
nnn
nnn=octal number 600-677
Word
Register Values
mmm
mmm=octal number 400-576
Even Bytes
Note1: Although the registers are 8 bits wide, the Workstation handles each pair of registers as if
it were a single 16-bit register, where the even-numbered register contains the low byte and the
odd-numbered register contains the high byte. For example, if you specify register 406, then 406
is the low byte and 407 is the high byte. ADP3 doesn't accept odd-numbered register addresses.
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block, use an address that is a multiple of 8.
Relay Type
Format
Range
On/off Block
Input/Output Bits
Bnnn
nnn=octal number 0-157
The last digit must be 0
Input/Output Bits
Bnnn
nnn=octal number 700-767
The last digit must be 0
Internal Relay Bits
Bnnn
nnn=octal number 160-377
The last digit must be 0
Shift Register Bits
Bnnn
nnn=octal number 400-577
The last digit must be 0
TMR/CTR Bits
Bnnn
nnn=octal number 600-677
The last digit must be 0
When the Workstation changes a relay, it reads a byte from the PLC that contains 8 relays,
changes the desired bit, and writes the byte to the PLC. These steps require more than one PLC
scan to complete, so your PLC ladder program must not control other bits within the same byte. If
it does, there is a risk that the Workstation will reverse a change that the PLC makes.
For example, if the Workstation changes B3, it reads B0 through B7 as a single byte, changes B3
within that byte, and writes that entire byte back to the PLC. If your PLC ladder changes some
other relay within that byte in the meantime, then the Workstation's subsequent write will cancel
that change.
3. Exam ple of the connections between PW S & RS232 of PLC TI305 -03 DM:
3.1 Exam ple of the connections between PW S & RS422 of PLC TI305-02DM:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS Setting
a.Communication Format
:RS422 or RS232C
b.NODE ADDRESS.
:None
c.Transmission Speed
:9600/19200 bps
d.Transmission Format
:8-bit; ODD or NONE; 1-bit
e.Operation Mode
:RUN Mode / HEX MODE.
PWS Workstation
Release 10/98
P-47
Communication Notice between PLCs and PWS
PLC Connections, pt03.tsk, TOSHIBA M20/M40 SERIES
1. The table below shows the form ats of every register the PW S can access.
Register Type
Format
Range
Input Relay Register
XWnn
nn=0-63
Output Relay Register
YWnn
nn=0-63
Internal Relay Register
RWnn
nn=0-63
Link Register
ZWnn
nn=0-31
Timer Register
Tnnn
nnn=0-127
Counter Register
Cnn
nn=0-95
Data Register
Dnnnn
nnnn=0-1535
Note 1: The Workstation can read up to 32 words in one read command.
Data Size
Word
Word
Word
Word
Word
Word
Word
2. The table below shows the format of every on/off location the Workstation can access.
When you specify the address of an On/off Block, use an address that its bit address("b") is 0.
Relay Type
Format
Range
On/off Block
Input Relay
Xnnb
b=0 Ex. X10
nn=0-31;b=0-f
Output Relay
Ynnb
b=0 Ex. Y00
nn=0-31;b=0-f
Internal Relay
Rnnb
b=0 Ex. R100
nn=0-63;b=0-f
Link Relay
Znnb
b=0 Ex. Z310
nn=0-31;b=0-f
Note 2: The Workstation can read up to 512 bits in one read command.
3. Exam ple of the connections between PW S & RS422 of PLC:
4. P.L.C. & PW S setting:
Please set the com m unication param eters & the DIP -Switch as below:
A. P.L.C. Setting
B. PWS Setting
a.Communication Format
:RS422
Programmer / computer link
:Computer link can be used
b.Node Address
:0
c.Transmission Speed
:9600bps
d.Transmission Format
:(8,E,1);(8,O,1); (8,N,1)
P-48
PWS Workstation
Release 10/98
© Copyright 2026 Paperzz